2B+G+1+3TYP.

MIXED USE - FIRE PUMP ROOM


Fire Hose System Reports

for

VICTOR NAZEEM R AGHA

Doha , Qatar

Prepared By:

AL-NAJM

01/3/2024
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 2

General Project Data Report

General Data
Project Title: 2B+G+1+3TYP.MIXED USE - Fire 2B+G+1+3TYP.MIXED USE
Project File Name:
Pump Room BUILDING-..fiw
Designed By: Date: 01/3/2024
Code Reference: Approving Agency:
Client Name: VICTOR NAZEEM R AGHA Phone:
Address: Doha , Qatar City, State Zip Code:
Company Name: AL-NAJM Representative:
Company Address: City And State:
Phone:
Building Name: 2B+G+1+3TYP.MIXED USE Building Owner: VICTOR NAZEEM R AGHA
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:

Project Data
Description Of Hazard: Ordinary 1 Hose System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm

Hose Specifications
Make: Model:
Size: 1 Temperature Rating: 140 F

Water Supply Test Data


Source Of Information:
Test Hydrant ID: Date Of Test:

Hydrant Elevation: 0 ft Static Pressure: 0.00 psi


Test Flow Rate: 0.00 gpm Test Residual Pressure: 65.00 psi
Calculated System Flow Rate: 80.01 gpm Calculated Inflow Residual Pressure: 62.15 psi

Calculation Project Data


Calculation Mode: Demand
HMD Minimum Residual Pressure: 51.02 psi Minimum Desired Flow Density: 0.15 gpm/ft²
Number Of Active Nodes: 19
Number Of Active Pipes: 18 Number Of Inactive Pipes: 0
Number Of Active Hoses: 2 Number Of Inactive Hoses: 0

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 3

Fire Hose Input Data

Node Input Data


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

Hose ---- 5.60 51.02 51.50 0.00


1
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 60.08 53.00 0.00


2
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.78 51.50 0.00


3
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.26 53.00 0.00


4
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.33 53.00 0.00


5
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.34 53.00 0.00


6
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.07 51.50 0.00


7
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.44 53.00 0.00


8
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.08 51.50 0.00


9
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.39 53.00 0.00


10
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 60.82 51.50 0.00


11
---- 0.000 0.0 ---- 0.0 0.00

Hose ---- 5.60 51.10 51.50 0.00


12
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 61.45 53.00 0.00


13
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.10 51.50 0.00


14
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.11 51.50 0.00


15
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.13 51.50 0.00


16
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.13 51.50 0.00


17
---- 0.000 0.0 ---- 0.0 0.00

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 4

Fire Hose Input Data

Node Input Data (cont'd)


Hose KFactor Pressure Node Elev (ft) Fixed Flow
Area Group
Node Node Description (K) Estimate (psi) Branch Non- (gpm)
Branch Dia.
No. Branch Description Branch Len. Branch Stnd Stnd Fittings Branch Sprk
(in)
(ft) Fittings (ft) KFactor (K)

No Discharge ---- N/A 62.14 51.50 0.00


18
---- 0.000 0.0 ---- 0.0 0.00

No Discharge ---- N/A 62.15 51.50 0.00


19
---- 0.000 0.0 ---- 0.0 0.00

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 5

Fire Hose Input Data

Pipe Input Data


Nominal Nominal Fitting Total CFactor
Beg. End. Type Fitting
Pipe Description Diameter Length Length Length (gpm/inch-
Node Node Group Data
(inch) (feet) (feet) (feet) psi)

1 2 SCHED 40 WET STEEL 1.000 0 EBGC 6.70 14.00 20.70 120

2 3 SCHED 40 WET STEEL 1.500 0 2E 10.00 8.00 18.00 120

3 4 SCHED 40 WET STEEL 2.500 0 E 12.00 6.00 18.00 120

4 5 SCHED 40 WET STEEL 4.000 0 3T 42.70 60.00 102.70 120

5 6 SCHED 40 WET STEEL 4.000 0 E 10.00 10.00 20.00 120

6 7 SCHED 40 WET STEEL 4.000 0 4E 84.50 40.00 124.50 120

7 8 SCHED 40 WET STEEL 6.000 0 2E 130.00 28.00 158.00 120

8 9 SCHED 40 WET STEEL 6.000 0 2T 24.50 60.00 84.50 120

9 10 SCHED 40 WET STEEL 4.000 0 2ET 24.00 40.00 64.00 120

10 11 SCHED 40 WET STEEL 1.500 0 2E 12.80 8.00 20.80 120

11 12 SCHED 40 WET STEEL 1.000 0 EBGC 6.70 14.00 20.70 120

8 13 SCHED 40 WET STEEL 8.000 0 2T 29.00 70.00 99.00 120

13 14 SCHED 40 WET STEEL 8.000 0 E 8.50 18.00 26.50 120

14 15 SCHED 40 WET STEEL 8.000 0 2E 48.90 36.00 84.90 120

15 16 SCHED 40 WET STEEL 8.000 0 4E 196.90 72.00 268.90 120

16 17 SCHED 40 WET STEEL 8.000 0 E 17.00 18.00 35.00 120

17 18 SCHED 40 WET STEEL 8.000 0 2E 29.00 36.00 65.00 120

3ETBG
18 19 SCHED 40 WET STEEL 8.000 0 30.40 150.00 180.40 120
C

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 6

Fire Hose Output Data

Overall Node Groupings Output Data


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)

1 2 0 -39.98 40.00 0.00 0.00 51.02

2 1 0 39.98 0.00 0.00 0.00 60.08 0.00839


2 3 0 -39.98

3 2 0 39.98 0.00 0.00 0.00 61.78 -0.00206


3 4 0 -39.98

4 3 0 39.98 0.00 0.00 0.00 61.26 -0.00066


4 5 0 -39.98

5 4 0 39.98 0.00 0.00 0.00 61.33 -0.00174


5 6 0 -39.98

6 5 0 39.98 0.00 0.00 0.00 61.34 0.00188


6 7 0 -39.98

7 6 0 39.98 0.00 0.00 0.00 62.07 -0.00186


7 8 0 -39.98

8 7 0 39.98 0.00 0.00 0.00 61.44 -0.00619


8 9 0 40.03
8 13 0 -80.01

9 8 0 -40.03 0.00 0.00 0.00 62.08 -0.00397


9 10 0 40.02

10 9 0 -40.02 0.00 0.00 0.00 61.39 -0.00603


10 11 0 40.02

11 10 0 -40.02 0.00 0.00 0.00 60.82 -0.00645


11 12 0 40.01

12 11 0 -40.01 40.03 0.00 0.00 51.10 0.02312

13 8 0 80.01 0.00 0.00 0.00 61.45 -0.00308


13 14 0 -80.02

14 13 0 80.02 0.00 0.00 0.00 62.10 0.00223


14 15 0 -80.01

15 14 0 80.01 0.00 0.00 0.00 62.11 0.00227


15 16 0 -80.01

16 15 0 80.01 0.00 0.00 0.00 62.13 -0.00448


16 17 0 -80.02

17 16 0 80.02 0.00 0.00 0.00 62.13 0.00111


17 18 0 -80.01

18 17 0 80.01 0.00 0.00 0.00 62.14 0.00202

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 7

Fire Hose Output Data

Overall Node Groupings Output Data (cont'd)


Pipe Segment Pipe Pipe Hose Flow Fixed Flow Beg. Node Imbalance
Beg. End. Type Flow Rate At Beg. Node Out (+) In (-) Residual Flow At Beg.
Node Node Group (gpm) (gpm) (gpm) (gpm) Pressure (psi) Node (gpm)
18 19 0 -80.01

19 18 0 80.01 0.00 0.00 -80.01 62.15

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 8

Fire Hose Output Data

Overall Pipe Output Data


Nom. Dia. q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual PF-(psi)
Elevation Inside Dia. Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure PE-(psi)
(feet) C-Value Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) PT-(psi)
(fps) Type-Grp (ft)

1 5.60 51.50 40.00 51.02 1.00 40.00 0.46903 6.70 9.709


2 0.00 53.00 0.00 60.08 1.049 39.98 EBGC 14.00 -0.650
SCHED 40 WET STEEL 120 14.84 0 20.70 9.059

2 0.00 53.00 0.00 60.08 1.50 0.00 0.05821 10.00 1.048


3 0.00 51.50 0.00 61.78 1.610 39.98 2E 8.00 0.650
SCHED 40 WET STEEL 120 6.30 0 18.00 1.697

3 0.00 51.50 0.00 61.78 2.50 0.00 0.00726 12.00 0.131


4 0.00 53.00 0.00 61.26 2.469 39.98 E 6.00 -0.650
SCHED 40 WET STEEL 120 2.68 0 18.00 -0.519

4 0.00 53.00 0.00 61.26 4.00 0.00 0.00067 42.70 0.069


5 0.00 53.00 0.00 61.33 4.026 39.98 3T 60.00 0.000
SCHED 40 WET STEEL 120 1.01 0 102.70 0.069

5 0.00 53.00 0.00 61.33 4.00 0.00 0.00067 10.00 0.013


6 0.00 53.00 0.00 61.34 4.026 39.98 E 10.00 0.000
SCHED 40 WET STEEL 120 1.01 0 20.00 0.013

6 0.00 53.00 0.00 61.34 4.00 0.00 0.00067 84.50 0.084


7 0.00 51.50 0.00 62.07 4.026 39.98 4E 40.00 0.650
SCHED 40 WET STEEL 120 1.01 0 124.50 0.733

7 0.00 51.50 0.00 62.07 6.00 0.00 0.00009 130.00 0.014


8 0.00 53.00 0.00 61.44 6.065 39.98 2E 28.00 -0.650
SCHED 40 WET STEEL 120 0.44 0 158.00 -0.635

8 0.00 53.00 0.00 61.44 6.00 0.00 0.00009 24.50 0.008


9 0.00 51.50 0.00 62.08 6.065 40.03 2T 60.00 -0.650
SCHED 40 WET STEEL 120 0.44 0 84.50 -0.642

9 0.00 51.50 0.00 62.08 4.00 0.00 0.00067 24.00 0.043


10 0.00 53.00 0.00 61.39 4.026 40.02 2ET 40.00 0.650
SCHED 40 WET STEEL 120 1.01 0 64.00 0.693

10 0.00 53.00 0.00 61.39 1.50 0.00 0.05831 12.80 1.213


11 0.00 51.50 0.00 60.82 1.610 40.02 2E 8.00 -0.650
SCHED 40 WET STEEL 120 6.31 0 20.80 0.563

11 0.00 51.50 0.00 60.82 1.00 40.03 0.46957 6.70 9.720


12 5.60 51.50 40.03 51.10 1.049 40.01 EBGC 14.00 0.000
SCHED 40 WET STEEL 120 14.85 0 20.70 9.720

8 0.00 53.00 0.00 61.44 8.00 0.00 0.00009 29.00 0.009


13 0.00 53.00 0.00 61.45 7.981 80.01 2T 70.00 0.000
SCHED 40 WET STEEL 120 0.51 0 99.00 0.009

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 9

Fire Hose Output Data

Overall Pipe Output Data (cont'd)


Nom. Dia. q (gpm) F. L./ft Pipe-Len.
Beg. Nodal Hose/Fix Residual PF-(psi)
Elevation Inside Dia. Q (gpm) (psi/ft) Fit-Len.
End. KFactor Discharge Pressure PE-(psi)
(feet) C-Value Velocity Fittings Tot-Len.
Node (K) (gpm) (psi) PT-(psi)
(fps) Type-Grp (ft)

13 0.00 53.00 0.00 61.45 8.00 0.00 0.00009 8.50 0.002


14 0.00 51.50 0.00 62.10 7.981 80.02 E 18.00 0.650
SCHED 40 WET STEEL 120 0.51 0 26.50 0.652

14 0.00 51.50 0.00 62.10 8.00 0.00 0.00009 48.90 0.007


15 0.00 51.50 0.00 62.11 7.981 80.01 2E 36.00 0.000
SCHED 40 WET STEEL 120 0.51 0 84.90 0.007

15 0.00 51.50 0.00 62.11 8.00 0.00 0.00009 196.90 0.023


16 0.00 51.50 0.00 62.13 7.981 80.01 4E 72.00 0.000
SCHED 40 WET STEEL 120 0.51 0 268.90 0.023

16 0.00 51.50 0.00 62.13 8.00 0.00 0.00009 17.00 0.003


17 0.00 51.50 0.00 62.13 7.981 80.02 E 18.00 0.000
SCHED 40 WET STEEL 120 0.51 0 35.00 0.003

17 0.00 51.50 0.00 62.13 8.00 0.00 0.00009 29.00 0.006


18 0.00 51.50 0.00 62.14 7.981 80.01 2E 36.00 0.000
SCHED 40 WET STEEL 120 0.51 0 65.00 0.006

18 0.00 51.50 0.00 62.14 8.00 0.00 0.00009 30.40 0.016


19 0.00 51.50 0.00 62.15 7.981 80.01 3ETBGC 150.00 0.000
SCHED 40 WET STEEL 120 0.51 0 180.40 0.016

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 10

Fire Hose Output Data

Overall Hose Output Data


Flowing Node Residual Flowing Hose
Area Group Hose Flowing Area
Hose Node Elevation Pressure Density Discharge
Code KFactor (K) (ft²)
No. (feet) (psi) (gpm/ft²) (gpm)

1 5.60 51.50 51.02 130.00 0.308 40.00


Sub Totals For Non-Group 130.00 0.308 40.00

12 5.60 51.50 51.10 130.00 0.308 40.03


Sub Totals For Non-Group 130.00 0.308 40.03

Totals For All Groups 260.00 0.308 80.03

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 11

Fire Hose Output Summary

Hydraulically Most Demanding Hose Node


HMD Hose Node Number: 1
HMD Actual Residual Pressure: 51.02 psi
HMD Actual GPM: 40.00 gpm

Hose Summary
Hose System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.053 gpm/ft²
Application Average Area Per Hose: 750.00 ft²
Hose Flow: 80.03 gpm
Average Hose Flow: 40.02 gpm

Flow Velocity And Imbalance Summary


Maximum Flow Velocity ( In Pipe 11 - 12 ) 14.85 ft/sec
Maximum Velocity Pressure ( In Pipe 11 - 12 ) 1.48 psi

Allowable Maximum Nodal Pressure Imbalance: 0.0100 psi


Actual Maximum Nodal Pressure Imbalance: 0.0083 psi
Actual Average Nodal Pressure Imbalance: 0.0074 psi
Actual Maximum Nodal Flow Imbalance: 0.0231 gpm
Actual Average Nodal Flow Imbalance: 0.0041 gpm

Overall Network Summary


Number Of Unique Pipe Sections: 18
Number Of Flowing Hoses: 2

Pipe System Water Volume: 1279.26 gal

Hose Flow: 80.03 gpm


Fixed Flow: 0.00 gpm

Minimum Required Residual Pressure At System Inflow


62.15 psi
Node:
Demand Flow At System Inflow Node: 80.01 gpm

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM


FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 12

Fire Hose Output Data

Hydraulic Supply/Demand Graph

100

90

80

70
Pressure psi

62
60

50

40

30

20

10

0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Flowrate(x100) gpm

Demand Curve Data


Calculated Residual Pressure: 62.15 psi
Calculated Flow Rate: 80.01 gpm
Pressure Required For First Sprinkler Downstream From Inflow Node To Flow: 0.00 psi

D:\Documents\Elite Software\Fire 6 Projects\2B+G+1+3TYP.fiw Sunday, July 28, 2024, 2:33 PM