COMMENTS
COMMENTS
Reinforcement.
G.L.
SECTION B-B
SECTION A-A 1) WHAT IS C/C DISTANCE OF SUPPORT ? NOT SHOWN IN DRG KINDLY INCORPORATE
2) PROVIDE SBC REPORT
3) HOW TO FIND SCOUR DEPTH IN DRG IF AS PER SITE IS INCRESED THEN HEIGHT OF PEDESTAL
ALSO INCERESED AND DESIGN ALSO CHANGE SO KIDNLY INCORPORATE DEPTH OF FOUNDATION
BELOW GL
B
4) IF THEIR ARE REIVER THEN ALSO CONSIDERED VELOCITY OF WATER ACT ON PEDESTAL
5) SEISMIC ANALYSIS REQUIRED TO INCORPORATE
6) PEDESTAL DESIGN AS COLUMN SO CHECK MINIMUM STEEL AS PER IS 456
7) ADD PROPER NOTES FOR SBC , VELOCOTY OF WATER , SEISMIC ZONE ETC
12# @300 c/c Surface 8) IN PEDESTAL PLAN DETAIL - STEEL NOT SHOWN PROPERLY
Reinforcement. 9) SHOWN CONNECTION DETAIL OF PIPE AND PEDESTAL IF ANY