SDMFbased Interference Rejectionand PDInterpretationfor Simulated Defectsin HVCable Diagnostics SUBMITTED
SDMFbased Interference Rejectionand PDInterpretationfor Simulated Defectsin HVCable Diagnostics SUBMITTED
net/publication/314298289
CITATIONS READS
6 98
9 authors, including:
Some of the authors of this publication are also working on these related projects:
Scalable Non-invasive Radiometric Wireless Sensor Network for Partial Discharge Monitoring in the Future Smart Grid View project
Special Issue "UHF and RF Sensor Technology for Partial Discharge Detection" View project
All content following this page was uploaded by Alistair Reid on 21 February 2019.
ABSTRACT
Partial Discharge (PD) in cable systems causes deterioration and failure, identifying
the presence of PD is crucial to Asset Management. In this paper presents methods for
interference signals rejection and for PD interpretation for five types of artificial defect
in 11 kV ethylene-propylene rubber (EPR) cable. Firstly, the physical parameters of the
artificial defects used for PD signal generation are introduced. Thereafter, the sample
stress regime, PD testing and detection systems, including IEC 60270 measurement
system and High Frequency Current Transformer (HFCT), are outlined. Following on,
a novel Synchronous Detection and Multi-information Fusion (SDMF) based signal
identification method is developed, to separate PD and interference signals within raw
data. Finally, a comparative PD analysis of two detection systems is carried out and
several characteristics of insulation related PD signals of EPR cables are reported. The
SDMF based data pre-processing and the comparative PD activity analysis contribute
to improvement of PD pattern recognition and assist in on-line PD monitoring systems.
Index Terms — Partial Discharge, Cable System, Signal Identification, Interference
Rejection, Feature Extraction.
Earth strap
HFCT
Fig. 6. Experimental setup for EPR cable sample, showing an example
defect, earth strap and stress cone.
Type 5 0 0 10 10 10 10 10 0 0 50
EPR cable samples of length 1.5 m to 2 m, each containing
3 SDMF BASED INTERFERENCE REJECTION FOR window. If a pulse has the correct shape and this time
EXPERIMENTAL DATA dependency, then the pulse is considered to be a PD pulse.
3 6
3.1 NOISE AND INTERFERENCE FROM DEFECTS Interference signals
2 4
Example sets of data from defect types 1 to 5 as detected by
PD Magnitude (mV)
PD Magnitude (V)
1 2
the HFCT and IEC 60270 systems are shown in Fig. 7. Fig. 7(a) 0 0
to (e) shows signals from defect types 1 to 5 respectively. Data -1 -2
in green, with axis on the right hand side of the figure, are PD -2 -4
PD signals
signal detected by the IEC 60270 system. Data in red, with
-3 -6
axis on the left hand side of the figure, are from the HFCT. 0 2 4 6 8 10
(a)
12 14 16 18
Time (ms)
20
2 5
Three typical noise and interference signals were detected PD signals
PD Magnitude (mV)
PD Magnitude (V)
during the experiments: white noise, regular interference 0 0
signals and random interference signals.
White noise was detected during PD testing the five -2 -5
Regular interference signals
types of defect. The SNR of data gathered using the HFCT
is lower than that in signals gathered using the IEC testing -4 -10
0 2 4 6 8 10 12 14 16 18 20
system. IEC 60270 recommends setting the threshold value 2
(b) Time (ms)
10
for PD pulse detection at two times the level of white noise
PD Magnitude (mV)
PD Magnitude (V)
but, as shown in Fig. 7 (a), this is a challenge for PD
detection using HFCT. When PD signals have a similar 0 0
-20
In addition to the white noise detected in all data sets, other 0 2 4 6 8 10
(c)
12 14 16 18
Time (ms)
20
4 20
pulsative noise signals were detected. During testing of defect Time(ms)
3 15
types 2 and type 3 regular pulsative interference signals were
PD Magnitude (mV)
2 10
PD Magnitude (V)
detected, examples of strong regular pulses are indicated with 1 5
PD Magnitude (V)
50
detected by HFCT, it is therefore essential to correctly 0 0
extract PD signals from raw data with white noise, regular -50
3.2 SDMF BASED INTERFERENCE SIGNAL Fig. 7. Examples of (a) Type 1, (b) Type 2, (c) Type 3, (d) Type 4, (e)
Type 5 PD data.
REJECTION
Examples of transient PD pulses contained within the 2
4
signals captured and shown in Fig. 7 (b) are presented in Fig. 8.
Transient signals from HFCT and IEC 60270 systems are
PD Magnitude (mV)
1 2
PD Magnitude (V)
HFCT pulses, due to the different responses and cable transfer Time
window
Signal detected by HFCT
(channel 2 of the oscilloscope)
Signal detected by IEC 60270 system
(channel 3 of the oscilloscope)
times. If a fixed time window of 500 ns is placed around an
HFCT pulse then the IEC pulse is contained in the time Fig. 8. PD Transient pulses from HFCT (lower trace) and IEC 60270
(upper trace).
A novel Synchronous Detection and Multi-information interference signals identified by the method shown in Fig.
Fusion (SDMF) based signal identification method has been 9. Fig. 10 (a) shows the PRPD pattern in terms of maximum
developed for automatic PD and interference signal magnitude of transient pulses; Fig. 10 (b) shows the PRPD
identification from the raw data captured in the experiments pattern in terms of Equivalent Bandwidth [14] of transient
discussed above. A flowchart of SDMF based PD signal pulses; Fig. 10 (c) shows the PRPD pattern in terms of
identification process is shown in Fig. 9. skewness of transient pulses. The visualisation of PRPD of
different parameters proves the effectiveness of the SDMF
Synchronously detected PD raw based interference signals rejection.
Data from Channel 2 and Channel 3
Channel 2: Channel 3:
Low SNR Data from High SNR Data from IEC
HFCT 60270 system
Threshold
Selection
Threshold
Selection
Transient Pulses
(a) Time (ms)
Extraction
Location
PD From Yes Information of (b) Time (ms)
Channel 3 in 500ns PDs
time windows?
No
Interference PD Signals of
Signals of Channel 2
Channel 2
fully synchronised with the AC signal collected in Channel Fig. 10. Identified PD and interference signals of defect type one captured
1. The raw data from an HFCT and from an IEC detection by HFCT, (a) PRPD of maximum voltage, (b) PRPD of equivalent
system (channels 2 and 3 respectively) are logged and bandwidth, (c) PRPD of skewness.
processed in pairs. SDMF based PD identification of five defect types are
Data from the IEC 60270 system has a high SNR and carried out: results are shown in Fig.11. IEC system results
few interference signals. This data is processed first, are shown in Fig. 11 (a), HFCT are shown in Fig. 11 (b).
according to threshold selection, transient pulse extraction
and PRPD based PD signal validation. Using the PD signal
location information, e.g. 16.556ms, the information is
applied to PD signal identification for the HFCT data.
Data from the HFCT channel has a low SNR: data
extracted, both PD and interference signals, are fused with
the location information from the IEC channel. The data
fusion judgement is carried out based on the 500 ns window
discussed previously. If the signals do not show good
correlation the pulses are judged to be interference signals.
SDMF based PD and interference signals detected by
HFCT from defect type 1 are shown in Fig. 10.
Data in green are PD signals, data in black are
Value 1
10
15
8
6 Value 2 10
4 Value 3
Value 4 5
2
Value 5
(a) (f)
7
2.5
5
(a) Time (ms)
1.5 3
0.5 1
(b) (g)
7 20
PD Magnitude (mV)
PD Magnitude (V)
15
5
10
3
5
1
(c) (h)
(b) Time (ms) 150
20
PD of Defect Type 1 PD of Defect Type 2 PD of Defect Type 3
15 100
PD of Defect Type 4 PD of Defect Type 5
10
50
Fig. 11. PD signals from defect types 1 to 5, (a) PD signals from the IEC 5
60270 system, (b) PD signals from the HFCT. 0
(d) (i)
100 6
4 COMPARATIVE ANALYSIS OF PARTIAL 80
4
DISCHARGE DATA DETECTED BY HFCT AND 60
40 2
IEC 60270 SYSTEM 20
0 0
Based on the PD data extracted by SDMF methods, 5 6 7 8 9 10 11 12 13
(e)
5 6 7 8 9 10 11 12 13
(j)
statistical analysis is carried out to compare the PD activity Test Voltage (kV) Test Voltage (kV)
behaviour of the five types of defects. Maximum Value Median Value
4.1 VARIATION IN PD MAGNITUDE WITH APPLIED Fig. 12. Violin plot of PD magnitude from defects (a) Type 1 HFCT, (b)
Type 2 HFCT, (c) Type 3 HFCT, (d) Type 4 HFCT, (e) Type 5 HFCT: (f)
VOLTAGE Type 1 IEC, (g) Type 2 IEC, (h) Type 3 IEC, (i) Type 4 IEC, (j) Type 5
Violin plots are a convenient way of graphically depicting IEC.
groups of numerical data, they combine a boxplot and a
(doubled) kernel density plot [15]. For each violin plot, five key From Fig. 12 the following conclusions may be drawn:
data parameters are indicated, i.e. maximum, minimum and Firstly, as the magnitudes of HFCT PD signals are in mV
median values and first and third quartiles. Violin plots of and those of IEC PD signals are in V, the PD signal level from
maximum PD magnitude of transient pulses in terms of the IEC 60270 system is always much greater than that from
applied voltage are shown in Fig. 12. In Fig. 12 (a), value 1 is the HFCT sensor. It is, however, essential that research on
the maximum value; value 2 is the third quartile; value 3 is the signal processing and pattern recognition is based on
median value; value 4 is the first quartile and value 5 is the commercial HFCTs if effective PD on-line monitoring system
minimum value. Violin plots also shows the statistical kernel is to be carried out.
density of the samples, in terms of a double distribution curves. Secondly, as PD signals from the commercial HFCT are of
Fig. 12 (a) contains 7 violin plots, which represent the small magnitude, e.g. the median value of PD signals for
statistical results of PD magnitude of defect type 1 changing defect types 1, 2 and 3 is less than 5 mV (Fig. 12(a) – (c)), it is
with the applied voltage, from 5 kV to 11 kV. a challenge to extract PD signals in data from noisy industrial
Fig. 12 (a) to (e) show violin plots of PD magnitude for five environments, as the white noise of most industrial detection
artificial defect types using statistical analysis of the HFCT systems is more than 5mV.
data. Fig. 12 (f) to (j) are the PD magnitude violin plots of the Thirdly, although the median PD magnitudes increase with
statistical analysis of the IEC data for the same faults. increasing voltage for most faults, for type 2 the median PD
magnitude decreases with voltages over 9 kV (Fig. 12(b) and
Fig. 12(g)).
4.2 VARIATION IN PD PULSE NUMBER WITH A rapid decrease of PD magnitude (Fig. 12 (b)) and a rapid
APPLIED VOLTAGE increase of pulse numbers (Fig. 13 (b)) might be an effective
Violin plots of PD numbers in 20 ms with applied voltage identifier of serous insulation degradation, which should be
are shown in Fig. 12. As the number of PD pulses detected by cautioned during on-line PD monitoring of EPR cables.
HFCT and IEC 60270 systems is the same only one set of
figures is presented.
For defect types 1, 3 and 4 the number of PD pulses in each
set of data is low: in some cases there is only one PD pulse in
20 ms. For types 1 and 3 the variation in PD numbers with
increasing voltage is inconsistent: for type 4 the number shows
an increasing number of PD with increasing voltage. For these
defects the trends for the PD number show strong similarity to
the PD magnitude trends, Fig. 12.
(a)
For defect type 2, there is a rapid increase in PD number
when the voltage is increased to 11 kV and above. If compared
with Fig. 12 (b), there is a rapid decrease in the median value
of the PD magnitude at 11kV and above.
For defect type 5, there is a rapid increase in PD number as
the voltage is increased throughout the test. This trend is
similarly shown in PD magnitude, Fig. 12 (e) and (j).
5 6
(b)
4 5
Fig. 14. Flashover of defect type 2 Damage to (a) EPR cable, (b) needle.
4
3
3
2 2 4.4 VARIATION IN PD CHARACTERISTICS WITH
1 1 SIZE OF VOID DEFECT
(a) (d)
To investigate the variation of PD characteristics when the
PD Pulse Number in 20 ms
20
15 size of a void in a cable increases, e.g. with insulation
15
10
degradation, the diameter of a void, shown as a defect type 1 in
10
Fig. 2, is changed from 1 mm to 3 mm in steps of 0.5 mm. The
5 5 depth of the voids is maintained at 2 mm, as defined in the
(b) 5 6 7 8 9 10 11 12 13
characteristics of the defects shown in Table 2. The test voltage
4 (e) for each defect type was varied, in 1 kV steps, up to the rated
Test Voltage (kV) voltage of the cable, 11kV. The values of voltages for which
3
Maximum Value results are reported are listed in Table 2.
2
Median Value Table 2. Characteristics of defect types 6 to 10 and test voltages
1
Diameter of Depth of
5 6 7 8 9 10 11 12 13 Defect Type Testing voltage
void (mm) void (mm)
(c)
Test Voltage (kV) Type 6 1 2 8kV, 9kV, 10 kV, 11kV
Fig. 13. Violin plot of PD Number in 20 ms for defects (a) Type 1, (b) Type 7 1.5 2 10 kV, 11kV
Type 2, (c) Type 3, (d) Type 4, (e) Type 5.
Type 8 2 2 8kV, 9kV, 10 kV, 11kV
0.006 400
pulse in 20 ms (Fig. 13 (a) (c) (d)).
0.004 300
• From analysis of PD characteristics prior to the
200
0.002
100
flashover incident, indicator of serious insulation
0 0
degradation of EPR cables might be the rapid
1 1.5 2 2.5 3 1 1.5 2 2.5 3 decrease of PD magnitude (Fig. 12 (b)) and the rapid
(a)
Maximum Value
Diameter of
void (mm)
(b) Diameter of
void (mm)
increase of PD pulse numbers (Fig. 13 (b)).
Median Value
• Analysis of PD characteristics when the size of a
Fig. 15. Violin plot of PD magnitude for a range of void diameters: (a)
HFCT, (b) IEC 60270. void is increased, to simulate insulation degradation,
shows that PD magnitude increases with size of void
but the relationship between PD magnitude and size of
From the analysis in sections 4.1, 4.2 and 4.4 of the paper void is not linear, and there is no change in the number
conclusions may be drawn, i.e. for PD based condition of PD pulses when the size of void is increased.
monitoring of a cable system, the symptoms of serious Based on the work carried out in this paper, 5672 sets of
insulation degradation might be: PD signals and 9687 sets of interference signals detected by
Rapid increase of PD magnitude (Fig. 15) due to changing HFCT have been automatously extracted from raw data.
dimension of the void; 2000 sets of PD signals with known defect type and 2000
Rapid decrease of PD magnitude (Fig. 12 (b)) due to interference signal have been randomly selected for further
changing local stress with defect type; pattern recognition investigation. The results of the study
will be published in a future paper.
Rapid increase in PD number (Fig. 13 (b)) due to variation
in local stress.
ACKNOWLEDGEMENT
5 DISCUSSION AND CONCLUSIONS The authors would like to thank National Natural Science
Foundation of China for funding the research under grants
This paper has presented information gathered from 51541705. The authors also would like to thank EPSRC
experimental work on 5 defects introduced to 11kV single- (UK) for funding the research, under grants EP/G028397/1
phase EPR cable. The defects replicate faults which are and EP/G029210/1.
found in in-service cables. The range of electrical stress
parameters applied to the cable faults is provided. A method
REFERENCES
of comparing IEC and HFCT data (Synchronous Detection
[1] A. J. Hunter, P. L. Lewin, L. Hao, C. Walton, M. Michel,
and Multi-information Fusion) allows signal interpretation
“Autonomous classification of PD sources within three-phase 11 kV
and pre-processing of PD data from the defects. Based on PILC cables”, IEEE Transactions on Dielectrics and Electrical
the comparative analysis of data collected from an IEC Insulation, Vol. 20, No. 6, pp. 2117-2124, 2013.
62070 system and a commercially available HFCT, [2] X. Peng, C. Zhou, D. M. Hepburn, M. D. Judd, W. H. Siew,
“Application of K-Means Method to Pattern Recognition in On-line
characteristics of PD signals are reported. Cable Partial Discharge Monitoring”, IEEE Transactions on
Conclusions are summarized as follows: Dielectrics and Electrical Insulation, Vol. 20, No. 3,pp. 754-761,
2013.
• The proposed SDMF based PD signal identification [3] L. Hao , P. L. Lewin, “Partial Discharge Source Discrimination
is effective for automatous PD and interference using a Support Vector Machine”, IEEE Transactions on Dielectrics
signal identification and to processing of large and Electrical Insulation, Vol. 17, No.1, pp. 189 -197. 2010.
volumes of experimental PD data if two kinds of [4] A. Rizzi,F. M. F. Mascioli,F. Baldini, C. Mazzetti, R. Bartnikas,
defection system are fully synchronised. “Genetic Optimization of a PD Diagnostic System for Cable
Accessories”, IEEE Transactions on Power Delivery, Vol. 24, No.3,
• PD from EPR cable detected by a commercial HFCT pp. 1728 -1738, 2009.
sensor was of relatively low magnitude, i.e. median [5] H. Ma, J. C. Chan, T. K. Saha, C. Ekanayake, “Pattern Recognition
value of PD magnitude from defect types 1 to 3 was Techniques and Their Applications for Automatic Classification of
Artificial Partial Discharge Sources”, IEEE Transactions on
below 5 mV (Fig. 12 (a) – (c)).
Dielectrics and Electrical Insulation, Vol. 20, No. 2, pp. 468-478,
• The magnitude of PD signals from an IEC 60270 2013.
system was observed to be several hundred times [6] A. J. Mcgrail, E. Gulski, E. R. S. Groot, D. Allan, D. Birtwhistle, T.
greater than those from a commercial HFCT sensor R. Blackburn, “Data Mining Techniques to Assess the Condition of
High Voltage Electrical Plant”, CIGRE Working Group 15.11, 2002.
(Fig. 12). As IEC systems are challenging to install [7] C. Zhou, M. Michel, D. M. Hepburn, G. Zhang, “Rough Set Theory
in practical situations, alternative methods of signal for Data Mining in an On-line Cable Condition Monitoring System”,
processing must be developed and deployed in order CIRED 2007, Vienna, Austria.
to make full use of HFCT technology. [8] J. Tang, F. Liu, X. Zhang, X. Liang, Q. Fan, “Partial discharge
recognition based on SF6 decomposition products and support vector
• Statistical analysis shows that for insulation related machine”, IET Science Measurement & Technology, Vol.6, No.4,
PD, pulse number in a 20 ms period is low. Despite pp. 198-2041, 2012.
insulation breakdown, PD pulse number in defect
[9] L. Li, J. Tang, Y. Liu, “Partial Discharge Recognition in Gas Alistair J. Reid (M’11-SM’15) graduated from
Insulated Switchgear Based on Multi-information Fusion”, IEEE the University of Strathclyde, UK, in 2004 with a
Transactions on Dielectrics and Electrical Insulation, Vol. 22, No. 2, B.Eng. (Hons) degree in Electrical and
pp. 1080-1087, 2015. Mechanical Engineering and received the Ph.D.
[10] S. M. Gargari, P.A.A.F Wouters, P. van der Wielen, E. F. Steennis, degree in 2007 for research on partial discharge
“Partial discharge parameters to evaluate the insulation condition of monitoring. Subsequently, he has worked as a
on-line located defects in medium voltage cable networks”, IEEE Post-Docroral Research at the University of
Transactions on Dielectrics and Electrical Insulation, Vol. 18, No. 3, Strathclyde, a Research Fellow at Glasgow
pp. 868-877, 2011. Caledonian University and a Visiting Research
[11] IEC International Standard 60270, “High Voltage Test Techniques - Associate at California Institute of Technology.
Partial Discharge Measurements”, International Electrotechnical He is presently a Lecturer in the School of Engineering and Built
Commission (IEC), Geneva, Switzerland, 3rd edition, 2000. Environment at Glasgow Caledonian University. His research interests
[12] A. J. Reid, X. Peng, X. Hu, M. D. Judd, W. H. Siew, C. Zhou, D. M. include diagnostic monitoring techniques and systems, partial discharge,
Hepburn, “Comparison Of Partial Discharge Characteristics From sensor design, embedded systems and energy harvesting. Alistair is a
Insulation Defects In 11kV EPR Cable”, Proc. 17th International Senior Member of the IEEE and a committee member of the Universities
Symposium on High Voltage Engineering, Hannover, Germany, High Voltage Network (UHVnet) in the UK.
2011.
[13] C. Zhou, M. Michel, D.M. Hepburn, X. Song, “On-line partial Martin D. Judd (M’02-SM’04) is the Technical
discharge monitoring in medium voltage underground cables”, IET Director of High Frequency Diagnostics Ltd. He
Science Measurement and Technology, Vol.3, Iss.5, pp. 354–363, graduated from the University of Hull in 1985
2009. with a first class (Hons) degree in Electronic
[14] G. C. Montanari, A. Cavallini, “A New Approach to Partial Engineering, after which he gained 8 years of
Discharge Testing of HV Cable Systems”, IEEE Electrical Insulation industrial experience, first with Marconi
Magazine, Vol. 22, No. 1, pp. 14-23, 2006. Electronic Devices and then with EEV Ltd.
[15] M. Correll, M. Gleicher, “Error Bars Considered Harmful Exploring Martin received his PhD from the University of
Alternate Encodings for Mean and Error”, IEEE Transactions on Strathclyde in 1996 for research into the
Visualization and Computer Graphics, Vol. 20, No. 12, pp. 2142- excitation of UHF signals by partial discharges in
2151, 2014. gas insulated switchgear. He has worked
extensively on UHF partial discharge location techniques for power
Xiaosheng Peng (M’11) received the B.Sc. and transformers and was latterly Professor of High Voltage Technologies at
M.Sc. degrees from Huazhong University of the University of Strathclyde, where he managed the High Voltage
Science and Technology, China in 2006 and 2009, Research Laboratory. In 2014 he founded High Frequency Diagnostics, a
respectively, and the Ph.D. in electrical engineering contracting and consultancy business that works in partnership with
at Glasgow Caledonian University in 2012 funded companies and universities to maximize the impact of R&D outputs by
by EPSRC. He has worked as a Post-Doctoral utilizing them in new technologies and applications.
Researcher in Glasgow Caledonian University
funded by EDF Energy. He is currently a lecturer in W. H. Siew (M’95) is a Reader in the Department
School of Electrical and Electronic Engineering of of Electronic & Electrical Engineering, University
Huazhong University of Science and Technology. of Strathclyde, Glasgow, Scotland. He is a triple
His research interests are partial discharge signal processing and condition alumnus of the University of Strathclyde with
monitoring of power plant. He is a member of IET. degrees of B.Sc. (Hons) in electronic & electrical
engineering; Ph.D. in electronic & electrical
Chengke Zhou (M’06) received the B.Sc. and engineering; and Master of Business
M.Sc. degrees in electrical engineering from Administration. His areas of research interest
Huazhong University of Science and Technology, include large systems electromagnetic
China in 1983 and 1986, respectively, and the Ph.D. compatibility; cable diagnostics; lightning
degree from the University of Manchester U.K., in protection; and wireless sensing systems. He is Convener of the CIGRE
1994. Since then, he worked in Glasgow WG C4.208 and a member of the Technical Advisory Panel for the IET
Caledonian University, U.K., as a Lecturer, Senior Professional Network on Electromagnetics. He is also a member of IEEE
Lecturer and in Heriot-Watt University as a Reader TC7. He is a Chartered Engineer and an MIEE.
until 2007 when he went back to Glasgow
Caledonian University as a Professor. He has
published more than 100 papers in the area of partial discharge based
condition monitoring of MV/HV plant and power system analysis. He is
member of IET.