We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 11
cure
International Conference on Large High Voltage Electric Systems
112, beuavard Houssmann ~ 75008 Paris
1974 Session — 21-29 August
12-03 °
A CRITICAL ASSESSMENT OF METHODS OF MEASURING PARTIAL DISCHARGES
IN EHV TRANSFORMERS
J.L,DOUGLAS F.C. PRATT —_—F, RUSHTON,
Centra Electricity Contra lectciy Ferrand
Generating Bosra Generating Board
(Unitas Kingdom)
SUMMARY
The paper reviews past and present practice in partial discharge calibration and measurement
techniques. Comment 1s made on these practices in the light of experimental work which has shown the
existence of long and short partial discharge pulses and which has investigated, over a range of measure
ment frequencies, the responses of ri. meters and a transformer winding to such pulses
In order to minimise calibration and measurement errors which are shown to be very large at IMHz,
when measuring such pulses, the use of measurement frequencies in the range 50 to 100 kHz is recom
‘mended in conjunction with narrow-band instruments.
The application of partial discharge measurement during reduced level, induced voltage tests on
transformers is discussed.
Bandwidth, Calibration, Measuring frequency, Partial discharge, Pulse shape, Transformer, Voltage test.
REPORT
1. INTRODUCTION
‘The use of partial discharge measurement as one criterion of goodness during voltage testing of
transformers has been studied during the past twenty years. The methods of measurement and their
interpretation have not been firmly agreed and it is only recently that charge measurements in
picocoulombs have become generally accepted as more soundly based than the previous almost total use
of microvolts.
Recent developments in specifications admit that the very high level induced voltage test may now
be superseded by an induced voltage test of much lower level for 2 longer time, However, this lower
voltage test removes from the purchaser the assurance, however nebulous, that a transformer which has
passed a test at high voltage level is likely to give good service experience. As yet there is no firm
evidence that the longer term test is equivalent to the short term, high voltage test. It follows that12-03 -2
some other assurance, such as partial discharge measurement, must be given to the purchaser as to the
soundness of the transformer insulation, The extended test time permits this measurement to be more
significant than during the one minute test.
‘Thus, there is a need for meaningful partial discharge measurements to be agreed before the introd-
uetion of these longer time tests. Recent recommendations by Working Group 01 of CIGRE Study
Committee 12 [1] have gone some way towards establishing soundly based methods of measuring partial
discharges in transformers, The present paper contains some supplementary data which it is hoped may
lead to a standardisation of the basis of measurements so that valid comparisons can be made between
transformers of different sizes and constructions.
2. REVIEW OF LITERATURE
Although sensitive partial discharge detectors and measuring techniques were developed over twenty
years ago [2], it was 1957 before results of corona (partial discharge) measurements in transformers were
first published by Adolphson and Vogel (3]. Their method of measurement was based on a modified
detector described by Quinn [4]. In the discussion of Adolphson and Vogel's paper, questions were raised
by Gehrig, Oliver and Evans et al relating to damaging effects of discharges and comparison of charge and
RLV, measurements, which have still not been answered satisfactorily. About that time, radio interference
‘meters were beginning to be used for partial discharge measurements in transformers. A NEMA Specification
[5] standardised the measuring procedures for assessing radio noise and, apart from minor modifications,
the method is largely unchanged today [6]. Essentially, the circuit employs a coupling capacitor of around
1000 pF to connect a specified resistance between line terminal and earth ; the Ril. voltage is measured
actos this resistor. Where it differs from a conventional partial discharge detector is in the method of
calibration. The NEMA method of calibration relates the values measured at the bushing tap to thoss which
‘would be obtained at the sample terminals in the absence of a coupling capacitor and with a pure resist-
ance of specified value,
Reference to the use of the transformer bushing as a coupling capacitor was made in 19$7 [7] but
it was not until 1965 that publications by Brown [8] and Narbut [9] established the validity of the bushing
tap method for transformer partial discharge or R.ILV. measurements. This method effectively eliminates
the need for additional coupling capacitors and it is now generally accepted as a reliable and convenient
method, whatever type of measuring instrument is used.
In Europe, ri, meters have been used extensively, but investigations with partial discharge detectors
indicated that the latter, calibrated in terms of charge in picocoulombs, have some advantages [10]. A
few years earlier, the quadratic mean method of charge measurement was developed by Renaudin [11]
jin France where much experience has been gained on transformers and other equipment. The main
advantage claimed for the quadratic mean method is that it responds mainly to the large discharges
but that numerous small discharges may contribute to the reading. At present there are insufficient data
to make a strict comparison between the quadratic mean, peak and quasi-peak methods of measurement
in transformers,
However, it is now generally accepted that the loss of charge at the transformer terminals is the
most informative partial discharge parameter to be measured, even though there is no simple relationship
between the apparent charge at the terminals and the damage to the dielectric involved at the discharge
site,
is not
It is felt that some of the difficulties in interpretation of results have arisen because it
clearly established which discharge quantities are being considered. There are four different discharge
‘quantities which are of interest in a transformer12-03
1) the charge dissipated at the source
2) the charge at the winding adjacent to the discharge site
3) the charge at the appropriate transformer terminals
4) the charge measured at the bushing tap.
‘The relationship between (3) and (4) can be established by the calibration procedure specified by the
LE.C, [12]. Attenuation along windings accounts for the difference between (2) and (3). It has been
claimed that the magnitude of (2) can be estimated from results of measurements at different terminals
[13], [26]. In the past, specifications have generally referred to partial discharge measurements at transf-
ormer line terminals, but WGO! of CIGRE Study Committee No. 12 have proposed that measurements
should be made at more than one terminal [1]. The actual charge quantity (1) cannot be measured,
although energy dissipated in a cavity can be estimated in a simple case [14] but is never used in the
complicated case of a transformer.
This Working Group also recommend that the measuring impedance should be essentially resistive
and within the range of 50 to 200 ohms. Previous work has shown that high sensitivities can be
achieved by the use of high input impedances [15] but care must be taken that long time constants of
the input circuit do not influence the results, NEMA Publication 107A, 1964, specifies that the measur-
ing impedance should be 150 ohms ; if the ri, meter has a lower input impedance then some form of
high impedance coupler is required to meet the specification. The advantages of this additional complication
are obscure, since neither sensitivity nor signal/noise ratio are increased by the higher input impedance.
‘The question of bandwidth has led to some confusion and the impression is gained from the
literature that true charge measurements can be made only with a wide band detector. In fact, charge in
individual pulses can be measured over a wide range of bandwidths [16] provided that the measuring
circuit is calibrated correctly [17]. Mole [16] has shown that the percentage error difference between
narrow and wide band detectors is small over a wide range of frequencies. One of the advantages of wide
band measurements on transformer windings is improved resolution of pulses but this effect is relatively
small ; another advantage is said to be that variations of meter response with frequency are averaged out,
but results on transformers indicate that an extremely wide band would be necessary to achieve this and
extrancous noise could then be a problem.
‘The measurement frequency is another factor which is controversial. IMHlz is specified by NEMA
whereas a much lower frequency has been advocated [18]. Both theoretical and practical investigations
indicate that partial discharge measurements on transformers should be made at less than 200 kHz [19]
although the precise frequency has never been specified unambiguously. Other authors [1] have susgested
that any measurement frequency is satisfactory, provided that high background disturbances and high at-
tenuation points are avoided. There is little doubt that the measurement frequency has a greater effect on
the measured values of partial discharges arising from sources within a transformer winding than for
sources near the measuring terminal
‘The types of instrument used to measure discharge magnitudes can vary in their response to repeated
pulses. During the past decade, much has been written about the advantages and disadvantages of the
various types of r.i, meters or partial discharge detectors in common use but no clear decisions can be
‘made from the published data, Apart from different calibration methods, data are often incomplete and
there have been no straight comparisons made between the various instruments. The conflicting statements
made, for example, on the relationship between picacoulombs and microvolts [20], [21] are due, at least
in part, to different measurement frequencies and bandwidths, different calibration methods and even
to different points of measurement on the transformer rather than the measuring instruments themselves.
The effect of the type of winding on the propagation of partial discharge pulses has been studied by
Kawaguchi and Yanabu [22] and by Bertula et al [23]12-03 4
3. EXPERIMENTAL WORK ON PULSE SHAPES OF PARTIAL DISCHARGES
3.1 Transformer Insulation Samples - As part of 2 programme of experimental work on discharge
measurement, the waveshapes of current pulses emanating from transformer insulation samples were investig-
ated. The pulses produced across a 1,000 ohm non-inductive resistor in series with the test sample were
recorded oscillographically. Of the many types of sample tested, three forms are shown in Figure 1,
which also includes some typical results of pulse shapes obtained. The SO Hz test voltage was of a level
just above inception of partial discharges. Long pulses of up to 16 usec duration were observed but many
pulses were of less than 1 usec overall time. In most cases, both short and long duration pulses were
observed on the same samples. This confirms observations by Bertula et al (23] and Izeki et al (24).
‘Typet asoanee
uecrione ammcenewr PULSE mavens
;
5.2000 KX. covouern se
Perea Eh anmsee
Te, raneT PAPER CoveRNG
: tee
1
ae a
qi me,
2Son120 x20
Ca)
Te, es
Figure 1 - Typical electrode arrangements and waveshapes
‘There was a tendency for long duration pulses to be associated with observed surface discharges and
it is noteworthy that during tests on paper covered conductors without oil duets, any pulses observed
were of short duration, In general, the short pulses were an order of magnitude lower in charge quantity
than the longer pulses and this may account for the first and second corona pulses which have been
described previously [25].
‘The partial discharge pulses recorded during the above tests were too random and variable to directly
measure the frequency spectra accurately. For subsequent measurements, simulated pulses were used to
produce the steady repetitive signals required. Pulses of 0.1/0.5 usec and 4/12 psec, representing pulses
towards the extremes of the measured values, were employed for the tests reported in the following
sections. These pulses were obtained from a high-impedance source and injected either across the meter
or at appropriate points in a transformer winding. This procedure is the same as used in conventional
charge calibrations.
3.2 Effect of Pulse Shape on Detector Response - The response of ri. meters to the two pulse shapes was
‘measured over a frequency range from 10 kHz to 1.5 MHz. The results shown in Figure 2 were obtained at a pulse
repetition rate of 100 pulses /s ; measurements at other rates between 50 and 10,000 pulses/s confirmed
earlier reports [20], [21], that the maximum error due to pulse repetition frequency would not exceed
6 GB for an r.i, meter complying with NEMA Specification 107 A. 1964.
Tests were repeated with the ri. meter connected to a simulated bushing tap (a 780/220 pF
capacitance divider). Results of pulses of both shapes fed to the divider were identical to those shown12-03
» uns os Puss
n
12s PULSES
‘a
L.METER READING, 2/1 .¥
w ie i
MEASURING FREQUENCY,
Figure 2 - Etfect of pulse shape on rl, meter reading
Figure 2 up to a measurement frequency of $00 kHz. Above this frequency there was a slight reduction
in meter reading due to the shunting effect of the 2200 pF capacitor. When an additional capacitance of
5000 pF (representing transformer terminal capacitance) was connected in parallel with the simulated
bushing, the shapes of the curves were similar to those obtained previously but the level was about 16 dB
down throughout the measurement frequency range, which is in accordance with theory. All results quoted
in this section refer to a bandwidth of 4.5 kHz and a measuring impedance of 150 ohms. It should be
noted that the results shown in Figure 2 are frequency dependent which would not be the case if
calibration was made using the conventional pulse calibrator of short front and long tail (16)
Measurements with two partial discharge detectors of the ERA type [2], one of 5 kHz bandwidth
at 500 KHz centre frequency (Model 2) and one with 10-60 kHz bandwidth (Model 3) confirmed that
short pulses were more accurately measured at higher frequencies and long pulses required a lower
measurement frequency
3.3 Effect of Transformer Winding - Pulses of the same waveshapes as used for the determination of meter
response were injected at various points along the winding of an e.h.v. single phase transformer (Pig. 3).
An ri. meter was connected across the lower end of a capacitance divider representing the bushing tap
4as shown. Pulse shapes of the injected pulses and those at the simulated bushing tap were recorded for
injection points at 100 %, 75 %, SO % and 25 % of the winding length ; ri, meter readings were noted
over the frequency range of 10 kHz to 1.$ MHz for each pulse shape and injection point.
With pulses injected across the complete winding, the results of bushing tap measurements shown
in Figure 4 were obtained. The results of measurements at 100 %, 75 % and SO % injection points are
illustrated in Figure 5 for long pulses and Figure 6 for short pulses.+ L toupee
Et Faoopr [soe
3 soooaRr
Figure 3 - Transformer winding measurements
FL METER READING, «6
sees pases
ie 18 100
requeucr, mo
Figure 4 - Effect on r4, meter reading of pulse shape injected at 100 %e position
LLMETER READING,
FREQUENCY,
Figure 5 - Effect of pulse injection point - 4/12 psec pulsesa 12-03
L,WETER READING, 2
FREQUENCY, Me
Figure 6 + Effect of pulse injection point - 0.1/0.5 pisee pulses
4. DISCUSSION
4.1 Experimental Results - The results reported in Section 3 were obtained when injecting long and short
pulses such as observed on samples, into a full size transformer winding. No work has yet been done in
the programme to examine the actual pulse shapes emanating from a transformer undergoing voltage test
but it was. observed that considerable distortion of the injected pulses occurred between the injection and
‘measuring points. It is reasonable to suppose that similar distortion would occur for any partial discharge
pulses initiated during a voltage test and that minimum distortion would occur in the case of pulses
emanating from @ source at or near the line end. Pulses emanating from a source further down the
winding would be expected to have reduced rates of rise when seen at the bushing tap but the extent
to which this would occur would be dependent on the a value of the winding and on its propagation
characteristics. It is possible, therefore, that long and short pulses of the type found on samples would
only be detectable during a voltage test if the source of discharge was very close to the line end. The
lack of evidence concerning pulse shapes occurring during a transformer test does not invalidate the
conclusions to be drawn from the Section 3 results since any slowing of the rate of rise would mean
a smaller high frequency component,
Examination of Figure 2 shows that if a meter is calibrated using a given pulse shape and the
pulses then measured are of a different shape, then the indicated values of pulse charge may be consider
ably in error. Assuming that the action of a winding is to distort pulse shapes so as to lessen the h.f.
content, it follows that the practical case of partial discharge measurement requires good Lf. sensitivity
and therefore a low measurement frequency. Furthermore, due to the long pulses being an order of
‘magnitude larger than the short pulses, it is believed that the former may be more indicative of insulation
damage and therefore should be the more accurately measured,
4.2 Methods of Measurement - If the acceptance criterion is no discharge at working voltage, then the
choice of measuring instrument is unimportant, provided that the sensitivity can be shown to be
adequate. If specifications are worded such that a certain discharge quantity is tolerable at a specified
test voltage, then calibration of the circuit is essential in terms of discharge quantity. It is assumed that
by the time the long term lower voltage test is introduced it will be generally accepted that calibration
in terms of picocowlombs is more logical than microvolts, irrespective of the type of measuring instrument
employed. The difficulties in changing from microvolts to picocoulombs are well appreciated but it is
hoped that the transition from one to the other will not extend over too long a period of time.
At the present time, there are no published data to indicate any one instrument has particular
advantages over others. Until comparative tests have been made on transformers with the various12-03 ~8—
detectors of interest, it must be assumed that laboratory experience is typical and that, provided it mects
the CIGRE recommendations, the instrument may record peak, quasi-peak, r.m.s. or mean values.
‘The differences are small compared with other possible large sources of error. It is generally agreed that
an oscillographic display is very helpful to identify spurious signals and in interpretation of results.
Experience indicates that the choice of measuring impedance is relatively unimportant, although it
has been recommended [1 ] that values should lie between 50 and 200 ohms and be essentially resistive
in character. Measurements with r.i. meters having input impedances between 50 and 150 ohms gave similar
results, apart from the question of sensitivity. The need for a purely resistive impedance is questioned,
since the authors’ experience with narrow band detectors does not support this. The requirement for 2
purely resistive impedance implies that with a high frequency measurement at a bushing tap, added
inductance must be used to compensate for the capacitance in parallel with the instrument input imped-
ance. This appears to be an unnecessary complication unless measuring sensitivity is inadequate and is
unacceptable if measurements are to be made at more than one frequency.
Wide band measurements are often recommended for transformer partial discharge tests. The main
advantage of a wide band detector is in the resolution of pulses and this is considered to be of limited
value in a transformer partial discharge test. Also, the practicability of making wide band measurements
in factories where the background noise level is high is doubted. On the other hand, although doubts are
often expressed about the validity of narrow band measurements, instruments of the ri, type have some
‘net advantages including the ability to select low background noise level, calibration over a range of
frequencies to select maximum sensitivity, and the capability of measurements over a wide frequency range
which can be informative about pulse attenuation. Many of the criticisms which have been levelled at the
use of ri, meters are considered to have been associated with the method of calibration and the insistence
on employing a measuring frequency of 1 MHz,
‘The use of such a high measurement frequency has been criticised by many authors but the recom-
mendations currently proposed adhere to a frequency range between 0.1 and 1.2 MHz. The main reason
advanced for a lower frequency is based on the response of transformer windings which attenuate most
frequencies above about 200 kHz. This present paper goes further and shows that the larger (and possibly
most damaging) pulses are of slow rise time even when the source of discharge is at the measurement
terminals. Therefore the high frequency components of such pulses are small and large errors exceeding,
20 dB may be introduced when measurements are made at high frequencies (Fig. 2). These graphs indicate
that there is no ideal frequency at which both short and long pulses can be accurately measured but at
frequencies in the range 100 to 200 kHz, the errors would be relatively small ; less than 6 dB. However,
the existence of these short pulses at transformer terminals is dubious, because the 0.5 sce tails measured
in section 3.1 were very dependent on the measuring impedance (Fig. 7). Therefore, it is considered that
the decrease in meter reading at frequencies below 300 kHz, because of the short tail, would not be
observed in practice. In any case, results show that the 0.1/0.5 psec pulses are extreme values and the
sm
TAR DECAY TE, 6
Row se TE 2
cy
ry iw 1 ‘mm
DETECTOR RESISTANCE, cbs
Figure 7 - Bffect of different values of detector resistor on a fast pulse.9 12-03
actual charge in these pulses is small. For these reasons, a value of between 50 and 100 kHz appears to
be the most suitable frequency for measuring the majority of pulses at transformer terminals.
Results illustrated in Figure 4 confirm that this frequency range is suitable for measuring partial
discharges occuring at transformer terminals. If the discharge source is within the winding, the magnitude
cannot be accurately measured, no matter at how many terminals the measurements are made. Again
it is seen from Figure 4 that the frequency range of 50 to 100 kHz appears to give the minimum error
for this particular transformer if the pulses are of the long type. But, because of the resonant peaks
and troughs, it is impossible to specify one particular frequency for a narrow band instrument. A wide
band instrument covering this range would be suitable but for the problem of extraneous disturbances.
Therefore, it is suggested that measurements should ideally be made at a few selected frequencies and
the mean value quoted as the estimated discharge magnitude. However it is recognised that there may be
practical difficulties in such a procedure.
4.3 Calibration Procedure - Much hes been written on the topic of calibration of partial discharge measur-
ing circuits which, in principle, should be simple but in practice leads to some difficulties and misunders-
tandings. Unfortunately, the facts presented in this paper further complicate the subject. This is becauseit
has been assumed in the past that partial discharge pulses to be measured have fast rise times of around
100 ns. Although partial discharges in a gas filled cavity behave in this way, breakdowns in oil or at an
oil/solid interface have much slower rise times of up to several microseconds. It can be seen in sections
3.2 and 3.3 that if measurements are made at high frequencies after calibrating with fast rising pulses,
then large errors can occur if the pulse fronts are much slower.
‘There are two approaches to the solution of this problem. The first is to calibrate the circuit using
simulated pulses of the same shapes as the partial discharge pulses, but this is impracticable when there
are several different pulse shapes. The alternative is to measure the pulses at a suitable frequency where the
response is similar for all pulse shapes ; this method has been adopted here.
If it is accepted that this procedure is logical, it should then be possible to calibrate simply by
injecting pulses of known charge at a defined repetition rate across the sample terminals and noting the
reading on the detecting instrument (meter or oscilloscope). The conversion factor is then given by the
ratio Input (pC)/Output (pC or #Y). If, as has been recommended, measurements are made at more than
one terminal of the transformer, calibration will be required at the appropriate terminals. Other correction
factors are not considered to be essential unless the level of partial discharge is high and some attempt is
to be made to locate the discharge sites. Problems concerned with location are outside the scope of this
paper.
44 Significance of Results - It is generally accepted that there should be no measurable discharge within a
transformer at working voltage and it is a reasonable premise that this criterion should also extend to a
limited overvoltage, say 120 %. Between this level and the long duration test level, which will be ap-
proximately 150 % of working voltage, some degree of discharge is believed to be permissible with two
provisos :
1) that the discharge level does not increase throughout the one hour test
2) that the discharge must extinguish before the reducing test voltage reaches 120 %.
Given that these two provisos are met and in the lack of knowledge concerning acceptable discharge
levels at the test voltage, it appears that an “act of faith” is required in accepting firstly the long duration
test and secondly reasonably high acceptance limits of partial discharge so that the test is not made unduly
onerous. Alternatively, if the partial discharges were measured at 150 % down to 120 % voltage levels and
could be extrapolated back to 100 % to show that there is negligible discharge, the difficulties associated
with measurements would disappear because absolute values would not be necessary.
All test specifications must include some proviso as to the action to be taken if the acceptance
criteria are not met. Bearing in mind that a transformer designed for long duration voltage testing may not
be able to withstand the hitherto normal high voltage test, it is clearly unrealistic to insist that reversion
to the old test voltage shall follow a failure to meet the criteria of the reduced level voltage test. Assuming
that the source of the discharge cannot be located and corrective measures taken, it is suggested that a
further possible test is one involving several hours, probably at a voltage around 120 %, coupled with12-03 —10—
continuous measurement of discharge, followed by a repeat of the reduced level high voltage test.
Reprocessing may of course render the 120 % voltage soak run unnecessary.
Additional evidence may be obtained from the results of gassin-oil measurements made at various
times in the test sequence.
5, CONCLUSIONS
1, Partial discharge pulses emanating from transformer insulation samples have been shown to have
many different waveshapes and pulse lengths. Pulse lengths varied from less than 1 psec up to 16 sec.
In general, there was an order of magnitude difference between the energies in the short and long pulses.
2. The responses of partial discharge measurement instruments have been determined when supplied
with similar pulses to those found on samples, It has been found that large errors will arise if long pulses
are measured at a frequency of 1 MHz and that the errors arising from different pulse shapes are minimised
if the measurement frequency is much tower.
3. Injection of pulses of different shapes at places on a full-size transformer winding and measurement
of the response at a simulated bushing tap confirmed the findings in (2) above. Such errors will be of great
importance in transformer partial discharge measurement if the: discharge pulses arriving at the terminals
are of the long duration type as seems likely from consideration of winding propagation characteristics.
4, Partial discharge measurements on transformers should be made with a narrow band instrument
in the frequency range of $0 to 100 kHz. More than one measurement frequency is preferred,
5. The choice of measuring instrument, measuring impedance and bandwidth is relatively unimportant
compared with the measurement frequency,
6. Because of uncertainties in measurement, no fixed rejection or acceptance levels can be agreed at
the present time.
6. ACKNOWLEDGEMENTS
‘This paper is published by kind permission of the Central Electricity Generating Board and the
Directors of Ferranti Ltd,
7. REFERENCES
[1] CIGRE SC12 WGOI - Measurement of partial discharges in transformers. (Electra, November, 1971,
No. 19 p. 13)
[2] MOLE G. - Improved methods of test for the insulation of electrical equipment. (Proc. LE.E., 1953,
Vol. 100, Part IA, p. 276)
[3] ADOLPHSON A.J. and VOGEL FJ. - Corona measurements in oil insulated transformers. (A.LE.E,
‘Trans, 1957, Vol. 76, Part III p. 798)
[4] QUINN G, E, - A method for detecting the ionization point on electrical apparatus. (A.LE,E. Trans
1940, Vol. 59, p. 680)
[5] NEMA - Methods of measurement of radio influence voltage (RIV) of high voltage apparatus. (1940,
Publication 107)ne 12-03
[6] NEMA - Methods of measurement of radio influence voltage (RIV) of high voltage apparatus. (1964,
Publication 107A)
(7] GEHRIG E.H. - Discussion on paper by Adolphson and Vogel. (A.LE.E, Trans., 1957, Vol. 76,
Part Ill, p. 801)
[8] BROWN R.D. - Corona measurement on high voltage apparatus using the bushing capacitance tap.
(LEE, Trans., 1965, Vol. PAS 84,p. 667)
[9] NARBUT P. - Transformer corona measurement using condenser bushing tap and resonant measuring
citeuits. (LE.E.E. Trans, 1965, Vol. PAS 84, p, 652)
[10] HARTHILL S.R., SMITH L., JAMES R.E., TAYLOR F.W, and RYDER Dull. - Some aspects
of internal corona discharges in transformers. (CIGRE, 1962, Paper No. 102)
[11] RENAUDIN D. - Instrument for measuring ionization in transformers. (CIGRE, 1954, Paper No. 105,
Appendix 2)
[12] LE.C, - Partial discharge measurements. (1968, LE.C. Publication No, 270)
[13] RAJU B.P., HICKLING G.H. and MORRIS L. - Experience with partial discharge measurements at
more than one terminal of a transformer. (I.E.B. Conference, 1973, Publication No. 94, p. 48)
[14] MASON J.H. - Discharges detection and measurements, (Proc. LE.E. ,1965, Vol. 112, No. 7, p. 1407)
[15] DAKIN T.W., WORKS C.L. and MILLER R.L. - Utilisation of peak reading voltmeters and recorders
for corona measurement. (LE.E.E, 1966, Paper 31 p. 66 - 341)
[16] MOLE G. - Basic characteristics of corona detector calibrators. (LE,E.E, Trans., 1970, Vol. PAS 89,
No. 2, p. 198)
[17] DOUGLAS J.L. - Calibration of circuits for measuring partial discharges in EHV transformers.
(LE.E. Conference, 1973, Publication No, 94 p. 40)
[18] HYLTEN - CAVALLIUS N. - CIGRE Discussion, (CIGRE, 1968, Vol. 1, Group 12, p. 2
[19] KREUGER F.H. - Discharge detection in high voltage equipment, (Heywood, London, 1964, p. 145)
[20] HARROLD R.T. and DAKIN T.W. - The relationship between the picocoulomb and microvolt for
corona measurements on h.v. transformers and other apparatus. (I-E.E.E. Trans., 1973, Vol.
PAS 92 p. 187)
[21] DEMBINSKI E.M. and DOUGLAS J.L. - Calibration and comparison of partial discharge and ra
interference measuring circuits. (Proc. LE.E., 1968, Vol. 115, No. 9, p. 1332)
[22] KAWAGUCHI Y. and YANABU S. - Partial discharge measurement on high voltage power transformers.
(LE.E.E, Trans,, 1969, Vol. PAS 88 p. 1187)
[23] BERTULA T., PALVA V, and TALVIO E. - Partial discharge measurements on oik-paper insulated
transformers. (CIGRE, 1968, Paper No. 12-07)
[24] IZEKI N., KURAHOSHI U. and MATSUURA K. - Behaviour of oil corona and damage of transformer
insulation, (ILE.E.E. Trans., 1971, Vol. PAS 90, p, 2330)
[25] YAKOV S., MADIN A.B., HONEY C.C. and KEIL C, - Corona in power transformers. (CIG!
Paper No. 12-06)
[26] WHERRY F.E. , TOOTHMAN L.R., YAKOV 8. and PRESTON L.L. - The significance of corona
‘measurements on transformers. (ILE.E.E., 1968, Paper No. 68 TP 59 - PWR)
1968,
Extmit de le Conférence Inremationale des Grands Réseaux Electriques
Session de 1974
Recent Experiences With Ac Hipot & PD Commissioning Testing of Xlpe Cable Systems Rated 69Kv and Above Mark. Fenger, Mark Credland, Howard Sedding Kinectrics Inc Canada