Chapter 3 Reinforced Concrete Walls - Design Example
Chapter 3 Reinforced Concrete Walls - Design Example
1
A shear wall of length 5 m and thickness b = 300 mm is considered and subjected to the following
forces (table 1 below). The overall height of the shear wall is, H = 4m. Deign the shear wall using
C-25/30 and S-415 materials.
Section A-A
A H=4m A
b
L=5m
Figure 3.3: Bar belled reinforced concrete wall
Solution:
Step 1: Material Properties
For C-30 Concrete:
γc = 1.5 for Class − I workmanship EBCS − 2 , Table 3.1, Page − 22
𝑁
𝑓𝑐𝑘 = 25
𝑚𝑚2
0.85𝑓𝑐𝑘 0.85 ∗ 25 𝑁
𝑓𝑐𝑑 = = = 14.17
𝛾𝑐 1.5 𝑚𝑚2
2 2
0.21(𝑓𝑐𝑘 )3 0.21(25)3 𝑁
𝑓𝑐𝑡𝑑 = = = 1.197
𝛾𝑐 1.5 𝑚𝑚2
1 1
𝐸𝑐𝑚 = 9.5(𝑓𝑐𝑘 + 8)3 = 9.5(25 + 8)3 = 29 𝐺𝑝𝑎
Page 7 of 17
For S-460 Reinforcing Steel:
γc = 1.15 for Class − I workmanship EBCS − 2 , Table 3. , Page − 22
𝑁
𝑓𝑦𝑘 = 415
𝑚𝑚2
𝑓𝑦𝑘 415 𝑁
𝑓𝑦𝑑 = = = 360.87
𝛾𝑠 1.15 𝑚𝑚2
Step 2: Design Load Calculation
The load combinations that are used for the design according to EBCS:2-1995:
𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 1 = 1.3𝐷𝐿 + 1.6𝐿𝐿
𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 2 = 0.75 𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 1 + 𝐸𝑄𝑋
𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 3 = 0.75 𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 1 − 𝐸𝑄𝑋
𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 4 = 0.75 𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 1 + 𝐸𝑄𝑌
𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 5 = 0.75 𝐶𝑜𝑚𝑏𝑖𝑛𝑎𝑡𝑖𝑜𝑛 1 − 𝐸𝑄𝑌
The calculated axial load, moment and shear force to be considered for the design by using the
above combinations are shown in the following table:
Table 2: Calculation of Axial load, Moment and shear force using load combinations
Load Combination Axial Load (KN) Moment (kNm) Shear Force (KN)
Combination 1 2500 1000 80
Combination 2 2275 6750 960
Combination 3 1475 -5250 -840
Combination 4 2275 6750 960
Combination 5 1475 -5250 -840
From the five load combinations the maximum values obtained are:
𝑁𝑠𝑑 = 2500 𝑘𝑁
𝑀𝑑 = 6750 𝑘𝑁
𝑉𝑑 = 960 𝑘𝑁
Step 3: Determination of design eccentricity in both directions:
𝑒𝑡𝑜𝑡 = 𝑒𝑎 + 𝑒0 + 𝑒2
Accidental (additional) eccentricity due to various imperfections:
Page 8 of 17
𝐻𝑒
𝑒𝑎 = ≥ 20 𝑚𝑚, 𝐸𝐵𝐶𝑆 2 − 1995 𝑆𝑒𝑐𝑡𝑖𝑜𝑛 4.4.3
300
Where; He = is the effective buckling length of the wall. Assuming the top end of the shear wall to
be simply supported, 𝐻𝑒 = 0.7𝐻; where H = height of wall
𝐻𝑒 = 0.7𝐻 = 0.7 ∗ 4 = 2.8 𝑚
2800
𝑇ℎ𝑒𝑟𝑓𝑜𝑟𝑒, 𝑒𝑎 = = 9.33 𝑚𝑚 < 20 𝑚𝑚 ∴ 𝐶𝑜𝑛𝑠𝑖𝑑𝑒𝑟 𝑒𝑎 = 20 𝑚𝑚
300
Step 4: Determination of design eccentricity in L direction:
First order eccentricity:
𝑀𝑑 6750
𝑒0 = = = 2.7 𝑚 = 2700 𝑚𝑚
𝑁𝑠𝑑 2500
Second order eccentricity:
Checking the slenderness of the wall: A wall may be considered as short walls when the ratio of
its effective height to its thickness does not exceed 7. Otherwise it shall be considered slender.
𝐻𝑒
≤ 7 𝑆ℎ𝑜𝑟𝑡 𝑊𝑎𝑙𝑙
𝑏
𝐻𝑒
> 7 𝑆𝑙𝑒𝑛𝑑𝑒𝑟 𝑊𝑎𝑙𝑙
𝑏
Where He = is the effective height of the wall.
The effective height of reinforced concrete walls in non-sway mode is given by: 𝐻𝑒 = 𝛽𝐻
Effective height of the wall:
Where: H = is the story height of the wall
β = is the coefficient which is determined from the following equation.
Page 10 of 17
𝑒𝑡𝑜𝑡 124.86 𝑚𝑚
𝑒𝑟𝑒𝑙 = = = 0.415
𝑏 300 𝑚𝑚
Equivalent eccentricity: eeq
𝑒𝑒𝑞 = 𝑒𝑡𝑜𝑡 (1 + 𝑘𝛼)
Where;
𝑒𝑒𝑞 = 𝑡𝑜𝑡𝑎𝑙 𝑒𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑖𝑡𝑦 𝑖𝑛 𝑡ℎ𝑒 𝑑𝑖𝑟𝑒𝑐𝑡𝑖𝑜𝑛 𝑜𝑓 𝑡ℎ𝑒 𝑙𝑎𝑟𝑔𝑒𝑟 𝑟𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑒𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑖𝑡𝑦
𝑘 = 𝑟𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑒𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑖𝑡𝑦 𝑟𝑎𝑡𝑖𝑜.
𝛼 = is obtained from table 4.1 of EBCS: 2-/1995(which is given below) as a function of the relative
normal Force,
𝑁𝑠𝑑
𝑣=
𝑓𝑐𝑑 ∗ 𝐴𝑐
Relative eccentricity ratio: The eccentricity ratio, for a given direction, is the ratio of the total
eccentricity, allowing for initial eccentricity and second-order effects in that direction, to the
column width in the same direction.
𝑠𝑚𝑎𝑙𝑙 𝑟𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑒𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑡𝑦 0.415
𝑅𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑒𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑖𝑡𝑦 𝑟𝑎𝑡𝑖𝑜, 𝑘 = = = 0.734
𝑙𝑎𝑟𝑔𝑒𝑟 𝑟𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑒𝑐𝑐𝑐𝑒𝑛𝑡𝑟𝑖𝑐𝑡𝑦 0.565
2500 𝑘𝑁
𝑅𝑒𝑙𝑎𝑡𝑖𝑣𝑒 𝑁𝑜𝑟𝑚𝑎𝑙 𝐹𝑜𝑟𝑐𝑒, 𝑣 = = 0.1176 ≥ 1
(14.17 ∗ 10)2 𝑘𝑁/𝑚2 (0.3 ∗ 0.5)
Therefore, v = 0.1176
𝑒𝑒𝑞 = 𝑒𝑡𝑜𝑡 (1 + 𝑘𝛼)
Where;
𝑒𝑡𝑜𝑡 = is total eccentricity in the direction of the larger relative eccentricity; 𝑒𝑡𝑜𝑡 = 2824.53 𝑚𝑚
Page 11 of 17
𝑀𝑠𝑑 = (4.31226 𝑚)(2500 𝑘𝑁) = 10780.65 𝑘𝑁 − 𝑚
Step 7: Designing vertical reinforcements
The area of vertical reinforcement shall not be less than 0.004Ac, nor more than 0.04Ac.
The upper limit shall be observed even where bars overlap.
The diameter of vertical bars shall not be less than 8 mm.
The spacing of vertical bars shall not exceed twice the wall thickness nor 300 mm.
Area of reinforcement
𝜔𝑓𝑐𝑑 𝐴𝐶
𝐴𝑆 =
𝑓𝑦𝑑
Page 12 of 17
𝐴𝑆,𝑡𝑜𝑡𝑎𝑙 6000 𝑚𝑚2
𝐴𝑆 = = = 3000 𝑚𝑚2
2 2
ℎ𝑎𝑆 5000 𝑚𝑚 ∗ 153.93 𝑚𝑚
𝑆= = = 256.56 ≈ 250 𝑚𝑚
𝐴𝑆 3000 𝑚𝑚2
2𝑏 = 2 ∗ 300 = 600 𝑚𝑚
𝑆𝑚𝑎𝑥 ≤ { ∴ 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
300 𝑚𝑚
Therfore, provide ∅14𝑚𝑚 vertical bars @ c/c 250 mm.
Step 8: Designing of shear reinforcements
Check for the diagonal compression failure of concrete, VRD:
Section resistance;
𝑉𝑅𝐷 = 0.25𝑓𝑐𝑑 𝑏𝑤 𝑑 = 0.25 ∗ 14.17 ∗ 300 ∗ 4750 = 5048.06 𝑘𝑁 ≥ 𝑉𝑑 = 960 𝑘𝑁 𝑂𝐾!
Note here that if VRD is less than Vd (i.e, VRD < Vd) the possible measures are:
Increase the grade of concrete:
Increase the cross-section (as it is barbell type shear wall i.e. fixed in the two edges it
means increasing the thickness of the wall).
𝑉𝐶 = 0.25𝑓𝑐𝑡𝑑 𝑘1 𝑘2 𝑏𝑤 𝑑 + 𝑉𝑐𝑛
𝑏𝑤 𝑑
𝑉𝑐𝑛 = 0.10 𝑁
𝐴𝐶 𝑠𝑑
𝑘1 = 1.6 − 𝑑 ≥ 1, 𝑤ℎ𝑒𝑟𝑒 𝑑 𝑖𝑠 𝑖𝑛 𝑚
𝑑 = ℎ − 𝑑′
𝑑′
𝑇𝑎𝑘𝑒 = 0.05, 𝑑 ′ = 0.05ℎ = 0.05 ∗ 5000 = 250 𝑚𝑚
ℎ
Page 13 of 17
𝑘2 = 1 + 50𝜌 ≤ 2.0
𝐴𝑠 6000 𝑚𝑚2
𝜌= = = 0.0042
𝑏𝑤 𝑑 (300 𝑚𝑚)(4750 𝑚𝑚)
𝑏𝑤 𝑑
𝑉𝐶 = 0.25𝑓𝑐𝑡𝑑 𝑘1 𝑘2 𝑏𝑤 𝑑 + 0.10 𝑁
𝐴𝐶 𝑠𝑑
300𝑚𝑚 ∗ 4750𝑚𝑚
𝑉𝐶 = 0.25 ∗ 1.197 ∗ 1 ∗ 1.21 ∗ 300 𝑚𝑚 ∗ 4750 𝑚𝑚 ∗ 10−3 + 0.10 ( ) ∗ 2500 𝑘𝑁
300𝑚𝑚 ∗ 5000𝑚𝑚
So, design for shear reinforcement EBCS provision for area of shear reinforcement (horizontal
reinforcement), According to section 6.2.1.2 of EBCS-2
Design for horizontal shear forces in the plane of the wall shall be in accordance with provisions
for beams give on EBCS 2/1995 section 4.5.3
Sections located closer to the base than a distance or, whichever is less, be designed for the
shear at . Or
The area of horizontal reinforcement shall not be less than one-half of the vertical reinforcement
𝐴𝑉 𝑑𝑓𝑦𝑑
𝑆= , 𝑤ℎ𝑒𝑟𝑒 𝑉𝑆 = 𝑉𝑑 − 𝑉𝑐 … . 𝐸𝐵𝐶𝑆2 − 1995 − 𝑆𝑒𝑐𝑡𝑖𝑜𝑛 4.5.4(4)
𝑉𝑆
2𝑏
𝑆𝑚𝑎𝑥 ≤ {
300𝑚𝑚
The horizontal reinforcement shall enclose the vertical reinforcement. The horizontal bars shall
enclose and be tied to the vertical bars so as to form rigid mat.
𝑉𝑑 = 960 𝑘𝑁
𝑏 300 𝐿 5000
= = 150 𝑚𝑚 < = = 2500 𝑚𝑚
2 2 2 2
Page 14 of 17
Position of Vc = 515.98 kN, using similarity of triangles will be;
515.98 𝑘𝑁 960 𝑘𝑁
= ∴ 𝑥 = 2149.92 𝑚𝑚
𝑥 4000 𝑚𝑚
Page 15 of 17
At the critical point (@ 150 mm from the base), the design shear using similarity of triangles will
be:
𝑉𝑑 960 𝑘𝑁
= ∴ 𝑉𝑑 = 924 𝑘𝑁
(4000 𝑚𝑚 − 150 𝑚𝑚) 4000 𝑚𝑚
Remember here that the critical section for beam is at d distance from the face of the column or
support. Similarly, the distribution of shear reinforcements in this wall is as follows.
For region between x = 0 and x = 150mm, design for shear at x = 150 mm, (Vd = 924 kN). Assume
Ø8mm shear reinforcements are going to be used:
𝜋𝐷2 𝜋(8)2
𝑎𝑆 = = = 50.26 𝑚𝑚2
4 4
2𝑏 = 2 ∗ 300 = 600 𝑚𝑚
𝑆𝑚𝑎𝑥 ≤ { ∴ 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
300𝑚𝑚
2 𝑁
𝐴𝑉 𝑑𝑓𝑦𝑑 (50.26 𝑚𝑚 )(4750 𝑚𝑚) (360.87 𝑚𝑚2 )
𝑆= = = 505.06 𝑚𝑚 > 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
𝑉𝑆 170.58 ∗ 103 𝑁
2𝑏 = 2 ∗ 300 = 600 𝑚𝑚
𝑆𝑚𝑎𝑥 ≤ { ∴ 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
300𝑚𝑚
2 𝑁
𝐴𝑉 𝑑𝑓𝑦𝑑 (50.26 𝑚𝑚 )(4750 𝑚𝑚) (360.87 𝑚𝑚2 )
𝑆= = = 505.06 𝑚𝑚 > 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
𝑉𝑆 170.58 ∗ 103 𝑁
Page 16 of 17
2𝑏 = 2 ∗ 300 = 600 𝑚𝑚
𝑆𝑚𝑎𝑥 ≤ { ∴ 𝑆𝑚𝑎𝑥 = 300 𝑚𝑚
300𝑚𝑚
Page 17 of 17