ZARUBEZHNEFT EP VIETNAM DAR ENERGY SDN BHD

FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’


GAS CONDENSATE FIELD

SPECIFICATION FOR HEAT TRACING


(CPP RONG DOI)

DOCUMENT NO.: 9001-2300-SE-0001-B1

Syahirah Azhar Ir Mohamad Ir Suhaimi


2024.03.07 Rizal Deraman
14:03:50 2024.03.07 2024.03.07
+08'00' 14:02:34 17:53:11+08'00'
+08'00'

B1 07-03-24 Issued for Implementation NSMA MRAB SD

A1 23-10-23 Issued for Review NSMA MRAB SD


Prepared Checked Approved Client
Rev No Date Purpose of Issue
By By By Approval
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

TRACK CHANGES

No Revision No Content of Changes Note

1 A1 Issued for Review

2 B1 Issued for Implementation

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 2/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

TABLE OF CONTENTS
1.0 INTRODUCTION .............................................................................................................5
1.1 PROJECT OVERVIEW ....................................................................................................5
1.2 FIELD DEVELOPMENT UPDATED INFORMATION .................................................6
2.0 PURPOSE AND SCOPE ...................................................................................................7
3.0 DEFINITIONS AND ABBREVIATIONS ........................................................................7
3.1 DEFINITIONS...................................................................................................................7
3.2 ABBREVIATION .............................................................................................................8
3.3 LANGUAGE .....................................................................................................................8
4.0 ORDER OF PRECEDENCE .............................................................................................9
4.1 INTERNATIONAL CODES AND STANDARDS ..........................................................9
5.0 REFERENCES ................................................................................................................10
6.0 SERVICES REQUIREMENTS .......................................................................................11
6.1 GENERAL .......................................................................................................................11
6.2 SERVICE CONDITIONS ...............................................................................................11
6.3 DESIGN LIFE .................................................................................................................12
6.4 SYSTEM RELIABILITY AND AVAILABILITY .........................................................12
6.5 UNITS ..............................................................................................................................12
7.0 VENDOR SCOPE OF SUPPLY .....................................................................................13
7.1 GENERAL REQUIREMENT .........................................................................................13
7.2 TYPICAL EQUIPMENT IN VENDOR SCOPE ............................................................14
7.3 EXPERIENCE DETAILS ...............................................................................................15
8.0 TECHNICAL REQUIREMENTS ...................................................................................15
8.1 AREA CLASSIFICATION .............................................................................................15
8.2 ELECTRICAL SUPPLY SYSTEM ................................................................................15
9.0 HEAT TRACING DESIGN REQUIREMENT ...............................................................15
9.1 HEAT TRACING DISTRIBUTION PANEL .................................................................16
9.2 SELF REGULATING HEATING CABLES ..................................................................19
9.3 JUNCTION BOXES ........................................................................................................19
9.4 THERMOSTAT...............................................................................................................20
9.5 CLADDING.....................................................................................................................21

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 3/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

9.6 THERMAL INSULATION .............................................................................................21


9.7 ACCESSORIES AND CONNECTIONS ........................................................................21
9.8 NAMEPLATE FOR HEAT TRACING DISTRIBUTION PANEL ...............................21
9.9 NAMEPLATE FOR HEAT TRACING SYSTEM .........................................................22
10.0 PAINTING REQUIREMENT .........................................................................................23
11.0 INSPECTION AND TESTING .......................................................................................23
11.1 HEAT TRACING DISTRIBUTION PANEL .................................................................24
11.2 HEAT TRACING SYSTEM ...........................................................................................25
12.0 PRE-COMISSIONING & COMMISSIONING ..............................................................25
12.1 FUNCTIONAL TEST .....................................................................................................26
12.2 VENDOR TECHNICAL ASSISTANCE ........................................................................26
13.0 SPARE PARTS ...............................................................................................................26
14.0 SPECIAL TOOLS ...........................................................................................................27
15.0 PACKING, PRESERVATION, AND TRANSPORTATION ........................................27
16.0 CERTIFICATION REQUIREMENT .............................................................................29
17.0 WARRANTY OBLIGATION .........................................................................................29
18.0 VENDOR QUALITY REQUIREMENT ........................................................................29
19.0 VENDOR DOCUMENTATION REQUIREMENT .......................................................30
APPENDIX A – DATASHEET FOR ELECTRICAL HEAT TRACING ...............................31
APPENDIX B – DEVIATION FORM .....................................................................................38
APPENDIX C – VENDOR DOCUMENT REGISTER LIST (VDRL) ...................................40
APPENDIX D – INSPECTION AND TEST PLAN ................................................................55
APPENDIX E – REFERENCE DRAWING ............................................................................58

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 4/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

1.0 INTRODUCTION

1.1 PROJECT OVERVIEW


The block 12/11 covers 5347.4 km2 (excluded the part of Premier Oil company and
returning area after completing the second of exploration phase) is 320 km from the
Vung Tau City, belongs to the South West of the Nam Con Son Basin. The block is
spread out from 07o08’ to 07o45’ north latitude and from 107o45’ to 108o30’ east
longitude, which is adjoined with 11-2/09 and 11-2 blocks to the north, 13/03 block to
the south, 20 and 21 blocks to the west and the 06/94 to the east. The block has a flat
bathymetry with the water depth of 70 – 120 m.

Figure 1.1: Thien Nga – Hai Au location in Block 12/11, Nam Con Son Basin
In 2010, Vietsovpetro and JSC Zarubezhneft got the Petrovietnam’s bidding invitation
for PSC of block 12/11 block after it had been returned by the Premier Oil Company.
In 2011, NIPI institute, Vietsovpetro have conducted the technical and economic
evaluation of 12/11 project for JSC Zarubezhneft. Following the bidding result, JSC

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 5/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

Zarubezhneft got the 100% interest of block 12/11 PSC, and Vietsovpetro then was
assigned to become the Operator.
In June 2023, Vietsovpetro had signed transferred of Operatorship to the custodian of
Zarubezhneft EP Vietnam.

1.2 FIELD DEVELOPMENT UPDATED INFORMATION


The scope of work includes BK-TNHA, subsea pipeline BK-TNHA – WHd (CPP)
Rong Doi, CPP Rong Doi upgrade, BK-TN, subsea pipeline BK-TNHA - BK-TN,
telecommunication system (microwave) between BK-TNHA & BK-TN.
09 production wells will be drilled and tie-back to cover 100% area of TN-3X, HA
and TN-4X. A Wellhead Platform will be located at TN-3X, named BK-TNHA, to
produce gas and condensate from 04 production wells, 02 future production wells and
03 spare slots (total 09 slots) at TN-3X and HA. 01 WHP, named BK-TN, to produce
gas and condensate from 03 production wells at TN-4X area. BK-TNHA will be
designed as an unmanned platform with minimal facilities for 06 production wells and
03 additional spare slots. BK-TN will be designed as unmanned platform with
minimum production facilities for 02 production wells, 01 future wells and 01
additional spare slot (total 04 slots) and connected by 3 km subsea pipeline 10” to
BK-TNHA. The produced gas and condensate from BK-TNHA will be transported
via approximately 36 km subsea pipeline 16” to the CPP Rong Doi for treatment,
compression and export. Required arrival pressure at CPP Rong Doi is 23 barg.
The construction and installation of BK-TNHA and BK-TN follow the phased
concept in which BK-TNHA is scheduled to be constructed and put in the first gas at
first. The first gas of BK-TN takes place a few years later subjected to production
decline.

The field development facilities according to Option 3A

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 6/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

2.0 PURPOSE AND SCOPE


The objective of this specification is to define the minimum technical requirement for
the design, manufacture, procurement, material, fabrication, painting, inspection,
testing, protective coating, documentation, preparation for shipping, and delivery of
Electrical Heat Tracing for CPP Rong Doi. This specification shall be read in
conjunction with the relevant data sheets, documents, and drawings where applicable.
Materials and work, both regarding design, construction, and workmanship, shall be
to the satisfaction of the COMPANY/CONTRACTOR.
All substitutions and deviations from this specification and International Code &
Standards shall be highlighted in writing to the CONTRACTOR, who in turn will
clarify with the COMPANY. The VENDOR shall not proceed with any such
substitution or deviation prior to receiving the COMPANY’s written approval.

3.0 DEFINITIONS AND ABBREVIATIONS

3.1 DEFINITIONS
All documents which will use the following words and expression shall have the
meanings given:

COMPANY Zarubezhneft EP Vietnam

CONTRACTOR means the party entering this CONTRACT with the


COMPANY for the performance of the WORKS or part
thereof as set forth in this CONTRACT and includes the
CONTRACTOR’s personnel, representatives, successors,
and authorized parties.

SUBCONTRACTOR means any party or parties, that has or have entered a


contract with the CONTRACTOR, for the performance of
any part of the WORKS.

VENDOR means the company that manufactures or supplies


equipment and services to perform the duties specified by
the COMPANY.

THIRD PARTY Organizations that are appointed by COMPANY to review


and approve deliverables submitted by DAR i.e., ICA etc.

Shall The words ‘shall’ indicates requirements.

Should The words ‘should’ indicates recommendations.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 7/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

WORK FEED Services for the Wellhead Platforms at ‘Thien Nga-


Hai Au’ Gas Condensate Field.

3.2 ABBREVIATION

AC Alternating Current
CPP Central Processing Platform
DAR DAR Energy Sdn Bhd
DC Direct Current
EHT Electric Heat Tracing
FAT Factory Acceptance Test
HAC Hazardous Area Classification
HSE Health Safety Environment
ICA International Classification Authority
IEC International Electrotechnical Commission
IP Ingress Protection
ISO International Organization for Standardization
ITP Inspection and Test Plan
kV Kilovolt
kVA Kilovolt Ampere
KVAR Kilovolt Ampere Reactive
kW Kilowatt
LV Low Voltage
MCB Miniature Circuit Breaker
MCCB Moulded Case Circuit Breaker
PSC Production Sharing Contracts
SAT Site Acceptance Test
SI International System of Units
V Volt
VR Vietnam Register

3.3 LANGUAGE
The language of all written communication, VENDOR documentation and drawings
shall be English.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 8/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

4.0 ORDER OF PRECEDENCE


All equipment shall be designed in accordance with the relevant section of the
national and international Codes, Standards and Regulations wherever applicable. The
latest editions of Codes and Standards including all addenda, supplements, or
revisions current at the time of order placement shall be followed.
It is expected that some deviations may occur on a case-by-case basis. In case of
contradictions between the various codes, standards and specifications, queries should
be submitted in writing to the COMPANY for approval. The order of precedence shall
be:
• Statutory Codes and Regulations
• Datasheets
• This Specification
• Other Project Specifications
• National Standard and Codes
All units shall be in the International System of Units (SI) unless otherwise specified
by the COMPANY.

4.1 INTERNATIONAL CODES AND STANDARDS


The following International Codes and Standards will be applicable for this project.
The latest revision shall be referred.

The following standards is referred to:

BS 6121 Mechanical Cable Glands. Specification for Metallic


Glands
BS 6351 Specification for Electric Surface Heating Devices
BS 6883 Elastomer Insulated cables for fixed wiring in ships and
on mobile and fixed offshore units
IEC 60050 International Electro technical Technology
IEC 60051 Direct action indicating electrical measuring instrument
and their accessories
IEC 60079-10-1 Electrical Apparatus for Explosive Atmospheres
IEC 60216-1 General guidelines for aging procedure and evaluation
of test results
IEC 60228 Conductors for insulated cables
IEC 60331 Fire resistance characteristics of electrical cables
IEC 60332 Test on Electrical Cables under Fire Condition

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 9/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

IEC 60445 Identification of Equipment Terminals and of


Terminations of Certain Designated Conductors,
Including General Rules for an Alphanumeric System
IEC 60529 Classification of Degrees of Protection provided by
Enclosures
IEC 60702 Mineral insulated heating cables with a rated voltage not
exceeding 750V
IEC 60751 Industrial Platinum resistance thermometer sensors
IEC 60800 Heating cables with a rated voltage 300/500V for
comfort heating and prevention of ice formation
IEC 60811-4-2 Common test methods for insulating and sheathing
materials of electric cables.
IEC 62086-1 Electrical resistance trace heating – Part 1: General and
testing requirements
IEEE 515 Recommended Practice for the testing, design,
installation and maintenance of Electric resistance heat
tracing for industrial applications
NEMA National Electrical Manufacturer’s Association
NFPA National Fire Protection Association
NFPA 72 National Electric Code
TCVN 6767-4 Fixed Offshore Platform – Part 4: Electrical Installation

5.0 REFERENCES
The following documents and drawings are references for this project:
1. Electrical Installation Specification VN01-200-25-E-SP-0001.
2. Piping Material Class Specification VN01-200-30-L-SP-0001.
3. Surface Preparation and Painting VN01-200-30-G-SP-1002.
4. Specification for Piping Welding, Fabrication and Installation VN01-200-
30-G-SP-1003.
5. Technical Specification for Corrosion Coupons and Fitting VN01-200-30-
G-SP-1005.
6. Corrosion Assessment and Materials Selection Report VN01-200-30-G-ST-
1001.
7. Specification for Insulation VN01-200-30-M-SP-0001.
8. Datasheet for Diesel Electrical Heat Tracing (CPP Rong Doi) 9001-2300-
KE-0001.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 10/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

9. Electrical Single Line Diagram – Heat Tracing Distribution Panel 230-DP-


8411 (CPP Rong Doi) 9001-2300-DE-1001.
10. Electrical Equipment Layout 9001-2300-DE-5801.
11. Equipment Layout.
12. HAC Drawings.
13. Process & Instrument Diagrams.
14. Process Line List 9001-2300-LP-0001.
15. Piping Isometric Drawings.

6.0 SERVICES REQUIREMENTS

6.1 GENERAL
The VENDOR shall ensure that the Electrical Heat Tracing meets the requirements as
defined in this specification. It is not the intent of this specification to strictly specify
all details of design and construction. All suggested changes to this specification to
improve the installation, operation, or cost-effectiveness of fabrication at no sacrifice
to quality and safety considerations will be considered provided that prior written
approval is obtained from the COMPANY.
VENDOR responsibility is to ensure Vietnamese Technical Standards (TCVN) and
Technical Regulations (QCVN) are compiled during design, fabrication, examination,
and delivery of the equipment. All necessary submission of documents, coordination
of any inspection (FAT, SAT, etc.), inter action and getting approval of the equipment
under this scope of supply from Vietnamese authorities (VR, PVN, etc.) wherever
required.
The selection of all materials and methods of fabrication not specified in this
specification, but which are necessary to complete the fabrication of the Electrical
Heat Tracing shall be the responsibility of the VENDOR.
VENDOR must submit a proven track record of their past acquired projects including
successful installation of Electrical Heat Tracing.

6.2 SERVICE CONDITIONS


The Electrical Heat Tracing shall be located offshore on the cellar deck of CPP Rong
Doi as per environmental conditions:
i. Ambient temperature: 18.2 deg C min to 35.1 deg C max.
ii. Environment: Salt laden moist
iii. Maximum Relative Humidity: 100%
iv. Wind: Operating 22m/sec
v. Seismic: Structure Resonance Factor 1.5, Horizontal Force Factor 2.0

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 11/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

vi. Vibration: 10-150 HZ


vii. Acceleration: 0.5G
viii. Displacement: 2.5pk to pk mm @ 10HZ
ix. Solar Radiation: 1.25 kW/m2
x. Flare Radiation: 4.7kW/m2
xi. Service Conditions: Arduous offshore, salt laden, oil field, continuous duty
xii. Service Life: 30 years (from 2006)
xiii. Maintenance: 25000 hours
xiv. Altitude: >14m and <48m above LAT Sea Level
The equipment shall in all respects be suitable for operation in a saliferous and dusty
atmosphere. The possibility of condensation on equipment surfaces shall be
considered.
VENDOR to ensure Electrical Heat Tracing supplied shall meet the minimum space
allocated for maintenance purpose.

6.3 DESIGN LIFE


The Electrical Heat Tracing System and its components shall be designed for
continuous service life of 15 years.

6.4 SYSTEM RELIABILITY AND AVAILABILITY


The system shall be designed to have reliability of 99% in the specified conditions
and require no more than one maintenance visit per year.
Reliability and availability of all equipment to perform in an offshore tropical marine
environment is essential. Unproven equipment not having a well-established operating
record will not be considered.
VENDOR shall provide availability, reliability and Mean Time Between Failure
(MTBF) data for similar unit in the service.

6.5 UNITS
The International System of Units (SI) shall be used in all design, engineering
documents and drawings, unless otherwise specified.
All dimensions are quoted in mm with the unit abbreviation.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 12/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

7.0 VENDOR SCOPE OF SUPPLY

7.1 GENERAL REQUIREMENT


This document is prepared as minimum technical requirement for Electrical Heat
Tracing to be installed on the CPP Rong Doi.
The VENDOR shall be responsible for design, supply of materials, manufacturing,
preparation of documents & drawings, MTO, assembly, testing, delivery, supervision,
onshore and offshore installation, pre-commissioning, and commissioning of
Electrical Heat Tracing.
The VENDOR shall note that this specification is a general document, which is
supplemented by other specifications, its appendices and applicable codes and
standard, datasheets, drawings, etc. which are provided as attachments or references
and to the specifications.
All applicable documents are attached with the specification. However, if the
VENDOR is not in possession of any of the listed or referred COMPANY documents,
it shall be his sole responsibility to obtain them from the CONTRACTOR. Otherwise,
it shall be assumed that VENDOR has received, read, and understood the total
contents of the inquiry/Purchase Order.
Should the VENDOR identify any discrepancy, or lack of clarity in any part of this
specification or attached documents, it is VENDOR’s responsibility to notify
CONTRACTOR with his proposed alternative(s) and any impact on the price and/or
schedule.
The VENDOR shall not commence any fabrication work prior to obtaining written
approval of drawings and/or procedures from COMPANY/CONTRACTOR. The
VENDOR is responsible for maintaining strict quality control procedures to ensure
compliance with codes, specifications, drawings, and instructions issued by
CONTRACTOR during the manufacture of equipment.
Preference in equipment selection will be given to VENDOR(s) who will extend
services and spare parts within this region.
COMPANY/CONTRACTOR reserves his rights for final acceptance of the
equipment subject to the successful completion of Commissioning and start-up at
offshore and equipment performance guarantee.
Heat tracing VENDOR shall submit complete Electrical Heat Tracing Datasheets
attached along with this specification. VENDOR shall clearly identify any
discrepancies between the P&ID’s, Piping Isometric Drawings, Process Line List,
with the specification. Any discrepancies in the above shall be under VENDOR’s
scope.
The VENDOR of the electric heating system shall be responsible for the calculations
for the heating system and to furnish the basis of his design for approval. VENDOR

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 13/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

shall identify offshore installation piping which requires heat tracing. The heat tracing
installation shall be under VENDOR scope.
The heating system shall be suitable for outdoor use, exposed to direct sunlight, and
without protective shelter. The possibility of condensation, as experienced during
large temperature fluctuations, shall be considered as well.
The heating system shall be designed and positioned to maintain the temperature at
the specified temperature.
The heating system is energized if the average temperature is less than its set point.
The heating system is de-energized if the average temperature is more than its set
point.
All items to make up a complete heat-tracing system from heat tracing distribution
panel to downstream distribution shall be VENDOR scope of work. VENDOR shall
be responsible for ensuring performance guarantee for this package.
VENDOR is expected to generate his own MTO as per project requirement in
accordance with the attached P&IDs, Process Line List, Piping Isometric and
Electrical Single Line Diagram.

7.2 TYPICAL EQUIPMENT IN VENDOR SCOPE


The VENDOR scope of supply shall include but not be limited to the design,
fabrication, supply, and installation of the followings as a minimum:
The electric heat tracing system shall consist of:
i. Heat tracing distribution panels
ii. Heating element tapes / cables
iii. Heat Tracing Insulation and Cladding
iv. Junction boxes
v. Low temperature alarm (TAL) supervision thermostats c/w support bracket
for alarming purposes
vi. Power connector, end connectors, T-connectors, tapes
vii. Special glands for trace heating tapes/cables.
viii. Special tools (recommended by VENDOR) required for installation,
removal and maintenance and testing purposes.
ix. Commissioning and spare parts
x. Documentation in accordance with VDRL
xi. Packing, preservation, and preparation for shipment
xii. Provide quality assurance scheme in accordance with ISO 9001 or
equivalent to ensure all work performed conforms to the specification.
xiii. Two (2) year operational spares list.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 14/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

xiv. Delivery shall be delivered to the CONTRACTOR warehouse before being


delivered offshore for installation.
xv. Assist offshore commissioning.
xvi. Onshore and Offshore Installation.
VENDOR shall furnish all components and ancillary equipment necessary to make
the Electrical Heat Tracing complete, safe, and ready for operation, in accordance
with this specification and datasheet.

7.3 EXPERIENCE DETAILS


The Electrical Heat Tracing System assembly shall have proven track record.
VENDOR shall submit project history record, related to oil and gas projects, with the
bid proposal.

8.0 TECHNICAL REQUIREMENTS

8.1 AREA CLASSIFICATION


All electrical equipment shall comply with the requirements of the relevant parts of
IEC 60079. The following types of protection shall be used:
• Junction boxes : Enclosure – Minimum IP56
• Thermostats : Enclosure – Minimum IP56
All electrical equipment enclosures shall have a minimum degree of Protection IP56
as per IEC 60529.

8.2 ELECTRICAL SUPPLY SYSTEM


The AC supply to the heating system shall be symmetrical 3 phases + neutral + earth
sub-divided into single phase with a nominal voltage and frequency as indicated
below.
• Nominal system voltage : 400V10%, 3 Phase+ N, solidly earthed.
• Nominal system frequency : 50 Hz 2%
In addition to the above, input voltage variations may be subject to transient voltage
variation of +10% and –20% of the nominal voltage.

9.0 HEAT TRACING DESIGN REQUIREMENT


Tracing systems shall be controlled for the following purposes:
i. Energy saving.
ii. To maintain the temperature within certain limits.
iii. To limit the maximum temperature.
iv. To prevent freezing.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 15/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

The temperature control can be achieved by means of electronic controller or


thermostats attached to the outer surface of traced equipment. VENDOR shall be
responsible for providing the proper temperature control.
These thermostats shall be factory calibrated and have an internally adjustable set
point and external readout. VENDOR shall specify in detail the length of the
capillary, the contact rating, the temperature range, accuracy and switching hysteresis.
Numbers of required electronic controller / thermostats shall be designed / determined
by the VENDOR based on the physical locations of the traced equipment.
The selection of heating strips and other devices shall be done by the VENDOR
considering the following:
i. Maintenance temperature.
ii. Minimum design ambient temperature.
iii. Exposure temperature both continuous and intermittent as dictated by
operating or commissioning requirements.
iv. Thermal insulation specified.
v. Tolerance on supply voltage and voltage drop on feeding cables.
vi. Tolerance in heater output.

9.1 HEAT TRACING DISTRIBUTION PANEL


The distribution panel shall be designed in accordance with IEC 60439, IEC 60529
and IEC 60079 and the requirements indicated in datasheets & drawings.
The distribution panel shall have an adequately rated system, fully shrouded/ insulated
high conductivity copper bus bar, rated, and braced to withstand short circuit current
of 10kA.
The outgoing MCBs shall have breaking capacity, equal to the fault rating of the
distribution panel bus bar.
VENDOR must design and determine the number of heat tracing circuit.
The distribution panel, which is installed outdoor at hazardous area Zone 2, IIA, T3
shall have degree of protection IP56. The final arrangement of the heat tracing
distribution panel shall be as per VENDOR design.
20% spare feeders and 10% spare shall be provided in for the distribution panel to
cater for future requirements.
The electrical characteristics and service requirements summarized as below:
• Supply Voltage/Frequency : 400V, 50Hz
• Supply Voltage Tolerance : ± 10%
• Supply Frequency Tolerance : ± 2%

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 16/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

• System Earthing : Solidly earthed neutral.


• Control Voltage : 230V ± 10%, Single Phase +
Neutral + Earth, 50 Hz ± 5%, or
as applicable.
Control supply shall be derived internally inside the panels if required.
Transient voltage depressions down to 80% rated voltage shall not affect the
equipment performance. All current carrying components of the equipment shall be
capable of continuous operation at the specified site conditions and the specified
ratings without exceeding the maximum temperature rise stated in the appropriate IEC
publications.
The phase, neutral and earth bus bars shall be of hard drawn, high conductivity copper
and tinned plated to minimize heating at the contact surface and inhibit corrosion.
The bus bars and connections shall be adequately sized, braced and supported to
withstand dynamic and thermal stresses due to rated momentary peak and short time
short circuit currents specified.
Type test results from similar design shall be submitted with proposal. Bus bar
supports and barriers shall be made from non-hygroscopic, non-tracking insulation
materials. Neutral bus bars shall have a continuous current rating similar to that of the
phase bus bars. Phase and neutral bus bars shall be insulated from earth.
Colour coding for phase bus bars shall be as follows:
• Phase R or L1 or U = Red
• Phase Y or L2 or V = Yellow
• Phase B or L3 or W = Blue
• Neutral = Black
• Earth = Green with Yellow Strip
All non-current carrying metal work making up the distribution panel shall be bonded
together with the earthing straps, for connection to the earth grid system.
The distribution panel shall have a stainless-steel earth M10 stud welded to the
distribution panel housing for external earth connections of single core earth cable.
Earthing bus bar size shall be suitable for termination of 35mm2 cable.
Each door shall be bonded to the main body by means of flexible connections.
The distribution panel incomer shall comprise of a MCCB (with current limiting
features) complete with padlocking facilities in the 'OFF' position. It shall be housed
in a type of protection in accordance with IEC 60079-1. In addition, the incomer
MCCB’s shall have built-in earth fault protection.
Voltmeter & ammeter (with selector switch) shall be provided for the distribution
panel incomer.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 17/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

Incomer breaker shall be pad-lockable in OFF position. Lamp test pushbuttons shall
be provided.
Provisions shall be made to enable the incoming circuit breaker to be switched
without opening the cover of the distribution panel enclosure.
Miniature circuit breakers (MCBs) shall be of current limiting type and equipped with
thermal-magnetic trip to protect against overload and short circuit and shall have
current limiting capability.
Each branch circuit shall be equipped with a circuit breaker (MCB) with a residual
current protection device with an operating current not greater than 30mA.
The MCB’s in general shall conform to IEC-60947-2; in addition, all MCB’s shall
comply with type C characteristics.
As a standard, contactors shall be of the holding coil type with an operating voltage
derived from phase and neutral.
Circuit breakers shall be permanent trip, bolt-on type. The circuit breaker shall be
ambient temperature compensated and internally tropicalized with anti-fungus
coating.
All materials used shall be in accordance with the COMPANY’s approved VENDOR
list.
The startup temperature determines the in-rush current (startup load). This
temperature determines the rating of the electrical protection (circuit breaker). The
maximum length of the heater circuit must be limited to a value where the startup load
does not exceed the circuit breaker rating.
Heater circuits shall be loaded with maximum 25A for single phase circuits.
Heating systems of duplicated process control lines shall not be connected to the same
circuit.
The distribution panel shall be naturally air cooled.
The assemblies shall be designed for continuous operation at full load. The
distribution panel shall be front access. Doors shall be hinged type.
Distribution panel shall be mounted on mounting structure with cable entry from
bottom for outdoor installation.
The distribution panel shall be supplied complete with earthing terminal.
Insulated barrier between phases shall be provided where necessary.
Terminals shall be suitable for copper conductors.
For bus wiring and outgoing control circuits, individual terminals shall be provided
for each external conductor. Cable entries, support facilities for cabling and earthing

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 18/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

facilities shall be provided and shall be suitable for the type, size and number of
cables.
The wiring shall be in accordance with IEC Standards. Internal cabling/wiring shall
flame retardant to comply with IEC 60332.
Incoming and outgoing cables should be armoured cables with cable gland earthing
and clamping amours. Wiring between terminals shall not have joints.
All wiring within the distribution panel shall be neatly run, fastened with strap, and
identified with suitable type markers.

9.2 SELF REGULATING HEATING CABLES


Self-regulating/self-limiting cables shall be utilized. The heating cable consists of two
parallel copper conductors, both being in contact with a self-regulating /self-limiting
semi-conductive material. This basic element shall be insulated by one or more non-
hygroscopic jackets and shall be covered with a corrosion resistant braided metal
screen covering at least 70% of the surface and the fluoropolymer outer jacket. The
braided metal screen shall have an electrical conductivity not less than the
conductivity of one of the conductors.
The heaters shall vary the power output in response to the thermostat setting at every
point of the surface. As the temperature increases, the heater output shall decrease
automatically, and vice versa. The natural reduction in heat output by increasing
temperatures shall be at least so much that the heater cable will not be damaged due to
overheating because of e.g., overlapping.
The minimum self-regulating index of the heating cable shall be specified by
VENDOR. The outer jacket shall be capable of protecting the inner part of the cable
against damage during installation as well as against the environmental conditions.
The heating cable shall have sufficient strength to withstand the installation work
without affecting its mechanical integrity or electrical properties.
Other cable types can be used when the required heat output or the operating
temperature is beyond the capabilities of self-regulating / self-limiting cables. This
shall be subject to COMPANY approval.

9.3 JUNCTION BOXES


The junction boxes shall be suitable for hazardous areas and constructed with
corrosion resistant material (Stainless steel or GRP), with degree of protection IP66.
Junction boxes shall be used for:
i. Connection between supply cable and heater cable.
ii. Distribution of supply from one circuit of the distribution panel to sub-
circuits.
NOTE: Combinations of i) and ii) are also possible.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 19/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

Connection boxes shall contain sufficient terminals for all connections to be made.
Individual terminals shall be provided for each conductor. The terminals shall be of
non-loosening construction and of the wedge type or cage clamp type, obviating the
use of cable lugs and constructed in such a way that direct contact between screw and
conductor is avoided. Terminals shall be identified in accordance with the related
diagram. In addition, sufficient earth terminals or an earth bar with sufficient earth
connection points shall be provided to earth the metal screens of all cables and
heaters. Only one circuit of the distribution panel shall be allowed in a connection
box.
All cables connected to the box shall enter the box through the bottom or the sides,
not the top. Sufficient cable glands, suitably sized for the associated cables, shall be
installed.
Cable gland shall be nickel-plated brass reversible armoured clamp cone & bi-
directional clamping ring and deluge cable gland with inner and outer seal for
armoured cable suitable for hazardous outdoor area with all types of SWA cable, type
of protection of gland should be minimum of IP66 The gland should be designed to
specification of BS6121 and provided with an explosion proof seal on the cable inner
sheath and an environmental seal on the cable outer sheath, mechanical cable
retention and electrical continuity via armour wire termination come with PCP
shroud, and nickel plated brass earth tag, locknut and sealing washer.
Power to the heat tracing system will be provided at various points via heat tracing
distribution panel. The scope thereon shall be by the heat tracing VENDOR including
the provision of Junction Boxes at this location.
Through connections or ‘Tee-offs’ shall not be made underneath the pipe insulation,
only end-seals and ‘cold-lead’ connections may be used. All other connections shall
be made in junction boxes. Sufficient heater capacity shall be installed to ensure that,
towards the end of the heating cable, the output does not drop below the minimum
design value owing to the voltage drop in the heater conductors.
Special requirements for heat tracing cable glands shall be specified by the heating
cable manufacturer.

9.4 THERMOSTAT
The thermostats shall be capillary type. The capillary shall be no more than 5 m long.
The contacts of thermostats used for direct switching shall have a minimum rated
capacity of 25A, which may be obtained by an integrated local contactor. Each
contact of thermostats shall not be loaded with more than 75% of its nominal rating.
The temperature setting accuracy shall be better than ±5% of the set value. The
switching hysteresis shall be between 5% and 10% of the actual setting.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 20/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

The thermostats shall be suitable for hazardous areas, with IP66. The enclosure shall
be corrosion resistant materials (stainless steel or GRP) / Thermoplastic
Polycarbonate.
VENDOR shall provide online thermostat for temperature control of heating cables.

9.5 CLADDING
The cladding shall be per the minimum requirement specified by the COMPANY.
Material for cladding shall be SS316. Other SS304, galvanized steel and Aluzinc steel
material are not permitted.

9.6 THERMAL INSULATION


The installation shall be in accordance with CINI Manual. The insulation material
shall be mineral wool type. VENDOR shall propose insulation thickness and provide
insulation thickness calculation for approval.

9.7 ACCESSORIES AND CONNECTIONS


Cold leads shall be provided suitable for termination in the junction boxes in such a
manner that any ingress of water through the cores, braiding or in between insulation
layers due to the capillary effect is excluded.
Insulation entry kits shall be provided where heating cables, cold leads or temperature
leads enter the thermal insulation to prevent damage and to ensure weatherproofing.
All fixation accessories shall be supplied in accordance with the VENDOR
installation standard. These shall include but not be limited to straps, tapes, warning
labels, etc.
Fixing materials for heaters shall ensure continuous and permanent contact between
the heater and heated surface. They shall be non-corrosive and suitable for the
relevant operating temperature and shall not damage the heater mechanically or
chemically.

9.8 NAMEPLATE FOR HEAT TRACING DISTRIBUTION PANEL


One or more nameplates of engraved stainless steel shall be mounted on the outside of
the enclosure of the distribution panel.
Information given on these nameplates shall be as follows but not be limited to:
1. Distribution panel tag number as shown in datasheet.
2. COMPANY's Purchase Order number.
3. Rated bus bar voltage, no. of phases and frequency.
4. Rated bus bar current and short circuit rating.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 21/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

5. Degree of protection.
6. Model.
Alphanumeric notation, generally in accordance with IEC 60445, shall be used for
identification and marking of phases, conductors, terminals, and components used.
Nameplates shall be of corrosion-resistant plastic material such as traffolyte and shall
be firmly fixed with corrosion resistant machine screws.
Nameplates shall be attached to the enclosure with stainless steel screws. Tape or
adhesive type nameplates shall not be used.
Safety covers and shrouds shall be provided with a warning label and the voltage level
of the equipment as follows:
DANGER……………………VOLTS

9.9 NAMEPLATE FOR HEAT TRACING SYSTEM


Permanent nameplates or labels shall be provided to identify the individual heat
tracing system assemblies, wherever applicable. In addition, labels shall be provided
as appropriate to convey operating instructions, warning notices, rating data and other
general information.
Identification of connection boxes, thermostats and tracing cables shall be such that
these shall include the circuit number of the tracing distribution.
Name, identification, instruction and warning plates and their fixing materials shall be
of stainless steel SS316. They shall be provided with indelible inscriptions in English
language. The entries on the rating plates shall be indelibly marked by etching or
engraving.
The rating plate shall include the following information as a minimum:
1. Type of equipment
2. Supply voltage, phase and frequency
3. Manufacturer’s name and address
4. Manufacturer’s serial number
5. Year of manufacture
6. COMPANY’s Purchase Order number
7. Enclosure IP protection category
8. Total Weight
Nameplates and/or rating plates shall be permanently fixed to a readily visible,
accessible, and non-removable part of the heat tracing system.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 22/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

10.0 PAINTING REQUIREMENT


Painting and coating shall be provided in accordance with the COMPANY
specification and design basis. The complete procedure shall be approved by the
COMPANY before the start of any work.

11.0 INSPECTION AND TESTING


Unless otherwise specified in the job specifications, datasheets, equipment, and
material certification shall be in accordance with the relevant code and standard.
Inspection and testing requirements shall be in accordance with the applicable
datasheets, specifications, codes, and standards.
All testing shall be carried out at the manufacturer’s test facility. The test equipment
shall be supplied by the manufacturer and shall be calibrated within six months of the
test date.
VENDOR shall include an Inspection and Test Plan (ITP) in their Tender documents.
The ITP shall list all inspections and tests proposed for the equipment by the
VENDOR, between the date of ordering and the date of delivery. The plan will be
reviewed and approved to become the approved Inspection and Test Plan for the
Project and form part of the contract documents.
VENDOR shall obtain certification form ICA for the design verification and
compliance of the package including materials, fabrication and testing as per material
specification.
The VENDOR shall be responsible for the planning and execution of all inspections
and tests, but the CONTRACTOR’s representative, ICA or VR shall have the right to
witness any or all the manufacturing, inspection, or tests.
VENDOR shall submit the Site Acceptance Test (SAT) procedure for approval by
COMPANY. Package VENDOR shall mobilize necessary personnel and testing
equipment necessary for the SAT (upon COMPANY request).
Site Acceptance Test shall include pre run checks, performance test package. The
performance test shall be conducted for at least seventy-two (72) hours at all possible
operating conditions. THE COMPANY or its designated representatives, or both, will
be present at the site and shall approve the test results and sign the test records to
indicate approval. If the unit does not meet Purchase Order requirements, VENDOR
and/or his sub - VENDORs shall correct the problems at no expense to COMPANY.
The VENDOR shall notify the CONTRACTOR, at least fourteen (14) days in
advance, of the date on which any of the inspections or tests nominated as Hold or
Witness points on the ITP are due to be carried out.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 23/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

Certificates of Test shall be provided for each item of equipment to prove it has been
satisfactorily tested to meet all requirements of its appropriate manufacturing
standards, whether witnessed or not by the CONTRACTOR.
Where appropriate, test certificates shall state values for all test results. Tests for
which the results are indicated as pass or fail shall be qualified by the relevant
acceptance criteria.

11.1 HEAT TRACING DISTRIBUTION PANEL


COMPANY/CONTRACTOR may require additional testing if test results are
unsatisfactory or marginal. Any components rejected shall be repaired or replaced to
COMPANY/ CONTRACTOR’s satisfaction and the test shall be repeated.
COMPANY/CONTRACTOR or its representative shall have free access to the
manufacturing location of VENDOR and sub-vendors during fabrication, assembly,
and testing of the equipment.
All test procedures shall be submitted for approval. COMPANY /CONTRACTOR or
its representative shall be given at least two weeks’ notice prior to the acceptance
testing. The VENDOR shall submit certified reports on all tests.
VENDOR shall submit an Inspection & Test Plan (ITP) mentioning inspection and
testing that shall be carried out for the package.
Inspection of package may include but not limited to:
i. Review of Quality Assurance documents
ii. Stage inspection during manufacturing
iii. Surface preparation & painting
iv. Dimensional & assembly inspection
The distribution panel and its associated low voltage components/materials shall be
tested in accordance with the standards and codes and witnessed by the
COMPANY/CONTRACTOR's representative. Testing shall be carried out as per
CONTRACTOR approval test program.
The test shall include but not be limited to the following:
i. 1-minute-high potential test of Phase, Neutral & Earth bus bars.
ii. Insulation resistance measurement and control wiring insulation test.
iii. Mechanical operation tests
iv. Polarity tests
v. Sequence operation/functional tests
vi. Interchangeability tests
Primary and secondary injection test for all metering/protection circuit including
thermal overload.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 24/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

11.2 HEAT TRACING SYSTEM


COMPANY /CONTRACTOR or its representative shall have free access to the plants
of VENDOR and sub-vendors during fabrication, assembly, and testing of the
equipment.
VENDOR check and inspect the piping for burrs, rough surfaces, or sharp edges shall
be remove if necessary.
All test procedures shall be submitted for approval.
COMPANY /CONTRACTOR or its representative shall be given at least two weeks’
notice prior to the acceptance testing. The VENDOR shall submit certified reports on
all tests.
Electrical heat tracing shall be designed and fully type tested in accordance with IEC
62086-1 (Electrical Apparatus for Explosive Atmosphere) by internationally
recognized independent accredited third-party laboratories such as KEMA, ASTA or
other CONTRACTOR recognized organizations.

12.0 PRE-COMISSIONING & COMMISSIONING


VENDOR shall provide procedures and checklist for equipment pre-commissioning
and commissioning including parameters for performing acceptance test. At least one
qualified commissioning engineer from VENDOR shall lead the commissioning of
the whole heat tracing system.
The minimum but not limited to the following items shall be checked and determined
during commissioning:
i. Heat loss of pipes
ii. Maintained temperature (in °C)
iii. Individual circuit load (in kW)
iv. Start-up current of each circuit
v. Thermal stability of heating cables
vi. Thermal output
Commissioning report shall be submitted to COMPANY /CONTRACTOR for review
two weeks after commissioning of the whole system.
The electric surface heating devices shall be tested and inspected at VENDOR’s
works. All materials employed by the VENDOR of the heater strip shall be subjected
(both before and after manufacture of the heater strip) inspection, testing and approval
by the COMPANY of his authorized representative.
COMPANY /CONTRACTOR or his authorized representative shall have the right to
enter the plant and inspect the equipment/material at any time during manufacturing.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 25/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

After completion of manufacture of heater strips, and prior to dispatch, these shall be
subjected to type and routine tests defined in applicable standards. Prior intimation of
a minimum of fourteen (14) days shall be given to enable the COMPANY to depute
its representative to witness the tests. Type test certificates shall be furnished along
with the offer.

12.1 FUNCTIONAL TEST


A complete functional test shall be performed on the Electrical Heat Tracing. The
correct functioning of all measuring instruments, alarms and indications, protection
and controls shall be verified.

12.2 VENDOR TECHNICAL ASSISTANCE


VENDOR shall be capable of supplying the services of a competent on-site service
engineer who shall be responsible for verifying proper installation, performing initial
start-up, and ensuring that the installation has complied with mechanical and design
requirements for the proper operation of the heat tracing system prior to being placed
in service.
VENDOR shall quote separate rates for this service engineer.
The service engineer shall be made available within fourteen (14) days’ notice during
the installation, start-up and warranty period with all essential tools and instruments
required for him to perform the above function.

13.0 SPARE PARTS


The VENDOR shall include in the base scope of supply all spare parts for successful
startup and commissioning, complete with detailed spare part inventory.
In addition to the above, a parts list of two years of operation spares shall be provided.
The prices of each part, delivery time, and the layout and sectional drawings
indicating the location of the parts with tag/reference identifications.
A price list, with a full description of the spare parts shall be provided. Each item
shall include the following information:
i. The manufacturer’s part number.
ii. A clear and concise description of the part.
iii. The price for each recommended part or set of parts delivered into the store
at site.
iv. Insurance spares that satisfy the requirements of the certifying/classification
authority.
Recommended spares should consider related factors of equipment reliability, effect
of equipment downtime on production and safety, cost for easy identification
according to equipment usage.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 26/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

All spare parts furnished by VENDOR shall be wrapped, packaged, and preserved in
original as-new condition under normal conditions of storage, and shall be properly
tagged and coded for easy identification according to equipment usage.
The start-up and operational spares shall be packaged separately, clearly marked as
‘Spare Parts’ and shipped at the same time as the equipment. Packing lists shall be
furnished so that the parts can be identified without un-crating the shipping
packaging. Packing shall clearly indicate the destination of spare equipment.
All spares shall be packed separately with clear identification and delivered with the
main equipment in packaging suitable for long-term storage.

14.0 SPECIAL TOOLS


All special tools necessary for the installation, alignment, operation, or maintenance
of the equipment shall be supplied with the delivered equipment.
VENDOR shall supply special tools and equipment required, if any, for the
installation, commissioning, and maintenance and testing of heat tracing system.

VENDOR shall describe the procedure for heat tracing system installation, removal,
and re-installation in the bid proposal.

15.0 PACKING, PRESERVATION, AND TRANSPORTATION


The equipment to be purchased shall have relevant marking with indication of:
i. Name, type
ii. Manufacture’s trademark
iii. Serial number
iv. Main characteristic
v. Manufacturing date
All equipment likely to become loose in transit shall be removed and separately
packed.
All equipment shall be produced not earlier than 1 year before delivery.
The VENDOR shall be responsible to provide packing, preservation, and adequate
protection of the equipment to prevent damage, deterioration and to ensure cleanliness
during transportation by air/sea transportation or road transportation to COMPANY
place, including storage and installation of the equipment.
The packing shall be designed and built to withstand shocks and vibration from
handling by fork lifts or other mechanical handling equipment and endure
transportation conditions on trucks, barges or boats and associated oceanographic
during transportation.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 27/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

All supplied items shall be thoroughly cleaned, dried out and made free of any loose
mill scale, weld spatter, rust etc. prior to shipment.
The VENDOR shall provide a list of any special precautions for handling the
equipment.
Measures for preservation and packing of the equipment as well as supplied in
complete set materials, accessories, spare parts, and tools shall provide their normal
transportation and storage provision for 12 months outdoor storage, considering
marine conditions, shall be provided. VENDOR shall provide full details of
preservation methods and any scheduled requirements during the 12 months.
General requirements prior of shipment include:
i. All supplied items shall be thoroughly cleaned and made free of any rust
and shall be properly fixed prior to shipment.
ii. All components shall be pre-assembled to the maximum extent possible.
iii. Any internal parts which might be subjected to damage or displacement
during transportation shall be protected with appropriate supports, bracing,
framing etc.
iv. All surfaces shall be cleaned and coated with a removable rust preservative.
v. The ends of the cables or the connection leads shall be suitably sealed by
heat shrinkable adhesive end-seals, which shall remain fitted until the final
connection is made.
vi. COMPANY shall inspect all items prior to shipment.
A careful inspection shall be made to ensure that all operating instructions and label
plates are in place, legible and have not been obscured during painting operations.
Each item shall be clearly identified with the VENDOR name, address, Purchase
Order, and tag number.
The treatment and protection of the metalwork may be in accordance with
manufacturer's standard but shall include cleaning, degreasing, rust resisting primers
and paint finishes that provide effective protection against corrosion.
Protection shall be provided against atmospheric corrosion while in transit and while
in outdoor storage. All exposed machined surfaces shall be protected with an easily
removable rust preventative compound.
The contents of all boxes or packages shall be recorded in detail on the packing list.
The transported package shall have the necessary fastenings, protections and lifting
facilities to satisfy lifting and sea-fastening loads and restraints.
The packing and preservation according to VENDOR requirements shall be approved
by the COMPANY.
All items shall be tagged, and gross weight shall be clearly shown at a box crates and
containers in accordance with instructions in the Purchase Order.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 28/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

16.0 CERTIFICATION REQUIREMENT


An official certificate issued by recognized International Classification Society is
obligatory to prove that the manufacturer’s Quality Management System meets the
requirement of ISO 9001 (latest edition) Standards. Availability of a certificate for
compliance of ISO 14001 Standard is encouraged.

VENDOR shall provide Certificates of Origin issued by Chamber of Commerce of


manufacturer’s country, Certificate of Quality issued by Manufacturer and
VENDOR’s Certificate of Guarantee.

17.0 WARRANTY OBLIGATION


VENDOR shall have the final and total responsibility for the design and performance
of all equipment supplied under this specification. VENDOR shall warrant the
equipment furnished by him and the performance of said equipment in accordance
with this specification. The warranty shall cover both, the supply of material and
manpower to make good any defective components or equipment offshore.

Guaranteed term is specified to be eighteen (18) months from delivery date or twelve
(12) months after the package have been successfully commissioned offshore,
whichever comes first.

During the guaranteed term the VENDOR, at his own expense and effort, within the
shortest possible period eliminates any faults or failures that have occurred in the heat
tracing system and replace the required components.

The period during which the heat tracing system cannot be used due to the defects is
not included in the guaranteed term. During the guaranteed term the VENDOR at his
own expense re-supplies spare parts and products consumed to eliminate the failure.

18.0 VENDOR QUALITY REQUIREMENT


The VENDOR shall ensure that purchased product conforms to the specified
requirements.

The VENDOR shall have an established and documented Quality System as a means
of ensuring that product conforms to specific requirements.

VENDOR shall select Sub-VENDORS based on their ability to meet contract


requirements, including quality requirements. The VENDOR shall establish and
maintain records of acceptable Sub-VENDORS. Purchase Orders to Sub-VENDORS
placed in support of the main Purchase Order shall not relieve the VENDOR from any
obligations specified in the order.

Provision shall be made for access by COMPANY and/or their representatives, to the
VENDOR’S premises and to those of Sub-VENDORS, following Purchase Order

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 29/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

award, for the purposes of surveillance and/or Quality System Audit. Verification by a
COMPANY representative shall not absolve the VENDOR of the responsibility to
provide acceptable products, nor shall it preclude subsequent rejection.

VENDOR shall provide objective evidence at bid submission that they operate an
effective quality system appropriate to the scope of supply. The evidence may be in
the form of either:

• VENDOR’S Quality Manual or description of VENDOR’S Quality system, or


• Where the VENDOR’S system has been approved by the independent
accredited certification body, the Certificate of Approval, together with a list
of available procedures, may be submitted instead of the Quality Manual.
VENDOR shall submit their ITPs which shall include:
• Those inspections and test performed by the VENDOR or Sub-VENDOR.
• The requirements for the inspections and tests (i.e., COMPANY, Industry,
Code, or VENDOR Standard Procedures).
• Description of Operation/Test/Inspection (i.e., sequence of operation, test, and
inspection for each main manufacturing activity).
• The Organisation responsible for performing them.
The ITP as agreed and accepted by COMPANY shall be deemed part of the
contractual quality requirements of the Purchase Order.

19.0 VENDOR DOCUMENTATION REQUIREMENT


VENDOR document requirements shall comply with the requirements given under
VENDOR Document Requirements List.

VENDOR shall submit the list of deviations from this specification along with the
bid.

All documentation shall be submitted in English stating the parameters in the SI Unit
System.

Doc No: 9001-2300-SE-0001-B1 Rev. B1 Page 30/30


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

APPENDIX A – DATASHEET FOR ELECTRICAL HEAT TRACING

Doc No: 9001-2300-SE-0001-B1 Rev. B1


ZARUBEZHNEFT EP VIETNAM DAR ENERGY SDN BHD

FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’


GAS CONDENSATE FIELD

DATASHEET FOR ELECTRICAL HEAT TRACING


(CPP RONG DOI)

DOCUMENT NO.: 9001-2300-KE-0001-B1

B1 28-12-23 Issued for Implementation NSMA MRAB SD

A1 18-10-23 Issued for Review NSMA MRAB SD


Prepared Checked Approved Client
Rev No Date Purpose of Issue
By By By Approval
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

DATASHEET FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

TRACK CHANGES

No Revision No Content of Changes Note

1 A1 Issued for Review

2 B1 Issued for Implementation

Doc No: 9001-2300-KE-0001-B1 Rev. B1 Page 2/6


CLIENT: Specification No.: 9001-2300-SE-0001
DATA SHEET Document No.: 9001-2300-KE-0001
DATASHEET FOR ELECTRICAL HEAT TRACING (CPP RONG DOI) Page: 3 of 6
Rev. No.: B1
CONTRACTOR: Item Tag No.: 230-DP-8411
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’
GAS CONDENSATE FIELD Service: Heat Tracing

CPP RONG DOI VIETNAM

ENVIRONMENTAL CONDITIONS ELECTRICAL SYSTEM


Location: Outdoor System Voltage: 400 V AC +/-10%
Ambient air temp: Min: 18.2°C Max: 35.1°C Sytem Frequency : 50 Hz +/-5%
Humidity: Min: 77% Max: 100% Altitude: <1000m Neutral Earthing: Solid Earth TN-S
Hazardous area classification: Zone 2, Outdoor
PARTICULARS OF EQUIPMENT UNIT PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE
OPERATING CONDITION
Applicable Standard IEC60079, IEC60947, IEC61439
Service Name Heat Tracing
Location Outdoor, Zone 2, IIA , T3
Manufacturer VTA
Type VTA
Design Life years 25
Service Continuous
Design Ambient Temperature °C 40
Design Humidity % 100
Atmospheric Contaminants Hazardous, Offshore, Salt laden
HEAT TRACING PIPE DATA
Pipe to be Electric Heat Traced Refer Line List
Pipe Length mtr Refer Piping ISO
Nominal Diameter of Pipe mm Refer Piping ISO
No. of Flanges Refer Piping ISO
No. of Valves Refer Piping ISO

Type of Thermal Insulation Refer Piping Material Class Specification

Insulation Thickness mm Refer Line List


Fluid to be Heat Traced Refer Line List
Fluid Degradation Temperature °C Refer Line List
Fluid Normal Temperature w/o EHT °C Refer Line List
Maintained Temperature °C Refer Line List
Max. Heater Exposure Temp. / Design Temp. °C Refer Line List
Heat Loss VTA
ELECTRICAL HEAT TRACING EQUIPMENT DATA
Type of Heating Cable Self-Regulating
Heater Cable Model No. VTA
Length of Heating Cable VTA
Installed Power VTA
Number of Circuit VTA
Circuits Power Consumptions VTA
Thermostat / Temp Control System Data:
Qty VTA
Type VTA
Connection / Junction Boxes:
Qty VTA
Type VTA
Termination System:
Qty VTA
Type VTA
End Kit:
Qty VTA
Type VTA
Other Accessories:
Qty VTA
Type VTA

Temperature Inspection Window Yes


CLIENT: Specification No.: 9001-2300-SE-0001
DATA SHEET Document No.: 9001-2300-KE-0001
DATASHEET FOR ELECTRICAL HEAT TRACING (CPP RONG DOI) Page: 4 of 6
Rev. No.: B1
CONTRACTOR: Item Tag No.: 230-DP-8411
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’
GAS CONDENSATE FIELD Service: Heat Tracing

CPP RONG DOI VIETNAM

PARTICULARS OF EQUIPMENT UNIT PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


HEAT TRACING DISTRIBUTION BOARD
Rated Input Voltage 400V AC, +/-10%, 3Ph+N
Rated Insulation Voltage kV,rms 2.5
Min. Busbar Rated Current A 150
Colour Coded (L1-Red, L2-Yellow, L3-
Busbar Identification
Blue, N-Black, E-Green/Yellow)
Hard Drawn High Conductivity (HDHC)
Busbar Material
Tinned Copper
Busbar Insulation Fully insulated
Prospective Short Time Withstand Current 10 kA RMS, 1 sec.
Frequency Hz 50
Earthing System TN-S
Neutral Earthing Arrangement Solid
Protection and Metering Device requirement As per Single Line Diagram
Type of Fuses DIN/BS
Measuring Instruments Analogue
Degree of Pollution 3
DISTRIBUTION BOARD GENERAL REQUIREMENT
Enclosure:
Explosion Protection Category Ex 'de',IIA, T3, Zone 2
IP Rating Min. IP56
Cubicle Type VTA
Material & Finishing Copper Free Aluminium
External & Internal Colour VTA
Type of Enclosure Metal/Multi-box
Padlock Hasp Size VTA
Ventilation Naturally Ventilated
Anti-Condensation Heater No
Access Front
All Cable Entries Bottom
Cable Gland Plate Pre-Drilled
Earthing Studs Yes
Gland type Metric
Drain and Breather Ex-certified Yes
Gland Required Yes
Lifting Lug (Eye Bolts) Yes
Overall Distribution Panel Dimension (L x W x H) mm VTA
Overall Mass of Distribution Panel kg VTA
GA Drawing Yes
Marine Application Certified Yes
Rain shed ( Yes/no) Yes
Make and Type VTA
Manufacturing Location (Assembly/Main Component) VTA/VTA

Incomer Circuit Breaker Device:


Number of Incomer 1
Type of Breaker MCCB
No. of Pole 4
Rated Current A VTA Note 9
Auxillary voltage V AC 230
Manufacturer/ Model VTA
Padlock Facility to be provided Yes
Ammeter with Selector Switch Yes
Voltmeter with Selector Switch Yes
LED Indication Lamp Yes
CLIENT: Specification No.: 9001-2300-SE-0001
DATA SHEET Document No.: 9001-2300-KE-0001
DATASHEET FOR ELECTRICAL HEAT TRACING (CPP RONG DOI) Page: of
Rev. No.: B1
CONTRACTOR: Item Tag No.: 230-DP-8411
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’
GAS CONDENSATE FIELD Service: Heat Tracing

CPP RONG DOI VIETNAM

PARTICULARS OF EQUIPMENT UNIT PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


HEAT TRACING DISTRIBUTION BOARD
Manual, Operable from external of
Operational of Switching
enclosure
2
Incoming Cable Type / Cable Size / Entry Size CU/EPR/EVA/SWB/EVA (4C+Ex95mm )
Short circuit rms As per Single Line Diagram

Outgoing Circuit Breaking Device:


Type of Breaker MCB
Rated Current As per Single Line Drawing
Auxillary voltage V AC 230
Manufacturer/Model VTA
Padlock Facility to be provided Yes
Note 9
Number of Circuits (Inclusive of Spares) As per Single Line Diagram
Spare Space Capacity 20%
Outgoing Cable Type / Cable Size / Entry Size VTA
Short circuit rms As per Single Line Diagram

Contactor:
Electro-magnetically operated, Air break
Type of Breaker
type
Rated Current As per Single Line Diagram
Short Circuit Current Rating As per Single Line Diagram
Utilization Category AC3
Duty Class Continuous
Auxillary Contact As per Single Line Diagram
Closing pick-up voltage(% rated voltage) 80% to allow for voltage dip
Drop out voltage below 65%
Auxillary voltage V AC 230

Current Transformer:
Protection & metering CT requirement As per Single Line Diagram
No of phases/No of cores As per Single Line Diagram
CT Accuracy class Class 1 (measuring purpose)
Class 5P ( Protection)
Saturation Factor VTA
VA Rating VTA
CT secondary ampere A 5
Short Circuit current rating As per Single Line Diagram

RACK / FRAMEWORK REQUIREMENTS


Rain / Sun Canopy Yes
Mounting Type Rack
Racking and Framework Requirement Yes
Total Racking / Framework Dimension (W x D x H) mm VTA
Total Mass with Enclosures kg VTA
Earthing Studs for each Racking / Framework yes, 2 nos
Painting / Surface Finishing Marine coated system
GA / Plinth Drawing Yes
CLIENT: Specification No.: 9001-2300-SE-0001
DATA SHEET Document No.: 9001-2300-KE-0001
DATASHEET FOR ELECTRICAL HEAT TRACING (CPP RONG DOI) Page: 6 of 6
Rev. No.: B1
CONTRACTOR: Item Tag No.: 230-DP-8411
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’
GAS CONDENSATE FIELD Service: Heat Tracing

CPP RONG DOI VIETNAM

PARTICULARS OF EQUIPMENT UNIT PURCHASER'S REQUIREMENTS VENDOR'S RESPONSE


MISCELLANEOUS
Signal Interface with PCS No
4-20 mA Current Monitoring No
4-20 mA Voltage Monitoring No
Common Fault Alarm and Running Status Yes
Main Incomer MCCB Command (24V DC, 2W Signal) No
Main Incomer MCCB Status (Volt-Free Contact) No
SIS Trip No

INSPECTION AND TESTING


Test Requirements
Routine Tests Yes
Type Tests Yes
Special Tests Yes
Primary Current Injection Test (CIT) Yes

NOTES:
1. VTA = VENDOR to Advise
N/A = Not Applicable
2. VENDOR response : C-COMPLY, X-EXCEPTION/DEVIATION
3. This datasheet shall be read together with Specification for Electrical Heat Tracing, Doc. No. 9001-2300-SE-0001
4. All circuits equipped with 25A MCB.
5. Short circuit rating shall be by VENDOR.
6. Complete lines to be heat traced shall be as per Line List, P&ID and Piping Isometric Drawings.
7. Vendor Shall refer to Single Line Diagram for Heat Tracing Distribution Panel.
All cable entries shall be pre-drilled inclusive of spare quantities with metric gland holes. Ex-rated blanking plugs shall be provided
for all the entries. All the entries size shall be reconfirmed with PURCHASER prior to drilling.
8. Vendor Shall refer to Insulation Specification and Pipe Specification.
9. Shall be determined by Vendor based on load requirement.
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

APPENDIX B – DEVIATION FORM

Doc No: 9001-2300-SE-0001-B1 Rev. B1


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

PROJECT FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS CONDENSATE FIELD

TITLE DEVIATION FORM

PACKAGE ELECTRICAL HEAT TRACING (CPP RONG DOI)

PAGE OF:

TECHNICAL EXCEPTIONS / DEVIATIONS PROJECT NO:

P.O.s No.:

No. Contractor's Document Contractor's Spec. Requirements Exception / Deviation Proposed by Clarification / Reason for Exception / CONTRACTOR Reply COMPANY Reply
Clause / Title SUBCONTRACTOR Deviation

Note: Any exceptions / deviations to the stipulated requirements shall be stated in the “Technical Exceptions / Deviations” Form attached with the requisition and submits togetherwith the bid. Technical
Exception/Deviations stated elsewhere shall not be accepted by CONTRACTOR.

Doc No: 9001-2300-SE-0001-B1 app B Rev. B1 Page 1/1


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

APPENDIX C – VENDOR DOCUMENT REGISTER LIST (VDRL)

Doc No: 9001-2300-SE-0001-B1 Rev. B1


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

diesel

APPLICABLE TO :  PROPOSAL ⚫ PURCHASE  AS BUILT/FINAL DATE ________ REVISION ______

⚫ OWNER : ZARUBEZHNEFT EP VIETNAM


⚫ PROJECT : FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI-AU’ GAS
CONDENSATE
⚫ SERVICE : ELECTRICAL HEAT TRACING (CPP RONG DOI)
SEE NOTES FOR FURTHER DESCRIPTION OF CODES AND REQUIREMENTS.

VDRL DESCRIPTION PROPOSAL REVIEW FINAL REVIEW VENDOR


CODE NEED DATE
DATE

A.00 INTERFACE INFORMATION


Drawings and documents within this class shall comprise all information which may interface with other
facilities of Purchaser, and are of major importance for platform facilities design.

A.01 General Arrangement Drawings


including:-
outline dimensions, location, size
and type of connections, weight YES YES YES 6 WAFO
and C of G, part list, bill of
materials/material of construction,
design data, deviation list, etc.

A.02 Shop details / assembly, cross-


sectional drawings details of
internal, weld details

A.03 Functional Description, Vendor


YES YES 2 WPTD
Literature /Mechanical catalogue

A.04 Cable Schedule YES YES 2 WPTD

A.05 Outline foundation loading


diagrams

A.06 Single Line Diagram YES YES YES 6 WAFO

A.07 Distribution Board Details


(drawings, schematic, installation, YES YES YES 6 WAFO
etc.)

A.08 Manufacturing and delivery


plan/Fabrication schedule
YES YES

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 1/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

VENDOR DOCUMENT REQUIREMENTS LIST (VDRL) – CONTINUED

VDRL DESCRIPTION PROPOSAL REVIEW FINAL REVIEW VENDOR


CODE NEED DATE
DATE

A.09 Experience list related to Design &


YES
fabrication of the Equipment

A.10 List of sub-Vendors and sub-


YES YES YES 4 WAFO
contracted work

A.11 Equipment Data Sheets -


Completed data sheets as defined in YES YES YES 6 WAFO
the functional specification

A.12 Utility Consumption List

A.13 Inspection Test Plan YES YES YES 6 WAFO

A.14 Vendor Master Document List YES YES 4 WAFO

B.00 DESIGN INFORMATION


Drawings and documents within this class shall provide detail design information to allow verification of
compliance with Purchaser’s specifications.

B.01 Cross Section Drawings & Parts


List
Shop Details/Assembly, Cross
sectional drawing with part list,
details of internals, weld details,
withdrawal space

B.02 Circuit Breaker


Curves

B.03 Design Calculation YES YES 6 WAFO

B.04 Mechanical Calculation

B.05 Thrust bearing sizing calculations

B.06 Battery sizing calculation

B.07 Engine exhaust silencer and piping


sizing calculation.

B.08 Torsional and Lateral Analysis

B.09 Lifting/Structural Calculations

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 2/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

VENDOR DOCUMENT REQUIREMENTS LIST (VDRL) – CONTINUED

VDRL DESCRIPTION PROPOSAL REVIEW FINAL REVIEW VENDOR


CODE NEED DATE
DATE

B.10 Reliability/Availability Data YES YES 6 WAFO

B.11 Schematic Diagrams YES YES 6 WAFO

B.12 Wiring Diagrams YES YES 6 WAFO

B.13 Preservation, packing and shipment


YES YES 8 WPTD
procedures

B.14 Spare Parts and Interchangeability


YES YES 8 WPTT/P
Record

B.15 Nameplate data and drawing YES YES 8 WPTT/P

B.16 Inspection and Test Plan YES 4 WAFO

B.17 Quality Plan YES YES 4 WAFO

C.00 TESTING PROCEDURES


These documents shall demonstrate to the Purchaser that the testing methods are acceptable.

C.01 NDE’s Test Procedures

C.02 Welding and welding repair


Procedures/WPS/PQR

C.03 Hydrostatic Test Procedures

C.04 Noise Test Procedures

C.05 Vibration Test Procedure

C.06 Controller Interface Test Procedure

C.07 Surface Preparation and Painting


Procedures

C.08 Overspeed Test Procedures

C.09 Functional Test Procedures YES YES 8 WPTT/P

C.10 Performance Test Procedures

C.11 NPSH and Submergence Test


Procedures

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 3/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

VENDOR DOCUMENT REQUIREMENTS LIST (VDRL) – CONTINUED

VDRL DESCRIPTION PROPOSAL REVIEW FINAL REVIEW VENDOR


CODE NEED DATE
DATE

D.00 RECORDS, REPORTS AND CERTIFICATES


These documents are required in order to demonstrate that material and equipment comply with
specifications

D.01 Cleaning/flushing/Record

D.02 Certificate of Compliance YES YES 2 WAT/P

D.03 Hydrostatic Test Record

D.04 Overspeed Test Reports

D.05 Functional/String Test Reports YES 4 WPTD

D.06 Performance Test Reports YES 4 WPTD

D.07 NPSH and Submergence Test

D.08 Equipment Hazardous Area


YES 4 WPTD
Certificates

D.09 Lifting Gear Test Certificates

D.10 Performance Guarantee YES YES 4 WPTD

D.11 Welder qualification records

D.12 NDE Technician Certificates

D.13 NDE’s test certificate

D.14 Corrosion Test Certificate.

D.15 Hardness Test Certificate.

D.16 Dis-Assembly Test Report

D.17 Noise Test Record

D.18 Vibration Test

D.19 Gearbox Performance Test Record

D.20 Engine Performance Test Record

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 4/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

VENDOR DOCUMENT REQUIREMENTS LIST (VDRL) – CONTINUED

VDRL DESCRIPTION PROPOSAL REVIEW FINAL REVIEW VENDOR


CODE NEED DATE
DATE

D.21 Positive Material Identification


Certificate

E.00 INSTRUCTIONS FOR INSTALLATION, OPERATION, AND MAINTENANCE


These documents shall comprehensively cover the delivered equipment, and shall give personnel at all
levels necessary and sufficient information for safe, correct, and efficient installation, operation and
maintenance of the equipment, system and/or plant.

E.01 Instruction for Lifting and


Transport to Fabrication Yard and
during Loadout.

E.02 Instruction for Unpacking,


YES 8 WPTD
Inspection and Storage

E.03 Instruction for Installation YES 8 WPTD

E.04 Instruction for Packing and


Preservation during Transport and
YES 8 WPTD
Storage before and after
Installation

E.05 Instruction for Commissioning YES 8 WPTD

E.06 Instruction for Operation and


YES 8 WPTD
Maintenance

E.07 Lubrication Charts

E.08 Special tools details YES YES YES 6 WAFO

E.09 User/Operating Manuals YES 6 WPTD

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 5/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

Abbreviation Used: Milestone

WAFO - Weeks After Firm Order Firm Order

WPTT - Weeks Prior To Test / Process Production Start

WAT - Weeks After Test / Process Test / Process

WPTD - Weeks Prior To Delivery Test / Process

Delivery

Notes:
1. STANDARD SIZE FOR DRAWINGS IS A3. LANGUAGE SHALL BE IN ENGLISH, UNITS IN S.I.
UNITS.
2. DOCUMENTS SHALL BE IN 80 GMS A4 SIZE OF PAPER.
3. FINAL DATA BOOK SHALL INCLUDE ALL ENGINEERING “AS-BUILT” INFORMATION ON
DRAWINGS AND
4. “FINAL” ON MANUAL & REPORTS.
5. A COPY OF THE FINAL DOCUMENTATION SHALL BE IN ELECTRONIC FORMAT. THE
DRAWINGS
6. PRODUCED SHALL BE IN DRAWING EXCHANGE (.dwg) AND ALL DOCUMENTS SHALL BE IN
PORTABLE
7. DOCUMENTS FILES (.pdf).

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 6/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

GENERAL REQUIREMENTS

The following software will be used for VENDOR information :


• Drawing in AUTOCAD latest revision
• Spreadsheet in MICROSOFT OFFICE latest revision
• Manual/documents in MICROSOFT OFFICE latest revision
• Database in MICROSOFT OFFICE
For “Equipment Information Sheet” (sample Attachment II) all data shall be type written.
VENDOR shall prepare as per the attached format (sample Attachment IIIA and Attachment IIIB) List of Contents and
List of As-built Drawing.
VENDOR shall submit all approved Final Documentation using 80gm A4 size paper.
As for As Built Drawings, VENDOR shall submit in A3 size paper.
VENDOR shall submit related document for final documentation which is readily punched with 3-holes or loose sheet.
All other documents e.g. hand-written test reports shall be scanned image in PDF format.
VENDOR to provide detail execution plan in his bid proposal for electronic based documentation i.e Vendor Master
Document List (VMDL) submission/ approval status.
VENDOR shall complete the Spare Parts List And Interchangeability Record (SPIR) forms as stated in the VDRL and to
follow requirements.
All finalized and approved documents as required in the VDRL must be of clean (without history) original documents or
good master print. All CERTIFICATES (i.e. Mill, Manufacturing, Test, Third party inspection) which is not of origin
copy must be stamped with “Certified True Copy” and signed by 3rd party certification agency for the purpose of Final
Documentation compilation.

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 7/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

Attachment II
EQUIPMENT INFORMATION SHEET (SAMPLE)

PURCHASE ORDER NO.

PURCHASE INQUIRY DOCUMENT (PID) DATE OF PO:

PID NO: REV. EXP. DATE OF WARRANTY:

EQUIPMENT

EQUIPMENT DESCRIPTION TAG NO. MODULE NO. MAKE

LOCAL AGENT/VENDOR PRINCIPAL/MANUFACTURER

Company Name: Company Name:


Company Address: Company Address:

Tel/Fax: Tel/Fax:
Contact Person: Contact Person:

REMARKS:

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 8/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

Attachment IIIA
FINAL DOCUMENTATION TABLE OF CONTENT
(non- instrumentation)

Name and Address of Manufacturer/ :


Supplier

P/O No. :
Project :
Owner :

INDEX DESCRIPTION N/A APPLICABLE

1.1 Equipment Information Sheet

1.2 Engineering Data Sheet

1.3 Warranty Certification

1.4 As Built Vendor Drawing

1.5 Operating and Maintenance Manual


- Recommended Spare Part List
- Recommended Maintenance Schedule Summary

1.6 Factory Acceptance Procedure / Report

1.7 Design Calculation

1.8 Test Certification

1.9 Material and Inspection Report

1.10 Others

Note :
Please tick ( / ) if applicable and ( x ) for NA (not applicable)

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 9/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

Attachment IIIB
LIST OF DOCUMENTS

ITEM DOCUMENTS NUMBER REV. NO. DOCUMENTS TITLES

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 10/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

Attachment IIIB

LIST OF AS-BUILT DRAWINGS

ITEM DRAWING NUMBER REV. NO. DESCRIPTION

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 11/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI))

GUIDELINE FOR CONVERTING HARD COPY DOCUMENT INTO ELECTRONIC FORMAT

Scanning from hard copy

1. Use good quality scanner, standard scanning resolution : 300 dpi


2. Scan hard copy into PDF format using Adobe Acrobat latest revision.
3. Quality control each scanned page; filter, remove specks, correct page rotation etc.
4. Remove staples and other stickies.
5. All coloured original documents to be colour scan.

PDF Preparation

1. Create bookmark for every pages, indent in and out the bookmarks as per table of content.
2. Create link for front page and table of content.
3. Create thumbnail for every pages.
4. Insert a vector front/cover page containing all information of the original hard copy front page.
5. The document opening should be “Page and Bookmark”
6. Name and file in systematic manner. Each filename should be unique.
a. Final Documentation filename shall be obtained from Document Custodian
b. Office document filename shall be the document number/name
c. Reports shall use report or document number as filename

Option
Contractor may submit, upon request by COMPANY, all softcopy in external hard drive or
equivalent.

Doc No: 9001-2300-SE-0001-B1 app C Rev. B1 Page 12/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

VENDOR MASTER DOCUMENT LIST (VDML)

VDRL Vendor Planned Rev Return Status Rev Return Status Rev Return Status
Item Description
Code Document Date A Date Code B Date Code 0 Date Code

Doc No: 9001-2300-SE-0001-B1 Appendix C Rev. B1 Page 13/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

STATUS CODES:

A - Approved Without Comments Updated On :

B - Approved As Noted - To incorporate marked-up comments and resubmit for approval Client :

C - Not Approved or Rejected - Resubmit for approval Project No. :

D - For info only. Review not required :

0 - Final Submission Document No. :

Doc No: 9001-2300-SE-0001-B1 Appendix C Rev. B1 Page 14/14


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

APPENDIX D – INSPECTION AND TEST PLAN

Doc No: 9001-2300-SE-0001-B1 Rev. B1


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

1.0 INSPECTION AND TEST PLAN


1.1 GENERAL
Inspection and testing requirements shall be in accordance with the applicable
datasheets, specifications, codes and standards.

All testing shall be carried out at the manufacturer’s test facility. The test equipment
shall be supplied by the manufacturer and shall be calibrated within six months of the
test date.

VENDOR shall include an Inspection and Test Plan (ITP) in their Tender documents.
The ITP shall list all inspections and tests proposed for the equipment by the
VENDOR, between the date of ordering and the date of delivery. The plan will be
reviewed and approved to become the approved Inspection and Test Plan for the
Project and form part of the contract documents.

The VENDOR shall be responsible for the planning and execution of all inspections
and tests, but the CONTRACTOR’s representative shall have the right to witness any
or all of the manufacturing, inspection or tests.

The VENDOR shall notify the CONTRACTOR, at least fourteen (14) days in
advance, of the date on which any of the inspections or tests nominated as Hold or
Witness points on the ITP are due to be carried out.

Certificates of Test shall be provided for each item of equipment to prove it has been
satisfactorily tested to meet all requirements of its appropriate manufacturing
standards, whether or not witnessed by the CONTRACTOR.

Where appropriate, test certificates shall state values for all test results. Tests for
which the results are indicated as pass or fail shall be qualified by the relevant
acceptance criteria.

1.2 FACTORY ACCEPTANCE TESTS (FAT)


Each component/material shall be tested in accordance with the standards and codes
listed in Section 2 of this document. Testing shall be carried out as per a COMPANY-
approved test program.

COMPANY may require additional testing if test results are unsatisfactory or


marginal. Any components rejected shall be repaired or replaced to the COMPANY’s
satisfaction and the test shall be repeated.

The planning / scheduling of maintenance and inspection for the equipment shall be
undertaken.

Doc No: 9001-2300-SE-0001-B1 app D Rev. B1 Page 1/2


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

The VENDOR/CONTRACTOR shall provide the maintenance and inspection


requirements (as applicable) for the following periods as a minimum; monthly, 3
monthly, 6 monthly, yearly, 2 yearly and 4 yearly.

1.3 SITE ACCEPTANCE TESTS (SAT)


VENDOR’s representative may be required to visit the installation site during the
commissioning period, as advised by the COMPANY.

Site acceptance test shall include functional tests and visual inspection as specified.

Doc No: 9001-2300-SE-0001-B1 app D Rev. B1 Page 2/2


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT ‘THIEN NGA-HAI AU’ GAS
CONDENSATE FIELD

SPECIFICATION FOR ELECTRICAL HEAT TRACING (CPP RONG DOI)

APPENDIX E – REFERENCE DRAWING

Electrical Single Line Diagram – Heat Tracing Distribution


Panel 230-DP-8411 (CPP Rong Doi)

Electrical Equipment Layout 9001-2300-DE-5801

Equipment Layout

HAC Drawings

Process & Instrument Diagram (P&ID)

Process Line List

Piping Isometric Drawings

Doc No: 9001-2300-SE-0001-B1 Rev. B1


DAR Energy Sdn Bhd

FEED FOR WELLHEAD PLATFORMS (BK-TNHA,BK-TN) AT


"THIEN NGA - HAI AU" GAS CONDENSATE FIELD
11 21 22
1 2 3 4 5 6 7 8 9
B2
B3
B1
B4
B
A1
Bridge
A2
A
WHd

PUQC

Flare Boom
KEY PLAN

CELLAR DECK EXTEND DECK


AT T.O.S. EL (+)17300

DAR Energy Sdn Bhd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


AS - BUILT HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


80.11
80.16
25.7 25.9
74.1 80.21

23.5
80.8 80.7 80.6
25.4 23.2
25.10 25.11 80.20 80.15 80.10 80.13
25.2
21.1
25.9 25.8 80.19 80.23 80.14 80.18 80.9
21.2 64.1

80.17
80.22 TURBINE/ENCLOSURE OUTLET (TYP)
25.1 ENCLOSURE EXHAUST 80.12

TURBINE INLET
ENCLOSURE INLET
TURBINE EXHAUST
23.7
80.3
23.10 ENCLOSURE EXHAUST

80.2
23.12
23.1 80.1 DOWN

WINCH
UP
OUT

CYLINDER
IN

ENCLOSURE INLET
TURBINE EXHAUST TURBINE INLET (TYP)
23.8 23.9 TURBINE INLET
ENCLOSURE INLET (TYP)

73.2
56.1 56.2
23.11
40.9 40.11 40.14

64.2

50.2 50.3
22.1

23.3 34.3 34.8 24


41.1 25.3 51.1
20.3 74.2
50.4 51.2 AS - BUILT
23.13

HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


44.3 44.4
99.4
25.5 99.4

99 20.1
44.1
99.1
23.6 23.4

80.5

21.1
99.4

20.2 70.2

37.2
40.4 40.6

70.1

41.4 40.9 40.12

34.2
34.4

34.6

34.8
99.4 61

34.7
34.5 34.1
AS - BUILT
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


22.4

22.3

11 21 22
1 2 3 4 5 6 7 8 9
B2
B3
B1
B4
B
A1
Bridge
A2
A
WHd
23.13 PUQC

Flare Boom
KEY PLAN

DAR Energy Sdn Bhd

FEED FOR WELLHEAD PLATFORMS (BK-TNHA,BK-TN) AT


"THIEN NGA - HAI AU" GAS CONDENSATE FIELD
80.21
80.16
25.7 23.8
80.11
25.9 23.10
74.1

80.10 80.15 80.20 23.12


64
80.9 80.14 80.19

21.2
23.5
80.18 80.23
25.4 25.6 23.7
SWL 1.5 TONNES

23.10

ENERPAC
80.6
TURBINE INLET
80.5
73.2 80.13 ENCLOSURE INLET

25.1 23.1

20.2
80.12 80.7 80.17 80.22 99.1
99

80.8 22.4 44.3 23.4


44
44.4
23.6
40.3
40.5

37.4

VIEW LOOKING WEST AS - BUILT


HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


50.1
56.1 56.2 40.9
40.11 40.14
20.4

74.1
25.3 23.3 34.8
SWL 1.5 TONNES

ENERPAC
34.3 64.2
24 74.2
50.2
23.13
50.3 51.2
51.1

41.1 73.2
34.4 34.6 34.7 34.5

41.4 70.1

22.3
48.1
40.4 40.6
34.2 40
40.9 40.12
20.4

VIEW LOOKING EAST


AS - BUILT
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Mohd Ir Suhaimi
Aizuddin Ir Zulkfley
YusofYusof
RONG DOI GAS FIELD DEVELOPMENT PROJECT
Nur Dhiyana Bin Rusli Mansor Deraman
Khalid
2024.01.23 13:52:16 2024.01.2 2024.01.24
+08'00' 3 Khali 2024.01.2
4 14:54:40
2024.01.24
15:20:02
17:24:00 14:23:10+08'00'
+08'00' d +08'00' +08'00'
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


FOR INFORMATION ONLY

HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


FOR INFORMATION ONLY

HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


FOR INFORMATION ONLY

HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

RONG DOI GAS FIELD DEVELOPMENT PROJECT


HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Yusof
Mohd
YusofKhalid Ir Zulkfley Ir Suhaimi
Aizuddin

RONG DOI GAS FIELD DEVELOPMENT PROJECT


Mansor Deraman
Nur Dhiyana
2024.01.23 13:54:49 Khali 2024.01.2
Bin Rusli
2024.01.2 4 2024.01.24
+08'00' 3 2024.01.24
17:26:02 d 14:57:00
+08'00' 14:25:19+08'00'
15:31:28
+08'00' +08'00'
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Mohd Yusof Ir Zulkfley Ir Suhaimi


Aizuddin
Yusof Khalid
RONG DOI GAS FIELD DEVELOPMENT PROJECT
Nur Dhiyana Bin Rusli Mansor Deraman
2024.01.23 13:54:38 2024.01.2
2024.01. 2024.01.24
+08'00'
Khalid4 14:57:21
23
17:26:22
2024.01.24
14:25:40+08'00'
15:31:49
+08'00'
+08'00' +08'00'
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Mohd YusoYusof Ir Zulkfley Ir Suhaimi


Aizuddin Khalid
f 2024.01. Mansor

RONG DOI GAS FIELD DEVELOPMENT PROJECT


Nur Dhiyana Bin Rusli Deraman
2024.01.23 13:57:12 2024.01. 2024.01.24
+08'00' 23
17:26:42
Khali 24
14:57:41
2024.01.24
14:25:58 15:32:21
+08'00' +08'00'
+08'00'
d +08'00'
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Mohd Yusof Ir Suhaimi


Aizuddin Ir Zulkfley
YusofKhalid

RONG DOI GAS FIELD DEVELOPMENT PROJECT


Nur Dhiyana Bin Rusli Mansor Deraman
2024.01.23 13:57:44
+08'00'
2024.01. Khali 2024.01.
24 2024.01.24
23 2024.01.24 15:37:19
17:28:51 d 14:28:51 14:40:18+08'00'
+08'00' +08'00' +08'00'
HEAVY INDUSTRIES CO., LTD.

Kvaerner E&C Singapore Pte Ltd

Mohd Yusof Ir Suhaimi


Aizuddin Ir Zulkfley
YusofKhalid

RONG DOI GAS FIELD DEVELOPMENT PROJECT


Nur Dhiyana Bin Rusli Mansor Deraman
2024.01.23 13:57:56
+08'00'
2024.01. Khali 2024.01.
24 2024.01.24
23 2024.01.24 15:35:25
17:28:31 d 14:28:31 14:40:00+08'00'
+08'00' +08'00' +08'00'
B1 9001-2300-DP-1203-01-B1
REV. DRAWING NO.

DISC. SIGN. DATE

CONST.

ELECT.

INSTR.

MAT'L.

MECH.
DAR Energy Sdn Bhd
PIPING

PROCESS PROJECT TITLE :

SAFETY
FEED FOR WELLHEAD PLATFORMS (BK-TNHA,BK-TN) AT
"THIEN NGA - HAI AU" GAS CONDENSATE FIELD
STRUC.
CONTRACT NO.: TITLE :
QA
Farhan
Pasihuddin
2024.01.24
12:40:01 +08'00'
Mohd
Aizuddin
Bin Rusli
2024.01.2
4 13:42:50
+08'00'
Yuso Yusof
Khalid
f 2024.01.
Khali 24
13:41:13
d +08'00'
Ir Zulkfley
Mansor

2024.01.24
14:21:32+08'00'
Ir Suhaimi
Deraman
2024.01.24
15:12:24
DV-449/21-NIPI-MSV CPP RONG DOI
+08'00'
SIZE :
B1 APPROVED FOR DESIGN 23.01.24 NS AIZ/MYK ZM SD A1 PRODUCTION PLATFORM PROCESS P&ID
A1 ISSUED FOR REVIEW 03.10.23 MFP MAR/NB ZM SD
SCALE :
CONDENSATE METERING PACKAGE
DISC. PROJ. CLIENT CAD FILENAME : DRAWING NO. SHT NO. REV.
GENERAL NOTES REFERENCE DRAWING TITLE DRAWING NO. COUNTER SIGN REV. DESCRIPTION DATE DRAWN CHECK
APPR. APPR. APPR. 9001-2300-DP-1203-01-B1 9001-2300-DP-1203-01-B1 1 of 1 B1
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT
"THIEN NGA - HAI AU" GAS CONDENSATE FIELD

PROCESS LINE LIST (CPP RONG DOI)

TITLE

PROCESS LINE LIST (RONG DOI)


FEED SERVICES FOR THE WELLHEAD PLATFORMS AT "THIEN NGA - HAI AU" GAS CONDENSATE FIELD

B1 24-01-24 ISSUED FOR IMPLEMENTATION RSI MYK/ ZM SD EXCEL FILENAME: 9001-2300-LP-0001-B1


CONTRACTOR
A1 23-10-23 ISSUED FOR REVIEW RSI / MAR ZM SD DRAWING NUMBER PAGE REV.
REV DATE DESCRIPTION PREPARED BY CHECKED BY PROJ. APPR. CLIENT APPR. 9001-2300-LP-0001-B1 1 OF 11 B1
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT "THIEN NGA - HAI AU" GAS CONDENSATE FIELD Doc. No : 9001-2300-LP-0001-B1

CPP RONG DOI - PROCESS LINE LIST Rev : B1

UNIT = UNIT NUMBER (barg, oC)


INSULATION & HEAT TRACING
SIZE = PIPE NOMINAL DIAMETER (INCH / ") CODE & LIM. P PERSONNEL PROTECTION
(FOR OPERATING TEMPERATURE >70oC)
H HEAT CONSERVATION

OPERATING CONDITIONS = NORMAL OPERATING CONDITIONS


THK. = INSULATION THICKNESS

RT% = PERCENT OF RADIOGRAPHY TEST


SERVICE INDENTIFIERS AI INSTRUMENT AIR
DC CLOSED DRAIN PIPE STRESS CATEGORY
DO OPEN DRAIN
HC HYDROCARBON LIQUID CATEGORY 1 PIPING IS CONSIDERED NON-CRITICAL AND NO COMPUTER ANALYSIS IS REQUIRED.
HG HYDROCARBON GAS CATEGORY 2 PIPING NOT FALL UNDER CAT 1 AND CAT 3 AND TO BE VERIFIED USING METHODS IN CLAUSE 319.4.1 ASME 31.3.
VH HIGH PRESSURE FLARE CATEGORY 3 PIPING TO BE ANALYZED USING CAESAR II SOFTWARE.
VL LOW PRESSURE FLARE
WO PRODUCED WATER

LINE NUMBERING

INSULATION CLASS

PIPING MATERIAL SPECIFICATION

SEQUENCE NUMBER

PROCESS SYSTEM NUMBER

SEDUCE CODE

NOMINAL PIPE DIAMETER (IN INCH/'')

GENERAL NOTES:

HOLDS:
1. THICKNESS TO BE CONFIRMED.

NOTE:
1. TO BE CONFIRM DURING DETAILS DESIGN STAGE.
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT "THIEN NGA - HAI AU" GAS CONDENSATE FIELD DOC NO. : 9001-2300-LP-0001-B1

PROCESS LINE LIST (HYDROCARBON LIQUIDS) REV : B1

OPERATING PIPING DESIGN HYDROTEST


INSULATION PROCESS DESIGN CONDITION
FLUID CONDITION CONDITION CONDITIONS
PIPING STRESS STRESS CALC.
NO SIZE SERVICE SYSTEM LINE NO PHASE FROM TO P&ID NO. MAX MIN RT % REMARK
CLASS THICKNESS PRESS TEMP PRESS PRESS TEMP PRESS CATEGORY NO
TYPE V/L/M TEMP TEMP MEDIUM
(mm) (barg) (oC) (barg) (barg) (oC) (barg)
(oC) (oC)
LIQUID/LIQUID SEPARATOR CONDENSATE HEATER 2300-DP-1200-01/ 19.36 -
1 3" HC 20 020 9C1 N/A N/A L 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
(230-V-2006) (230-E-3404) 2300-DP-1203-01 20.85

CONDENSATE HEATER CONDENSATE METERING Heat traced and


2 3" HC 20 023 9C1 HT (HOLD 1) L 2300-DP-1203-01 21.5 32.5 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
(230-E-3404) PACKAGE (230-A-3401) insulated.

6"-HC-20-025-9C1-HT/ Heat traced and


3 6" HC 20 024 9C1 HT (HOLD 1) L 3"-HC-20-023-9C1-HT 2300-DP-1203-01 21.5 32.5 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN08
RELIEF VALVE (PSV-3404B) insulated.
Heat traced and
4 6" HC 20 025 9C1 HT (HOLD 1) L 6"-HC-20-024-9C1-HT RELIEF VALVE (PSV-3404A) 2300-DP-1203-01 21.5 32.5 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN08
insulated.

19.36 -
5 2" HC 20 026 9C1 N/A N/A L SLUG CATCHER (230-V-2005) 4"-HC-20-028-9C1 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
20.85

19.36 -
6 2" HC 20 027 9C1 N/A N/A L SLUG CATCHER (230-V-2005) 4"-HC-20-028-9C1 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
20.85

2"-HC-20-026-9C1/
2"-HC-20-027-9C1/ 19.36 -
7 4" HC 20 028 9C1 N/A N/A L 4"-DC-48-316-1A2 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
2"-HC-20-030-9C1/ 20.85
2"-HC-20-031-9C1

LIQUID/LIQUID SEPARATOR 19.36 -


8 4" HC 20 029 9A1 N/A N/A L SLUG CATCHER (230-V-2005) 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
(230-V-2006) 20.85
LIQUID/LIQUID SEPARATOR 19.36 -
9 2" HC 20 030 9C1 N/A N/A L 4"-HC-20-028-9C1 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
(230-V-2006) 20.85
LIQUID/LIQUID SEPARATOR 19.36 -
10 2" HC 20 031 9C1 N/A N/A L 4"-HC-20-028-9C1 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
(230-V-2006) 20.85
LEVEL CONTROL VALVE 2300-DP-1203-01/ 19.36 - Heat traced and
11 3" HC 34 030 3C1 HT (HOLD 1) L STANDPIPE 21.5 46 85 -29 41.4 / 28.6 -100 / 204 WATER 69.0 100% 1 -
(LCV-2008) 230-P-DW-2020 20.85 insulated.
CONDENSATE METERING LEVEL CONTROL VALVE 19.36 - Heat traced and
12 3" HC 34 031 9C1 HT (HOLD 1) L 2300-DP-1203-01 21.5 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
PACKAGE (230-A-3401) (LCV-2008) 20.85 insulated.

Heat traced and


insulated. Line to be
tied-in at condensate
CONDENSATE SURGE DRUM 19.36 -
13 3" HC 34 032 3R1 HT (HOLD 1) L STANDPIPE 230-P-DW-2020 21.5 46 85 -29 51.7 / 42.4 -46 / 204 WATER 69.0 100% 1 - compartment of
(230-V-2004) 20.85
existing Condensate
Surge Drum (230-V-
2004).
FEED SERVICES FOR THE WELLHEAD PLATFORMS AT "THIEN NGA - HAI AU" GAS CONDENSATE FIELD DOC NO. : 9001-2300-LP-0001-B1

PROCESS LINE LIST (HYDROCARBON GAS) REV : B1

OPERATING PIPING DESIGN HYDROTEST


INSULATION PROCESS DESIGN CONDITION
FLUID CONDITION CONDITION CONDITIONS
PIPING STRESS STRESS CALC.
NO SIZE SERVICE SYSTEM LINE NO PHASE FROM TO P&ID NO. MAX MIN RT % REMARK
CLASS THICKNESS PRESS TEMP PRESS PRESS TEMP PRESS CATEGORY NO
TYPE V/L/M TEMP TEMP MEDIUM
(mm) (barg) (oC) (barg) (barg) (oC) (barg)
(oC) (oC)
2300-DP-1200-01/ 19.36 -
1 12" HG 20 050 9C1 N/A N/A V SLUG CATCHER (230-V-2005) GAS HEATER (230-E-2201) 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN01
2300-DP-1201-01 20.85
19.36 -
2 2" HG 20 051 9A1 N/A N/A V SLUG CATCHER (230-V-2005) RELIEF VALVE (PSV-2005B) 2300-DP-1200-01 22 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 3 CPPRD-CN06
20.85
19.36 -
3 2" HG 20 052 9A1 N/A N/A V 4"-HG-20-051-9A1 RELIEF VALVE (PSV-2005A) 2300-DP-1200-01 22 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 3 CPPRD-CN06
20.85
19.36 -
4 8" HG 20 054 9C1 N/A N/A V 12"-HG-20-050-9C1 8"-VH-41-227-1B1 2300-DP-1200-01 22 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN01
20.85
GAS METERING PACKAGE 2300-DP-1201-01/ 22.22 -
5 12" HG 20 055 9C1 HT (HOLD 1) V GAS HEATER (230-E-2201) 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN07
(230-A-2202) 2300-DP-1202-01 23.82

2"-HG-20-058-9C1/
22.22 -
6 2" HG 20 056 9C1 HT (HOLD 1) V 12"-HG-20-055-9C1 2"-HG-20-059-9C1/ 2300-DP-1201-01 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
23.82
RELIEF VALVE (PSV-2201A)

22.22 -
7 8" HG 20 057 9C1 HT (HOLD 1) V 12"-HG-20-055-9C1 8"-VH-41-236-9B1 2300-DP-1201-01 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN07
23.82
22.22 -
8 2" HG 20 058 9C1 HT (HOLD 1) V 2"-HG-20-056-9C1 RELIEF VALVE (PSV-2201B) 2300-DP-1201-01 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
23.82
22.22 -
9 2" HG 20 059 9C1 HT (HOLD 1) V 2"-HG-20-056-9C1 3"-VH-41-238-9B1 2300-DP-1201-01 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 1 -
23.82

2200-DP-1100-01/ CPPRD-CN02/
19.64 -
10 12" HG 20 065 9A1 N/A N/A M 16"-HG-35-001-E033 SLUG CATCHER (230-V-2005) 225-P-DW-2001/ 22.5 - 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 3 CPPRD-CN04/
19.92
2300-DP-1200-01 CPPRD-CN05

19.87 -
11 6" HG 20 066 9A1 N/A N/A V 12"-HG-20-065-9A1 6"-VH-41-240-9B1 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 3 CPPRD-CN04
19.92

LIQUID/LIQUID SEPARATOR 19.36 -


12 2" HG 20 067 9A1 N/A N/A V SLUG CATCHER (230-V-2005) 9001-2300-DP-1200-01 22 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 1 - Equalisation Line
(230-V-2006) 20.85

Line to be tied-in
230-P-DW-2008/
13 2" HG 21 020 9B1 N/A N/A V 12"-HG-21-002-9B1 12"-HG-20-055-9C1 98 42 118 85 -46 153.1 / 131 -46 / 204 WATER 177.0 100% 1 - from existing line no
2300-DP-1202-01
12"-HG-21-002-9B1
Line to be tied-in to
GAS METERING PACKAGE 2300-DP-1202-01- 22.22 -
14 12" HG 22 010 9C1 N/A N/A V 14"-HG-25-001-9R1 20.6 118 85 -29 124.1 / 85.5 -100 / 204 WATER 177.0 100% 3 CPPRD-CN03 existing line no 14"-
(230-A-2202) 230-P-DW-2002 23.80
HG-25-001-9R1

Pressurisation line for


the pressurization of
2300-DP-1202-01/ 16" pipeline to
15 2" HG 22 011 9B1 N/A N/A V 12"-HG-22-010-9B1 12"-HG-20-065-9A1 98 42 118 85 -29 153.1 / 131 -46 / 204 WATER 177.0 100% 1 -
2300-DP-1200-01 facilitate initial start-
up of BK-TNHA
facility.

Heat traced and


insulated. Line to be
tied-in at condensate
CONDENSATE SURGE DRUM 19.36 -
16 3" HG 34 050 3R1 HT (HOLD1) V STANDPIPE 230-P-DW-2020 21.5 46 85 -29 51.7 / 42.4 -46 / 204 WATER 69.0 100% 1 - compartment of
(230-V-2004) 20.85
existing Condensate
Surge Drum (230-V-
2004).

BK-TNHA FWS
19.87 -
17 16" HG 35 001 E033 N/A N/A M BK-TNHA FWS RECEIVER (220-R-3503)/ 2200-DP-1100-01 23 118 85 -29 118 -29 / 86 WATER 177.0 100% 3 CPPRD-CN04
19.92
12"-HG-20-065-9A1
19.87 -
18 2" HG 35 002 9A1 N/A N/A L 16"-HG-35-001-E033 2"-DC-48-310-1A2 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 1 -
19.92
BK-TNHA FWS RECEIVER 19.87 -
19 2" HG 35 003 9A1 N/A N/A L 2"DC-48-311-1A2 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 1 -
(220-R-3503) 19.92
19.87 -
20 2" HG 35 004 9A1 N/A N/A M 16"-HG-35-001-E033 6"-HG-35-005-9A1 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 1 - Balance Line
19.92
BK-TNHA FWS RECEIVER
19.87 -
21 6" HG 35 005 9A1 N/A N/A M (220-R-3503)/ 12"-HG-20-065-9A1 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 3 CPPRD-CN04
19.92
2"-HG-35-004-9A1
BK-TNHA FWS RECEIVER 19.87 -
22 2" HG 35 006 9A1 N/A N/A M 2"-VH-41-223-9B1 2200-DP-1100-01 23 118 85 -29 153.1 / 131 -29 / 204 WATER 177.0 100% 1 -
(220-R-3503) 19.92