SM6 Switchgears

MV switchgear, type SM6

1
https://electrical-engineering-portal.com/substation-data-center

SM6 Switchgears

MV switchgear, type SM6

https://electrical-engineering-portal.com/substation-data-center

SM6 Switchgears
MV/LV dry type transformer without
enclosure installed in Data Center

LV switchgear installed in Data Center

2
SM6 Switchgears

 The SM6 range is made up of modular units


containing fixed or withdrawable metal-
enclosed SF6 switchgear, including:
- Switch-disconnectors;
- Fluarc SF1 or SFset circuit breakers;
- Rollarc 400 or 400D contactors;
- Disconnectors.

 SM6 units are used for the MV section in


MV/LV transformer substations in public
distribution systems and MV consumer or
distribution substations up to 24 kV.

 SM6 units are designed for indoor


installation (IP2XC).

The secondary distribution solution

standards
• recommendations:
IEC 298, 265, 129,
694, 420, 56;

primary distribution

secondary distribution

7
BMTBD-nxcuong

3
MV/LV transformer substations
Public distribution
Consumer substations

Primary distribution

Secondary distribution

8
BMTBD-nxcuong

Industrial
distribution
substations

9
BMTBD-nxcuong

4
Switch cubicles
2

1 1. switchgear
4 2. busbars
3. operating mechanism
3
4. low voltage
5. connection

10
BMTBD-nxcuong

Circuit breaker cubicles

5
1 1. switchgear
3 2. busbars
3. operating mechanism
4. connection and circuit breaker
5. low voltage

3
4

11
BMTBD-nxcuong

5
Switchgear (switch and disconnector) compartment

 0,4 bar relative pressure

 Sealed pressure system

 safety membrane

 switch-diconnector

 Earthing switch

12
BMTBD-nxcuong

Switchgear compartment

1 enclosure
2 cover
3 operating shaft
4 fixed contact
5 moving contact
6 seal

13
BMTBD-nxcuong

6
Switchgear compartment

 3-position switch
 Isolation
 Making capacity of earthing switch
 Optimized breaking technique

closed open earthed

14
BMTBD-nxcuong

Busbar compartment

 Connection in horizontal plane


 Field distributors
 Insulated busbars
 No risk of error

15
BMTBD-nxcuong

7
Connection and switchgear (circuit breaker) compartment

 All types of cables


 up to 240 mm2 - 630 A and
 up to 630 mm2 - 1250 A

 Single-handed connection

 Field distributors

 Fluarc SF1 or SFset circuit breakers

16
BMTBD-nxcuong

SF6 circuit breaker

 SF1 circuit breaker: 630 or 1250 A

 combined with an electronic relay and standard sensors

 auxiliary power supply

17
BMTBD-nxcuong

8
SF6 circuit breaker

 SFset enhanced circuit breaker - 630 A

 special sensors
 dedicated electronic relays
 no auxiliary power supply

18
BMTBD-nxcuong

Fluarc SFset or SF1 circuit breaker

1 enclosure
2 bottom cover
3 operating shaft
4 main moving contact
5 moving arcing contact
6 fixed arcing contact
7 sealing system
8 compression chamber
9 moving piston
10 valves
11 insulating nozzle

19
BMTBD-nxcuong

9
breaking principle

20
BMTBD-nxcuong

Vacuum type circuit breaker: Evolis

 Evolis circuit breaker: 630 or 1250 A

 combined with an electronic relay and standard sensors

 auxiliary power supply

21
BMTBD-nxcuong

10
Operating mechanism compartment

 optional motorized operation


 low maintenance
 clear, animated mimic panels
 accessible with busbars energized

22
BMTBD-nxcuong

Positive break

 Position indicator on operating shaft

 Direct and reliable transmission mechanism

 Natural interlocking

Closed Open Earthed

23
BMTBD-nxcuong

11
For protection and control/monitoring systems

 For protection and control/monitoring systems


 Accessible with cables and busbars energized

24
BMTBD-nxcuong

Protection and control monitoring functions

 Easergy P3 relay

• Protection of substation (incoming,


outgoing line and busbars).
• Protection of transformers.
• Protection of motors, and generators.

25
BMTBD-nxcuong

12
Protection and control monitoring functions

26
BMTBD-nxcuong

Protection and control monitoring functions

27
BMTBD-nxcuong

13
Connection to networks

 Incoming or outgoing unit  Outgoing unit,


right or left

IM 375 IMC 500 IMB 375

29
BMTBD-nxcuong

Protection

 Fuses-switch  Fuses-switch
unit combination unit

PM 375 QM 375

30
BMTBD-nxcuong

14
Protection

 Fuses-switch  Fuses-switch
combination unit combination unit,
right or left outgoing line

QMC 625 QMB 375

31
BMTBD-nxcuong

Protection

 Contactor unit  Fused-contactor unit

CRM 750 CRM 750

32
BMTBD-nxcuong

15
Protection

 Single-isolation circuit
 Single-isolation
breaker unit right or
circuit breaker unit
left outgoing line

DM1 - A 750 DM1 - D 750

33
BMTBD-nxcuong

Protection

 Double-isolation circuit breaker unit,


right or left outgoing line

DM2 750

BMTBD-nxcuong
Disconnector: Double-function operating mechanism CS 34

16
Protection

 Withdrawable  Withdrawable single-isolation


single-isolation circuit circuit breaker unit, right or
breaker unit left outgoing line

DM1 - W 750 DM1 - Z 750

35
BMTBD-nxcuong

MV metering

 Voltage transformers  Voltage transformers for mains


for mains with earthed with insulated neutral system
neutral system

CM 375 CM2 500

36
BMTBD-nxcuong

17
MV metering

 Current and/or voltage  Current and/or voltage


measurement unit, right measurement unit
or left outgoing line

GBC - A 750 GBC - B 750

37
BMTBD-nxcuong

Functions required by private networks

 Intermediate  Extension unit  Connection unit


bus unit VM6/SM6 right/left outgoing line

GIM 125 GEM 125 GBM 375

38
BMTBD-nxcuong

18
Functions required by private networks

 Incoming  Incoming
cable-connection unit cable-connection unit

GAM 2 375 GAM 500

39
BMTBD-nxcuong

Functions required by private networks

 Disconnector unit  MV/LV transformer


unit for auxiliaries

SM 375 TM 375

40
BMTBD-nxcuong

19
Functions required by private networks

 Busbars power supply for main incoming line on right or left


and cables for stanby line

NSM-barres 375 NSM-cables 375

41
BMTBD-nxcuong

Electrical characteristics

NA: Non Available


(1) 3 phases
(2) In 20 kA / 3 s for SM6-24 only, consult us
(3) In 800 A, consult us.
BMTBD-nxcuong (4) NA for SM6-36 42

20
Electrical characteristics

NA: Non Available


(1) 3 phases
(2) In 20 kA / 3 s for SM6-24 only, consult us
(3) In 800 A, consult us.
(4) NA for SM6-36
43
BMTBD-nxcuong

Easy installation

 Simplified civil works

 Symmetric cable connection

 Identical cubicle heights and


floor-level depths

44
BMTBD-nxcuong

21
Overall quality

 Routine tests

 Inspections
EDF/SEPIA
 mechanical quality audit
 operating times
 seal Annual production
 Dielectric line sampling

 Measurements Production sites


with ISO 9002
 operating stresses certification by AFAQ
 voltage drop