Danfoss T2 TE2 Expansion Valves
Danfoss T2 TE2 Expansion Valves
REFRIGERATION &
AIR CONDITIONING DIVISION
T2 / TE2: reliable and easy to use
Thermostatic expansion valves regulate the injection of liguid refrigerant into evaporators.
Injection is controlled by the refrigerant superheat. Therefore the valves are especially suit-
able for liquid injection in ”dry“ evaporators where the superheat at the evaporator outlet
is proportional to the evaporator load.
Facts - Can be supplied with MOP - Valves for special temperature ranges can
(Max. Operating Pressure). be supplied.
Protects the compressor motor against ex- - Flare / solder adaptor can be supplied.
cessive evaporating pressure during normal
operation.
Capillary tube in
stainless steel
Laser-welded stainless
steel power element
Interchangeable orifice
assembly with dirt Easy adjustment of
protection filter superheat setting
Thermostatic element with: bulb strap, without: orifice, filter cone and nuts Flare × solder connection
Connection Code no.
Pressure Capillary
Refrigerant Valve type equalization tube Range N Range NL Range B
Inlet Outlet –40 to +10°C –40 to –15°C –60 to –25°C
Solder Flare ODF solder
m Without MOP MOP +15°C MOP –10°C Without MOP MOP –20°C
TX 2 - 1.5 3
/8 in. 1
/2 in. 068Z3281 068Z3287 068Z3357 068Z3319
TX 2 - 1.5 10 mm 12 mm 068Z3302 068Z3308 068Z3366 068Z3361 068Z3276
R22
TEX 2 ¼ in. 1.5 /8 in.
3
/2 in.
1
068Z3284 068Z3290 068Z3359 068Z3220
TEX 2 6 mm. 1.5 10 mm 12 mm 068Z3305 068Z3311 068Z3367 068Z3363 068Z3277
TZ 2 - 1.5 3
/8 in. 1
/2 in. 068Z3329
TZ 2 - 1.5 10 mm 12 mm 068Z3502 068Z3514
R407C
TEZ 2 ¼ in. 1.5 3
/8 in. 1
/2 in. 068Z3446 068Z3447
TEZ 2 6 mm. 1.5 10 mm 12 mm 068Z3503 068Z3515
TN 2 - 1.5 3
/8 in. 1
/2 in. 068Z3383 068Z3387
TN 2 - 1.5 10 mm 12 mm 068Z3384 068Z3388
R134a
TEN 2 ¼ in. 1.5 3
/8 in. 1
/2 in. 068Z3385 068Z3389
TEN 2 6 mm. 1.5 10 mm 12 mm 068Z3386 068Z3390
TS 2 - 1.5 3
/8 in. 1
/2 in. 068Z3414 068Z3416 068Z3429 068Z3418 068Z3420
TS 2 - 1.5 10 mm 12 mm 068Z3435 068Z3423 068Z3436 068Z3425 068Z3427
R 404A/R507
TES 2 ¼ in. 1.5 3
/8 in. 1
/2 in. 068Z3415 068Z3417 068Z3430 068Z3419 068Z3421
TES 2 6 mm. 1.5 10 mm 12 mm 068Z3422 068Z3424 068Z3437 068Z3426 068Z3428
Orifice assembly
Range N: –40 to +10°C Range B: –60 to –25°C Code no.
Rated capacity Rated capacity Rated capacity Rated capacity
Orifice in tons (TR) in kW in tons (TR) in kW Flare × Flare Solder adaptor
no.
R404A R404A R404A R404A version version
R22 R407C R134a R22 R407C R134a R22 R22
R507 R507 R507 R507
0X 0.15 0.16 0.11 0.11 0.50 0.50 0.40 0.38 0.15 0.11 0.50 0.38 068-2002 068-2089
00 0.30 0.30 0.25 0.21 1.0 1.1 0.90 0.70 0.20 0.21 0.70 0.70 068-2003 068-2090
01 0.70 0.80 0.50 0.45 2.5 2.7 1.8 1.6 0.30 0.45 1.0 1.6 068-2010 068-2091
02 1.0 1.1 0.80 0.60 3.5 3.8 2.6 2.1 0.60 0.60 2.1 2.1 068-2015 068-2092
03 1.5 1.6 1.3 1.2 5.2 5.6 4.6 4.2 0.80 1.0 2.8 3.5 068-2006 068-2093
04 2.3 2.5 1.9 1.7 8.0 8.6 6.7 6.0 1.2 1.4 4.2 4.9 068-2007 068-2094
05 3.0 3.2 2.5 2.2 10.5 11.3 8.6 7.7 1.5 1.7 5.2 6.0 068-2008 068-2095
06 4.5 4.9 3.0 2.6 15.5 16.7 10.5 9.1 2.0 1.9 7.0 6.6 068-2009 068-2096
The rated capacity is based on: Evaporating temperature te = +5°C for range N and te = –30°C for range B,
condensing temperature tc = +32°C, and refrigerant temperature ahead of valve tl = +28°C.
Related products
Electronic
thermostat
Thermostatic
Solenoid valve expansion
valve
Temperature
sensor
Thermostatic exp. valves Thermostatic exp. valves Electronically controlled Electronically controlled Electronically controlled
in stainless steel for for smaller and medium exp. valves for smaller exp. valves for medium exp. valves for larger
smaller plants sized plants plants sized plants plants