SP-PSU-4A Security Expert - Power Module 4A - Installation Guide
SP-PSU-4A Security Expert - Power Module 4A - Installation Guide
Grounding Requirements 7
Safety Grounding 7
Earth Ground Connection 7
Mounting 9
Removal 9
Cabinet Tamper Switch 9
Vibration Sensor 10
Connection 10
Modes of Operation 11
Installation Procedure 11
Wiring Diagram 13
Mains Power 14
Backup Battery 15
Connecting the Battery 15
Backup Battery Test 16
Backup Battery Thresholds 16
Inputs 21
Trouble Inputs 21
Outputs 22
Online Mode 22
Programmable Outputs 22
Offline Mode 22
AC Fail Status Output 23
Battery Fail Status Output 23
Intelligent Monitoring 25
Monitoring Setup 25
Address Configuration 26
LED Indicators 27
4A Security Purpose Power Module
Status Indicator 27
Fault Indicator 27
Power Indicator 27
V1 Output/V2 Output Indicators 27
Battery Indicator 28
Temp Indicator 28
Output Current Indicator 28
Mechanical Diagram 30
Mechanical Layout 31
Technical Specifications 32
Maximum Total Output Current: UL and cUL Installations 33
European Standards 35
UK Conformity Assessment Mark 37
UL and cUL Installation Requirements 38
UL/cUL Installation Cabinet Options 38
cUL Compliance Requirements 38
CAN/ULC-60839-11-1 38
CAN/ULC-S304 39
CAN/ULC-S319 42
CAN/ULC-S559 42
UL Compliance Requirements 47
UL1610 47
UL294 48
June 2024 4
4A Security Purpose Power Module Introduction
Introduction
The Security Expert 4A Security Purpose Power Module provides 12VDC power suited to
powering security, access control or automation devices along with large numbers of Security
Expert network powered modules, and allows for simple and powerful monitoring of supply
currents and voltages.
Flexible module network architecture allows large numbers of modules to be connected to the
RS-485 module network, over a distance of up to 900M (3000ft). Further span can be achieved
with the use of a network repeater module.
The current features of the power supply include:
l Secure encrypted RS-485 module communications
l Industry standard DIN rail mounting
l Online and remote upgradeable firmware
June 2024 5
4A Security Purpose Power Module Installation Requirements
Installation Requirements
This equipment is to be installed in accordance with:
l The product installation instructions
l UL 294 - Access Control System Units
l UL 681 - Installation and Classification of Burglar and Holdup Systems
l UL 827 - Central-Station Alarm Services
l CAN/ULC-S301, Central and Monitoring Station Burglar Alarm Systems
l CAN/ULC-S302, Installation and Classification of Burglar Alarm Systems for Financial and
Commercial Premises, Safes and Vaults
l CAN/ULC-S561, Installation and Services for Fire Signal Receiving Centres and Systems
l CAN/ULC-60839-11-1, Alarm and Electronic Security Systems – Part 11-1: Electronic
Access Control Systems – System and Components Requirements
l The National Electrical Code, ANSI/NFPA 70
l The Canadian Electrical Code, Part I, CSA C22.1
l AS/NZS 2201.1 Intruder Alarm Systems
l The Local Authority Having Jurisdiction (AHJ)
Wiring
Aux Wiring: Minimum 22AWG, maximum 16AWG (depends on length and current
consumption).
For wire/cable size, a maximum of 5% voltage drop at the terminals of the powered device has
to be observed.
Module Network Wiring:
l Minimum 24AWG (0.51mm) shielded twisted pair with characteristic impedance of
120ohm. Maximum length 900m (3000ft).
l CAT5e / CAT6 also supported for data transmission when using ground in the same cable.
Maximum length 100m (330 ft).
Do not use extra wires in the cable to power devices.
June 2024 6
4A Security Purpose Power Module Grounding Requirements
Grounding Requirements
An effectively grounded product is one that is intentionally connected to earth ground through
a ground connection or connections of sufficiently low impedance and having sufficient
current-carrying capacity to prevent elevated voltages which may result in undue hazard to
connected equipment or to persons.
Grounding of the Security Expert system is done for three basic reasons:
1. Safety
2. Component protection
3. Noise reduction
Safety Grounding
The object of safety grounding is to ensure that all metalwork is at the same ground (or earth)
potential. Impedance between the Security Expert system and the building scheme ground
must conform to the requirements of national and local industrial safety regulations or
electrical codes. These will vary based on country, type of distribution system and other
factors. The integrity of all ground connections should be checked periodically.
General safety dictates that all metal parts are connected to earth with separate copper wire or
wires of the appropriate gauge.
June 2024 7
4A Security Purpose Power Module Grounding Requirements
DIN Rail Ground Connections (one or more cabinets installed in the same room)
Module Network
(RS-485 N+, N-, NA, NB)
V-
Output Expander
AC Mains Wiring
Earth Ground
Link Connection
DIN Rail Ground Connections (multiple cabinets in different rooms, sectors, or buildings)
Module Network (RS-485 N+, N-, NA and NB)
V-
Earth Ground
Link Connection
The Dialer's Earth Ground Connection applies to modem model controllers only.
Note that the DIN rail enclosure earth terminal is connected to the power supply V- terminal.
There must be only one single earth grounding point per system.
June 2024 8
4A Security Purpose Power Module Mounting
Mounting
Security Expert DIN rail modules are designed to mount on standard DIN rail either in
dedicated DIN cabinets or on generic DIN rail mounting strip.
When installing a DIN rail module, ensure that there is adequate clearance around all sides of
the device and that air flow to the vents of the unit is not restricted. It is recommended that you
install the module in a location that will facilitate easy access for wiring. It is also recommended
that the module is installed in an electrical room, communication equipment room, secure
cabinet, or in an accessible area of the ceiling.
1. Position the DIN rail module with the labeling in the correct orientation.
2. Hook the mounting tabs (opposite the tab clip) under the edge of the DIN rail.
3. Push the DIN rail module against the mount until the tab clips over the rail.
Removal
A Security Expert DIN rail module can be removed from the DIN rail mount using the following
steps:
1. Insert a flat blade screwdriver into the hole in the module tab clip.
2. Lever the tab outwards and rotate the unit off the DIN rail mount.
Tamper Switch
NO C NC C TP
June 2024 9
4A Security Purpose Power Module Mounting
Vibration Sensor
Protection is provided by a DSC SS-102 Shockgard seismic vibration sensor mounted within
the system enclosure.
Tamper Switch
NO C NC C TP
MAX MIN
OFF
6 5 4 3 2 1
Sensor
- +
7 4 3 2 1
S2
(V+)
0V +12V } PSU
(V-)
Connection
l Terminals 1(V+) and 2(V-). 12V power connection, reverse polarity protected.
l Terminals 3 and 4. N.C. alarm output contacts, with built in 10 ohm resistor in series.
June 2024 10
4A Security Purpose Power Module Mounting
Modes of Operation
When using the sensor in momentary mode it will be necessary to connect using a 4 core
cable.
Installation Procedure
1. Select the intended position for installation, ideally positioned horizontally in the vertical
center of the enclosure, 50mm to the right of the large opening.
Ensure the surface is clean and clear of any irregularities.
2. Remove the sensor cover by unscrewing the single captive screw until the cover can
easily be removed from the base.
3. Carefully lift the printed circuit board from the base.
4. Position the base in the mounting position and mark the desired fixing holes (3.1mm drill).
5. If rear cable entry is required, cables should be threaded through the rear of the base.
6. Fix the base in position using M3 pan head machine screws to the captive nuts provided in
the enclosure, or with nuts and washers if located in an alternative position.
Take care not to let the screw protrude further than the nut height on the rear of the
enclosure.
7. Carefully push the printed circuit board onto the base.
8. Make the electrical connections to the Shockgard SS-102, wired in series with the
enclosure tamper switch 24HR monitor.
9. If side cable entry is being used, remove the appropriate knockout from the cover and
insert a grommet.
10. Setting up and adjustment:
June 2024 11
4A Security Purpose Power Module Mounting
l With the unit in momentary operation (See Modes of Operation: Dual stage linear
sensitivity above), use a terminal screwdriver to turn the sensitivity control fully
clockwise to maximum (Position 6).
l Using a suitable implement, bang or tap the protected area, observing the LED
response.
l Reduce the sensitivity by a small amount (turn sensitivity control anti-clockwise) and
bang or tap the protected area.
l Repeat this process until the unit only just responds to the desired impact.
11. Replace the sensor cover, tighten the fixing screw and check its response to the desired
impact.
June 2024 12
4A Security Purpose Power Module Wiring Diagram
Wiring Diagram
CAUTION: Incorrect wiring may result in damage to the unit.
4A Power Supply
N+ N- NA NB B- B+ NC C NC C TP L N
System Controller
NB
NA
N-
Next
modules
N-
on network
N+
June 2024 13
4A Security Purpose Power Module Mains Power
Mains Power
The power supply should be supplied by a dedicated electrical power source rated for a
minimum 5 amp load and have a dedicated circuit breaker.
Connect the power supply module to mains input via an appropriate IEC-C7 90 degree cable.
L N
Mains Input
The earth wire shall be routed to the V- terminal on the power supply.
Warning:
l This installation should be made by qualified service personnel and should conform to
all local codes.
l Termination of wiring to the power supply while power is applied or the battery is
connected may cause serious damage to the power supply and will VOID ALL
WARRANTIES OR GUARANTEES. Power the unit only after all wiring, configuration
and jumper settings are completed.
l Extra care must be taken when wiring the AC inputs. Improper connection will cause
permanent damage to the power supply.
June 2024 14
4A Security Purpose Power Module Backup Battery
Backup Battery
A battery backup must be connected to the module network to provide a monitored supply.
The battery plays an important role in power conditioning and provides a continuous source of
power in the event of a power outage.
The battery type must be a valve regulated sealed lead acid (VRLA) rechargeable battery that
can supply at least 12V DC. It is recommended that the main backup battery has a minimum
capacity of 7Ah.
UL/cUL Installations
For UL/cUL installations the following battery specifications must be observed:
l Battery Type to be used: VRLA (valve regulated sealed lead acid type rechargeable
battery)
l Recommended Battery: Yuasa model: NP7-12, 12V, 7Ah (www.yuasabatteries.com)
l Nominal Voltage: 12V
l Nominal Capacity: 7Ah minimum
If more battery capacity is required, a second 7Ah battery may be connected in parallel.
Larger capacity batteries are permitted, but are typically too large for standard cabinet
spacing. See Maximum Total Output Current: UL and cUL Installations for specific
requirements.
l Battery Maintenance: It is recommended to replace the battery every 3-5 years.
EN 50131-1
To comply with EN 50131-1 only one battery can be connected and monitored per system. If
more capacity is required a single larger battery must be used.
The power supply will not detect the backup battery if the power supply is off when the
battery is connected. After the mains supply is connected, the power supply will detect the
battery and begin charging or drawing current as required.
B- B+
BATTERY
Backup Battery
If required and permitted by regulations, two batteries may be connected in parallel to provide
more capacity. It is recommended that two identical batteries of the same age are used to
prevent continuous discharge from the newer battery to the older battery.
June 2024 15
4A Security Purpose Power Module Backup Battery
B- B+
BATTERY
Backup Battery
Backup Battery
Warning:
l Only attach standard lead acid batteries.
l Do not connect the battery wires or B+ and B- plugs of the module to any other ancillary
device (siren, lock, mag clamp, etc.).
l An incorrect connection may cause erroneous faults or serious damage to the module
and will VOID ALL WARRANTIES OR GUARANTEES.
June 2024 16
4A Security Purpose Power Module Encrypted Module Network
NA NB
Always connect the power supply NA and NB terminals to the NA and NB terminals of the
communication network.
V+ V-
The diagram above shows how a single power supply can be connected to supply the module
network. This connection is suitable for smaller systems, provided that the following values are
all lower than or equal to the values outlined in the Technical Specifications section of this
manual:
l Maximum total output current,
l AUX DC output current,
l Controller bell DC output current, and
l Total combined current
June 2024 17
4A Security Purpose Power Module Encrypted Module Network
If any of these currents are exceeded, a separate power supply must be used, as shown
below.
V- V+ V-
V+
N+ N- NA NB N+ N- NA NB N+ N- NA NB N+ N- NA NB
Module Network
The 12V N+ and N- communication input must be supplied from only one point.
Connections from more than one 12V supply may cause failure or damage to the unit or the
device supplying network power.
Module Wiring
The recommended module network wiring specifications are:
l Minimum 24AWG (0.51mm) shielded twisted pair with characteristic impedance of 120
ohm
l Maximum total length of cable is 900m (3000ft)
l CAT5e / CAT6 are also supported for data transmission when using ground in the same
cable (to a maximum length of 100m (328ft))
Warning: Unused wires in the cable must not be used to carry power to other devices.
N+ N- NA NB N+ N- NA NB
330R 330R
To From
Next Previous
Module Module
June 2024 18
4A Security Purpose Power Module Output Load Connection
When any inductive load, including electric locking devices, is powered (directly or indirectly)
by the power supply a reverse EMF protection diode must be placed across the positive (V1+
or V2+) and negative (V-) terminals at the device.
12VDC Electric
Locking Device
-
+
IN4007 Diode
Note: The 1N4007 diode shown must be installed across the + and – terminals of any
inductive load such as electric locks, magnetic or motorized devices.
June 2024 19
4A Security Purpose Power Module Output Load Connection
Core Temperature
Output Load Operation Status <70°C 70-80°C >80°C
Outputs Enabled (Mains Power)
June 2024 20
4A Security Purpose Power Module Inputs
Inputs
The power supply has no physical input connections.
Trouble Inputs
Each power supply can monitor up to 8 trouble inputs.
Trouble inputs are used to monitor the module status and in most cases are not physically
connected to an external input.
The following table details the trouble inputs that are configured in the system and the trouble
groups that they are associated with.
Default
Default
Trouble
Input Number Description Trouble
Group
Group
Option
System
AExxx:01 Module Tamper System
Tamper
Module
AExxx:08 Module Offline System
Offline
Replace 'xxx' with the appropriate address of the module that you are programming.
The power supply emulates an analog expander module on the Security Expert module
network. This means that all programming, trouble input and output information is stored in
and reported by the analog expander records when programming via a Security Expert
keypad or Security Expert software.
June 2024 21
4A Security Purpose Power Module Outputs
Outputs
The power supply has two 50mA outputs that can operate as either programmable outputs or
as predefined status outputs, depending on the network status of the module on the Security
Expert system.
Online Mode
Upon successfully completing the initial registration with any Security Expert system controller,
the outputs of the power supply operate in online mode. The module will then continue to
operate in online mode until a firmware update is carried out. While in online mode the two
outputs function as programmable outputs and can be used to activate bell sirens, lighting
circuits, door locks, relay accessory products and other automation points.
Programmable Outputs
The 2 programmable outputs each have a 50mA solid-state relay.
The connection example below shows the control of an external LED indicator.
0V +12V AUX
NC C NC C TP
LED
1K5 OHM
Warning: Switching inductive loads that can produce high back EMF voltages or large
voltage-induced spikes can cause the module to behave unexpectedly and should be
avoided. A suitable isolation circuit must be installed between the relay contacts of the
module and the inductive load.
These outputs are rated for low power use only (50mA, 12V Max). Incorrect use may cause
erroneous faults or serious damage to the power supply and will VOID ALL WARRANTIES
OR GUARANTEES.
Offline Mode
Until connection to a Security Expert system controller is established, the outputs of the power
supply operate in offline mode. While in offline mode the two outputs function as status
outputs. In addition to the comprehensive front panel diagnostic indicators, these status
outputs offer additional information that can aid the installer in diagnosing faults and
conditions.
June 2024 22
4A Security Purpose Power Module Outputs
Z4
C
Z3
Z2
NC C
C
Z1
NC
V-
C
V+
TP
Input Expander Power Supply
This output is suited for connection to an input on a Security Expert module with spare inputs
available so that the power supply AC status can be externally monitored. The connection
example above shows monitoring of the AC status set up in conjunction with a Security Expert
input expander.
NC C
C
Z1
NC
V-
C
V+
TP
This output is suited for connection to an input on the Security Expert system for early
detection of complete power failure. The connection example above shows monitoring of the
battery status set up in conjunction with an input expander.
June 2024 23
4A Security Purpose Power Module Outputs
These outputs are rated for low power use only (50mA, 12V Max). Incorrect use may cause
erroneous faults or serious damage to the power supply and will VOID ALL WARRANTIES
OR GUARANTEES.
June 2024 24
4A Security Purpose Power Module Intelligent Monitoring
Intelligent Monitoring
The power supply is able to relay information about critical system voltages, currents and
temperature to the Security Expert controller by registering as an analog expander module on
the Security Expert network. The controller can then store these values in variables that can be
viewed live from the Security Expert interface.
Monitoring Setup
The power supply will register with the Security Expert controller as an analog expander
module, AExxx.
The channels for each power supply will monitor:
l Channel 1: Voltage at V2+ output
l Channel 2: Voltage at V1+ output
l Channel 3: Power supply module core voltage
l Channel 4: Total current output
Each channel can be associated with a data value and each data value assigned to a variable.
These variables can then be monitored on a status page or floor plan.
The Log Channel Data option may also be selected to view the raw data as it is received in
the event log. However, this will create a large number of events and should only be used for
verifying the reception of data.
For more information on programming this feature, see the Security Expert Operator Manual.
June 2024 25
4A Security Purpose Power Module Address Configuration
Address Configuration
The module address is configured via programming and will require knowledge of the module
serial number. The serial number can be found on the identification sticker on the product.
Refer to the Security Expert system controller configuration guide for address programming
details.
The controller has a set limit on the number of modules of each type that it can support.
When adding and configuring modules always refer to the Maximum Module Addresses
table in the controller configuration guide.
June 2024 26
4A Security Purpose Power Module LED Indicators
LED Indicators
Security Expert DIN rail modules feature comprehensive diagnostic indicators that can aid the
installer in diagnosing faults and conditions. In some cases an indicator may have multiple
meanings depending on the status indicator display at the time.
Status Indicator
The status indicator displays the module status.
State Description
Fast flash (green) Module attempting registration with controller
When the fault and status indicators are flashing alternately, the module is in identification
mode, enabling the installer to easily identify the module in question. Upon either a module
update or the identification time period expiring, the module will return to normal operation.
Fault Indicator
The fault indicator is lit any time the module is operating in non-standard mode. If the fault
indicator is flashing, the module requires a firmware update or is in firmware update mode.
When the fault indicator is on, the status indicator will flash an error code.
State Description
Continuous slow flash
Module is in boot mode awaiting firmware update
(red)
Module is in error state and will flash an error code with the status
Constantly on (red)
indicator
Power Indicator
The power indicator is lit whenever the correct module input voltage is applied across the
mains input terminals.
State Description
Constantly on Correct module input voltage applied
State Description
On (green) 12VDC output operating OK
June 2024 27
4A Security Purpose Power Module LED Indicators
Battery Indicator
The battery indicator shows the status of the backup battery.
Flashing Mains has failed and the PSU is drawing power from the battery. State is
(green) Battery Restore
Temp Indicator
The temp indicator shows the status of the unit's core temperature.
State Description
On (red) Core temperature exceeded. Over Temp Shutdown Activated
State Description
Constantly on Output current exceeded. Over Current Shutdown Activated
Constantly on (all
Maximum output current level reached
indicators)
June 2024 28
4A Security Purpose Power Module Error Code Indication
Firmware Version
The firmware version on the module is not compatible with the system controller.
2
To clear this error, update the module using the module update feature in the
controller's web interface.
Address In Use
The address is already in use by another module. To clear this error set the
4 address to one that is not currently occupied. Use the view network status
command to list the attached devices, or the network update command to refresh
the registered device list.
Locked Device
7 The module or system controller is a locked device and cannot communicate on
the network. Return the unit to the distributor for replacement.
June 2024 29
4A Security Purpose Power Module Mechanical Diagram
Mechanical Diagram
The mechanical diagram shown below outlines the essential details needed to help ensure the
correct installation of the power supply.
June 2024 30
4A Security Purpose Power Module Mechanical Layout
Mechanical Layout
The mechanical layout below outlines the essential details needed to help ensure correct
installation and mounting. All measurements are shown in millimeters.
156.80
90.00
44.68
Front
156.80
(2x)
Scre 4.67
w Ho
le
35.40
Back
139.18
June 2024 31
4A Security Purpose Power Module Technical Specifications
Technical Specifications
The following specifications are important and vital to the correct operation of this product.
Failure to adhere to the specifications will result in any warranty or guarantee that was
provided becoming null and void.
Ordering Information
SP-PSU-4A Security Expert 4A Security Purpose Power Module
Power Supply
Mains Input Voltage 120VAC (90-264VAC, 47-63Hz)
Communication
RS-485 Isolated Module Network
Outputs
Outputs 2 Solid-State Relay Outputs, 50mA 12V Max each
Inputs
Tamper Dedicated Hardware Tamper Input
Dimensions
Dimensions (L x W x H) 156 x 90 x 60mm (6.14 x 3.54 x 2.36")
Operating Conditions
UL/cUL 0° to 49°C (32° to 120°F) : EU EN -10° to 55°C (14°
Operating Temperature
to 131°F)
Mean Time Between Failures 242,266 hours (calculated using RDF 2000 (UTE C 80-810)
(MTBF) Standard)
It is important that the unit is installed in a dry cool location that is not affected by humidity. Do
not locate the unit in air conditioning or a boiler room that can exceed the temperature or
humidity specifications.
June 2024 32
4A Security Purpose Power Module Technical Specifications
Schneider Electric continually strives to increase the performance of its products. As a result
these specifications may change without notice. We recommend consulting our website
(www.schneider-electric.com) for the latest documentation and product information.
Maximum
Maximum Charging
Minimum
Total Output Current Battery
Application System in
Current Rating
Standby (mains
Available
present)
UL 294 and CAN/ULC- 2 x 12VDC
S319 4000mA 240mA 500mA 7Ah =
4hr backup 14Ah
2 x 12VDC
CAN/ULC-S304
4000mA 180mA 500mA 7Ah =
24hr backup
14Ah
2 x 12VDC
CAN/ULC-S559
4000mA 180mA 500mA 7Ah =
24hr backup
14Ah
2 x 12VDC
UL 1610, UL 1635
4000mA 240mA 500mA 7Ah =
4hr backup
14Ah
2 x 12VDC
UL 1610, UL 1635
4000mA 180mA 500mA 7Ah =
24hr backup
14Ah
2 x 12VDC
UL 1610, UL 1635
4000mA 180mA 500mA 7Ah =
72hr backup
14Ah
Note: the Maximum Total Output Current Available is the maximum current that can be
supplied to the auxiliary and bell DC outputs.
These are the maximum current values to ensure compliance with the standby requirements.
June 2024 33
4A Security Purpose Power Module New Zealand and Australia
June 2024 34
4A Security Purpose Power Module European Standards
European Standards
CE Statement
Conforms where applicable to European Union (EU) Low Voltage Directive (LVD) 2014/35/EU,
Electromagnetic Compatibility (EMC) Directive 2014/30/EU, Radio Equipment Directive
(RED)2014/53/EU and RoHS Recast (RoHS2) Directive: 2011/65/EU + Amendment Directive
(EU) 2015/863.
This equipment complies with the rules, of the Official Journal of the European Union, for
governing the Self Declaration of the CE Marking for the European Union as specified in the
above directive(s).
WEEE
Information on Disposal for Users of Waste Electrical & Electronic Equipment
This symbol on the product(s) and / or accompanying documents means that used electrical
and electronic products should not be mixed with general household waste. For proper
treatment, recovery and recycling, please take this product(s) to designated collection points
where it will be accepted free of charge.
Alternatively, in some countries you may be able to return your products to your local retailer
upon purchase of an equivalent new product.
Disposing of this product correctly will help save valuable resources and prevent any potential
negative effects on human health and the environment, which could otherwise arise from
inappropriate waste handling.
Please contact your local authority for further details of your nearest designated collection
point.
Penalties may be applicable for incorrect disposal of this waste, in accordance with your
national legislation.
For business users in the European Union
If you wish to discard electrical and electronic equipment, please contact your dealer or
supplier for further information.
Information on Disposal in other Countries outside the European Union
This symbol is only valid in the European Union. If you wish to discard this product please
contact your local authorities or dealer and ask for the correct method of disposal.
EN50131 Standards
This component meets the requirements and conditions for full compliance with EN50131
series of standards for equipment classification.
EN 50131-1:2006+A2:2017, EN 50131-3:2009, EN 50131-6:2008+A1:2014, EN 50131-
10:2014, EN 50136-1:2012, EN 50136-2:2013, EN 60839-11-1:2013
Security Grade 4
Environmental Class II
Equipment Class: Fixed
Readers Environmental Class: IVA, IK07
SP1 (PSTN – voice protocol)
SP2 (PSTN – digital protocol)
SP6 (LAN – Ethernet) and DP1 (LAN – Ethernet + PSTN)
SP6 (LAN – Ethernet) and DP1 (LAN – Ethernet + USB-4G modem)
Tests EMC (operational) according to EN 55032:2015
Radiated disturbance EN 55032:2015
Power frequency magnetic field immunity tests (EN 61000-4-8)
June 2024 35
4A Security Purpose Power Module European Standards
June 2024 36
4A Security Purpose Power Module UK Conformity Assessment Mark
June 2024 37
4A Security Purpose Power Module UL and cUL Installation Requirements
All cabinet installations of this type must be located inside the Protected Area.
Not to be mounted on the exterior of a vault, safe or stockroom.
All cabinet internal covers and lids/doors must be connected to the cabinet's main ground
point for electrical safety and static discharge protection.
June 2024 38
4A Security Purpose Power Module UL and cUL Installation Requirements
l If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
l The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
CAN/ULC-S304
l Auto Arming
Control units that support auto arming shall provide an audible signal throughout the
protected area not less than 10 min prior to the auto arming taking place. The control unit
shall allow authorized users to cancel the auto arming sequence and transmit such
cancelation to the signal receiving center with the identification of the authorized user that
canceled the action.
The following options must be enabled in the Security Expert system when using the Auto
Arming feature. When the defer warning time is programmed to 10 minutes, the output
group will be activated 10 minutes before the system performs the Auto Arming in the
associated Area.
l The Defer Output or Output Group must be programmed. Refer to the section
Areas | Outputs in the Operator Reference Manual for programming instructions.
l The Defer Warning Time must be programmed to not less than 10 minutes. Refer to
the section Areas | Configuration in the Operator Reference Manual.
l The Defer Automatic Arming option must be enabled. Refer to the section Areas |
Options (2) in the Operator Reference Manual.
l Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a cUL
security, signaling or fire standard. If intended to be mounted outside, it must be rated for
outdoor use.
l Double EOL Input Configuration
Only double EOL Input Configuration shall be used. Refer to the Inputs section of this
manual and the section Inputs | Options in the Operator Reference Manual.
l Multiplex System and Poll Time
The Security Expert controller is compatible with the ArmorIP Internet Monitoring
Receiver. Poll Time must be set to 40 seconds and the Grace Time must be set to 20
seconds.
In the Security Expert system, the reporting service must be configured to 40 seconds.
The following options are required for the service selected as Report IP type:
l The Log Polling Message option must be enabled. Refer to the section Report IP |
Options in the Operator Reference Manual.
l The Poll Time must be programmed to 40 seconds. Refer to the Report IP | General
section in the Operator Reference Manual.
l Central Station Signal Receiver
The common equipment of each signal receiving center control unit shall be limited to
1000 alarm systems.
l Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter
shall make a minimum of 5 and a maximum of 10 attempts. Where the maximum number
of attempts to complete the sequence is reached, an indication of the failure shall be made
at the premises.
In the Security Expert system, the reporting service selected as Contact ID must have the
number of attempts programmed to 5 attempts. The Dial Attempts option must be
programmed. Refer to the section Contact ID | Settings in the Operator Reference Manual.
June 2024 39
4A Security Purpose Power Module UL and cUL Installation Requirements
If the SP-4G-USB cellular modem is being used as the secondary reporting option in the
installation, the Report IP service assigned to the cellular modem must be programmed
as above.
l Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
l Trouble Input Service Test Report
l The Test Report Time must be programmed. Refer to the section Controllers |
Configuration in the Operator Reference Manual.
l The Generate Input Restore on Test Input option must be enabled. Refer to the
section Controller | Options in the Operator Reference Manual.
l The Test Report Time is Periodic option must be enabled. Refer to the section
Controller | Options in the Operator Reference Manual.
l Primary Communication Channel
The first attempt to send a status change signal shall utilize the primary communication
channel.
An ethernet Report IP service must be used as the primary service. The backup service
may use Contact ID over the phone line or Report IP over the cellular network if the SP-
4G-USB cellular modem is being used as the secondary communication channel.
The following options are required:
l The primary service (Report IP) must have the Backup service set to the secondary
reporting service (Contact ID or Report IP over 4G modem). The Service mode must
be set to 1 - Start with controller OS.
l The backup service must have Service operates as backup enabled. For ULC-S304
P3 applications, Enable offline polling must be enabled and configured so that the
backup service is monitored even when it is not active.
l For Report IP services, the Reporting protocol must be set to Armor IP.
l Refer to the Services section in the Operator Reference Manual.
l Status Change Signal
An attempt to send a status change signal shall utilize both primary and secondary
communication channels.
l Local Annunciation if Signal Reporting Failure
Failure of the primary communication channel or secondary communication channel shall
result in a trouble signal being transmitted to the signal receiving center within 240
seconds of the detection of the fault. Failure of either communication channel shall be
annunciated locally within 180 seconds of the fault.
The following options must be enabled in the Security Expert system:
l The Ethernet Link Failure trouble input must be programmed.
l The Trouble Input Area must be armed. Refer to the section Trouble Inputs | Areas
and Input Types in the Operator Reference Manual.
l Network and Domain Access
Neither the subscriber control unit nor the signal receiving center receiver shall be
susceptible to security breaches in general-purpose operating systems.
Network access policies should be set to restrict unauthorized network access and
"spoofing" or "denial of service" attacks.
l Ethernet Connections
All ethernet network connections shall be installed within the same room as the
equipment.
l Encryption
For active communications channel security, encryption shall be enabled at all times.
The ArmorIP-E (UDP) protocol must be used and the Encryption Type must be set to AES-
256.
June 2024 40
4A Security Purpose Power Module UL and cUL Installation Requirements
The following options must be enabled for the Report IP service in the Security Expert
system.
l The Reporting Protocol must be set to ArmorIP (UDP) Encrypted. The AES key
must be set as specified by monitoring station.
l Refer to the section Report IP | General in the Operator Reference Manual.
l Server Configuration
Where a server is employed for control over network addressing, encryption or re-
transmission, such shall be designed to remain in the "on state" at all times.
Communicators are not suitable for active communication channel security and medium or
high risk applications unless such can be "online" at all times, have a minimum 128 bit
encryption scheme, have encryption enabled, network and domain security implemented.
Network access policies shall be set to restrict unauthorized network access and
"spoofing" or "denial of service" attacks.
l Internet Service Provider (ISP)
The Internet Service Provider (ISP) providing service shall meet the following
requirements:
l redundant servers/systems
l back-up power
l routers with firewalls enabled and
l methods to identify and protect against "Denial of Service" attacks (i.e. via "spoofing")
l Information Technology Equipment, Products or Components of Products
Products or components of products, which perform communications functions only, shall
comply with the requirements applicable to communications equipment as specified in
CAN/CSA-C22.2 No. 62368-1, Audio/video, information and communication technology
equipment - Part 1: Safety requirements. Where network interfaces, such as the following,
are internal to the subscriber control unit or receiver, compliance to CAN/CSA-C22.2 No.
62368-1 is adequate. Such components include, but are not limited to:
l A) Hubs;
l B) Routers;
l C) Network interface devices;
l D) Third-party communications service providers;
l E) Digital subscriber line (DSL) modems; and
l F) Cable modems.
l Backup Power Requirements
Power for network equipment such as hubs, switchers, routers, servers, modems, etc.,
shall be backed up or powered by an uninterruptible power supply (UPS), stand-by battery
or the control unit, capable of facilitating 24h standby, compliant with Clauses 16.1.2 and
16.4.1 of CAN/ULC-S304.
For communications equipment employed at the protected premises or signal receiving
center and intended to facilitate packet switched communications, as defined in
CAN/ULC-S304, 24h back-up power is required.
l Compromise Attempt Events
ArmorIP detects the reception of any invalid packet on the programmed port as a potential
system compromise attempt. Each compromise attempt sends a notification to the
receiver, and logs a Compromise Attempt event under the Live Panel Events.
The event is sent with the following details:
l Account Code as defined in the Serial Receiver settings
l Event Code 0x163
l Group Code as defined in the Serial Receiver settings
l Point Code as defined in the Serial Receiver settings
June 2024 41
4A Security Purpose Power Module UL and cUL Installation Requirements
Refer to the section Global Settings | Serial Receiver in the ArmorIP Version 3 Internet
Monitoring Application User Manual.
For UL and cUL installations the Central Station Receiving software must have the
Contact ID details as specified, programmed for the Compromise Attempt event.
l Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
CAN/ULC-S319
l The Security Expert controller and reader expander module are intended to be mounted
within the enclosure (refer to UL/cUL Installation Cabinet Options), installed inside the
protected premise, and are CAN/ULC-S319 Listed for Class I applications only.
l Exit devices and wiring must be installed within the protected area.
l For the Security Expert controller and reader expander module, all RS-485 and reader
terminal connections must be made using shielded grounded cable.
l All readers must be connected with shielded, grounded cable.
l A bell or visual indicator used as an arming acknowledgment signal must be listed to a cUL
security, signaling or fire standard. If intended to be mounted outside, it must be rated for
outdoor use.
l Fail secure locking mechanisms shall only be installed where allowed by the local
authority having jurisdiction (AHJ) and shall not impair the operation of panic hardware
and emergency egress.
l If fire resistance is required for door assembly, portal locking device(s) must be evaluated
to ULC-S533 and CAN/ULC-S104.
l Must be installed with CAN/ULC-S319 listed portal locking device(s) for cUL installations.
l If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
l The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
CAN/ULC-S559
l Signal Reporting
Any fault of an active communication system shall be annunciated and recorded at the
signal receiving center within 180 s of the occurrence of the fault.
The Report IP and Contact ID services must be programmed and enabled within the
Security Expert system. The following options are required:
l The Contact ID Reporting Service must be enabled and the Service Mode must be
configured to start with the operating system.
l Refer to the section Contact ID in the Operator Reference Manual.
l The Report IP Service must be enabled as the primary communication channel, the
Service Mode must be configured to start with the operating system, and the
Reporting Protocol must be set to ArmorIP.
l Refer to the section Report IP in the Operator Reference Manual.
l The Trouble Area must be armed. Refer to the section Trouble Inputs | Areas and
Input Types in the Operator Reference Manual.
In the ArmorIP Internet Monitoring Software the Poll Time must be set to 40 seconds and
the Grace Time must be set to 20 seconds. Refer to the section Poll/Grace Time in the
ArmorIP Version 3 Internet Monitoring Application User Manual.
l Central Station Signal Receiver
June 2024 42
4A Security Purpose Power Module UL and cUL Installation Requirements
The maximum number of signal transmitting units connected to any transmission channel
shall conform to the manufacturer's recommendations. The ArmorIP Receiver supports up
to 10000 simultaneous connections.
Refer to the section Internet Connections Requirements in the ArmorIP Receiver
Installation Manual for further details.
l Number of attempts
In the event of unsuccessful communication, a digital alarm communicator transmitter
shall make a minimum of 5 and a maximum of 10 attempts. Where the maximum number
of attempts to complete the sequence is reached, an indication of the failure shall be made
at the premises.
In the Security Expert system, the reporting service selected as Contact ID must have the
number of attempts programmed to 5 attempts. The Dialing Attempts option must be
programmed. Refer to the section Contact ID | Settings in the Operator Reference Manual.
If the SP-4G-USB cellular modem is being used as the secondary reporting option in the
installation, the Report IP service assigned to the cellular modem must be programmed
as above.
l Check-In Time
DACT communication channel check-in time is not to exceed 24 hrs.
l Trouble Input Service Test Report
l The Test Report Time must be programmed. Refer to the section Controllers |
Configuration in the Operator Reference Manual.
l The Generate Input Restore on Test Input option must be enabled. Refer to the
section Controller | Options in the Operator Reference Manual.
l The Test Report Time is Periodic option must be enabled. Refer to the section
Controller | Options in the Operator Reference Manual.
l Ethernet Connections
All ethernet network connections shall be installed within the same room as the
equipment.
l External Wiring
All wiring extending outside of the enclosure must be protected by conduit.
l Power Supply Mains Power Connection
If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
l Arming Signal
A bell or visual indicator used as an arming acknowledgment signal must be listed to a cUL
security, signaling or fire standard. If intended to be mounted outside, it must be rated for
outdoor use.
l Keypad Wiring
The RS-485 connection to the keypad must be wired such that the shorts and other faults
on the RS-485 line connection of the keypad will not cause the controller to malfunction.
l Fire Areas
Fire areas shall be separated from burglar areas through area partitioning.
NOTE: Any available dry relay contact on the Security Expert controller or output
expander may be used for the FACP system, provided the selected output is programmed
as the Report OK output.
June 2024 43
4A Security Purpose Power Module UL and cUL Installation Requirements
CAN/ULC-S559
CONTROLLER
ACTIVE COMMUNICATION
Metal Conduit Note: All cables shall be protected within metal conduits.
ENCLOSURE
12V DC
MAINS SUPPLY AC + +
(120V AC) TELECOM
AC - - ETHERNET
EQUIPMENT
INTERNET
485 485
AC BATT
12VDC FAIL FAIL
+ - C NC C NC
FIRE Z1
SUPERVISORY Z2
Programmable Z4
COM STATUS / FB
Output
* The AC FAIL output on the Power Supply MUSTbe programmed to follow the AC Trouble Input as follows:
AC FAIL = OPEN on fail
* Fire zones shall be separated from burglar zones through area partitioning.
* Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell output
* Fire Zone Z4 N.O Push Button to be used as monitoring reset switch.
* EOL resistor must be installed at the Fire Alarm Control Panel Output.
June 2024 44
4A Security Purpose Power Module UL and cUL Installation Requirements
CAN/ULC-S559
CONTROLLER
PASSIVE COMMUNICATION: MODEM DIALER
Metal Conduit Note: All cables shall be protected within metal conduits.a
ENCLOSURE
12V DC
MAINS SUPPLY AC + +
(120V AC) TELECOM
AC - - ETHERNET
EQUIPMENT
INTERNET
485 485
AC BATT
12VDC FAIL FAIL
+ - C NC C NC
PSTN
DIALER TELECOM
EQUIPMENT
FIRE ALARM PANEL
FIRE Z1
SUPERVISORY Z2
Z4
Programmable
COM STATUS / FB
Output
* The AC FAIL output on the Power Supply MUSTbe programmed to follow the AC Trouble Input as follows:
AC FAIL = OPEN on fail
* Fire zones shall be separated from burglar zones through area partitioning.
* Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell output
* Fire Zone Z4 N.O Push Button to be used as monitoring reset switch.
* EOL resistor must be installed at the Fire Alarm Control Panel Output.
June 2024 45
4A Security Purpose Power Module UL and cUL Installation Requirements
CAN/ULC-S559
CONTROLLER
ACTIVE COMMUNICATION: CELLULAR MODEM
Metal Conduit Note: All cables shall be protected within metal conduits.
ENCLOSURE
12V DC
MAINS SUPPLY AC + +
(120V AC) TELECOM
AC - - ETHERNET
EQUIPMENT
INTERNET
485 485
AC BATT
12VDC FAIL FAIL USB
+ - C NC C NC
CELLULAR MODEM
SIM ANTENNA ANTENNA
CELLULAR
NETWORK
FIRE ALARM PANEL
12VDC IN
USB N+ N-
FIRE Z1
SUPERVISORY Z2
Programmable Z4
COM STATUS / FB
Output
* The AC FAIL output on the Power Supply MUSTbe programmed to follow the AC Trouble Input as follows:
AC FAIL = OPEN on fail
* Fire zones shall be separated from burglar zones through area partitioning.
* Fire zones Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed to activate the bell output
* Fire Zone Z4 N.O Push Button to be used as monitoring reset switch.
* EOL resistor must be installed at the Fire Alarm Control Panel Output.
June 2024 46
4A Security Purpose Power Module UL and cUL Installation Requirements
Note: Any available dry relay contact on the Security Expert controller or output expander
may be used for the FACP system, provided the selected output is programmed as the
Report OK output.
Please refer to section Contact ID | Settings in the Operator Reference Manual.
l Fire inputs Z1-Z3 shall be used exclusively for fire monitoring and cannot be programmed
to activate the bell output.
UL Compliance Requirements
UL1610
For Security Grade 4 installations, two forms of reporting are required. This can be satisfied
using the onboard 2400bps modem included with the modem controller model, or through the
incorporation of the SP-4G-USB cellular modem module into the installation with the non-
modem controller model.
l A local alarm sounding device, alarm housing, and control unit shall comply with the
mercantile requirements in the Standard for Police Station Connected Burglar Alarm Units
and Systems, UL365.
l A bell or visual indicator used as an arming acknowledgement signal must be listed to a
UL security, signaling or fire standard. If intended to be mounted outside, it must be rated
for outdoor use.
l Exit and entry delay must not exceed 60 seconds. To program the entry and exit delay
time, refer to the section Areas | Configuration in the Operator Reference Manual.
l All ethernet network connections shall be installed within the same room as the
equipment.
l Signals between the premises control unit and the receiving equipment, when not carried
by wireless means, shall be protected by the following method:
l Onboard modem telco connection must be dedicated to the Security Expert controller.
Modem model only.
l Ethernet connection to the Internet Service Provider (ISP) with a fixed IP Address
must be dedicated to the Security Expert controller.
l To comply with the dual signal line transmission system requirement, both transmission
lines (onboard modem and IP reporting) must be enabled. Signals shall be sent
simultaneously to both the primary communications channel and the Backup Service.
The Report IP and Contact ID services must be programmed and enabled within the
Security Expert system. The following options are required:
l The Contact ID Reporting Service must be enabled and the Service Mode must be
configured to start with the operating system.
l Refer to the section Contact ID in the Operator Reference Manual.
l The Report IP Service must be enabled as the primary communication channel, the
Service Mode must be configured to start with the operating system, and the
Reporting Protocol must be set to ArmorIP.
l Refer to the section Report IP in the Operator Reference Manual.
l When more than one means of signal transmission is used, loss of communication with
the receiving system shall be annunciated at the receiver within 200 seconds. If a fault is
detected on any of the signal transmission means, at least one of the signal transmission
channels shall send a signal to the central-station to report the fault within 200 seconds.
The Report IP and Contact ID services must be programmed and enabled within the
Security Expert system.
The Security Expert controller is compatible with the ArmorIP Internet Monitoring
Receiver. Poll Time must be set to 40 seconds and the Grace Time must be set to 20
seconds.
June 2024 47
4A Security Purpose Power Module UL and cUL Installation Requirements
In the Security Expert system, the reporting service must be configured to 40 seconds.
The following options are required for the service selected as Report IP type:
l The Poll Time must be programmed to 40 seconds. Refer to the Report IP | General
section in the Operator Reference Manual
l The Contact ID Reporting Service must be enabled and the Service Mode must be
configured to start with the operating system.
l Refer to the section Contact ID in the Operator Reference Manual
l The Report IP Service must be enabled as the primary communication channel, the
Service Mode must be configured to start with the operating system, and the
Reporting Protocol must be set to ArmorIP.
l Refer to the section Report IP in the Operator Reference Manual.
l The Trouble Input Area must be armed in 24h mode. Refer to the section Trouble
Inputs | Areas and Input Types in the Operator Reference Manual.
In the event of unsuccessful communication, a digital alarm communicator transmitter
shall make a minimum of 5 and a maximum of 10 attempts. Where the maximum number
of attempts to complete the sequence is reached, an indication of the failure shall be made
at the premises.
In the Security Expert system, the reporting service selected as Contact ID must have the
number of attempts programmed to 5 attempts. The following options are required:
l The Dial Attempts option must be programmed. Refer to the section Contact ID |
Settings in the Operator Reference Manual.
l DACT communication channel check-in time is not to exceed 24 hrs.
l Trouble Zone Service Test Report
l The Test Report Time must be programmed. Refer to the section Controllers |
Configuration in the Operator Reference Manual.
l The Generate Input Restore on Test Input option must be enabled. Refer to the
section Controller | Options in the Operator Reference Manual.
l The Test Report Time is Periodic option must be enabled. Refer to the section
Controller | Options in the Operator Reference Manual.
l ArmorIP detects the reception of any invalid packet on the programmed port as a
potential system compromise attempt. Each compromise attempt sends a
notification to the receiver, and logs a Compromise Attempt event under the Live
Panel Events.
The event is sent with the following details:
n Account Code as defined in the Serial Receiver settings
n Event Code 0x163
n Group Code as defined in the Serial Receiver settings
n Point Code as defined in the Serial Receiver settings
Refer to the section Global Settings | Serial Receiver in the ArmorIP Version 3 Internet
Monitoring Application User Manual.
For UL and cUL installations the Central Station Receiving software must have the
Contact ID details as specified, programmed for the Compromise Attempt event.
l If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
l The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
UL294
l The Security Expert controller and reader expander module are intended to be mounted
within the enclosure (refer to UL/cUL Installation Cabinet Options), installed inside the
protected premise, and are UL 294 Listed for Attack Class I applications only.
l Exit devices and wiring must be installed within the protected area.
June 2024 48
4A Security Purpose Power Module UL and cUL Installation Requirements
l For the Security Expert controller and reader expander module, all RS485 and reader
terminal connections must be made using shielded grounded cable.
l All readers must be connected with shielded, grounded cable.
l A bell or visual indicator used as an arming acknowledgment signal must be listed to a UL
security, signaling or fire standard. If intended to be mounted outside, it must be rated for
outdoor use.
l Fail secure locking mechanism shall only be installed where allowed by the local authority
having jurisdiction (AHJ) and shall not impair the operation of panic hardware and
emergency egress.
l If fire resistance is required for door assembly, portal locking device(s) must be evaluated
to UL10B or UL10C.
l Must be installed with UL 1034 listed electronic locks for UL installations.
l AC power on shall be indicated by an external panel mount LED (Lumex SSI-LXH312GD-
150) and fitted into a dedicated 4mm hole in the cabinet to provide external visibility. This
shall be wired between 12V and a PGM output that is programmed to follow the AC trouble
input as shown below:
LED
1K5 OHM
BZ L1 D1 DO Z4 V- Z3 Z2 V- Z1 V- V+
READER 1 INPUT 1-4 12VDC OUT
l If a flexible cord is used to connect to line voltage, strain relief must be provided for the
cord inside the enclosure or at the knockout.
l The power supply is not intended to be mounted on the exterior of vault, safe, or
stockroom.
June 2024 49
4A Security Purpose Power Module FCC Compliance Statements
June 2024 50
4A Security Purpose Power Module Industry Canada Statement
June 2024 51
4A Security Purpose Power Module IEC 62368-1:2014
IEC 62368-1:2014
This power supply has been tested and confirmed to comply with IEC 62368-1. This satisfies
the requirements for:
l Australia/New Zealand: AS/NZS 62368-1
l Canada/USA: CSA/UL 62368-1
l Europe: EN 62368-1
l Great Britain: BS EN 62368-1
l Japan: J62368-1
June 2024 52
Schneider Electric
www.schneider-electric.com
© 2024 Schneider Electric. All rights reserved.
June 2024