Thermography Report

Customer / Site
Address

Thermography Date
Thermographer
ModifiedDate
EXECUTIVE SUMMARY

An Infrared Thermal Inspection was performed at the site noted on the preceding Title Page.

PLANT INSPECTED

All of the facilities examined during this visit are listed on the following pages.

FOLLOW UP INSPECTION

We would recommend further Infrared Thermal Inspections at twelve (12) monthly intervals. This
will assist you with the effective maintenance and reduction of unscheduled outages and failure of
your facilities.

We thank you for the opportunity to carry out the Infrared Thermal Inspection and look forward to a
continued mutually beneficial association.
Fault Diagnosis - Criteria

REPORT GUIDELINES - GENERAL

This report has been prepared in accordance with the “Guideline for Infrared Inspections of Electrical
and Mechanical Systems” First Edition, Copyright 1993 Infraspection Institute Inc.
The subsequent delta T (temperature difference) criteria applied to evaluate the temperature severity of
an exception, is the “Experienced-based” criteria for electrical and/or mechanical equipment.

This report is designed to caution against temperature anomalies and/or exceptions that may indicate
the possible deterioration or failure of a component or system. It is not a guarantee against failure, nor
is it a quantitative measure of deterioration or malfunction. This report serves only as an indication of an
exception which may or may not lead to deterioration or failure. It is the responsibility of the contracted
end user to resolve the diagnosis and determine any corrective measures, if required. Excel Power isnot
responsible for determining fault diagnosis or rectification procedures, and as such, it is recommended
that all faults be investigated by qualified personnel of the end user.

In no event shall Excel Power be liable to anyone for special, collateral, incidental or consequential
damages in conjunction with or arising from the use of this survey
Inspection Summary

Image Date Barcode Location Object ID Page Fault Rating


number
00001229 Main Switchboard Changeover Switch 5 1 Normal

00001229 Main Switchboard Distribution Section 6 1 Normal

00001229 Main Switchboard DB1a 7 1 Normal

00001233 Coldroom outside Distribution Board 8 1 Normal

4 /
FLIR0336.jpg

File information
Created 17/01/2024 12:06:00 PM
Camera model FLIR T540
Camera serial 79320250
Lens FOL18D
Emissivity 0.98
Atmospheric temp. 24.0 °C

Measurements
Sp1 37.4 °C
Li1
Max 38.3 °C
Avg 36.6 °C
Min 34.2 °C
Fault Rating

1 Normal

Image Data
Company
Barcode 00001229
Location Main Switchboard
Object ID Changeover Switch
Fault Description No thermal fault found
Remedy Maintain regular thermal imaging inspections
Fault Rating Normal
Thermographer

Corrective Action Performed:


Work Performed Repaired By:
Date:

5 /
FLIR0337.jpg

File information
Created 17/01/2024 12:09:23 PM
Camera model FLIR T540
Camera serial 79320250
Lens FOL18D
Emissivity 0.98
Atmospheric temp. 24.0 °C

Measurements
Sp1 36.8 °C
Li1
Max 37.4 °C
Avg 36.4 °C
Min 34.9 °C
Fault Rating

1 Normal

Image Data
Company
Barcode 00001229
Location Main Switchboard
Object ID Distribution Section
Fault Description No thermal fault found
Remedy Maintain regular thermal imaging inspections
Fault Rating Normal
Thermographer

Corrective Action Performed:


Work Performed Repaired By:
Date:

6 /
FLIR0338.jpg

File information
Created 17/01/2024 12:10:33 PM
Camera model FLIR T540
Camera serial 79320250
Lens FOL18D
Emissivity 0.98
Atmospheric temp. 24.0 °C

Measurements
Sp1 36.4 °C
Li1
Max 37.0 °C
Avg 36.4 °C
Min 35.4 °C
Fault Rating

1 Normal

Image Data
Company
Barcode 00001229
Location Main Switchboard
Object ID DB1a
Fault Description No thermal fault found
Remedy Maintain regular thermal imaging inspections
Fault Rating Normal
Thermographer

Corrective Action Performed:


Work Performed Repaired By:
Date:

7 /
FLIR0339.jpg

File information
Created 17/01/2024 12:28:13 PM
Camera model FLIR T540
Camera serial 79320250
Lens FOL18D
Emissivity 0.98
Atmospheric temp. 24.0 °C

Measurements
Sp1 44.8 °C
Li1
Max 48.1 °C
Avg 42.6 °C
Min 39.3 °C
Fault Rating

1 Normal

Image Data
Company
Barcode 00001233
Location Coldroom outside
Object ID Distribution Board
Fault Description No thermal fault found
Remedy Maintain regular thermal imaging inspections
Fault Rating Normal
Thermographer

Corrective Action Performed:


Work Performed Repaired By:
Date:

8 /