Sample Hydraulic Calculation - FHR
Sample Hydraulic Calculation - FHR
for
Doha , Qatar
Prepared By:
AL-NAJM
01/3/2024
FIRE - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
hazem 2B+G+1+3TYP.MIXED USE - Fire Pump Room
heaven Page 2
General Data
Project Title: 2B+G+1+3TYP.MIXED USE - Fire 2B+G+1+3TYP.MIXED USE
Project File Name:
Pump Room BUILDING-..fiw
Designed By: Date: 01/3/2024
Code Reference: Approving Agency:
Client Name: VICTOR NAZEEM R AGHA Phone:
Address: Doha , Qatar City, State Zip Code:
Company Name: AL-NAJM Representative:
Company Address: City And State:
Phone:
Building Name: 2B+G+1+3TYP.MIXED USE Building Owner: VICTOR NAZEEM R AGHA
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:
Project Data
Description Of Hazard: Ordinary 1 Hose System Type: Wet
Design Area Of Water Application: 1500 ft² Maximum Area Per Hose: 130 ft²
Default Hose K-Factor: 5.60 K Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 gpm Outside Hose Stream Allowance: 0.00 gpm
In Rack Sprinkler Allowance: 0.00 gpm
Hose Specifications
Make: Model:
Size: 1 Temperature Rating: 140 F
3ETBG
18 19 SCHED 40 WET STEEL 8.000 0 30.40 150.00 180.40 120
C
Hose Summary
Hose System Type: Wet
Specified Area Of Application: 1500.00 ft²
Minimum Desired Density: 0.150 gpm/ft²
Application Average Density: 0.053 gpm/ft²
Application Average Area Per Hose: 750.00 ft²
Hose Flow: 80.03 gpm
Average Hose Flow: 40.02 gpm
100
90
80
70
Pressure psi
62
60
50
40
30
20
10
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Flowrate(x100) gpm