Project Checklist-Csa Work
Project Checklist-Csa Work
I
P.C.C PLANT SIRPUR REV 0
Document Title : CSA CHKLIST DATE 16/10/2024
Document No. : TTH/SMI/CSA-CHK PROJ P.C.C PLANT
INTRODUCTION
It is difficult during a visit to a construction site to memorise all of the details that need to be
checked and while the obvious ones stand out, many other items that should be checked are
forgotten. Supervisors may get distracted or over extended due to time constraints and
overlook items that may have more serious consequences later in the project.
These Check Lists provide a guide to the inspections that are required on site for a particular
project. They can be referred back to the specification if the full text of the particular item is
required. The Check Lists will remind you of some potential problems in materials,
workmanship, and coordination between trades.
Project specific checks may be added to the Check Lists for individual projects and the
experience of Supervisors can be shared by the addition of particular checks on items or
operations that are generally of concern on site.
Provide one copy of the Check Lists book to the Supervisor and one copy to the Contractor
for the particular project.
HOW TO USE THESE CHECK LISTS
Take photocopies of the relevant Check List sections before going on site and study these.
Mark any items in the Check List that are of particular concern.
At the project site, check off the work against the Check Lists and make notes of any action
required in the space provided.
When the work is completed and the final check has been made sign off and date in the box
provided. There is also space to provide comments.
Keep a record of all of the completed Check Lists for future reference if required. These could
prove to be valuable if disputes arise on the project.
There is no better way to document actual site conditions or details than by photographs, so
don’t forget to take a camera on site and take images to go with particular items in the Check
Lists.
PROJECT CHECKLISTS
MAJOR CSA WORKS
CONTENTS
SECTION
01 General Requirements
02 Demolition
03 Groundworks
04 Termite Control
05 Concrete
06 Structural Steel
07 Light Steel Framing
08 Masonry
09 Woodwork
10 Roofing
11 Cladding
12 Windows
13 Glazing
14 Doors
15 Hardware
16 Suspended Ceilings
17 Partitions
18 Lining
19 Rendering and Plastering
20 Metalwork
21 Fixed Furniture and Joinery
22 Tiling
23 Resilient Finishes
24 Carpets
25 Painting
26 Miscellaneous Fixtures
27 Stormwater
28 Sanitary Services
28 Water
29 General Electrical Requirements
30 Wiring and Accessories
37 Uninterruptible Power Supply (UPS)
38 Switchboards
39 Luminaires
40 Communications
41 Master Antenna TV
42 Fire Detection
43 Lightning and Surge Protection
44 Electronic Security and Access Control
INSPECTION
Notice given before covering up works
SAMPLES
Received and approved
TESTING
NATA endorsed testing authority
CONTRACTORS SUBMISSIONS
Amended drawings proposed procedure received
CEMP received
PCP received
ITPs received
SAFETY
Work Health and Safety Management Plan received
Safety equipment, clothing, devices and first aid kits available on site
PROJECT NOTICE BOARDS - SUPPLY, ERECT AND MAINTAIN PROJECT NOTICE BOARDS
Project notice board installed if required
Final Check
Made by: Date:
Comments
DEMOLITION
Temporary supports provided as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
TREES TO BE RETAINED
Trees marked as specified
EXISTING SURFACES
locations of existing underground services marked
ENVIRONMENTAL PROTECTION
Erosion control plan in place
SITE CLEARING
Site clearing limited to required area
EXCAVATION
Correct levels
Supports as specified
GRADING
External areas graded to fall away from buildings
Subfloor area ground surface graded to fall away from buildings
without ponding
SURFACE PREPARATION
Ground surface prepared before placing fill material
Benching as specified
FILL
Correct type used
PLACING FILL
Layers and density as specified
REQUIRED DENSITY
Required density is as specified
PROOF ROLLING
Roller type and size as specified
DENSITY TESTS
NATA registered testing laboratory
SANDLAYER
Materials as specified
PILING
Bored piers as specified
SERVICE TRENCHES
Trench widths and depths as specified
Final Check
Made by: Date:
Comments
TESTS
Certificate of chemical soil barrier type testing received
RETICULATION SYSTEM
Material and components as specified
PROTECTION
System protected from other works in progress
GUARANTEE
System guarantee provided as specified
COMPLETION
Certificates issued for each stage of treatment
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
PROCESS TESTING
Compressive strength test results received
CONTRACTOR’S SUBMISSIONS
Saw joint methods received
TERMITE BARRIER
Barriers installed as specified
VAPOUR BARRIER
Sand bedding in place
Installation as specified
FORMWORK
Installed as specified
REINFORCEMENT
Reinforcement, including tie wires, support chairs, spacers etc. as
specified
Dowels as specified
PRESTRESSED TENDONS
As specified if required
EMBEDDED ITEMS
Correctly positioned as specified
CONCRETE
Ready mixed concrete as specified
Placing as specified
ADDITION OF ADMIXTURES
As specified
PRECAST UNITS
Manufactured as specified
Installed accurately
WATERPROOF MEMBRANES
Correct type used
Substrate accepted
CEMENTITIOUS TOPPINGS
Hardened surfaces prepared as specified
Correct thickness
Finish is as specified
JOINTS
Construction joints installed where specified
INTEGRAL FINISHES
Finish type as specified
GROUT
Grout beneath footings as specified
MISCELLANEOUS ITEMS
Clothes hoist footing installed as specified
Final Check
Made by: Date:
Comments
CONTRACTOR’S SUBMISSIONS
Shop drawings submitted
CONSTRUCTION GENERALLY
Steel clearly Identified as specified
WELDING
Weld procedure specification approval
Preparation as specified
BOLTING
Nuts and bolts as specified
PROTECTIVE COATING
Inspector name and qualifications provided
Final Check
Made by: Date:
Comments
CONSTRUCTION
Frames fitted firmly as specified
FRAMES
Stud spacing, nogging and bracing is as specified
ROOF TRUSSES
Shop drawings and certification received
Final Check
Made by: Date:
Comments
SAMPLES
Samples received
CONSTRUCTION GENERALLY
Masonry cleaned as work proceeds
Coursing correct
FACEWORK
Correct wall face side used
Joints as specified
CAVITY WALLS
Cavity widths correct as specified
No bridging of cavities
WALL TILES
Wall ties, type, spacing and installation as specified
MOVEMENT JOINTS
Joint material as specified
Width correct
REINFORCED MASONRY
Reinforcement installed as specified
STEEL LINTELS
Correct corrosion protection used
BAGGING
Joints cut flush
Acceptable texture
Final Check
Made by: Date:
Comments
GENERAL
Handling and storage as specified
CONTRACTOR’S SUBMISSIONS
Roof truss certification received
TIMBER
Certification provided
SHEET PRODUCTS
Adhesives as specified
FLOORS
Termite shields installed
Structural sheet flooring
Level
Junctions have a smooth and level finish
Fibre cement flooring
Sheet ends joined correctly
Expansion joints installed as specified
Timber decking
Decking securely nailed to bearers
Nails galvanised as specified
Joints are flush and directly over floor joists
WALL FRAMING
Frame sizes and grades are as specified
ROOF TRUSSES
Approved manufacturer used
Fabrication:
Camber provided
Connector plates in place and free from knots
No gaps greater than 2 mm
Installation:
Support trusses correctly positioned
Ties and wind bracing provided
Ceiling batten type is as specified
Battens fixed as specified
GLUED-LAMINATED MEMBERS
End joints installed as specified
TRIM
Skirting installed at wall junctions
Final Check
Made by: Date:
Comments
APPROVED FIXERS
Fixers approved by the roofing manufacturers
PROTECTION
Roof free from swarf
THERMAL MOVEMENT
Expansion breaks provided to manufacturer’s recommendation
METAL SEPERATION
Incompatible metals separated
Fasteners as specified
METAL ROOFING
Pitch as specified
ROOF PLUMBING
Material finishes checked:
Flashings
Cappings
Gutters
Rainwater heads
Outlets
Downpipes
Jointing sheet metal rainwater goods as specified
Flashing and cappings:
Roof junction checked
Upstands
Abutments
Projections through roof
Gutters generally
Turned down into outlets
Overflows provided
Minimum falls checked
Joints in gutters as specified
Valley gutters as specified
ROOF VENTILATORS
Proprietary roof ventilator system as specified
Final Check
Made by: Date:
Comments
PROTECTION
Cladding free from swarf
THERMAL MOVEMENT
Expansion breaks provided to manufacturer’s recommendation
METAL SEPERATION
Incompatible metals separated
Plywood as specified
Hardboard as specified
Fasteners as specified
CONSTRUCTION GENERALLY
To NT Deemed to Comply Manual
Fixings as specified
METAL CLADDING
Correct size and type
Fixed as specified
FRL as specified
Final Check
Made by: Date:
Comments
Requirements as specified
Final Check
Made by: Date:
Comments
CONTRACTOR’S SUBMISSIONS
Shop drawings and certification received
Names and contact details of proposed manufacturers and installers
received
Operation and maintenance manual received
DESIGN
All windows conform to specified standards
FRAME SECTIONS
Frame sections as specified
Flashings as specified
Fasteners as specified
CONSTRUCTION GENERALLY
Joints fitted tightly
INFILL PANELS
Material as specified
Fixings as specified
INSECT SCREENS
Aluminium framed screens
Fixed as specified
Finish matches window frames
Mesh is taught and without distortion
Fixed screens
Fitted with clipping device for removal
Finish matches window frames
Sliding screens
Fixed as specified
Finish matches window frames
Hinged screens hardware and hinged at the top as specified
DEBRIS SCREEN
Type and finish is as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Certification received
Samples received
Warranties received
Mirrors as specified
GLAZING
Installation:
Each piece permanently fixed
Building movements are not transferred to the glass
External work airtight/watertight
Certification received as specified
Glazing data received as specified
Frameless installations:
Joints installed correctly
Panels spaced correctly
Finish is clean and free of defects
Preglazing is as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Type test results fire and smoke doorsets
CONSTRUCTION GENERALLY
Doorframes engraved with identifier
Seals as specified
Trim as specified
TIMBER DOORS
Installation as specified
Thickness 38 mm minimum
Flush doors:
Edge strips as specified
Cut-outs 120 mm minimum from door edges
Primed before painting
Painting as specified
Manufacturer branding visible on exposed top or bottom rail
edge
Special facings as specified
Hardware as specified
Installation as specified
Installation as specified
ALUMINIUM DOORSETS
Materials and components as specified
Installation as specified
OVERHEAD DOORS
Roller shutters as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Manufacturer's published product data received
INSTALLATION
Fixings
Correct type
Non-corrosive
Back support provided where required
Door hardware
Correct type
Correct mounting height
Door stops are positioned correctly
HINGES
Correct number of hinges as specified
Correct type
KEYING
Correct key type
Correctly identified
DOOR CONTROLLERS
Fire door and smoke door closers operating correctly
HARDWARE FIXTURES
Installed as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Fire hazard properties received
Warranties received
PERFORMANCE CRITERIA
System tested as specified
PROTOTYPE
Sample installation provided
CONSTRUCTION GENERALLY
Grid set-out is as specified
Bulkheads braced
ACCESS PANELS
Installed where specified
Reinforcement provided
Identification provided
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Warranties submitted for materials and components, and installation
Aluminium as specified
Fasteners as specified
CONSTRUCTION GENERALLY
Base prepared receive the partitions
PRODUCTS
Marked as specified
Accessories as specified
EXECUTION
Cubicle system installation to manufacturer’s recommendations
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Fire hazard properties received
Plasterboard as specified
Fasteners as specified
CONSTRUCTION GERERALLY
Area enclosed and weather tight
PLASTERBOARD LINING
Supports installed as specified
Installation as specified
Installation as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Plaster system samples received
SUBSTRATE
All defects repaired
PLASTERING
Number of coats and thickness is as specified
Curing as specified
Two coat set plaster
Undercoat applied
Setting coat applied
White set plaster as specified
Waterproof render
Correct mixture
Penetrations re-sealed
Tyrolean render as specified
JOINTS
Movement joints installed as specified
Terminations as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Operation and maintenance manuals received
Fasteners as specified
CONSTRUCTION GENERALLY
Correct fasteners used
Neat bends
FINISHES
Visible joints finishing as specified
Electroplating as specified
Anodizing as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Product warranty received and installation warranty received
Particleboard as specified
Dry-processed fibreboard (including medium density fibreboard) as
specified
Decorative overlaid wood panels as specified
BENCHTOPS
Laminate benchtops:
Material as specified
Thickness as specified
Underside sealed
Scribed to walls
Joint sealant to match finish
Splashback:
Material as specified
Thickness as specified
VANITY UNIT
Correct material
Installation as specified
WARDROBES
Correct material
Installation as specified
Installation as specified
SHELVES
Correct material
Installation as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Waterproofing membrane report received
Samples received
Accessories provided
Adhesives as specified
Grout as specified
SUBSTRATE
Curing as specified
Falls as specified
Bedding as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Fire hazard properties received
Warranties received
Underlay as specified
Cork as specified
Linoleum as specified
Rubber as specified
PVC as specified
Adhesives as specified
SUBSTRATE
Substrate clean and free of deleterious material
Junctions:
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Name and contact details of proposed specialist applicators provided
Warranties received
Samples received
SAMPLES
Samples submitted for approval
Putty as specified
PAINTING
ITPs provided
Application:
Manufacturers product datasheets and application
specifications available
Safety Data Sheets available
Fixtures removed prior to painting
Restoration as specified
Fillers as specified
POWDER COATING
Colour selection as specified
Warranties received
Final Check
Made by: Date:
Comments
FIRE FIGHTING
Fire extinguishers and signs in place as specified
WHITEBOARDS
Size and type correct
Installed as specified
Installed as specified
PINBOARDS
Size and type correct
Installed as specified`
CHALKBOARDS
Size and type correct
Installed as specified
PROJECTION SCREENS
Size and type correct
Installed as specified
CLOTHES HOISTS
Size and type correct
Installed as specified
LETTER BOXES
Size and type correct as per drawings
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
TESTS
Hydrostatic test results received
CONTRACTOR SUBMISSIONS
Work-as-executed drawings submitted
CONNECTION
Local authorities draining plans obtained
PIPEWORK MATERIALS
Exposed pipework, including fittings and supports finishes as specified
SANITARY DRAINS
Inspection chambers installed as specified
Levels as specified
SEWERAGE TREATMENT
Septic tank type as specified
SANITARY PLUMBING
Pipe supports materials as specified
SANITARY FIXTURES
Products listed in the WaterMark Product Database
Accessories provided
Sealants as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
TESTS
Hydrostatic test results received
CONTRACTOR SUBMISSIONS
Work-as-executed drawings submitted
CONNECTION
Local authorities draining plans obtained
FILL MATERIAL
Standard fill as specified
TRENCHES
STORMWATER DRAINS
Levels and gradients are as specified
TABLE DRAINS
Correct size as specified
SUBSOIL DRAINS
Pipe depths are as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
TESTS
Hydrostatic test results received
CONTRACTORS SUBMISSIONS
Work-as-executed drawings submitted
CONNECTION
Local authorities arrangement
PIPEWORK MATERIALS
Polyethylene (PE) Piping as specified
Finishes as specified
PIPEWORK INSTALLATION
Piping installed in straight lines and uniform grades
Concealment as specified
ACCESSORIES
Products listed in the WaterMark Product Database
Type as specified
Installed as specified
WATER FILTER
Proprietary item as specified
Installed as specified
Commissioning as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
QUALITY
Superintendent written approval:
Manufacture of switchboards
Confirmation of orders for luminaires
CONTRACTOR’S SUBMISSIONS
Shop drawings submitted
EXISTING SYSTEMS
Surveyed and identified on drawings
Equipment and components new, of good quality and fit for purpose
Software ownership and access:
Ownership transferred to the Principal
Unrestricted rights to modify or replace
Password access
Software upgrades to the end of the Defects Liability Period
Equipment selection:
Established manufacturers used
Same manufacturer or source throughout project
Safety as specified
Manufacturers’ or suppliers’ recommendations
Transport, deliver, store, handle, protect, finish, adjust and
prepare to manufacturer’s recommendations
Recommendations and instructions submitted
Product modifications as specified
Product certification as specified
Manufacturers’ name plates provided as specified
INSTALLATION
Equipment and services installed parallel or perpendicular to building
elements
Clearance as specified
Protection as specified
Access as specified
Fixing:
Details of types of fixings, locations, and loads submitted for
approval
No piercing of water proof roofs, floors, walls, or vapour
barriers
Fasteners as specified
Corrosion protection as specified
IDENTIFICATION
Label, marker or identifier submitted
Labelling as specified
Contents as specified
Operating instructions and schematic diagrams mounted alongside
equipment
TRAINING
Comprehensive training course provided to Principal’s staff
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR'S SUBMISSIONS
Shop drawings submitted
POWER CABLES
Selection as specified
Minimum size 20 mm
Set-out as specified
Columns as specified
Construction as specified
Installation as specified
CABLE SUPPORTS
Complete cable support system provided consisting of baskets, trays
or ladders, and including brackets, fixings and accessories
Single manufacturer used for baskets, trays, ladders and accessories
Cable baskets:
Interior material as specified
Exterior material hot-dip galvanised steel or stainless steel
Cuts made good by galvanizing
All accessories, supports, joints, bends, tees and radii
selected from the same manufacturer’s product range
Cable trays:
Interior material as specified
Exterior material hot-dip galvanised steel
Cuts made good by galvanizing
Minimum steel thickness as specified
Folded edge greater 19 mm deep and radiused
Admiralty pattern, reverse stamping
Fish plates or splines for tees, crosses and joints
Cable ladders:
Manufacture as specified
Material galvanised steel
Rung spacing 300 mm maximum
Cables less than 13 mm diameter run in cable trays or ducts
Structural sections as specified
BUSDUCTS
Systems as specified
Selection as specified
Installation as specified
UNDERGROUND CABLES
To cited standards and Power and Water Corporation requirements
Trenches as specified
CABLE PITS
Proprietary cable pits as specified
COLUMNS
Design, manufacture, and testing by approved manufacturer
Construction as specified
ACCESSORIES
General:
Selection compatible with the final interior design
Orientation compatible with the final interior design
Position as specified
Acoustic separation as specified
Proprietary labels provided
Construction as specified
Location as specified
Plant rooms as specified
Lighting and socket outlet switches:
Appliances:
Internally wired and complete with control switches, controllers
or connecting links
Isolating switch adjacent to each directly connected appliance
Separate neutral and earth for 3 phase equipment
Flexible conduit for equipment within 60 mm of a wall
Equipment greater than 600 mm from a wall - concealed
conduit, in-floor ducting cast into the slab or in a service pole
Ceiling fan sweeps:
Minimum height from blades to finished floor level 2200 mm
Minimum 1200 mm from blade tip to wall cupboards or shelves
that require access by ladder or steps
Speed Regulators
Utilisation as specified
Installation as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR”S SUBMISSIONS
Calculated input power factor and harmonic content submitted
SYSTEM
Performance as specified
Protection as specified
RECTIFIER
Performance meets system requirements
BATTERY CHARGER
Performance meets system requirements
BATTERY
Performance as specified
INVERTER
Performance meets system requirements
Testing as specified
Class A classification
COMPLETION
Spare parts supplied
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR’S SUBMISSIONS
Type test certificates submitted
TESTING
Type tests as specified
CUSTOM-BUILT SWITCHBOARDS
Approved manufacturers details provided
Construction as specified
Degrees of protection:
Indoor minimum IP42
Outdoor minimum IP56W
Fault levels as specified
Separation as specified
Spare facilities:
Main switchboard 20%
Sub-switchboards 25%
Distribution boards 25% only on number of poles
Expansion provided as detailed on the drawings
Hardware as specified
Finishes as specified
Gland plates:
Removable fitted with gaskets to maintain the degree of
protection
Material as specified
Doors:
Width 900 mm
120°swing
Stays provided
Construction as specified
Hanging as specified
Hardware as specified
Lockable-keys provided
Door mounted equipment protected
PROPRIETARY SWITCHBOARDS
As for CUSTOM-BUILT SWITCHBOARDS checklist
Earthing as specified
Wiring as specified
Installation as specified
Layout as specified
Terminals as specified
Jointing as specified
Wiring as specified
Terminations as specified
SWITCHGEAR
Moulded case and miniature circuit breakers as specified
Fuses as specified
Contactors as specified
ACCESSORIES
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR’S SUBMISIONS
Operation and maintenance manuals submitted
Samples submitted
PROPRIETARY LUMINAIRES
Same type from the same brand and country of manufacture
FLUORESCENT LAMPS
Fluorescent lamp properties as specified
DISCHARGE LAMPS
Discharge lamp ballasts as specified
Capacitors as specified
Screw fixed
WIRING
External flexible cords as specified
LIGHTING CONTROL
Manual control of luminaires into groups, zones and to individual
devices provided
Digital control system as specified
Remote monitoring:
Common alarm provided
BMS interface provided
ACCESSORIES
Electrical accessories from the same manufacturer provided
RE-USE OF LUMINAIRES
Modifications and refurbishing as specified
SUPPORTS
Suspended luminaires
Surface mounted luminaires:
Packing pieces and packing strips fitted
Fixing as specified
Recessed luminaires installed in trimmed openings in the suspended
ceiling
WIRING CONNECTION
Recessed luminaires connected to a plug socket outlet
ACCESSORIES
Installation as specified
COMPLETION
Operation of all luminaires verified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR’S SUBMISSIONS
Product certification and installation certification submitted
Samples submitted
SYSTEM DESCRIPTION
Accommodation as specified
DISTRIBUTORS
Building distributors and floor distributors for voice and data provided
Cable termination racks, patch panels, equipment mounting racks for
servers and routers complete with power outlets provided
Equipment racks as specified
Cross connect patch panels:
Terminated directly to the modular connector
Patch cord ends terminated with appropriate registered jacks
Vendor certification and 20 year warranty received
CABLES
External cables to ACIF C524
Stranded UTP fly leads to 50% of the UTP outlets installed provided
Pre-terminated patch cords for 100% of the total incoming and
outgoing UTP and fibre ports provided
SURGE PROTECTION DEVICES (SPD)
SPD provided as specified
TELECOMMUNICATIONS OUTLETS
Outlets as specified
Pinouts as specified
EXECUTION
Installation as specified
Reinstatement as specified
Redundant structured cabling system removed and site drawings
updated
Firestop:
Penetrations through fire rated building elements
Certification of firestop system submitted
Cable Installation as specified
EARTHING SYSTEM
Communications earth system as specified
LABELS
Cables labelled with the origin and destination of the cable
Outlets labelled with the origin of the cross-connect, the workstation or
outlet number and the port designation
TESTING
Rest results received
Copper as specified
COMPLETION
Cable management log books submitted
Warranty submitted
Final Check
Made by: Date:
Comments
TESTS
GIVE SUFFICIENT NOTICE SO THAT THE SUPERINTENDENT MAY WITNESS TESTING:
CONTRACTOR’S SUBMISSIONS
Installer's statement and certificates submitted
Facilities as specified
Mounting as specified
Cabinet as specified
Panel as specified
Manufactured as specified
DETECTORS
General:
Do not obstruct filters access panels and the like
Readily accessible
Access panels provided 150 mm x 450 mm
Field wiring as specified
Self-test facilities in place
Unique circuit or serial number identification
EWIS INTERFACE
EWIS interface as specified
EXTERNAL ALARM
Red strobe light installed as specified
BLOCK DIAGRAM
Block diagram installed as specified
COMMISSIONING
Commissioning tests :
Commissioning program submitted
Testing as specified
Test reports submitted
Acceptance testing:
Acceptance test procedure submitted
Testing as specified
Test reports submitted
Final Check
Made by: Date:
Comments
Records submitted
Thermal expansion:
Expansion loops as specified
Saddles as specified
Saddle spacing as specified
Air Terminations:
Mounting as specified
Placement and connection as specified
Requirement as specified
Downconductors:
Steel reinforcement encased in concrete and steel framed
buildings as specified
Independent downconductors as specified
Equipotential bonding conductors:
Bonding as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR”S SUBMISSIONS
Records submitted
SHOP DRAWINGS
Shop drawings submitted
PRODUCTS
Alarm system panels or processors:
Separate sectors for each nominated detection device zone
Adjustable time delay entry/exit for each sector
Sealed battery and charger system contained within each control
panel provided
Activation:
Keypads, cards, card readers and other activation devices
provided
Installed 1100 mm from floor level
External audible and visual alarms as specified
Anti-tamper devices to control panels, external equipment, control and
activating devices, and access control devices provided
Alarm circuit supervision as specified
ACCESS CONTROL
Access control processors or panels:
Capacity as specified
Lock status and door position monitoring of door control
devices provided
Door control devices connected in a fail-safe mode
Double leaf doors (solid frame) as specified
Vehicle control:
Vehicle access control system as specified
Exit loop detection as specified
Photo electric beam safety interlock provided
Push-buttons and readers as specified
Mounting height 1000 mm from floor level
Reed switches as specified
Intercom:
Intercom base station, interconnected with the individual local
stations
Wall mounted flush stainless steel panel
IP56
Digital push-button type
Schedule as specified
Local station as specified
Internal station type surface mounted removable handset type
Operation as specified
Door control as specified
INTRUDER ALARM
Volumetric detection systems as specified
DURESS ALARM
Duress alarm switches as specified
VIDEO MONITORING
CCTV system as specified
EXECUTION
Mains supply:
Licensed electrician used
Permanent power supply:
- Intruder alarm panels
- Access control panels
- Intercom stations
- CCTV monitors
Marking as specified
COMPLETION
Training provided
Final Check
Made by: Date:
Comments
Condensate drains:
20 mm minimum drains provided and as specified
UPVC pressure pipes and fittings
Installation as specified
Soaker pit provided as specified
Drip tray provided as specified
Electrical as specified
Condensate drains:
20 mm minimum drains provided and as specified
UPVC pressure pipes and fittings
Drip tray provided as specified
Soaker pit provided as specified
Fan coil unit insulation as specified
Installation:
Cyclonic regions to Northern Territory Building Act
Non cyclonic regions to manufacturer's recommendations
Fan coil units as specified
Condensing units as specified
Refrigeration piping as specified
Control as specified
Electrical as specified
Installation as specified
Electrical as specified
Control as specified
EVAPORATIVE COOLERS
Construction:
Corrosion resistant materials suitable for outdoor operation
Structural frame as specified
Cabinet as specified
Water reservoir as specified
Supply air fan as specified
Installation:
To manufacturer's recommendations
Upstands as specified
Above roof as specified
Floor mounting within plantroom as specified
Floor mounting at ground level as specified
Water supply connected to each unit, automatically controlled by a ball
float valve
Bleed, drain and overflow as specified
Control as specified
Electrical as specified
FANS
General:
Quite operation and as specified
Balancing as specified
AIR FILTERS
Media as specified
Frames as specified
Measurement as specified
PUMPS
Material as specified
Construction:
Casing as specified
Components as specified
Motors as specified
Couplings as specified
Base plates as specified
Installation:
Alignment as specified
Doweling as specified
Shaft seal drip trays as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
CONTRACTOR’S SUBMISSIONS
Technical data provided
PRODUCTS
Marking as specified
Materials:
Pipe connections as specified
Fibreglass treatment as specified
Fibreglass gel coat as specified
Nozzles ABS or polypropylene
Hardware for wetted parts type 316 stainless steel to
ASTM A240/A240M
Fill and drift eliminators as specified
Galvanized steel components as specified
Fibreglass towers:
Casing material fibreglass
Cold water basin fibreglass
Atmospheric corrosivity category as specified
Stainless steel towers:
Casing material stainless steel
Cold water basin stainless steel
Mechanical equipment support stainless steel
Non-wetted structure stainless steel
Hardware for non-wetted parts stainless steel
Accessories as specified
Sumps as specified
CASING
Louvres and splash guards:
Readily removable air inlet louvres and splash guards
provided
Air inlet louvres as specified
Air inlet screens as specified
Cell partitions as specified
Gearboxes as specified
Fan stacks smoothly contoured with minimum fan blade tip clearance
Motors as specified
EXECUTION
Mounting bases and frames
Requirement as specified
Seismic restraint provided
Steel components hot-dip galvanized
Vibration isolating mountings as specified
COMPLETION
Spread of water is even over the fill
COMPLETION TESTS
Type tests/production tests results provided
Final Check
Made by: Date:
Comments
TESTS
GIVE SUFFICIENT NOTICE SO THAT THE SUPERINTENDENT MAY WITNESS TESTING:
DESIGN
Design pressures as specified
CONTRACTOR'S SUBMISSIONS
Manufacturer's specifications and reports submitted
COPPER PIPING
Jointing as specified
Fittings:
Capillary fittings as specified
Compression fittings as specified
Unions as specified
Flanges as specified
Bends and tees as specified
Centreline radius of bend or tee branch ≥ 1.5 times the pipe
diameter
3.4.4 Permanent joints as specified
STEEL PIPING
Steel pipe for closed systems
3.5.3 Jointing
3.5.4 Fittings:
Welded pipe as specified
Bends and tees as specified
Centreline radius of bend or tee branch ≥ 1.5 times the pipe
diameter
Steel for fabricated pipe fittings same grade and wall thickness
as the pipe
Non-vertical lines as specified
STAINLESS STEEL PIPING
Pipes as specified
Jointing as specified
Fittings:
Material stainless steel of the same grade and wall thickness
as the pipe
Unions as specified
Flanges as specified
Bends and tees as specified
Centreline radius of bend or tee branch ≥ 1.5 times the pipe
diameter
Stainless steel nuts bolts and washers of the same grade as
the pipe used
Welding as specified
ABS PIPING
Installation as specified
Jointing as specified
PVC PIPING
Installation as specified
Jointing as specified
Jointing as specified
Strainers as specified
STEAM SEPARATORS
Baffle type as specified
Strainers as specified
INSTRUMENTS - GENERAL
Locations as specified
PRESSURE GAUGES
Bourdon tube type as specified
Full scale range between 130% and 200% of maximum working
pressure
Construction as specified
Installation as specified
THERMOMETERS
Dial thermometers:
Mercury in steel
Accuracy within ± 1% of full scale deflection or better
Construction as specified
Installation as specified
SENSING POINTS
REFRIGERATION PIPING
Pips as specified
Bends as specified
Sleeves as specified
Layout as specified
INSTALLATION
General:
Requirement as specified
Layout as specified
Arrangement as specified
Spacing as specified
Dissimilar metals as specified
Structural point loads submitted
Secondary support necessary to transfer piping mass through
to the primary structure provided
Vibration suppression devices provided
Connections as specified
Accessibility as specified
CLEANING
Scale, rust, burrs and grease removed
Protection as specified
SUPPORTS
Support systems as specified
FLEXIBILITY
General:
Requirement as specified
Anchors and guides as specified
Flexible connections as specified
SLEEVES
Provided where penetrations through walls, floors, and other building
elements
Cover plates as specified
JOINTS
Demountable joints as specified
UNDERGROUND PIPING
Underground piping separated from electrical cables, gas pipes and
other services by ≥ 300 mm
Installation:
Pipe underlay as specified
Bedding material as specified
Chases as specified
Pipe surrounds as specified
TESTING
Completion tests as specified
Final Check
Made by: Date:
Comments
RESPONSIBILITIES
Performance as specified
CONTRACTOR'S SUBMISSIONS
Calculations submitted
Selection and fixing statements submitted for vapour barrier
installation
Exposed cold surfaces details submitted
Samples submitted
INSULATION PERFORMANCE
Material R-value as specified
PRODUCTS
Insulation materials as specified
INSTALLATION - GENERALLY
Preparation as specified
Supports as specified
Joints as specified
Material as specified
R-value as specified
Application as specified
Sheathing as specified
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
RESPONSIBILITIES
General:
Ratings and capacities of existing points for connection
confirmed
Terminations as specified
Commissioning and re-commissioning of staged works as
specified
Commissioning points locations provided
Experienced personnel engaged
CONTRACTOR'S SUBMISSIONS
Calibration certificates submitted
Certification submitted:
Fire and life safety
Manual and automatic safety devices
Penetrating services
Deemed to comply provisions
Completion program submitted
COMMISSIONING
Fire safety measures as specified
Reports submitted
RELATED TESTS
Factory performance testing as specified
INSTRUMENTATION
Calibration certificates
Air quantity at diffusers, outlets and grilles:
Hood adjustment factors as specified
Instruments as specified
Air pressures and differential pressures as specified
External as specified
AIR BALANCING
Diversity as specified
Instrumentation as specified
Tolerances as specified
WATER BALANCING
Balancing conditions met
Diversity as specified
Procedure as specified
AUTOMATIC CONTROLS
Tested for correct operation
Sensors calibrated
SAFETY CONTROLS
Testing as specified
Monitoring as specified
COMPLETION TESTS
Heating and air conditioning performance tests as specified
HANDOVER
Handover meeting provided
HANDOVER MEETING
Handover meeting minutes provided
HANDOVER TRAINING
Handover training provided
Final Check
Made by: Date:
Comments
PAVING GENERALLY
Substrate clean and dust free
Tolerances as specified
BASE COURSE
Subgrade 150 mm compacted to 95% MMDD CBR 10
Base material for gravel and asphalt paving:
Urban areas fine crushed rock as specified
Outside urban areas natural gravel as specified
Spread and compacted as specified
Spreading as specified
Compaction as specified
UNIT PAVING
Masonry units are as specified
Formwork secure
Surface is level
Correct thickness
Edge restraint installed
GRAVEL DRIVEWAYS
Type 3 material used
Falls 1:100
Final Check
Made by: Date:
Comments
TESTS
Give sufficient notice so that the Superintendent may witness testing:
Reinstatement as specified
EARTHWORKS
Excess material as specified
Tolerances as specified
SPRAY SEALING
Material requirements as specified
Spraying as specified
Compaction as specified
CONFORMANCE TESTING
Panel Period Contractors contractor list provided
Notice of testing
PAVEMENT MARKING
Painting Contractor Certification Program accreditation
Road marking paint:
Conforming to APAS 0041/5
Suitable for application by spray equipment to asphalt and
bituminous seal road surfaces
Suitable for use with Intermix drop on spherical glass beads
Paint Certificate of Compliance submitted
Materials as specified
Tolerances as specified
Workmanship:
Markings straight, with smooth even curves
Defective marking removed by sand blasting, or other
approved methods
Applications protected from traffic
Tyre pickup marks removed
Delineators as specified
Final Check
Made by: Date:
Comments
Wire as specified
Concrete as specified
CONSTRUCTION GENERALLY
Fence alignment cleared as specified
GATES
Location as per drawings
Hardwire as specified
FENCE TYPES
Domestic fences as specified
Final Check
Made by: Date:
Comments
CONTRACTOR SUBMISSIONS
Suppliers data received
Certificates identifying seed species and germination viability
Material source
Planting and maintenance recommendations
Samples received
Warranties received
PREPARATION
Weeds eradicated
EARTH MOUNDS
150 mm clean fill layers
ROCK WORK
Existing rock work as specified
SUBSOIL
Ripping depth as specified
Cultivation as specified
TOPSOIL
Site topsoil as specified
FERTILIZER
Correct type
BARRIERS, BOLLARDS
Location as per drawings
Precast concrete bollards
Correct material
Installed as specified
Timber bollards
Correct material
Installed as specified
Termite protection provided
Steel tube bollards
Correct material
Tube filled with concrete
Concrete footing provided as specified
Recycled plastic bollards
Correct material
Installation as per manufacturer recommendations
GARDEN EDGING
Masonry edging installed as specified
GRASS SEEDING
Preparation as specified
Sowing as specified
Watering as specified
Germination as specified
TURFING
Watering as specified
Application as specified
Watering as specified
MOWING
Grass height between 40 to 80 mm
Spoil removed
Storage as specified
Watering as specified
Placement as specified
MULCHING
Mulch sample received
TREE SURGERY
Qualified arborist employed
PLANTING ESTABLISHMENT
Maintenance work as specified
Final Check
Made by: Date:
Comments