MANUFACTURER'S ADDRESS FINAL ROUTINE & ACCEPTANCE TEST


M/S MEHRU ELECTRICAL & MECHANICAL ENGINEERS PVT. LTD.
E-1247,RIICO Industrial Area ,Phase -1(Ext.) Ghatal,
BHIWADI- 301019 ( RAJ.) - UNIT 1 ITEM : POTENTIAL TRANSFORMER QP NO : MEH/QAP-PT/1802
SP 2 /180 RIICO Industrial Area KAHRANI BHIWADI UNIT - 2 VOLTAGE CLASS - UPTO 220 KV REV.NO. : 00
Tel No. 01493 - 222010,225412, Fax No 01493 - 222212 DATE : 18.07.2019
E - Mail [email protected] , [email protected] PAGE : 1 OF 1
SL. COMPONENTS CHARACTERISTICS CLASS TYPE OF QUANTUM REFERENCE ACCEPTANCE FORMAT INSPECTION
REMARKS
NO. & OPERATION CHECK OF CHECK DOCUMENT NORMS OF AGENCY
M C/N RECORD M C N
1 2 3 4 5 6 7 8 9 10 11
1.0 FINAL INSPECTION & TESTING (CUSTOMER INSPECTION 10%)
Routine & Visual & Dimension Check Critical Measure 1sample/ lot 1 Sample App. Drg./ GTP App. Drg./ GTP Test Report P W W
Acceptance Test Power-frequency voltage withstand tests DO Test 100% 10% Drg./ GTP/IS 16227 Drg./ GTP/IS 16227 DO P W W
on primary terminals
Induced over voltage test DO DO DO DO IS 16227 - 3 IS 16227 - 3 DO P W W
Partial discharge measurement DO DO DO DO DO DO DO P W W
Power-frequency voltage withstand tests DO DO DO DO DO DO DO P W W
between sections
Power-frequency voltage withstand tests DO DO DO DO DO DO DO P W W
on secondary terminals
Test for Accuracy- Determination of Ratio & DO DO DO DO DO DO DO P W W
Phase angle Error according to requirement
of appropriate accuracy class.
Verification of Markings & Polarity DO DO DO DO DO DO DO P W W
Enclosure tightness test at ambient DO DO DO DO DO DO DO P W W
temperature/ Oil Leakage test
Measurement of capacitance and dielectric DO DO DO DO DO DO DO P W W Applicable only for
dissipation factor Um ≥72.5 kV.

2.0 PACKING & DISPATCH


1 Check for Proper Packing Major Physical 100% - As per Plant Std. As per Plant Std. - P - -
2 Preparation of Invoice DO DO DO - - - - P - -
MANUFACTURER MAIN SUPPLIER

LEGEND:- M : MANUFACTURER, C : CONTRACTOR, N : CUSTOMER ,


" P " PERFORM AND " W " WITNESS.

SEAL & SIGNATURE REVIEWED BY APPROVED BY APPROVAL SEAL