MD5 Series

Small, Light, High Speed & Torque 5-Phase Stepper Motor Driver
Features
● Bipolar constant pentagon drive method
● Includes auto current down and self-diagnosis function
● Low speed rotation and high accuracy controlling with
microstep-driving (MD5-HD14, MD5-HF14, MD5-HF14-AO,
MD5-HF28)
[Max. resolution 250 division: In case of 5-phase stepper motor of
which basic step angle is 0.72°, it enables to control up to 0.00288°
per pulse and it requires 125,000 pulses per rotation.]
● Photocoupler input insulation method to minimize the
MD5-HF14 MD5-HD14
effects from external noise MD5-HF28 MD5-ND14
MD5-HF14-AO
Please read “Safety Considerations”
in the instruction manual before using.

Ordering Information
MD 5 H F 14 (only for MD5-HF14(-AO),
※1
No mark Zero point excitation output MD5-HF28 model)
Output AO Alarm output
RUN current 14 1.4A/Phase
28 2.8A/Phase
Power supply D 20-35VDC
F 100-220VAC
Step type (resolution) H Micro step (250-division)
N Normal Step ※KR-55MC can be replaced with MD5-HD14.
Motor phase ※KR-5MC can be replaced with MD5-ND14.
5 5-phase
Item ※MD5-MF14 can be replaced with MD5-HF14.
MD Motor Driver ※KR-505G can be replaced with MD5-HF28.
※1: Except MD5-ND14
Specifications
Model MD5-HD14 MD5-HF14 MD5-HF14-AO MD5-HF28 MD5-ND14
※ ※
Power supply 20-35VDCᜡ 1 100-220VACᜠ 50/60Hz 20-35VDCᜡ 1
Allowable voltage range 90 to 110% of the rated voltage

Max. current consumption 2 3A 5A 3A

RUN current 3 0.4-1.4A/Phase 1.0-2.8A/Phase 0.5-1.5A/Phase
25 to 75% of RUN
STOP current 27 to 90% of RUN current (set by STOP current switch) current (set by STOP
current volume)
Drive method Bipolar constant current pentagon drive
Basic step angle 0.72˚/step
Resolution 1, 2, 4, 5, 8, 10, 16, 20, 25, 40, 50, 80, 100, 125, 200, 250-division (0.72 to 0.00288 /Step) 1, 2-division (0.72, 0.36/step)
Pulse width Min. 1㎲ (CW, CCW), Min. 1ms (HOLD OFF) Min. 10㎲ (CW, CCW),
Min. 1ms (HOLD OFF)
characteristic

Duty rate 50% (CW, CCW)


Input pulse

Rising/Falling time Below 130ns (CW, CCW)


Pulse input voltage [H]: 4-8VDCᜡ, [L]: 0-0.5VDC
※4
Pulse input current 7.5-14mA (CW, CCW), 10-16mA (HOLD OFF, DIVISION SELECTION, ZERO OUT)
Max. input※pulse
frequency 5 Max. 500kHz (CW, CCW) Max. 50kHz (CW, CCW)
270Ω (CW, CCW),
270Ω (CW, CCW), 270Ω (CW, CCW),
390Ω (HOLD OFF, 390Ω
Input resistance 390Ω (HOLD OFF, DIVISION SELECTION), 390Ω (HOLD OFF),
DIVISION SELECTION), (CW, CCW, HOLD OFF)
10Ω (ZERO OUT) 10Ω (ALARM)
10Ω (ZERO OUT)
Insulation resistance Over 100MΩ (at 500VDC megger, between all terminals and case)
Dielectric strength 1000VAC 50/60Hz for 1min (between all terminals and case)
±500V the square wave ±500V the square wave
Noise immunity noise (pulse width: 1μs) ±2kV the square wave noise (pulse width: 1μs) by the noise simulator noise (pulse width: 1μs)
by the noise simulator by the noise simulator
Mechanical 1.5mm amplitude at frequency 5 to 60Hz (for 1 min) in each X, Y, Z direction for 2 hours
Vibration
Malfunction 1.5mm amplitude at frequency 5 to 60Hz (for 1 min) in each X, Y, Z direction for 10 min
0 to 40℃, 0 to 40℃,
Environ- Ambient temp. storage: -10 to 60℃ 0 to 50℃, storage: -10 to 60℃ storage: -10 to 60℃
ment
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval ᜢ ᜢᜧ ᜢᜧ ᜢᜧ ᜢ
Weight 6
※ Approx. 327.5g Approx. 840g Approx. 820g Approx. 1.35kg Approx. 183g
(approx. 220g) (approx. 680g) (approx. 660g) (approx. 1.2kg) (approx. 130g)
※1: When using over 30VDC power supply, torque characteristics are improved but the driver temperature raise. The unit should be installed at the well ventilation
environment.
※2: Based on ambient temperature 25℃, ambient humidity 55%RH.
※3: RUN current varies depending on the input RUN frequency and max. RUN current at the moment varies also varies depending on the load.
※4: In case of MD5-HF14-AO, MD5-ND14, there are no DIVISION SELECTION, ZERO OUT function.
※5: Max. input pulse frequency is max. frequency to be input and is not same as max. pull-out frequency or max. slewing frequency.
※6: The weight includes packaging. The weight in parenthesis is for unit only. ※Environment resistance is rated at no freezing or condensation.

AA-4
5-Phase Stepper Motor Driver (1.4A/Phase, DC Power)

5-Phase Micro Stepper Motor Driver [MD5-HD14]


Unit Description Resolution switch RUN current switch
STOP current switch
SENSORS

CONTROLLERS

MOTION DEVICES

SOFTWARE

Input
Power indicator terminal Motor
Function Zero connection Power
selection output terminal terminal
DIP switch ※Refer to ' Specifications'.

Functions
Function selection DIP switch (Y)
Closed Loop
Stepper System
Switch position
No. Name Function
ON OFF (default)
(Z)
1 TEST Self diagnosis function 30rpm rotation Not use Stepper Motors

2 1/2 CLK Pulse input method 1-pulse input method 2-pulse input method
3 C/D Auto current down Not use Use (AA)
Drivers
TEST
Self diagnosis function is for motor and driver test.
(AB)
This function makes the motor rotate with 30rpm in full step. Rotation speed varies with resolution settings. Motion
Rotation speed = 30rpm/resolution Controllers

In 1-pulse input method, it rotates to CCW, and in 2-pulse input method, it rotates to CW.
※Be sure that the TEST switch is OFF before supplying the power.
If the TEST switch is ON, the motor operates immediately and it may be dangerous.
1/2 CLK
1/2 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
C/D (auto current down)
 his function is to reduce the current provided for motor automatically for preventing severe motor's heat when motor stops.
T
If motor RUN pulse is not applied, the current provided for motor reduces as the set STOP current.
※Be sure that when motor RUN current is reduced, the stop torque of motor also reduced.
※Set the STOP current by the STOP current switch.

Setting RUN current


Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Current 0.4 0.5 0.57 0.63 0.71 0.77 0.84 0.9 0.96 1.02 1.09 1.15 1.22 1.27 1.33 1.4
(A/Phase)
Setting RUN current is for the current provided for motor when the motor runs.
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.
Setting STOP current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F

% 27 31 36 40 45 50 54 58 62 66 70 74 78 82 86 90

Setting STOP current is for the current provided for motor when the motor stops for preventing severe motor's heat.
This setting is applied when using C/D (current down) function.
Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) S
 et RUN current as 1.4A and STOP current as 40%.
STOP current is set as 1.4A×0.4=0.56A
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.

AA-5
MD5 Series
Zero point excitation output signal (ZERO OUT)
ON
CW Pulse
OFF
ON
CCW Pulse
OFF
ON
ZERO OUT
OFF
0 1 2 3 4 5 6 7 8 9 0 1 2 1 0
 his output indicates the initial step of excitation order of stepper motor and rotation position of motor axis.
T
This signal outputs every 7.2° of rotation of the motor axis regardless of resolution.
(50 outputs per 1 rotation of the motor.)
E.g.) Full step: outputs one time by 10 pulses input, 20-division: outputs one time by 200 pulses input.

HOLD OFF function


 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.

Setting Microstep (microstep: resolution)


Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Resolution 1 2 4 5 8 10 16 20 25 40 50 80 100 125 200 250
Step angle 0.72° 0.36° 0.18° 0.144° 0.09° 0.072° 0.045° 0.036° 0.0288° 0.018° 0.0144° 0.009° 0.0072° 0.00576° 0.0036° 0.00288°
Setting Resolution (same as MS1, MS2)
The MS1, MS2 switches is for resolution setting.
Select MS2 or MS2 by DIVISION SELECTION signal ([L]: MS1, [H]: MS2)
Select the step angle (motor rotation angle per 1 pulse).
The set step angle is dividing basic step angle (0.72°) of 5-phase stepper motor by setting value.
The calculation formula of divided step angle is as below.
Basic step angle (0.72°)
Set step angle =
Resolution
When using geared type motor, the angle is step angle divided by gear ratio.
Step angle / gear ratio = Step angle applied gear
E.g) 0.72° / 10 (1:10) = 0.072°
※Must stop the motor before changing the resolution.

I/O Circuit and Connections


[Signal] +5VDC
1 ※CW
270Ω CW 2-pulse input method (CW rotation signal input)
2 1-pulse input method (operating rotation signal input)
3 ※CCW
270Ω CCW 2-pulse input method (CCW rotation signal input)
4 1-pulse input method (rotation direction signal input)
5 → [H]: CW, [L]: CCW
390Ω HOLD
OFF ※HOLD OFF
6
Control signal for motor excitation OFF
7 → [H]: Motor excitation OFF
390Ω DIVISION
SELECTION ※DIVISION SELECTION
8 Division selection signal
GND
9 → [L]: Operated by MS1 setting resolution
10Ω [H]: Operated by MS2 setting resolution
ZERO OUT
10 ※ZERO OUT
Zero point excitation output signal → Zero point status ON
[Motor] Pentagon Standard
connection connection ※If the power for driving pulse from external is over
than +5VDC, please connect resistor at the outside.
BLUE 1 Blue Gray+Red
(input power max. 24VDC, input current 10-20mA)
RED 2 Red Yellow+Black

ORANGE 3 Orange Orange+White Motor


GREEN 4 Green Brown+Green
※This connection cable color is only for Autonics motors.
BLACK 5 Black Blue+Purple It may different cable color when using other motors.
1 +
[Power] Power
2 - 20-35VDC

AA-6
5-Phase Stepper Motor Driver (1.4A/Phase, DC Power)

Connections
SENSORS

CONTROLLERS

MOTION DEVICES

SOFTWARE

+ -
POWER
20-35VDC (Y)
Closed Loop
Division selection + Black Stepper System
signal -
Green
Zero point +
CW+
CW-
CCW+
CCW-
HOLD OFF+
HOLD OFF-

(Z)
excitation - Orange Stepper Motors
User output signal Motor
Red
Controller
Blue
(AA)
Drivers
※In case of standard connection,
refer to 'Stepper Motors' section.
(AB)
Motion
Controllers

Dimensions
(unit: mm)

86
76.5
74
4.5 38
100

100
105
94

20
4.5
39.5

AA-7
MD5 Series

5-Phase Micro Stepper Motor Driver [MD5-HF14]


Unit Description Function selection DIP switch STOP current switch Resolution
RUN current switch switch
Alarm indicator (red)
Input
Power indicator
terminal

Motor Power
connection terminal
terminal
※Refer to ' Specifications'.
Functions
Function selection DIP switch
Switch position
No. Name Function
ON OFF (default)
1 TEST Self diagnosis function 30rpm rotation Not use
2 2/1 CLK Pulse input method 1-pulse input method 2-pulse input method
3 C/D Auto current down Not use Use
TEST
Self diagnosis function is for motor and driver test.
This function makes the motor rotate with 30rpm in full step. Rotation speed varies with resolution settings.
Rotation speed = 30rpm/resolution
In 1-pulse input method, it rotates to CCW, and in 2-pulse input method, it rotates to CW.
※Be sure that the TEST switch is OFF before supplying the power.
If the TEST switch is ON, the motor operates immediately and it may be dangerous.
2/1 CLK
2/1 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
C/D (auto current down)
 his function is to reduce the current provided for motor automatically for preventing severe motor's heat when motor stops.
T
If motor RUN pulse is not applied, the current provided for motor reduces as the set STOP current.
※Be sure that when motor RUN current is reduced, the stop torque of motor also reduced.
※Set the STOP current by the STOP current switch.
Setting RUN current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Current 0.4 0.5 0.57 0.63 0.71 0.77 0.84 0.9 0.96 1.02 1.09 1.15 1.22 1.27 1.33 1.4
(A/Phase)
Setting RUN current is for the current provided for motor when the motor runs.
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.

Setting STOP current


Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F

% 27 31 36 40 45 50 54 58 62 66 70 74 78 82 86 90

Setting STOP current is for the current provided for motor when the motor stops for preventing severe motor's heat.
This setting is applied when using C/D (current down) function.
Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) Set RUN current as 1.4A and STOP current as 40%.
STOP current is set as 1.4A×0.4=0.56A
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.

AA-8
5-Phase Stepper Motor Driver (1.4A/Phase, AC Power)

Zero point excitation output signal (ZERO OUT)


ON
CW Pulse
OFF SENSORS

ON
CCW Pulse
OFF
CONTROLLERS
ON
ZERO OUT
OFF
0 1 2 3 4 5 6 7 8 9 0 1 2 1 0
MOTION DEVICES
 his output indicates the initial step of excitation order of stepper motor and rotation position of motor axis .
T
This signal outputs every 7.2° of rotation of the motor axis regardless of resolution.
(50 outputs per 1 rotation of the motor.)
SOFTWARE
E.g.) Full step: outputs one time by 10 pulses input, 20-division: outputs one time by 200 pulses input.
HOLD OFF function
 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.
Setting Microstep (microstep: resolution) (Y)
Closed Loop
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F Stepper System

Resolution 1 2 4 5 8 10 16 20 25 40 50 80 100 125 200 250


Step angle 0.72° 0.36° 0.18° 0.144° 0.09° 0.072° 0.045° 0.036° 0.0288° 0.018° 0.0144° 0.009° 0.0072° 0.00576° 0.0036° 0.00288° (Z)
Stepper Motors
Setting Resolution (same as MS1, MS2)
The MS1, MS2 switches is for resolution setting.
(AA)
Select MS2 or MS2 by DIVISION SELECTION signal ([L]: MS1, [H]: MS2) Drivers
Select the step angle (motor rotation angle per 1 pulse).
The set step angle is dividing basic step angle (0.72°) of 5-phase stepper motor by setting value. (AB)
The calculation formula of divided step angle is as follow. Basic step angle (0.72°) Motion
Set step angle = Controllers
Resolution
When using geared type motor, the angle is step angle divided by gear ratio.
Step angle / gear ratio = Step angle applied gear
E.g) 0.72° / 10 (1:10) = 0.072°
※Must stop the motor before changing the resolution.
Alarm indication
Overheat: When the temperature of driver base is over 80℃, the alarm indicator (red) turns ON and motor stops with holding the excision.
Overcurrent: When overcurrent occurs due to motor damage by burn, driver damage, or error, the alarm indicator (red) turns ON and the
motor becomes HOLD OFF.
※Turn OFF the power and remove the causes of alarm. Re-supply the power and the alarm indicator turns OFF and the driver is normal
operation.

I/O Circuit and Connections


+5VDC ※CW
[Signal] 2-pulse input method (CW rotation signal input)
1
270Ω CW 1-pulse input method (operating rotation signal input)
2 ※CCW
3 2-pulse input method (CCW rotation signal input)
270Ω CCW 1-pulse input method (rotation direction signal input)
4
→ [H]: CW, [L]: CCW
5 ※HOLD OFF
390Ω HOLD
OFF
Control signal for motor excitation OFF
6
→ [H]: Motor excitation OFF
7 ※DIVISION SELECTION
390Ω DIVISION SELECTION
8 +5VDC
Division selection signal
2kΩ
→ [L]: Operated by switch MS1
9 [H]: Operated by switch MS2
10Ω ZERO OUT
10
※ZERO OUT
Zero point excitation output signal → Zero point status ON
Pentagon Standard
[Motor] connection connection
BLUE ※If the power for driving pulse from external is over
1 Blue Gray+Red
than +5VDC, please connect resistor at the outside.
RED 2 Red Yellow+Black (input power max. 24VDC, input current 10-20mA)
ORANGE 3 Orange Orange+White Motor

GREEN 4 Green Brown+Green

BLACK 5 Black Blue+Purple ※This connection cable color is only for Autonics motors.
It may different cable color when using other motors.
[Power] L AC
Power 100-220VAC
50/60Hz
N AC
G
GND

AA-9
MD5 Series

Connections

Blue
Red F.G.
Orange
Motor 100-220VAC 50/60Hz
Green
Black

※In case of standard connection,


refer to 'Stepper Motors' section.
Division selection +
signal -
Zero point excitation +
output signal -
CW+
CW-
CCW+
CCW-
HOLD OFF+
HOLD OFF-

User
Controller

Dimensions
(unit: mm)

20 7 108
156

170

120

4-M4 Tap Depth: 8


5
40 5.4
122
42
133.5

AA-10
5-Phase Stepper Motor Driver (1.4A/Phase, AC Power, Alarm Output)

5-Phase Micro Stepper Motor Driver [MD5-HF14-AO]


Unit Description Function selection DIP switch STOP current switch SENSORS

RUN current switch


Alarm indicator (red)
Input/Output
Power indicator Resolution switch
terminal CONTROLLERS

MOTION DEVICES

SOFTWARE

Motor Power
connection terminal
terminal
※Refer to ' Specifications'.

Functions (Y)
Closed Loop

Function selection DIP switch


Stepper System

Switch position
No. Name Function (Z)
ON OFF (default) Stepper Motors

1 TEST Self diagnosis function 30rpm rotation Not use


2 2/1 CLK Pulse input method 1-pulse input method 2-pulse input method (AA)
Drivers
3 C/D Auto current down Not use Use
TEST (AB)
Self diagnosis function is for motor and driver test. Motion
Controllers
This function makes the motor rotate with 30rpm in full step. Rotation speed varies with resolution settings.
Rotation speed = 30rpm/resolution
In 1-pulse input method, it rotates to CCW, and in 2-pulse input method, it rotates to CW.
※Be sure that the TEST switch is OFF before supplying the power.
If the TEST switch is ON, the motor operates immediately and it may be dangerous.
2/1 CLK
2/1 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
C/D (auto current down)
T
 his function is to reduce the current provided for motor automatically for preventing severe motor's heat when motor stops.
If motor RUN pulse is not applied, the current provided for motor reduces as the set STOP current.
※Be sure that when motor RUN current is reduced, the stop torque of motor also reduced.
※Set the STOP current by the STOP current switch.
Setting RUN current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Current 0.4 0.5 0.57 0.63 0.71 0.77 0.84 0.9 0.96 1.02 1.09 1.15 1.22 1.27 1.33 1.4
(A/Phase)
Setting RUN current is for the current provided for motor when the motor runs.
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.
Setting STOP current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F

% 27 31 36 40 45 50 54 58 62 66 70 74 78 82 86 90

Setting STOP current is for the current provided for motor when the motor stops for preventing severe motor's heat.
This setting is applied when using C/D (current down) function.
Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) S
 et RUN current as 1.4A and STOP current as 40%.
STOP current is set as 1.4A×0.4=0.56A
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.

AA-11
MD5 Series
HOLD OFF function
 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.

Setting Microstep (microstep: resolution)


Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Resolution 1 2 4 5 8 10 16 20 25 40 50 80 100 125 200 250
Step angle 0.72° 0.36° 0.18° 0.144° 0.09° 0.072° 0.045° 0.036° 0.0288° 0.018° 0.0144° 0.009° 0.0072° 0.00576° 0.0036° 0.00288°
Setting Resolution (MS1)
 he set step angle is dividing basic step angle (0.72°) of 5-phase stepper motor by setting value.
T
The calculation formula of divided step angle is as below.
Basic step angle (0.72°)
Set step angle =
Resolution
When using geared type motor, the angle is step angle divided by gear ratio.
Step angle / gear ratio = Step angle applied gear
E.g) 0.72° / 10 (1:10) = 0.072°
※Must stop the motor before changing the resolution.
Alarm indication/output
Overheat: When the temperature of driver base is over 80℃, the alarm indicator (red) turns ON and motor stops and alarm output turns
ON with holding the excision.
Overcurrent: When overcurrent occurs due to motor damage by burn, driver damage, or error, the alarm indicator (red) turns ON and
alarm output turns ON. The motor becomes HOLD OFF.
※Turn OFF the power and remove the causes of alarm. Re-supply the power and the alarm indicator turns OFF and alarm output turns OFF.
The driver is normal operation.

I/O Circuit and Connections


+5VDC ※If the power for driving pulse from external is over than +5VDC,
[Signal] please connect resistor at the outside.
1 (input power max. 24VDC, input current 10-24mA)
CW
270Ω
2 ※CW
2-pulse input method (CW rotation signal input)
3 1-pulse input method (operating rotation signal input)
CCW
270Ω ※CCW
4
2-pulse input method (CCW rotation signal input)
5 1-pulse input method (rotation direction signal input)
390Ω HOLD OFF → [H]: CW, [L]: CCW
6 5-24VDC ※HOLD OFF
Control signal for motor excitation OFF
7 → [H]: Motor excitation OFF
10Ω
Alarm OUT +
8 ※When alarm occurs, the motor becomes HOLD OFF. Turn OFF
2kΩ the power and remove the causes to normal operation.
Alarm OUT -
9
Over heat:
10
Over current:
Pentagon Standard
[Motor] connection connection
BLUE 1 Blue Gray+Red

RED 2 Red Yellow+Black

ORANGE 3 Orange Orange+White Motor

GREEN 4 Green Brown+Green


※This connection cable color is only for Autonics motors.
BLACK 5 Black Blue+Purple
It may different cable color when using other motors.

[Power]
L AC
Power 100-220VAC
N AC 50/60Hz

G
GND

AA-12
5-Phase Stepper Motor Driver (1.4A/Phase, AC Power, Alarm Output)

Connections
SENSORS

CONTROLLERS

MOTION DEVICES

Blue
SOFTWARE
Red F.G.
Orange
Motor
Green 100-220VAC 50/60Hz
Black

※In case of standard connection, (Y)


refer to 'Stepper Motors' section. + Closed Loop
Alarm
3-5VDC Stepper System
output -
CW+
CW-
CCW+
CCW-
HOLD OFF+
HOLD OFF-

(Z)
Stepper Motors
User
Controller
(AA)
Drivers

(AB)
Motion
Controllers

Dimensions
(unit: mm)

20 7 108
170

120
156

4-M4 Tap Depth: 8

5 5.4
122
40 133.5
42

AA-13
MD5 Series

5-Phase Microstep Motor Driver [MD5-HF28]


Unit Description Resolution switch
RUN current switch
STOP current switch

Power indicator Function


Alarm indicator (red) selection
※KR-505G can be replaced with MD5-HF28. DIP switch
※Power supply 100-220VAC and socket type wire terminal blocks are
upgraded comparing to KR Series.
※Refer to ' Specifications'.

Functions
Function selection DIP switch
Switch position
No. Name Function
ON OFF (default)
1 TEST Self diagnosis function 30rpm rotation Not use
2 2/1 CLK Pulse input method 1-pulse input method 2-pulse input method
3 C/D Auto Current Down Not use Use
TEST
Self diagnosis function is for motor and driver test.
This function makes the motor rotate with 30rpm in full step. Rotation speed varies with resolution settings.
Rotation speed = 30rpm/resolution
In 1-pulse input method, it rotates to CCW, and in 2-pulse input method, it rotates to CW.
※Be sure that the TEST switch is OFF before supplying the power.
If the TEST switch is ON, the motor operates immediately and it may be dangerous.
2/1 CLK
2/1 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
C/D (auto current down)
This function is to reduce the current provided for motor automatically for preventing severe motor's heat when motor stops.
If motor RUN pulse is not applied, the current provided for motor reduces as the set STOP current.
※Be sure that when motor RUN current is reduced, the stop torque of motor also reduced.
※Set the STOP current by the STOP current switch.
Setting RUN current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Current 1.14 1.25 1.36 1.50 1.63 1.74 1.86 1.97 2.10 2.20 2.30 2.40 2.50 2.60 2.78 2.88
(A/Phase)
Setting RUN current is for the current provided for motor when the motor runs.
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.
Setting STOP current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F

% 27 31 36 40 45 50 54 58 62 66 70 74 78 82 86 90

Setting STOP current is for the current provided for motor when the motor stops for preventing severe motor's heat.
This setting is applied when using C/D (current down) function.
Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) Set RUN current as 2.5A and STOP current as 40%.
STOP current is set as 2.5A×0.4=1A
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.

AA-14
5-Phase Stepper Motor Driver (2.8A/Phase, AC Power)
Zero point excitation output signal (ZERO OUT)
ON
CW Pulse
OFF SENSORS

ON
CCW Pulse
OFF
CONTROLLERS
ON
ZERO OUT
OFF
0 1 2 3 4 5 6 7 8 9 0 1 2 1 0
 his output indicates the initial step of excitation order of stepper motor and rotation position of motor axis.
T MOTION DEVICES

This signal outputs every 7.2° of rotation of the motor axis regardless of resolution.
(50 outputs per 1 rotation of the motor.)
E.g.) Full step: outputs one time by 10 pulses input, 20-division: outputs one time by 200 pulses input. SOFTWARE

HOLD OFF function


 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.
Setting Microstep (microstep: resolution)
(Y)
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F Closed Loop
Stepper System
Resolution 1 2 4 5 8 10 16 20 25 40 50 80 100 125 200 250
Step angle 0.72° 0.36° 0.18° 0.144° 0.09° 0.072° 0.045° 0.036° 0.0288° 0.018° 0.0144° 0.009° 0.0072° 0.00576° 0.0036° 0.00288° (Z)
Stepper Motors
Setting Resolution (same as MS1, MS2)
The MS1, MS2 switches is for resolution setting.
Select MS2 or MS2 by DIVISION SELECTION signal ([L]: MS1, [H]: MS2) (AA)
Drivers
Select the step angle (motor rotation angle per 1 pulse).
The set step angle is dividing basic step angle (0.72°) of 5-phase stepper motor by setting value.
The calculation formula of divided step angle is as follow. Basic step angle (0.72°) (AB)
Set step angle = Motion
Resolution Controllers
When using geared type motor, the angle is step angle divided by gear ratio.
Step angle / gear ratio = Step angle applied gear E.g) 0.72° / 10 (1:10) = 0.072°
※Must stop the motor before changing the resolution.
Alarm indication
Overheat: When the temperature of driver base is over 80℃, the alarm indicator (red) turns ON and motor stops with holding the excision.
Overcurrent: When overcurrent occurs due to motor damage by burn, driver damage, or error, the alarm indicator (red) turns ON and the
motor becomes HOLD OFF.
※Turn OFF the power and remove the causes of alarm. Re-supply the power and the alarm indicator turns OFF and the driver is normal
operation.

I/O Circuit and Connections


+5VDC
[Signal] ※CW
1 2-pulse input method (CW rotation signal input)
270Ω CW
2 1-pulse input method (operating rotation signal input)
※CCW
3
CCW 2-pulse input method (CCW rotation signal input)
270Ω
4 1-pulse input method (rotation direction signal input)
→ [H]: CW, [L]: CCW
5
390Ω HOLD ※HOLD OFF
6 OFF Control signal for motor excitation OFF
→ [H]: Motor excitation OFF
7
390Ω DIVISION SELECTION ※DIVISION SELECTION
8 +5VDC Division selection signal
2kΩ → [L]: Operated by switch MS1
9 [H]: Operated by switch MS2
10Ω ZERO OUT
※ZERO OUT
10
Zero point excitation output signal → Zero point status ON
Pentagon Standard ※If the power for driving pulse from external is over
[Motor] connection connection than +5VDC, please connect resistor at the outside.
BLUE 1 Blue Gray+Red
RED 2 Red Yellow+Black

ORANGE 3 Orange Orange+White Motor

GREEN 4 Green Brown+Green

5 Black Blue+Purple
BLACK ※This connection cable color is only for Autonics motors.
[Power] It may different cable color when using other motors.
L AC
Power 100-220VAC
N AC 50/60Hz

G
GND

AA-15
MD5 Series

Connections

F.G.
100-220VAC 50/60Hz

Black
Green
Orange Motor
Division selection+ Red
signal - Blue
Zero point excitation +
output signal -
※In case of standard connection,
CW+
CW-
CCW+
CCW-
HOLD OFF+
HOLD OFF-

refer to 'Stepper Motors' section.


User
Controller

Dimensions
(unit: mm)

49 145.3
20 127.5 10.5
5
5.5
163

200
185

211.5
4-Ø6

Ø5
4-R0.5
54.1

R5 146

AA-16
5-Phase Stepper Motor Driver (1.5A/Phase, DC Power)

5-Phase Stepper Motor Driver [MD5-ND14]


Unit Description SENSORS

CONTROLLERS

MOTION DEVICES

SOFTWARE
Input
Motor
terminal
connection Power
RUN current
volume terminal terminal
Function
selection
STOP DIP switch
※Refer to ' Specifications'. current
volume

Functions (Y)
Closed Loop
Function selection DIP switch Stepper System

Switch position
No. Nameplate Function (Z)
ON OFF (default) Stepper Motors
ON
1 2 1 1/2 CLK Pulse input method 1-pulse input method 2-pulse input method
2 FULL↔HALF Select resolution 1-division (0.72°) 2-division (0.36°) (AA)
※Changing pulse input method or resolution is available only when stepper motor stops. Drivers

If changing the resolution during operation, the motor may be out of phase.
(AB)
1/2 CLK Motion
Controllers
1/2 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
FULL ↔ HALF
FULL ↔ HALF switch is to set basic step angle for 5-phase stepper motor.
※Change resolution only when the motor stops.

Setting RUN current


RUN CURRENT
Setting RUN current is for the current provided for motor when the motor runs.
1.0A
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.
0.5A 1.5A

Setting STOP current


Setting STOP current is for the current provided for motor when the motor stops.
STOP CURRENT Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) Set RUN current as 1.4A and STOP current as 40%.
STOP current is set as 1.4A×0.4=0.56A.
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.
25% 75%

HOLD OFF function


 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.

AA-17
MD5 Series

I/O Circuit and Connections

[Signal] +5VDC

1 ※CW
CW 2-pulse input method (CW rotation signal input)
390Ω 1-pulse input method (operating rotation signal input)
2

※CCW
3 2-pulse input method (CCW rotation signal input)
CCW
1-pulse input method (rotation direction signal input)
390Ω
→ [H]: CW, [L]: CCW
4

※HOLD OFF
5 Control signal for motor excitation OFF
390Ω HOLD → [H]: Motor excitation OFF
OFF
6 ※If the power for driving pulse from external is over
GND than +5VDC, please connect resistor at the outside.
(input voltage max. 24VDC, input current 10-20mA)

※In case of standard connection, refer to 'Stepper Motors' section.

[Motor] Pentagon Standard


connection connection
BLUE 1 Blue Gray+Red

RED 2 Red Yellow+Black

ORANGE 3 Orange Orange+White Motor

GREEN 4 Green Brown+Green


※This connection cable color is only for Autonics motors.
BLACK 5 Black Blue+Purple It may different cable color when using other motors.

1 + Power
[Power]
2 - 20-35VDC

3 +5VDC Max. 30mA output

AA-18
5-Phase Stepper Motor Driver (1.5A/Phase, DC Power)

Time Chart
1-pulse input method SENSORS

[H]
CW CONTROLLERS
[L]
[H]
CCW
[L] MOTION DEVICES

SOFTWARE
Rotation
position CW CCW

CW
2-pulse input method
[H]
CW
[L] (Y)
Closed Loop
Stepper System
[H]
CCW
[L]
(Z)
Stepper Motors

Rotation
position (AA)
CW CCW Drivers

(AB)
※Do not input CW, CCW signals at the same time in 2-pulse input method. Motion
Controllers
It may not operate properly if another direction signal is inputted when one of CW or CCW is [H].

Dimensions
(unit: mm)
22.5

45
4.5

80

87

93 55.5
87
32
20
4.5

AA-19
MD5 Series

Low Noise, Low Vibration Multi-Axis 5-Phase Stepper Motor Driver


Features
● Simultaneous operation of 2, 3-axis by single power supply
20-35VDC
● Small, light weight and advanced quality by custom IC and
surface mounted circuit
● Realizing low noise, low vibration rotation with microstep-driving
● Low speed rotation and high accuracy controlling
with microstep-driving
● Max. resolution 250 division: In case of 5-phase stepper motor
of which basic step angle is 0.72°, it enables to control up to MD5-HD14-3X
0.00288° per pulse
● Includes auto current down and self-diagnosis function
● Photocoupler input insulation method to minimize the effects MD5-HD14-2X

from external noise


Please read “Safety Considerations”
in the instruction manual before using.

Ordering Information
MD 5 H D 14 2X
Axis 2X 2-axis
※1
3X 3-axis
RUN current
14 1.4A/Phase
Power supply
D 20-35VDC
Step type (resolution)
H Micro step (250-division)
Motor phase
5 5-phase
Item ※1: Built-in zero point excitation output
MD Motor Driver signal is optional.
Specifications
Model MD5-HD14-2X MD5-HD14-3X
※1
Power supply 20-35VDCᜡ
Allowable voltage fluctuation range 90 to 110% of the rated voltage
※2
Max. current consumption 5A 7A
※3
RUN current 0.4-1.4A/Phase
STOP current 27 to 90% of RUN current (set by STOP current switch)
Drive method Bipolar constant current pentagon drive
Basic step angle 0.72 /Step
Resolution 1, 2, 4, 5, 8, 10, 16, 20, 25, 40, 50, 80, 100, 125, 200, 250-division (0.72 to 0.00288 /Step)
Pulse width Min. 1μs (CW, CCW), Min. 1ms (HOLD OFF)
characteristic

Duty rate 50% (CW, CCW)


Input pulse

Rising/Falling time Below 130ns (CW, CCW)


Pulse input voltage [H]: 4-8VDCᜡ, [L]: 0-0.5VDC
Pulse input current 7.5-14mA (CW, CCW), 10-16mA (HOLD OFF, ZERO OUT)
※4
Max. input pulse frequency Max. 500kHz (CW, CCW)
Input resistance 270Ω (CW, CCW), 390Ω (HOLD OFF), 10Ω (ZERO OUT)
Insulation resistance Over 100MΩ (at 500VDC megger, between all terminals and base)
Dielectric strength 1,000VAC 50/60Hz for 1 min (between all terminals and base)
Noise immunity ±500V the square wave noise (pulse width: 1μs) by the noise simulator
Mechanical 1.5mm amplitude at frequency 5 to 60Hz (for 1 min) in each X, Y, Z direction for 2 hours
Vibration
Malfunction 1.5mm amplitude at frequency 5 to 60Hz (for 1 min) in each X, Y, Z direction for 10 min
Envi- Ambient temp. 0 to 40℃, storage: -10 to 60℃
ron-ment Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Approval
※5
Weight Approx. 446g (approx. 292g) Approx. 597g (approx. 411g)
※1: When using over 30VDC power supply, torque characteristics are improved but the driver temperature raise. The unit should be installed
at the well ventilation environment.
※2: Based on ambient temperature 25℃, ambient humidity 55%RH.
※3: RUN current varies depending on the input RUN frequency and max. RUN current at the moment varies also varies depending on the load.
※4: Max. input pulse frequency is max. frequency to be input and is not same as max. pull-out frequency or max. slewing frequency.
※5: The weight includes packaging. The weight in parenthesis is for unit only.
※Environment resistance is rated at no freezing or condensation.

AA-20
5-Phase Stepper Motor Driver (1.4A/Phase, DC Power, Multi-Axis)

Functions
Function selection DIP switch SENSORS
Switch position
No. Name Function
ON OFF (default)
1 TEST Self diagnosis function 30rpm rotation Not use
CONTROLLERS
2 1/2 CLK Pulse input method 1-pulse input method 2-pulse input method
3 C/D Auto Current Down Not use Use
TEST MOTION DEVICES
Self diagnosis function is for motor and driver test.
This function makes the motor rotate with 30rpm in full step. Rotation speed varies with resolution settings.
Rotation speed = 30rpm/resolution
SOFTWARE
In 1-pulse input method, it rotates to CCW, and in 2-pulse input method, it rotates to CW.
※Be sure that the TEST switch is OFF before supplying the power.
If the TEST switch is ON, the motor operates immediately and it may be dangerous.
1/2 CLK
1/2 CLK switch is to select pulse input method.
1-pulse input method: CW → operating rotation signal input, CCW → rotation direction signal input ([H]: CW, [L]: CCW)
2-pulse input method: CW → CW rotation signal input, CCW → CCW rotation signal input.
C/D (auto current down)
This function is to reduce the current provided for motor automatically for preventing severe motor's heat when motor (Y)
Closed Loop
stops. Stepper System
If motor RUN pulse is not applied, the current provided for motor reduces as the set STOP current.
※Be sure that when motor RUN current is reduced, the stop torque of motor also reduced. (Z)
※Set the STOP current by the Setting STOP current switch. Stepper Motors

Setting RUN current


(AA)
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F Drivers

Current (A/Phase) 0.4 0.5 0.57 0.63 0.71 0.77 0.84 0.9 0.96 1.02 1.09 1.15 1.22 1.27 1.33 1.4
(AB)
Motion
Setting RUN current is for the current provided for motor when the motor runs. Controllers
※When RUN current is increased, RUN torque of the motor is also increased.
※When RUN current is set too high, the heat is severe.
※Set RUN current within the range of motor's rated current according to its load.
※Change RUN current only when the motor stops.
Setting STOP current
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F

% 27 31 36 40 45 50 54 58 62 66 70 74 78 82 86 90

Setting STOP current is for the current provided for motor when the motor stops.
This setting is applied when using C/D (current down) function.
Setting value of STOP current is percentage (%) ratio of the set RUN current.
E.g.) Set RUN current as 1.4A and STOP current as 40%.
STOP current is set as 1.4A×0.4=0.56A
※When STOP current is decreased, STOP torque of the motor is also decreased.
※When STOP current is set too low, the heat is lower.
※Change STOP current only when the motor stops.
Zero point excitation output signal (ZERO OUT) [Option]
ON
CW Pulse
OFF
ON
CCW Pulse
OFF
ON
ZERO OUT
OFF
0 1 2 3 4 5 6 7 8 9 0 1 2 1 0
 his output indicates the initial step of excitation order of stepper motor and rotation position of motor axis.
T
This signal outputs every 7.2° of rotation of the motor axis regardless of resolution.
(50 outputs per 1 rotation of the motor.)
E.g.) Full step: outputs one time by 10 pulses input,
20-division: outputs one time by 200 pulses input.
HOLD OFF function
 his signal is for rotating motor's axis using external force or used for manual positioning.
T
When hold off signal maintains over 1ms as [H], motor excitation is released.
When hold off signal maintains over 1ms as [L], motor excitation is in a normal status.
※Must stop the motor for using this function.
※Refer to ' I/O Circuit and Connections'.

AA-21
MD5 Series
Setting Microstep (microstep: resolution)
Switch No. 0 1 2 3 4 5 6 7 8 9 A B C D E F
Resolution 1 2 4 5 8 10 16 20 25 40 50 80 100 125 200 250
Step angle 0.72° 0.36° 0.18° 0.144° 0.09° 0.072° 0.045° 0.036° 0.0288° 0.018° 0.0144° 0.009° 0.0072° 0.00576° 0.0036° 0.00288°
Resolution (MS1)
 he set step angle is dividing basic step angle (0.72°) of 5-phase stepper motor by setting value.
T
The calculation formula of divided step angle is as below.
Basic step angle (0.72°)
Set step angle =
Resolution
 hen using geared type motor, the angle is step angle divided by gear ratio.
W
Step angle/gear ratio = Step angle applied gear
E.g) 0.72°/10 (1:10) = 0.072°
※Must stop the motor before changing the resolution.

I/O Circuit and Connections ※CW


+5VDC
[Signal] 2-pulse input method (CW rotation signal input)
1 1-pulse input method (operating rotation signal input)
270Ω CW
2 ※CCW
3 2-pulse input method (CCW rotation signal input)
270Ω CCW
1-pulse input method (rotation direction signal input)
4
→ [H]: CW, [L]: CCW
5
HOLD OFF
390Ω ※HOLD OFF
6
GND Control signal for motor excitation OFF
7 → [H]: Motor excitation OFF
10Ω
ZERO OUT
8 ※ZERO OUT (option)
Zero point excitation output signal → Zero point status ON
Pentagon Standard
[Motor] connection connection ※If the power for driving pulse from external is over
BLUE 1 Blue Gray+Red than +5VDC, please connect resistor at the outside.
RED 2 Red Yellow+Black (input voltage max. 24VDC, input current 10-20mA)
ORANGE 3 Orange Orange+White Motor ※In case of standard connection, refer to 'Stepper Motors' section
GREEN 4 Green Brown+Green
※This connection cable color is only for Autonics motors.
BLACK 5 Black Blue+Purple It may different cable color when using other motors.
+
※Power input of 2/3-axis are used as same and
1
[Power] Power I/O terminals are proportional to the number of axes.
2 20-35VDC
-

Unit Description
MD5-HD14-2X

2-axis 1-axis

MD5-HD14-3X

RUN current
switch

Resolution STOP current


switch switch
Function
selection
DIP switch

3-axis 2-axis 1-axis

Motor I/O terminal Power ※Each axis structure is same.


connector terminal terminal

AA-22
5-Phase Stepper Motor Driver (1.4A/Phase, DC Power, Multi-Axis)

Dimensions
MD5-HD14-2X (unit: mm) SENSORS
190
180 4-M3 Tap
CONTROLLERS

MOTION DEVICES

80
66
5
SOFTWARE

C B A
2-axis 1-axis

180

40
(Y)
Closed Loop

20
Stepper System

80
MD5-HD14-3X
(Z)
Stepper Motors

260
249 4-M3 Tap (AA)
Drivers

(AB)
Motion
66 Controllers
5

C B A
3-axis 2-axis 1-axis

245

40
5

80
※Accessory connector specification
Connector Qty.
Accessory
Manufacturer Model No. MD5-HD14-2X MD5-HD14-3X
A Power 2-wire housing VHR-2N 1 1
B Motor 5-wire housing VHR-5N 2 3
C Signal 6-wire housing JST XAP-06V-1 2 3
- Power/Motor terminal pin SVH-21T-P1.1 12 17
- Signal terminal pin SXA -001T-P0.6 12 18

Time Chart 2-pulse input method


1-pulse input method
[H]
[H] CW [L]
CW
[L] CCW [H]
[H] [L]
CCW
[L]
Rotation
position CW CCW
Rotation
position CW CCW
CW

※Do not input CW, CCW signals at the same time in 2-pulse input method.
It may not operate properly if another direction signal is inputted when one of CW or CCW is [H].

AA-23
MD5 Series

Cautions during Use


(Common Specifications of 5-Phase Stepper Motor Driver)
1. For signal input 5. For installation
①Do not input CW, CCW signal at the same time in 2-pulse ①The unit must be installed with heat protection.
input method. Failure to follow this instruction may result in The conditions of ②, ③ should be satisfied.
malfunction. It may not operate properly if another direction signal (※MD5-ND14)
is inputted when one of CW or CCW is [H]. ②In order to increase heat protection efficiency of the driver,
②When the signal input voltage is exceeded the rated voltage, must install the heat sink close to metal panel and keep it well-
connect additional resistance at the outside. ventilated.
③Excessive heat generation may occur on driver. Keep the heat
2. For RUN current, STOP current setting sink under 80℃ when installing the unit.
①Set RUN current within the range of motor's rated current. Failure (at over 80℃, forcible cooling shall be required.)
to follow this instruction may result in severe heat of motor or ④If the unit is installed in distribution panel, enclosed space or
motor damage.
place with heat, it may cause product damage by heat. Install a
②I f motor stops, switching for STOP current executed by the ventilation. (only for MD5-HF28)
current down function. When hold off signal is [H] or current down ⑤For heat radiation of driver, install a fan as below figure. (distance
function is OFF, the switching does not execute. (except MD5-
between the ⓐ fan and the unit: approx. within 70mm, ⓑ min.
ND14)
airflow: 0.71m3/min at least)
③Use the power for supplying sufficient current to the motor.
(only for MD5-HF28)
④Check the polarity of power before operating the unit. (only for
MD5-HD14, HD14-2X/3X, ND14)

3. For rotating motor
(only for MD5-HD14, HD14-2X/3X, ND14)
①For rotating the motor when driver power turns OFF, separate the
motor from the driver.
(if not, the driver power turns ON)
ⓑ Air Flow
②For rotating the motor when driver power turns ON, use Hold
OFF function. 6. For using setting switches
①Be sure that the TEST switch is OFF before supplying the power.
4. For cable connection If the TEST switch is ON, the motor operates immediately and it
may be dangerous.
①Use twisted pair (over 0.2mm2) for the signal cable which should (except MD5-ND14)
be shorter than 2m.
②Do not change any setting switch during the operation or after
②The thickness of cable should be same or thicker than the motor supplying power. It may cause malfunction.
cable's when extending the motor cable.
③Must separate between the signal cable and the power cable
over 10cm.
7. Autonics motor driver does not prepare
protection function for a motor.

8. T
 his product may be used in the following
environments.
① Indoors
② Altitude max. 2,000m
③ Pollution degree 2
④ Installation category Ⅱ

AA-24