항목 Display Display contents Trouble shooting guide

1. Excessive connection of indoor units compared to capacity of Outdoor Unit.


E01 Excessive or less capacity of indoor units ( Over 160% or less than 50% ratio)
2. Check communication status between outdoor and indoor unit.(Check the number of indoor units)

1. In case emergency control of system occurs during determining cycle stability


E02 System unstable Error
(Re-check the amount of system refrigerant, installed environment.)

E03 Temperature Range Error 1. In case outdoor and indoor unit are outside the range of operable temperature.

1. Unstable Test Run when the frost condition is met.


E04 Defrost Operation Error
2. Check the temperature value of the ambient, hex temperature included upper/lower.

In case error occurs during sense


1. Re-execute Test Run after the error is generated.
E05 checking process.
(Errors and emergency controls can be checked through LGMV Display)
(system error, emergency status)

Occurs when the indoor unit number is one


E06 1. Check communication status between outdoor and indoor unit.(Execute address settings as needed)
or non operational indoor unit is installed.
1. Re-execute Test Run after reset of outdoor unit
E08 Test Run forced termination
(E08 does not mean termination)
1. In case auto addressing is not operated or the number of addressed indoor unit is zero.
E12 Auto addressing error
(Check communication status between outdoor and indoor unit.(Execute address settings as needed)
1. Check Pipe in/out temperature before and after operation of indoor unit.
E13 SVC V/V Closed error
2. Check svc valve is closed or not.

*Emergency control : Low / High pressure limit, compression ratio limit, excessive increase of discharge or IPM temperature of Compressor, etc.
*Non Operational Indoor unit : AHU Model, Hydro Kit(LRD-L1600A, LRD-L3200A, LRD-L5200A, LRD-L1600B, LRD-L2500B)
ERV DX(LZ-H500NX, LZ-H800NX, LZ-H1000NX, LZ-H500HX, LZ-800HX, LZ-1000HX)