Code Check Electrical
Code Check Electrical
8th Edition
Based on the 2017 NEC – Including selected changes to the 2014 & 2017 NEC
®
C
ode Check Electrical 8th Edition is a field guide to common code issues in residential electrical installations. It is based on the 2017 National Electrical
Code (NEC)®. Significant changes in the 2017 NEC and the 2014 NEC are highlighted throughout the text and summarized on p.64, so this book is current
for areas using either the 2014 or 2017 NEC. Before beginning any electrical project, check with your local building department to determine the code edition
used in your area. In addition to a model code, energy codes and utility rules may also apply to electrical installations. The smoke & carbon monoxide alarm rules here
are from the 2015 edition of the International Residential Code, published by the International Code Council.
1
Back to Previous Page Table of Contents Abbreviations Code Changes
Code changes are highlighted by placing the code citation in a different color. The EVSE = electric vehicle supply equipment NM = nonmetallic-sheathed cable
superscript number at the end of the citation refers to the code change number on EXC = exception(s) OBC AFCI = Outlet Branch Circuit
p.65, as in this example from p.28, under the subheading of “Locations requiring FMC = flexible metal conduit AFCI
GFCI protection” ft. = foot, feet O.C. = on center
GEC = grounding electrode conductor OCPD = overcurrent protection device
n Outlets supplying dishwashers________________________________ 210.8D32 (breaker or fuse)
GES = grounding electrode system
This line tells us that all dishwashers in residential construction now require GFCI = ground-fault circuit interrupter PV = photovoltaic
GFCI protection. The reference number for code change 32 on page 31 tells us GFPE = ground-fault protection of equipment PVC = rigid polyvinyl chloride conduit
this change took place in the 2014 NEC. req = require, requiring, requirement
hp = horsepower
The 2017 NEC had a follow-up change to this section, also noted on p.42: IMC = intermediate metal conduit req’d = required
n DW cords 3 ft.— 61/2 ft. measured from back of appliance______422.16B2(3)52 in. = inch(es) req’s = requires
n DW receptacle in space adjacent to dishwasher____________ 422.16B2(6)52 IBT = Intersystem Bonding Terminal RMC = rigid metal conduit
IRC = International Residential Code RS = rapid shutdown (photovoltaics)
These lines tell us that dishwasher receptacles can no longer be in the space RTRC = reinforced thermosettting resin
kcmil = 1,000 circular mil units
directly behind the dishwasher, and the maximum allowable cord length has conduit
(conductor size – formerly MCM)
been increased since the cord must reach to the adjacent space. This is also an SCC = short circuit current
L&L = listed & labeled, listing & labeling
example of how sections of the NEC are interconnected. GFCI devices must be SCCR = short circuit current rating
readily accessible (a rule that first came into the 2011 NEC) and a receptacle LCDI = leakage-current detector-interrupter
LED = light-emitting diode SER = service entrance cable (round)
directly behind the dishwasher would be accesssible, but not readily accessible.
lb. = pound(s) SEU = service entrance cable (flat)
LFMC = liquidtight flexible metal conduit SFD = single-family dwelling
ABBREVIATIONS LFNC = liquidtight flexible nonmetallic sq. = square, as in sq. in.
conduit temp = temperature
A = amp(s), amperage, amps stated as “number” (#8 = 8 AWG)
max = maximum TR = tamper-resistant
AC = air conditioning CO = carbon monoxide
MC = metal-clad cable UF = underground feeder cable
AC = alternating current COM = communication wire
MFR = manufacturer(s) USB = universal serial bus
AC = armored cable, a.k.a. “BX” cu. = cubic, as in cu. in.
min = minimum USE = underground service entrance
AFCI = arc-fault circuit interrupter Cu = copper
n/a = minimum cable
AFF = above finished floor or grade DC = direct current
NEC = National Electrical Code V = volt(s), such as a 120V circuit
AHJ = Authority Having Jurisdiction EGC = equipment grounding conductor
NEMA = National Electrical Manufacturers VA = volt-ampere(s), units of apparent
Al = aluminum EMT = electrical metallic tubing power
Association
AMI = in accordance with manufacturer’s ENT = electrical nonmetallic tubing, a.k.a. w/ = with
NFPA = National Fire Protection
instructions “Smurf tubing”
Association W = watt(s), units of true (useful) power
AWG = American Wire Gauge, commonly EV = electric vehicle
WR = weather-resistant
2
Back to Previous Page Table of Contents Abbreviations Code Changes
3
Back to Previous Page Table of Contents Abbreviations Code Changes
4
Back to Previous Page Table of Contents Abbreviations Code Changes
3 ft.
8 ft.
.B ≥18 in.
.A
3 ft. .C
.I .
18 ft. or .C
10 ft.
per utility
.G 12 ft.
.E .F 10 ft. ≤4 ft..
.D
3 ft.
.H
5
Back to Previous Page Table of Contents Abbreviations Code Changes
6
Back to Previous Page Table of Contents Abbreviations Code Changes
Working space is essential for worker safety. These requirements apply to panels
and all electrical equipment that requires examination, adjustment, servicing, or
maintenance while energized. Working space should not be used for storage.
General F2 17 NEC Working space height
n Front working clearance min 36 in. deep_______________________ 110.26A1 6 ft. 6 in. AFF, or Req’d working space
n Distance measured from exposed live parts or face of enclosure____ 110.26A1 height of equipment, must extend to floor
n Min headroom 61/2 ft. AFF or equipment height EXC_____________ 110.26A3 whichever is greater or grade.
• Existing service equipment up to 200A OK < 61/2 ft.____________ 110.26A3X1
n Work space extends from floor to req’d height EXC_____________ 110.26A3
• Related equipment may extend 6 in. beyond panel front_____________ 110.26A3
n Clear width min 30 in. wide or width of equipment______________ 110.26A2
n Equipment doors or hinged panels must be openable at least 90º_ 110.26A2
n Working space not to be used for storage______________________ 110.26B
n Illumination req’d for working space at all indoor panels___________ 110.26D
7
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 3
SEPARATE BUILDINGS
Separate Buildings
To avoid objectionable currents on conductive paths between buildings, an EGC
must be installed in addition to the insulated neutral feeder conductor. Existing Service
panel Each building or structure Subpanel
installations with bonded neutrals can remain if there are no parallel current paths.
containing more than 1 branch
Outside Feeders 17 NEC circuit req’s its own GES.
n Trees may not support overhead conductors______________________ 225.26
n Overhead feeder mast – same rules as services F1____________ 225.17—19 Cover depth per T1
n Height above roofs < 4:12 slope 8 ft. 6 in. F1___________________ 225.19A5
n Provide proper cover for buried cable or conduit F4, T1______________ 300.5
n Each building or structure req’s GES F3, F6 EXC_______________ 250.32A
• Building or structure w/ only 1 branch circuit & w/ EGC________ 250.32AX Feeders to separate buildings req an
n Raceways entering building from outside must be sealed___________ 225.276 Service insulated neutral in addition to an EGC.
lateral Panels in separate buildings are subpanels F17.
n Max 1 feeder or branch circuit to or back from each building EXC_____225.30
• EV chargers L&L for more than single branch circuit or feeder____225.30A77
n Disconnect req’d at each building F3____________________________ 225.31
n Disconnect must consist of max 6 switches or breakers_____________ 225.33
n 4-conductor feeder to panel in separate building –
do not bond neutral to EGC or GEC EXC______________________ 250.32B
• Existing installations to separate buildings with no continuous metal
paths, e.g., metal water pipe, etc., between the 2 structures____ 250.32BX1
n Disconnect rated as service equipment when using above exception__225.36
8
Back to Previous Page Table of Contents Abbreviations Code Changes
9
Back to Previous Page Table of Contents Abbreviations Code Changes
TEMPORARY WIRING
General 17 NEC
n Allowed only during period of construction________________________590.3A
n Services same height, grounding, clearance, etc., as permanent F1,5_ 590.4A
n NM & SE allowed in any height building & SE OK underground__ 590.4B&C8
n No receptacles on branch circuits supplying temporary lighting_____ 590.4D1
n Lampholders req guards_______________________________________ 590.4F
n Splices in NM cable or MC cable OK without splice box if EGC
continuity maintained (including listed metal cable fittings)__________590.4G9
n Protect cords & cables from accidental damage__________________ 590.4H
n Cords & cables not OK on floor or ground exc extension cords______ 590.4J10
n GFCI req’d on all 125V 15, 20 & 30A temporary receptacles_____ 590.6A111
n Listed GFCI cord-sets OK only to supplement GFCI on temporary
receptacles or as first device on permanently wired receptacle__590.6A1&211
n Other receptacles GFCI, special purpose GFCI, or assured grounding_ 590.6B12
FIG. 5
Temporary Power Pole
Typical 6×6 post with 18 ft. or per
block above weatherhead utility
GFCI Receptacles
10
Back to Previous Page Table of Contents Abbreviations Code Changes
11
Back to Previous Page Table of Contents Abbreviations Code Changes
12
Back to Previous Page Table of Contents Abbreviations Code Changes
13
Back to Previous Page Table of Contents Abbreviations Code Changes
14
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 6
OK to use building steel to Service OK to use water pipe within 5 ft. of entry Single rod with
Grounding interconnect GECs panel to building to interconnect GECs resistance > 25 ohms
must be supplemented
Electrode
by another electrode
Conductors Size Per T5
Size Per T5 other than water pipe
#2 OK to use Ufer extension to Water pipe
interconnect GECs in location w/10 ft. in
#4 Ufer #4 #6
Ground protected from corrosion contact with
ring earth
15
Back to Previous Page Table of Contents Abbreviations Code Changes
16
Back to Previous Page Table of Contents Abbreviations Code Changes
17
Back to Previous Page Table of Contents Abbreviations Code Changes
Machine
screws OK
Sheet metal
screws NOT
OK Continuity must be Grounding
maintained if device Bonding Grounding
wedge
is removed. bushing wedge
18
Back to Previous Page Table of Contents Abbreviations Code Changes
19
Back to Previous Page Table of Contents Abbreviations Code Changes
20
Back to Previous Page Table of Contents Abbreviations Code Changes
21
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 16 FIG. 17
Barriers over
Service
exposed service
Panel lugs or bus bars Subpanel
Bonding
bushing F13 SUPPLY SIDE
req’d for All multiwire
service LOAD SIDE circuits req.
conductors handle ties or Do not bond
entering single-handle neutral in
Neutral conductor 2-pole breaker.
through subpanel.
identified (white
concentric
tape encircling If more than one
knockouts.
end of conductor) circuit in raceway,
Bond neutral in tie neutrals to their
GEC associated circuit
service enclosure
conductors, or use
tags or numbers
Panelboard on each wire. Also
(article 408) EGC applies to race-
Breaker ways with more
protects Cabinet
(article 312) No wire tie than one multiwire
panel & circuit.
subpanel needed for
4-conductor multiwire
feeder circuit in cable.
22
Back to Previous Page Table of Contents Abbreviations Code Changes
23
Back to Previous Page Table of Contents Abbreviations Code Changes
Open neutral
n All conductors must originate from same panel____________________210.4A
n Neutrals may not feed through devices whose removal would 240V Utility Transformer Secondary
interrupt continuity (use pigtails from neutral to devices in box)_____ 300.13B 120V
n All multiwire circuits req handle ties or single handle breaker_________ 210.4B
n All conductors of multiwire circuit must be identified or grouped
(wire ties or other means) inside enclosures EXC F17___ 200.4B & 210.4D22
• Cable systems where grouping is obvious F17________________ 200.4BX1
• Where passing through box w/out splice or loop______________ 200.4BX222
0.83A
0.83A
0.5A
2.5A
2.5A
2.5A
Most utility transformers for 1- and 2-family dwelling services have two unground-
2A
5A
Neutral
ed “hot” conductors and a neutral derived from the center of the transformer, as
point
depicted in F19. The neutral is connected to earth and is a “grounded” conductor.
The neutral limits the voltage on either of the hot conductors to 120V to ground. 120V 120V 120V 120V 200V 40V
The service is a “3-wire” shared-neutral circuit. 120V branch circuits with shared
neutrals are known as multiwire circuits (also called “Edison” circuits). If the neutral
is broken or loose, voltages become erratic, as in F19 .C . TV sets, motors, and
computers don’t do well with fluctuating voltages. Signs of unstable voltage, such
as incandescent bulbs growing brighter or dimmer as other loads change, could 60W 60W
.A 300W 300W .B 300W .C 300W
indicate a loose neutral either at a branch circuit or at the utility.
.A PROPER CIRCUIT 2 unequal loads are fed by a 3-wire circuit. The
neutral carries the imbalance between the 2 loads1.
.B OVERLOADED NEUTRAL Without voltage potential between the
hot conductors, the neutral carries the sum of the loads. In a 3-conduc-
tor NM cable, the black & red wires must originate from different poles.
.C OPEN NEUTRAL Two unequal loads in series across 240V from the
transformer. The load with lowest resistance sees the lower voltage.
Voltage at each load depends on other loads and is unstable.
1. On 120/208 systems, the neutral always carries current, even in properly
balanced circuits. The principles here still apply.
24
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 20
ARC-FAULT CIRCUIT INTERRUPTERS (AFCIs) AFCIs — Replacements & Extensions
AFCIs provide fire protection by tripping when an arcing fault is detected. AFCI
breakers and GFCI breakers look similar F21,24, and you must read the label to New Box &
determine if a breaker is an AFCI or a GFCI. Dual function breakers that provide Existing Receptacle
Receptacle
both AFCI & GFCI protection are also available F21. Outlet branch-circuit type Protected on extended
Replace with
(OBC) AFCIs are also available, including ones that are also GFCIs, and the codes extension circuit
OBC AFCI at
have changed substantially to recognize these new methods.
first outlet of
The number of areas requiring AFCI protection expands in each code cycle. The branch circuit
Unprotected
time to plan for the AFCIs is during the rough wiring, so that separate cables are being extended
home run
provided for the circuits requiring AFCI protection. Not all brands and models of
AFCI are compatible with multiwire circuits.
Replace with
Beginning January 1, 2008, all AFCIs were req’d to meet the UL standard for “com- dual-function GFCI
bination” types rather than the older “branch/feeder” type. Combination AFCIs pro- & OBC AFCI with
vide a broader range of protection than branch/feeder types. OBC AFCIs provide AFCI at origin
of branch appropriate labels
the same range of protection as combination types, and when installed at the first (see p.28)
outlet box on a circuit protected by an older “branch/feeder” AFCI, that circuit then circuit Replacement
complies with the 2014 and 2017 NEC. of Existing
New Box & Ungrounded
Areas Requiring AFCI Protection 17 NEC Receptacle Receptacle
n Req’d for all 120V 15A & 20A branch circuits supplying outlets
or devices in family rooms, dining rooms, living rooms, parlors,
libraries, dens, bedrooms, sunrooms, recreation rooms, closets,
hallways kitchens, laundry areas & similar rooms EXC____________ 210.12A23
• May be omitted on individual circuit to a fire alarm circuit in RMC, IMC,
EMT, or steel-armored AC or MC cable w/ metal junction boxes that is
part of central-station system in accordance w/ NEC Article 760 __ 210.12AX
n Req’d for all 120V 15A & 20A branch circuits supplying
outlets & devices in dormitory unit bedrooms, living rooms,
hallways, closets, bathrooms, & similar rooms__________________ 210.12B24
25
Back to Previous Page Table of Contents Abbreviations Code Changes
26
Back to Previous Page Table of Contents Abbreviations Code Changes
27
Back to Previous Page Table of Contents Abbreviations Code Changes
A GFCI receptacle can provide protection for other receptacles downstream on Locations Requiring GFCI Protection 17 NEC
the circuit. GFCI protection can be provided by GFCI breakers, blank face devic- See p.62 for GFCI req’s for pool equipment
es, or GFCI receptacles F24 n GFCIs req’d to be in readily accessible locations___________________ 210.8
n Distance measurements = shortest path w/out piercing
FIG. 24 GFCIs floor, wall, ceiling, fixed barrier, doorway, or window_______________ 210.828
GFCI protection is req’d for 15A & 20A receptacles in the following locations:
n Bathrooms ________________________________________________ 210.8A1
n Garages & accessory buildings (no exceptions)__________________ 210.8A2
n Outdoors EXC_____________________________________________ 210.8A3
• GFPE circuit dedicated to non-readily accessible receptacles
for snow-melting or deicing equipment_______________________ 210.8A3X
n Crawl spaces at or below grade level__________________________ 210.8A4
n Unfinished portions of basements or basement areas
not intended as habitable rooms EXC__________________________ 210.8A5
• Permanently installed fire or burglar alarm system (see p.14)_____ 210.8A5X
n Where serving kitchen countertop surfaces F25_________________ 210.8A6
n Within 6 ft. of all sinks______________________________________ 210.8A729
Receptacle Type Blank face Circuit breaker n Within 6 ft. of tub or shower stalls F43________________________ 210.8A930
n Laundry areas_____________________________________________210.8A1031
A GFCI will operate properly without an equipment ground. The receptacle should n Outlets supplying dishwashers________________________________ 210.8D32
be labeled “no equipment ground” & any downstream protected receptacles should n Hydromassage (whirlpool) tubs_________________________________680.71
also have that label as well as a label stating that they are GFCI protected. Labels Modern GFCIs have greater resistance to corrosion & surges. They are more
are not req’d for properly grounded GFCI-protected receptacles. reliable than earlier verions & do not have the problem of “nuisance tripping.” The
numerous exceptions that once existed for GFCIs have been removed from the
code. Installation instructions for GFCIs are now standardized for consistency
and they require checking GFCI operation after installation to ensure that devices
are properly wired. They should be tested on a regular basis thereafter.
28
Back to Previous Page Table of Contents Abbreviations Code Changes
29
Back to Previous Page Table of Contents Abbreviations Code Changes
Full height
cabinet
Foyer
6 ft. max
between wall
receptacles
AFF does not count
Bar-type counters are considered measured at as req’d receptacle
wall space and a receptacle is floor/wall line
Refrigerator can be req’d on the wall within 6 ft. of
2 ft. max
12 ft. max
not possible due to
Countertop
6 ft. Max
Peninsula
12 ft. max
4 ft. max 2 ft. max 2 ft. max 4 ft. max 12 ft. max 6 ft. max 6 ft. max
30
Back to Previous Page Table of Contents Abbreviations Code Changes
31
Back to Previous Page Table of Contents Abbreviations Code Changes
32
Back to Previous Page Table of Contents Abbreviations Code Changes
33
Back to Previous Page Table of Contents Abbreviations Code Changes
3 9/32 in.
8-32 mounting holes
Support & Rating
n Boxes must be supported______________________________________ 314.23
n PVC & EMT not OK for box support_________________________ 314.23E&F
n PVC & EMT OK for conduit body support_____________________ 314.23E&F 6-32 Octagonal box 8-32
Example of mounting mounting holes
n Wall luminaire boxes rated other than 50 lb. must be so marked_____ 314.27A1
overfilled holes
n Luminaires only in boxes designed for luminaires EXC_____________ 314.27A 18 cu. in. box,
• Wall sconces ≤ 6 lb. on device boxes F31 w/ 2 #6 screws__________314.27A1X see T10
Paddle fans req. 10-32 screws on L&L fan box.
34
Back to Previous Page Table of Contents Abbreviations Code Changes
35
Back to Previous Page Table of Contents Abbreviations Code Changes
Box Fill Factors T9,10 17 NEC TABLE 10 BOX FILL WORKSHEET NEC 314.16
n Count each conductor exiting box EXC________________________ 314.16B1
• EGCs from luminaires or up to 4 conductors < #14 Item Size # Total
from luminaires with domed canopies ________________________ 314.16B1X #14 conductors exiting box 2.00
n Unbroken conductors passing through box count #12 conductors exiting box 2.25
as only 1 conductor EXC_____________________________________314.16B1 #10 conductors exiting box 2.50
• Looped unbroken conductors > 12 in. count as 2_________________314.16B1
#8 conductors exiting box 3.00
n Do not count pigtailed conductors to devices__________________ 314.16B1
n Internal clamps count only 1, based on largest conductor in box___ 314.16B2 #6 conductors exiting box 5.00
n Support fittings (studs or hickeys) count as 1 conductor for Largest grounding conductor—count only one 1
each fitting type based on largest conductor in box______________ 314.16B3 Devices: 2× connected conductor size
n Count devices as 2 conductors based on connected wire size____ 314.16B4 Internal clamps—one based on largest wire present 1
n All EGCs count only as 1 based on largest____________________ 314.16B5
Fixture fittings—one for each type based on largest wire
TOTAL
FIG. 33
Max. plaster FIG. 34
gap 1/8 in.
Improper Box
Installation
Pancake
Boxes
Box set too
deep into wall
Opening cut 3 in. diameter
4 in. diameter
too large 4 cu. in. volume
6 cu. in. volume
Box A 6 cu. in. pancake box can be used at the end of a run of 14/2 NM cable
Max. setback 1/4 in. if extender if there is no internal clamp in the box. Otherwise, pancake boxes can only
noncombustible surface, (goof ring) be used with luminaires having a raised canopy with the volume that is
zero if combustible sufficient and is marked in the luminaire.
36
Back to Previous Page Table of Contents Abbreviations Code Changes
New high-
temp wire #14 conductors can be used on a
Old low- 20A circuit between the added box &
temp wire the luminaire box if the added box is
min. 12 in. from the luminaire box &
the wire is AC or MC or in a raceway
& min. 18 in. max. 6 ft.
Added box
37
Back to Previous Page Table of Contents Abbreviations Code Changes
38
Back to Previous Page Table of Contents Abbreviations Code Changes
SWITCHES FIG. 38
Switches (Equipment ground not shown for clarity)
Switches with electronic lighting controls such as occupancy sensors or vacancy
sensors are always active. A neutral is needed at the switch to complete the circuit Placing the switch in the location
for the sensor. Older switch legs with retrofitted electronic controls often use the shown on the left allows a “vacancy
equipment ground for the return current. Up to a 0.5mA load, this has been allowed 120V Switch sensor” switch to connect to the
by the UL standards, though beginning January 1, 2020 these older switches will neutral wire.
require retrofitting unless doing so would require removing finish materials.
General 17 NEC 2 wire+g NM
n Screws used for mounting switches must be 6-32 or Switch legs such as the one
to the right are not allowed
be installed AMI as part of listed assembly_____________________ 404.10B33 to be arranged this way in 120V
n All switching in ungrounded conductors F38___________________ 404.2A&B habitable rooms, bathrooms,
n Provide neutral in switch box controlling lighting in hallways, bathrooms, hallways, & stairways
stairways, & habitable rooms as defined in building code EXC_______ 404.2C Reidentified (taped or marked) white wire
Black wire is the return ungrounded “hot” wire to the luminaire
• In raceway with sufficient room to add neutral__________________ 404.2C1
• Where switch wiring not enclosed by building finishes___________ 404.2C2 3-Way & 4-way-
• Where lights controlled by central lighting control panel_________ 404.2C444 Switches:
• Switches controlling receptacles____________________________ 404.2C544 120V
n Electronic switches cannot introduce current on EGC____________ 404.2245
n Snap switches & dimmers req grounding EXC____________________ 404.9B
• Replacements where no grounding means present 2 wire+g NM 3 wire+g NM 2 wire+g NM
OK with plastic faceplate or GFCI protection___________________ 404.9BX
n Grounding OK by screws to grounded metal box________________ 404.9B1
n Metal faceplates must be grounded_____________________________ 404.9B 120V
n Faceplate must completely cover wall opening_____________________404.9A
n Switch at each entrance of stairs with ≥ 6 risers______________ 210.70A2(3) A 3-way switch connects a common conductor to one or the other “traveler”. All switch-
n Dimmers only for incandescent lights not receptacles_______________404.14E ing must be done in the ungrounded “hot” conductors. A 4-way switch is a double-pole
n Current-carrying conductors of circuit grouped F38_______________ 300.3B double-throw switch. Any number can be placed between the 2 3-way switches..
n OK to re-identify white wires as ungrounded w/ tape at ends F38___ 200.7C
n Reidentified white wires only OK for supply to switch,
not for return to luminaire F38_________________________________ 200.7C
n “CO/ALR” switch req’d if direct Al wire connection_______________ 404.14C
39
Back to Previous Page Table of Contents Abbreviations Code Changes
40
Back to Previous Page Table of Contents Abbreviations Code Changes
41
Back to Previous Page Table of Contents Abbreviations Code Changes
42
Back to Previous Page Table of Contents Abbreviations Code Changes
43
Back to Previous Page Table of Contents Abbreviations Code Changes
TABLE 12
AMBIENT TEMPERATURE CORRECTION1 TABLE 14 DWELLING UNIT SERVICE CONDUCTOR SIZEA,B,C
310.15B2a
Rating Cu Wire Al Wire Rating Cu Wire Al Wire
For Ambient Temp. > 30°C (86°F), Multiply the (Amps) Size (AWG) Size (AWG) (Amps) Size (AWG) Size (AWG)
Ambient Ampacity in T11 by the Following Percentages: Ambient
Temp. °C Temp. °F 100 4 2 200 2/0 4/0
60°C 75°C 90°C 125 2 1/0 225 3/0 250 kcmil
31–35 0.91 0.94 0.96 87–95 150 1 2/0 400 400 kcmil 600 kcmil
36–40 0.82 0.88 0.91 96–104 A. Based on 83% of ampacity in T11 per 310.15B7 3
B. 2014 NEC restricted to 120/240V systems, 2017 NEC also allows 120/208V.55
41–45 0.71 0.82 0.87 105–113 C. This table is allowed for service conductors or main power feeders that carry the entire
load of the service to an individual dwelling using conductors rated ≥ 75°C.
46–50 0.58 0.75 0.82 114–122
51–55 0.41 0.67 0.76 123–131 TABLE 15 BRANCH CIRCUIT & FEEDER SIZES (SIMPLIFIED)A
56–60 — 0.58 0.71 132–140 Fuse or Wire Size (AWG) Fuse or Wire Size (AWG)
61–65 — 0.47 0.65 141–149 Breaker Cu Al Breaker Cu Al
66–70 — 0.33 0.58 150–158 15 14 12 100 2 1/0
1. This table is important in remodels with older (pre-1984) 60°C wire, especially with hot attic spaces. 20 12 10 110 2 1/0
DERATING FOR CONDUCTOR BUNDLING 30 10 8 125 1 1/0
TABLE 13
310.15B3a 40 8 6 150 1/0 2/0
Number of Current-Carrying Wires Ampacity Correction 50 6 6 175 2/0 3/0
4–6 0.80
60 6 4 200 3/0 4/0
7–9 0.70
70 4 4 225 4/0 250 kcmil
10–20 0.50
90 3 1 400 500 kcmil (2)250
Modern 90°C small conductors that do not req an ambient temperature correction can have as many as 9
current-carrying conductors and still be within the sizes in the simplified table T15. A. Based on T11 before application of derating or temperature correction
44
Back to Previous Page Table of Contents Abbreviations Code Changes
45
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 46
Licensed exlusively to TonyFIG.47
Escamilla Cable
- unauthorized
Protectionduplication prohibited
In Attics F50 17 NEC
UF Cable NM Cable n Provide guard strips for cables on face of floors, joists,
rafters, or studs within 6 ft. of attic scuttle_______________________ 320.23A
n If attic has permanent stair or ladder, protect
cables to height of 7 ft. in entire attic___________________________ 320.23A
NM is only suitable for dry n Running boards or guard strips not req’d for cables on sides
locations; UF is suitable for of framing members if set back 11⁄4 in. from face_________________ 320.23B
dry, damp, or wet locations.
n Cables min 11⁄2 in. below sheet steel roof decks___________________300.4E
FIG. 48 The code citations above are for AC cable. For NM the citation is 334.23, for MC
Underfloor Cable in Basement or Crawl Space 330.23, for UF 340.10(4), and for SE 338.10B4.
46
Back to Previous Page Table of Contents Abbreviations Code Changes
SE—Service-Entrance Cable - Type SE F51 17 NEC UF—Underground Feeder Cable F46 17 NEC
n OK as service entrance conductor (see p.6)____________________ 338.10A n May be installed as NM & also in wet locations or buried T1, F52_____340.10
n Interior installations follow same rules as NM__________________ 338.10B4a n Protection where emerging from grade use RMC, IMC,
n Not OK underground, including inside raceways EXC_____________ 338.12A RTRC-XW, PVC-80 conduit, or equivalent F52__________________ 300.5D4
• Temporary power during construction (see p.10)______________ 590.4B&C8 n Bushing or gland req’d between underground
n Uninsulated conductor only for EGC EXC_____________________ 338.10B2 cables & their protective conduit F52___________________________ 300.5H
• Existing feeder to qualifying separate building (see p.8)________ 338.10B2X n Protective conduit must extend from req’d depth (max 18 in.) & 8 ft.
• Existing clothes dryer circuit originating from service panel_____ 338.10B2X above grade or to conductor termination, whichever is less F52____ 300.5D1
n Min bend radius 5× cable diameter______________________________338.24 n Must be marked as sunlight resistant if exposed outdoors ___________340.12
n Not OK strung through air without support messenger_______________ 340.12
FIG. 51 n Min bend radius 5× cable diameter_______________________________ 340.12
SE Cable
SE cable Style R is used for feeders
& for appliances such as ranges & FIG. 52
dryers.
Protecting Underground Cable
47
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 53
MC—Metal-Clad Cable F53 17 NEC MC Cable
n Dry locations only EXC______________________________________ 330.10A
• Where supplied w/ corrosion-resistant jacket___________________ 330.10A
n Not OK where subject to physical damage________________________330.12
n Secure & support at max 6 ft. intervals_______________________330.30B&C
• Holes in studs OK as support for horizontal runs________________ 330.30C
n Secure within 12 in. of box or other termination EXC______________ 330.30B
• Where fished_____________________________________________ 330.30D MC cable contains an insulated EGC. The metal
sheath of AC cable, supplemented by an aluminum
• Whip ≤ 6 ft. to luminaire in accessible ceiling to luminaire________ 330.30D bonding conductor in contact with the sheath, is
• ≤ 3 ft. from end where flexibility needed (motors)________________ 330.30D the EGC. The bonding conductor is not brought
n Min bend radius 7× cable diameter of corrugated armor___________ 330.24B into the box. AC fittings req a “redhead” bushing.
FIG. 54
In addition to traditional MC & AC cable, hybrid cables are available that have both an insu-
lated EGC and a bond strip in contact with the cable armor. AC Cable
48
Back to Previous Page Table of Contents Abbreviations Code Changes
49
Back to Previous Page Table of Contents Abbreviations Code Changes
50
Back to Previous Page Table of Contents Abbreviations Code Changes
FIG. 56
EMT—Electrical Metallic Tubing PVC — Rigid Polyvinyl Chloride Conduit F58 17 NEC
n Cover above buried conduits per T1_____________________________300.5A
Raintight wet n Support per T17 with fastening method that allows
Dry location
location movement from thermal expansion & contraction___________________352.30
n Horizontal runs supported by holes in framing OK if securely
Older “raintight” fittings did not meet modern listing standards. fastened within 3 ft. of box, conduit body, or cabinet______________ 352.30B
Listed raintight connectors have identifying features to indicate they
n Bushings or adapters req’d to prevent wire abrasion_______________ 352.46
are not the older type. Some have bronze collars to indicate they
contain the required gland inside the fittings. n Smoothly insulating bushings req’d for conductors ≥ #4 ___________ 300.4G
n Expansion fittings req’d if subject to ≥ 1/4 in. movement T20___________ 352.44
FIG. 57
n Not OK for support of luminaires or boxes______________________ 352.12B
RMC —Rigid Metal Conduit FIG. 58 n Not permitted in environments > 50°C (122°F)__________________ 352.12D
PVC 40 Conduit & Connector
51
Back to Previous Page Table of Contents Abbreviations Code Changes
52
Back to Previous Page Table of Contents Abbreviations Code Changes
53
Back to Previous Page Table of Contents Abbreviations Code Changes
DISTANCE AT WHICH PVC CONDUIT REQ’S 40% AREA FOR RACEWAY FILL
TABLE 20 TABLE 21
EXPANSION FITTINGS T352.44 (CHAPTER 9 TABLE 4)
Max Temp Distance Max Temp Distance Max Temp Distance Trade
Max Area for Conductors Based on T18 Conductor Sizes
Change OF A (ft.– in.) Change OF A (ft.– in.) Change OF A (ft.– in.) Size
40 15 – 5 80 7–9 120 5–2 EMT ENT FMC LFMC LFNCA IMC RMC PVC80 PVC40
50 12 – 4 90 6 – 10 130 4–9 ⁄
12 0.122 0.114 0.127 0.125 0.125 0.137 0.125 0.087 0.114
54
Back to Previous Page Table of Contents Abbreviations Code Changes
55
Back to Previous Page Table of Contents Abbreviations Code Changes
56
Back to Previous Page Table of Contents Abbreviations Code Changes
ALUMINUM WIRE
From 1964 to 1971, NM cable containing a utility-grade alloy (AA-1350) of alumi-
num wire was on the market, and millions of homes were wired with this product.
In 1972 it was replaced in the market by improved alloys (AA-8000 series). Special
precautions are needed for termination of aluminum wire, particularly in small con-
ductor sizes, and today aluminum is available only in sizes of #8 and larger.
Aluminum Wiring 17 NEC
n New Al wire req’d to be AA-8000 series alloy__________________ 310.106B
n Switches ≤ 20A directly connected to Al req L&L as “CO/ALR” ____ 404.14C
n Receptacles ≤ 20A directly connected to Al req L&L as “CO/ALR”___406.3C
n Splicing devices for dissimilar metals (AL & Cu) must be
identified for the purpose & installed per their listing________________ 110.14
n Anti-oxidant compounds req installation AMI______________________ 110.14
n Terminals (including on breakers) for Al req identification for same___110.14A
57
Back to Previous Page Table of Contents Abbreviations Code Changes
58
Back to Previous Page Table of Contents Abbreviations Code Changes
Arrays & Utility-Interactive Inverters 17 NEC Overcurrent Protection & Wiring 17 NEC
n DC > 80V req’s arc-fault protection_____________________________ 690.11 n Source circuit currents = 125% × sum of parallel module SCC_______ 690.8A1
n DC arrays req list PV ground-fault detection_____________________ 690.41B n Size conductors for 125% max source circuit SCC______________ 690.8B1
n Interactive systems to automatically disconnect in grid outage EXC__ 705.40 n Exposed single conductor cable in outdoor source
• OK to feed subpanel isolated from service by transfer switch________705.40 circuits req’d to be either type USE or L&L PV wire______________ 690.31C1
n Permanent plaque denoting location of each power source must n PV DC circuits inside a building req either metal raceways or MC cable
be installed at service equipment & other disconnect locations_______ 705.10 marked “WARNING: PHOTOVOLTAIC POWER SOURCE” F64__ 690.31G3
Grounding n Max allowable DC voltage in SFD 600V_________________________ 690.7C
n Mounting systems used for bonding modules req L&L for PV 690.43A n DC OCPD L&L for PV, ratings min 125% of max current ratings_____ 690.9B
n EGCs < #6 between modules req protective raceway______________ 690.46 n Single OCPD OK for series-connected string____________________ 690.9C
n Size EGCs of PV source & output circuit per T6 & min #14 _________690.45 n Sum of PV & main breakers OK up to 120% of panel rating if:______ 705.12B2
n EGC must be in same raceway or cable as circuit conductors_____ 690.43C • PV breaker located at opposite end of bus from main or feeder input
n Ground & roof-mounted arrays permitted to have auxiliary GES____ 690.47B66 • Warning label against moving PV breaker applied to panel F64
n PV circuits may not be shared in raceways with non-PV systems____690.31B
Disconnects
n PV system req’s readily accessible disconnecting means____________690.13
n Disconnecting means for system connected to supply side of
service must be L&L as suitable for use as service equipment______ 690.13C
n Isolating devices req’d for components (modules, converters, etc.)
may be L&L connectors rated to open under load_________ 690.15 & 690.33
59
Back to Previous Page Table of Contents Abbreviations Code Changes
Required
Rap-
id-Shut-
down
Labels &
Wording
Min. 3/16 in.
lettering black
on white
background
60
Back to Previous Page Table of Contents Abbreviations Code Changes
61
Back to Previous Page Table of Contents Abbreviations Code Changes
62
Back to Previous Page Table of Contents Abbreviations Code Changes
FOUNTAINS
General 17 NEC
n GFCI protection req’d for pumps, luminaires, other submersibles___ 680.51A
n GFCI protection req’d for all cord-&-plug connected equipment____ 680.56A
n Submerged boxes bonded, potted, secured & corrosion-resistant___ 680.52B
HOT TUB/SPA
Outdoor hot tubs and spas follow the same rules as swimming pools in addition
to the general rules below. A hydromassage tub (p.42) is not a spa because it is For further information about the entire line of Code Check Books, articles by the
emptied after each use. Code Check team, how you can obtain the Code Check Illustrations, fun stuff and
General 17 NEC more, visit: www.codecheck.com
n LFMC or LFNMC OK for package unit________________________ 680.42A1
Why Do We Feaure Ben?
n Bands to secure hot tub staves exempt from bonding_____________ 680.42B
n Bonding not req’d for L&L package unit installed AMI & Benjamin Franklin was chosen
min 28 in. above all perimeter surfaces ≤ 30 in. from unit_________ 680.42B70 as the main character in our Code
n Outlets supplying self-contained packaged spa/hot tub or Check illustrations for a number
field-assembled spa/hot tub req’s GFCI (including 240V) EXC_______680.44 of reasons. The “First American’s”
• Outlets supplying listed units with integral GFCIs_______________ 680.44A insatiable curiosity, scientific ge-
n Cord for package unit up to 15 ft. OK where GFCI-protected_______680.42A2 nius, and civic-mindedness drove
him to promote fire safety, safe ex-
Indoor Spas iting, public sanitation, improved
n Listed indoor packaged units ≤ 20A OK for cord & plug___________ 680.43X heating methods to reduce air pol-
n Min 1 receptacle min 6 ft. max 10 ft. from inside wall of spa_______ 680.43A1 lution, and of course, electricity.
n Wall switches min 5 ft. from inside wall of spa___________________ 680.43C Franklin contributed to each of the
After proving lighting and electricity are the same four main disciplines of building in-
thing, Ben invented the lightning rod, which he
believed was his most important invention.
spection: Building, Plumbing, Me-
chanical, and Electrical.
To find out more, visit:
www.codecheck.com/why-do-we-feature-ben
63
Back to Previous Page Table of Contents Abbreviations Code Changes
Other temp receptacles req GFCI, special purpose GFCI (UL 26 26 14 Exemption from AFCI upgrade if length of wire < 6 ft.
12 10 17
943C class C or D) or assured EGC program. Replacement receptacles in 2-wire systems w/ no EGC or
13 16 17 Connection of metal frame to Ufer can be hold-down bolts. practical means to add one can be non-AFCI if AFCIs not
27 26 17
available for panel, replacement is GFCI, no new wire, &
Recognition that Ufer can be extended above foundation for dual-function AFCI/GFCI receptacles not available.
14 &
14 16 connection point; 2017 also req’s location of connection to
17
have protection against corrosion.
64
Back to Previous Page Table of Contents Abbreviations Code Changes
65
Back to Previous Page Table of Contents Abbreviations Code Changes
66