Unnamed Project
Unnamed Project
DTM Info
FDT version : 1.2.0.0
DTM name : DDCHEPMSLib
DTM vendor : Emerson
DTM version : 1.4.124
ProgId : DDCHEPMSFDT12Main.CFDT12BO
Dll File : C:\Program Files (x86)\Common Files\DTMstudio\DDCHEPMSFDT12Main.dll
Parameterize
Offline Parameters
Parameter Value Lower Value Upper Value State
Unit mbar ok
LRV -1013,2760 mbar ok
URV -799,9216 mbar ok
Transfer function Linear ok
Damping 0,40 s ok
Process Connector 1/2in,NPTF ok
Process Conn Matl 316 SST ok
O ring matl None ok
Drain vent matl None ok
# of diaph. seals None ok
Seal type Unknown ok
RS isoltr matl Unknown ok
Seal fill fluid Unknown ok
Tag ok
Date 16/03/2006 ok
Descriptor ok
Message ok
Meter type Eng unit ok
Select dec pt pos 2 ok
CM Lower Value 0,00 unknown -999.99 unknown 999.99 unknown ok
CM Upper Value 100,00 unknown -999.99 unknown 999.99 unknown ok
CM Units DEFLT ok
CM xf fnct Linear ok
Local keys Enable ok
Final asmbly num 8147827 ok
Burst mode 252 ok
Burst option Process variables ok
Diagnosis
Status Information
Status Information / Device status
Parameter Value Lower Value Upper Value State
Process applied to the primary variable i 0 ok
s outside the operating limits of the fiel
d device
Process applied to the non-primary varia 0 ok
ble is outside the operating limits of the
field device
Analog output 1 and its digital represent 1 ok
ation are outside the operating range lim
its, and not responding to input
Analog output 1 and its digital represent 0 ok
ation are in fixed mode, and not responsi
ve to input changes
Field device has more status available 0 ok
A reset or self test of the field device ha 0 ok
s occurred, or power has been removed a
nd reapplied
A modification has been made to the con 1 ok
figuration of the field device
Field device has malfunctioned due to a 0 ok
hardware error or failure
Observe
Process Variables
Parameter Value Lower Value Upper Value State
AO 20,800 mA ok
Pres -8,1 mbar ok
Snsr temp 29,6 C ok
Parameterize Online
Online Parameterize
Parameter Value Lower Value Upper Value State
Pres -8,1 mbar ok
AO 20,800 mA ok
LRV -1013,3 mbar ok
URV -799,9 mbar ok
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 2
Parameter Value Lower Value Upper Value State
Temperature coefficients checksum err 0 ok
or
Software error #3 0 ok
Software error #2 0 ok
Software error #1 0 ok
Sensor board not initialized 0 ok
CPU board not initialized 0 ok
Incompatible CPU board & module 0 ok
Online Parameterize / Device setup / Diag/Service / Test device / Status / Status group 3
Parameter Value Lower Value Upper Value State
4k snsr EEPROM error-factory 0 ok
1k snsr EEPROM error-factory 0 ok
4k micro EEPROM error-factory 0 ok
4k snsr EEPROM error-user 0 ok
1k snsr EEPROM error-user 0 ok
4k micro EEPROM error-user 0 ok
1k snsr EEPROM error-user-no out 0 ok
4k micro EEPROM error-user-no out 0 ok
Online Parameterize / Device setup / Diag/Service / Calibration / Sensor trim / Sensor trim points
Parameter Value Lower Value Upper Value State
Lo snsr trim pt 0,0 mbar ok
Up snsr trim pt -8,2 mbar ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Process variables
Parameter Value Lower Value Upper Value State
Pres -8,1 mbar ok
% rnge 471,106 % ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Sensor trim
Parameter Value Lower Value Upper Value State
Snsr trim cal typ Absolute (AP) ok
Online Parameterize / Device setup / Detailed setup / Sensors / Pressure sensor / Sensor trim / Sensor trim points
Parameter Value Lower Value Upper Value State
Lo snsr trim pt 0,0 mbar ok
Up snsr trim pt -8,2 mbar ok
Online Parameterize / Device setup / Detailed setup / Signal condition / Process variables
Parameter Value Lower Value Upper Value State
Pres -8,1 mbar ok
% rnge 471,106 % ok
Online Parameterize / Device setup / Detailed setup / Signal condition / Range values
Online Parameterize / Device setup / Detailed setup / Output condition
fdtCONTAINER application M&M Software GmbH 5 of 8
06/24/2024 13:13 6 of 8
Online Parameterize / Device setup / Detailed setup / Output condition / Process variables
Parameter Value Lower Value Upper Value State
Pres -8,1 mbar ok
% rnge 471,106 % ok
AO 20,800 mA ok
Online Parameterize / Device setup / Detailed setup / Output condition / Analog output
Parameter Value Lower Value Upper Value State
AO Alrm typ Lo ok
Online Parameterize / Device setup / Detailed setup / Output condition / HART output
Parameter Value Lower Value Upper Value State
Poll addr 0 ok
Num req preams 5 2 20 ok
Burst mode 252 ok
Burst option Process variables ok
Online Parameterize / Device setup / Detailed setup / Output condition / Meter options
Parameter Value Lower Value Upper Value State
Meter type Eng unit ok
CMV 471,10 unknown -999.99 unknown 999.99 unknown ok
Online Parameterize / Device setup / Detailed setup / Output condition / Meter options / CM Setup
Parameter Value Lower Value Upper Value State
CM Upper Value 100,00 unknown -999.99 unknown 999.99 unknown ok
CM Lower Value 0,00 unknown -999.99 unknown 999.99 unknown ok
CM Units DEFLT ok
Online Parameterize / Device setup / Detailed setup / Device information / Field device info / Revision #'s
Parameter Value Lower Value Upper Value State
Universal rev 5 ok
Fld dev rev 3 3 253 ok
Software rev 178 ok
Online Parameterize / Device setup / Detailed setup / Device information / Sensor information
Online Parameterize / Device setup / Detailed setup / Device information / Diaphram seal info
Parameter Value Lower Value Upper Value State
Seal type Unknown ok
Seal fill fluid Unknown ok
RS isoltr matl Unknown ok
CM xf fnct Linear ok
Local keys Enable ok
Universal rev 5 ok
Fld dev rev 3 3 253 ok
Software rev 178 ok
Hardware rev 1 ok
Physicl signl code Bell 202 current ok
Final asmbly num 8147827 ok
Dev id 7725203 ok
Burst mode 252 ok
Burst option Process variables ok
Poll addr 0 ok
Num req preams 5 2 20 ok
Distributor Rosemount ok