Contrans I – Interface Modules

Product Catalog

Signal matching, binary or analog


Electrical isolation of field signals
HART compatible and FSK bus capable
Clearly arranged instrumentation with plug-in modules
Easy DCS coupling through standardized backplane

instrumentation

understanding measurement analysis control integration optimization


Contrans I
Interface Modules
Catalog 17.1 EN
Contrans I: Interface Modules

Introduction Page

Contrans I – System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4


General data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Binary Modules

Switch Amplifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Solenoid Drivers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Coupling Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Analog Modules

Input Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Transmitters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Output Isolators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Monitoring Modules

Trip Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Sockets, Backplanes

Sockets, Backplanes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105

Accessories

Cross Wiring Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108


Straight Through Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
FSK Bus Amplifier . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Programming Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
System cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
Power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Mounting and Installation Instructions

Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118


Encoding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

12.00 3
Contrans I – System description

The Contrans I family stands out with its modular design, which
permits electronic units to be plugged in a standard sockets or
backplanes. Only the DIN rail sockets are required for wiring.
This makes it easy to conduct functional matching even during
the commissioning phase.

If maintenance becomes necessary, the defective module can


be removed and replaced by just plugging the substitute into the
standard socket. The replacement is done. There is no
necessity to disconnect and reconnect wires. One source of
error is thus removed. No expert is required.

In order to reduce the expenditure for planning and wiring,


prewired backplanes for 8 or 16 plug-in function modules are
provided. Power is fed from a central source. A multi-core
system cable with two pluggable ends enables all modules to be
connected directly to the input and output modules of the control
unit.
In the field of process automation, the functionality of input or
output modules of programmable logic control or distributed
The result: reduced expenditure for planning, documentation
control systems is often inadequate for applications. For the
and wiring; also reduced time for installation, combined with
ensuing signal matching between the field and control levels,
extrem maintenance- and user-friendliness. All of these makes
the interface family Contrans I has a comprehensive program
Contrans I a very cost-effective solution.
involving electrically isolated signal processing components for
the supply of power to transmitters, for load increasing, for
measuring temperatures, setting alarms, also including further
modules for processing binary signals such as switch amplifiers, Contrans I – socket mounting
relays and optocouplers.
Type of modules for binary signals:
Analog modules are suitable for transmitting the HART field ■ Switch Amplifier
communication protocol. A central PC makes it possible to ■ Solenoid Driver
parameterize and centrally configure the underlying field unit ■ Coupling Module
level with the aid of special FSK bus amplifiers. All modules are
optionally provided with intrinsically safe signal circuits.
Type of modules for analog signals:
Contrans I – Separation of wiring and function ■ Input Isolator
– Loop Powered Supply
– Isolating Power Supply
– Input Isolator
– Input Isolator,
programmable
– Universal Isolator
■ Transmitter
– Temperature Transmitter
– Intelligent Transmitter
■ Output Isolator
– Loop Powered Isolator
– Isolating Driver
■ Trip Amplifier

The size of the modules depends to the functionality. The size 3


is not used today.

Module size 1 2 3 4

4 12.00
Contrans I – System description

Contrans I – Backplane mounting

Type of Backplanes:

8-way 1 2 1 X103
1
2
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6

+ -
X102

1 2 2

■ 8 slots for modules


1
2
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5

+ - 5
24VDC
X104

6
X101
5
T1,6A T2,5A 6

■ 1 slot for the FSK bus amplifier (HART)


1 2 3 4 5 6 7 8

■ Power supply with separate fusing for the power distribution


to the modules and for the signals
14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

16-way T2,5A T1,6A

1 2 1 2 43 44 3 4 5 6

■ 16 slots for modules X101 X102 X108


+ - 24 VDC + - K101 FSK FSK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

■ 1 slot for the FSK bus amplifier (HART)


■ Redundant power supply and separate fusing for the
power distribution to the modules and for the signals.
Dry contact for signalling of a fuse fault
14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

21-way
■ 21 slots for modules
24VDC X105
+ - + - H101 FSK 1...21 FSK 22...42 FSK
10.3
10.6

11.3
11.6
12.3
12.6
13.3
13.6
14.3
14.6
15.3
15.6
16.3
16.6
17.3
17.6
18.3
18.6
19.3
19.6
20.3
20.6
21.3
21.6
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
9.3
9.6

1 2 3 4 43 44
1
2

T2A 5 5 6 6
X103 X104
10.4
10.5

X106 X107
11.4
11.5
12.4
12.5
13.4
13.5
14.4
14.5
15.4
15.5
16.4
16.5
17.4
17.5
18.4
18.5
19.4
19.5
20.4
20.5
21.4
21.5
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
9.4
9.5

X302
1
2

X301

■ 2 slots for the FSK bus amplifier (HART)


T3,15A X101 X102
K101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

■ Redundant power supply and separate fusing for the power


distribution to the modules and for the signals.
Dry contact for signalling of a fuse fault 14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13

■ Especially design for using with 19“ racks

Customer-specified solutions
Backplanes can be fit according to customer
requirements.

12.00 5
Contrans I – System description

Module housing
Smallest amount of components to realise an effective
production.
Labelling by laser beam and well-arranged mapping
of the functions.

Module and sockets


Identical pinning of termination
– Power supply: terminals 1, 2
– Channel 1: terminals 4, 5 (control room side) 14, 15 (field side)
– Channel 2: terminals 3, 6 (control room side) 13, 16 (field side)

Coding for voltages > 42 V

230 V (enclosed plate for 230 V)

Module jack 1
1
2
Module jack 2 Legend plates 3
Encoding 4 Legend plates
terminals 5
6
Encoding terminals 7

EExi identification
(enclosed plate, light blue)

Encoding
The sockets on slots of the backplanes can be coded to avoid a mixup
of modules. Break off the coding pin at the module and code with the
encoding star the correspondend coding pins in the socket. Encoding
stars are included in the delivery of sockets on backplanes.

1
2
3
4
Encoding star (enclosed) 5
6
7

6 12.00
Contrans I – System description

FSK bus: an system upgrade without additional effort


Independent HART communication is standard for all work can be connected through a HART modem to a perso-
Contrans I backplanes. The FSK bus amplifier is only to nal computer. This HART network is independent of the run-
plug-in and the analog HART FSK bus for one backplane is ning communication software. Of course the software
installed. Only wiring with 2 wires between all the backpla- “SMART VISION“ is working with this HART network. This is
nes is necessary to create a HART network. This can be also the easiest way of HART communication and the best tool
done as an upgrade in existing installations. The HART net- for service and maintenance in the plant.

12.00 7
Contrans I – System description

General data Functional data


Mounting All Contrans I Modules meet the requirements of the EMC gui-
outside hazardous areas deline 89/336/EWG and the low voltage 73/23/EWG
Mounting orientation Behaviour of analog modules
vertical or horizontal Features for reference condtions to DIN IEC 770
Storage temperature Electromagnetic compatibility
-25...85 °C DIN EN 50 081-2 (1992)
Operating temperature DIN EN 50 082-1 (1997)
-20...60 °C; vertical mounting -20...55 °C DIN EN 50 082-2 (1995) are met
For the types V17151-74_, -75_, -34: NAMUR recommendation NE 21 is met
at vertical mounting -20...40 °C Functional modification through jumpers
(vertical mounting: top-hat rail vertical) The respective Data Sheets and block diagrams provides
Relative humidity functional informations of the delivered device and matching
< 85 %, 3K3 to IEC 721, part 3-3, no condensation possibilities of the modules.

The function can only be modified through jumpers off-line.


Explosion protection To do this, remove the module from the socket or backplane.
After removing the front panel with a screwdriver, the printed
Prozess inputs or outputs circuit board can be pulled out from the housing.
[EEx ia] IIC or [EEx ia] IIB or [EEx ib] ...

Housing
Safety data
Material
Polycarbonate DIN EN 61010-1; DIN VDE 0411, part 1
Fire protection class Overvoltage category
V2 to UL 94 (DIN IEC 707) II
Colour Degree of pollution
Module RAL 7043, dark grey 2
Socket, Type of protection to EN 60 259/DIN VDE 0470, part 1
Backplane RAL 7035, light grey IP 20
Contact material
Phosphorous bronze, gold-plated 0.8 µm Max. requirements on power supplies
(for backplanes with 16 modules and approx. 3.1 W power
Mechanical features consumption)
Transport/shoc Power supply Max. inrush Rated current
30 g, 18 ms, 2M2 to DIN IEC 721, part 3-2 current < 100 µs
Function/Vibrations 19.2 V 6.4 A 3.1 A
2 g/± 0.15 mm/5...150 Hz/3 x 5 cycles 24 V 8.0 A 2.5 A
2 g/10 mm/1...35 Hz/3 x 1 cycle 30 V 9.9 A 2.0 A
3M2 to DIN IEC 721, part 3-3

8 12.00
Binary Modules

Switch Amplifier

Switch Amplifier 2 channels 2 x relay outputs V17131-13

Switch Amplifier 2 channels 2 x transistor outputs V17131-16

Switch Amplifier Ex 1 channel 1 x relay output V17131-51

Switch Amplifier Ex 1 channel 2 x relay outputs V17131-52

Switch Amplifier Ex 2 channels 2 x relay outputs V17131-53

Switch Amplifier Ex 1 channel 1 x transistor output V17131-54

Switch Amplifier Ex 1 channel 2 x transistor outputs V17131-55

Switch Amplifier Ex 2 channels 2 x transistor outputs V17131-56

12.00 9
Binary Modules

Switch amplifier

V17131-13
V17131-16
V17131-51
V17131-52
V17131-53
V17131-54
V17131-55
V17131-56
Selection table

Output
Control room

Relay x x x x
Transistor x x x x
Multi channel amount of channels 2 2 2 2
2. Output x x
Reversible signal flow direction x x x x x x x x
Input
to DIN 19234 NAMUR x x x x x x x x
Sensor/actor Proximiy detector x x x x x x x x
Field

Switching contact x x x x x x x x
Explosion protection [EExia]IIC / [EExib]IIC x/x x/x x/x x/x x/x x/x
Wire break x x x x x x x x
Monitoring
Short circuit x x x x x x x x
19,2...30VDC x x x x x x x x
Power supply
95...253VAC o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹
Input-output x x x x x x x x
Electrical galvanic Input-power supply x x x x x x x x
isolation Output-power supply x x x x x x x x
General data

Channel 1 - channel 2 x x x x
Modules fits for:
V17111-11, Socket x x x x x x x x
V17111-12, Socket with power supply 24/24
V17111-13, Socket with power supply 230/24 x x x x x x x x
V17111-2_ _, Backplane 8 way x x x x x x x x
V17111-3_ _, Backplane 16 way x x x x x x x x
V17111-6_ _, Backplane 21 way x x x x x x x x

x = ok; o¹= only with V17111-13; o² = only with V17111-12, -13

10 12.00
Switch Amplifier V17131-13
2 channels, 2 x relay outputs

■ Switching contacts, proximity detectors


A
■ Electrical isolation between input, output and B

power supply
Contrans I
BA
1 2
■ Wire break and short-circuit monitoring
BA
■ Reversible signal flow direction
BA
A V17131-13
B

J4 J1 J6 J3 J5 J2
Module size 2
Module fits for:
Output per channel Socket Backplane
Contact load 250 V AC, cosϕ > 0.7 V17111-11 ● V17111-2 _ _ ●
30 V DC, 2 A resistive load V17111-12 ❍ V17111-3 _ _ ●
Mech. life expectancy, operating cycles > 3 · 107 V17111-13 ● V17111-6 _ _ ●
Contact life frequency,
operating cycles under load > 106
Max. switching frequency < 20 Hz 19.2...30 V DC

Start delay approx. 20 ms 1 2 5 4 6 3

Drop delay approx. 20 ms + -


A B A B
J3 J6

Input per channel


Rated voltage to EN 50227, NAMUR A B ye A B ye
J2 J5
No load voltage approx. 7.8 V DC
>1
-
Input resistance approx. 980 Ω gn
Short-circuit current approx. 7.9 mA rd
Switching span 1.2...2.1 mA
J1 J4
Overlap approx. 0.23 mA A B A B

Input pulse length ≥ 500 µs + + – + + –


Input pulse pause ≥ 500 µs 11 14 15 12 13 16

Line break monitoring (relay de-energized) I < 150 mA


Short-circ. monitoring (relay de-energized) R < 100 Ω Channel 1 Channel 2

1k 1k
General data J1 / 4

1)
LED indicator, power “On“ (green) 10 k
A B
10 k

LED indicator, “Switching state relay“ (yellow) J1 / 4

2) A B
LED indicator, “Wire break/short-circuit“ (red)
Max. ambient temperature -20...+60 °C J1 / 4

Isolation 3) A B
10 k 10 k
Input – output – power supply 2.3 kV . J1 / 4

4) .
Channel 1 – channel 2 1.35 kV A B

Weight 90 g . J1 / 4
5) .
Power supply A B

Rated voltage 19.2...30 V DC 1) Contact with wire break and short-circuit monitoring
Power consumption 0.94 W 2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
4) NAMUR transmitter without wire break and short-circuit monitoring
5) Contact without wire break and short-circuit monitoring

Functions of the plug-in jumpers J.:


Channel 1: J1, J2, J3
Channel 2: J4, J5, J6
J1/J4 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked
J2/J5 Effective direction
A = inverse
B = direct
J3/J6 Relay output
A = NC contact
B = NO contact
The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)

11

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier V17131-16
2 channels, 2 x transistor outputs

■ Switching contacts, proximity detectors


■ Electrical isolation between input, output and
power supply
Contrans I

1 2
■ Wire break and short-circuit monitoring
BA
■ Reversible signal flow direction
BA
A V17131-16
B

J4 J1 J5 J2
Module size 2
Module fits for:
Output per channel Socket Backplane
Rated voltage 8...33 V DC V17111-11 ● V17111-2 _ _ ●
Rated current (limited current) 100 mA V17111-12 ❍ V17111-3 _ _ ●
Residual current < 10 µA V17111-13 ● V17111-6 _ _ ●
Max. switching frequency 1 kHz
Start delay < 500 µs
Drop delay < 500 µs 19.2...30 V DC

Voltage drop < 2.5 V 1 2 4 5 3 6

+ - + - + -

Input per channel


Rated voltage to EN 50227, NAMUR
No load voltage approx. 7.8 V DC A B ye A B ye
J2 J5
Input resistance approx. 980 Ω
>1
-
Short-circuit current approx. 7.9 mA gn
Switching span 1.2...2.1 mA rd
Overlap approx. 0.23 mA
Input pulse length ≥ 500 µs J1 J4
A B A B

Input pulse pause ≥ 500 µs + + – + + –


Line break monitoring I < 150 mA 11 14 15 12 13 16

(output high-impedance)
Short-circuit monitoring R < 100 Ω Channel 1 Channel 2
(output high-impedance) 1k 1k
J1 / 4

1)
General data 10 k
A B
10 k

LED indicator, power “On“ (green) J1 / 4

2) A B
LED indicator, “Switching state transistor“ (yellow)
LED indicator, “Wire break/short-circuit“ (red) J1 / 4

Max. ambient temperature -20...+60 °C 3) A B


10 k 10 k
Isolation . J1 / 4

4) .
Input – output – power supply 2.3 kV A B

Channel 1 – channel 2 1.35 kV .


5) . J1 / 4

Weight 90 g A B

Power supply 1) Contact with wire break and short-circuit monitoring


Rated voltage 19.2...30 V DC 2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
Power consumption 0.62 W 4) NAMUR transmitter without wire break and short-circuit monitoring
5) Contact without wire break and short-circuit monitoring

Functions of the plug-in jumpers J.:


Channel 1: J1, J2, J3
Channel 2: J4, J5, J6
J1/J4 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked
J2/J5 Effective direction
A = inverse
B = direct
J3/J6 Transistor output
A = NC contact
B = NO contact
The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)

12

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-51
1channel, 1 x relay output

■ Switching contacts, proximity detectors


A
■ Electrical isolation between input, output and B

power supply
Contrans I

1
■ Wire break and short-circuit monitoring
■ Reversible signal flow direction
BA
A V17131-51
B

J1 J3 J2
Module size 2
Module fits for:
Output (safe area) Socket Backplane
Contact load 250 V AC, cosϕ > 0.7 V17111-11 ● V17111-2 _ _ ●
30 V DC, 2 A resistive load V17111-12 ❍ V17111-3 _ _ ●
Mech. life expectancy, operating cycles > 3 · 107 V17111-13 ● V17111-6 _ _ ●
Contact life frequency,
operating cycles under load > 106
Max. switching frequency 20 Hz 19.2...30 V DC

Start delay approx. 20 ms 1 2 5 4

Drop delay approx. 20 ms + - A B


J3

Input (hazardous area)


A B ye
Rated voltage to EN 50227, NAMUR J2
No load voltage approx. 7.8 V DC
gn
Input resistance approx. 980 Ω
rd
Short-circuit current approx. 7.9 mA
Switching span 1.2...2.1 mA J1
A B
Overlap approx. 0.23 mA
+ + –
Input pulse length ≥ 500 µs 11 14 15

Input pulse pause ≥ 500 µs


Line break monitoring (relay de-energized) I < 150 mA
Short-circ. monitoring (relay de-energized) R < 100 Ω 1k

Explosion protection [EEx ia] IIC 1)


J1

A B
Certificate of conformity PTB 99 ATEX 2119X 10 k

J1

Max. short-circuit current Io = 18 mA 2) A B

Max. voltage Uo = 10.6 V


Max. power Po = 48 mW 3) J1

A B
Permitted external inductance La = 4 mH .
10 k
J1

Permitted external capacitance Ca = 545 nF 4) . A B

.
5) J1

General data .
A B

LED indicator, power “On“ (green) EEx ia


LED indicator, “Switching state relay“ (yellow)
LED indicator, “Wire break/short-circuit“ (red) Hazardous area
Max. ambient temperature -20...+60 °C
Isolation 1) Contact with wire break and short-circuit monitoring
2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
Input – output – power supply 2.3 kV 4) NAMUR transmitter without wire break and short-circuit monitoring
5) Contact without wire break and short-circuit monitoring
Weight 90 g
Power supply
Rated voltage 19.2...30 V DC Functions of the plug-in jumpers J.:
Power consumption 0.51 W J1 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked

J2 Effective direction
A = inverse
B = direct

J3 Relay output
A = NC contact
B = NO contact

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

13

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-52
1 channel, 2 x relay output

■ Switching contacts, proximity detectors


A
■ Electrical isolation between input, output and B

power supply
Contrans I
BA
1 2
■ Wire break and short-circuit monitoring
■ Reversible signal flow direction
BA
A V17131-52
B

J1 J6 J3 J5 J7 J2
Module size 2
Module fits for:
Output output 1/output 2 (safe area) Socket Backplane
Contact load 250 V AC, cosϕ > 0.7 V17111-11 ● V17111-2 _ _ ●
30 V DC, 2 A resistive load V17111-12 ❍ V17111-3 _ _ ●
Mech. life expectancy, operating cycles > 3 · 107 V17111-13 ● V17111-6 _ _ ●
Contact life frequency, Output 1 Output 2
operating cycles under load > 106
Max. switching frequency 20 Hz 19.2...30 V DC

1 2 5 4 6 3
Start delay approx. 20 ms
+ -
Drop delay approx. 20 ms A B
J3
A B
J6

Input per channel (hazardous area) ye ye


A B A B
Rated voltage to EN 50227, NAMUR J2 J5
J7
No load voltage approx. 7.8 V DC B
1
gn
Input resistance approx. 980 Ω A

rd
Short-circuit current approx. 7.9 mA
Switching span 1.2...2.1 mA J1
A B
Overlap approx. 0.23 mA
+ + –
Input pulse length ≥ 500 µs 11 14 15
Input pulse pause ≥ 500 µs
Line break monitoring (relay de-energized) I < 150 mA
Short-circ. monitoring (relay de-energized) R < 100 Ω
1k
Explosion protection [EEx ia] IIC J1
1)
Certificate of conformity PTB 99 ATEX 2119X 10 k
A B

Max. short-circuit current Io = 18 mA J1

2) A B
Max. voltage Uo = 10.6 V
Max. power Po = 48 mW J1
3)
Permitted external inductance La = 4 mH 10 k
A B

.
Permitted external capacitance Ca = 545 nF 4) . J1

A B

.
General data 5) . J1

LED indicator, power “On“ (green)


A B

EEx ia
LED indicator, “Switching state relay“ (yellow)
LED indicator, “Wire break/short-circuit“ (red)
Hazardous area
Max. ambient temperature -20...+60 °C
Isolation 1) Contact with wire break and short-circuit monitoring
Input – output – power supply 2.3 kV 2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
4) NAMUR transmitter without wire break and short-circuit monitoring
Channel 1 – channel 2 1.35 kV 5) Contact without wire break and short-circuit monitoring
Weight 90 g Functions of the plug-in jumpers J.:
Power supply J1 Wire break monitoring
A = without, jumper plugged
Rated voltage 19.2...30 V DC B = with, jumper parked
Power consumption 0.8 W J2 Effective direction output 1
A = inverse
B = direct
J5 Effective direction output 2
A = invers
B = direct
J3/J6 Relay output 1/2
A = NC contact
B = NO contact
J7 Output 2
A = wire break and short-circuit monitoring
A = (J5 set on position A)
B = set (as output 1)
The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)
14

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-53
1 channel, 2 x relay output

■ Switching contacts, proximity detectors


A
■ Electrical isolation between input, output and B

power supply
Contrans I
BA
1 2
■ Wire break and short-circuit monitoring
BA
■ Reversible signal flow direction
BA
A V17131-53
B

J4 J1 J6 J3 J5 J2
Module size 2
Module fits for:
Output per channel (safe area) Socket Backplane
Contact load 250 V AC, cosϕ > 0.7 V17111-11 ● V17111-2 _ _ ●
30 V DC, 2 A resistive load V17111-12 ❍ V17111-3 _ _ ●
Mech. life expectancy, operating cycles > 3 · 107 V17111-13 ● V17111-6 _ _ ●
Contact life frequency,
operating cycles under load > 106
Max. switching frequency 20 Hz 19.2...30 V DC

Start delay approx. 20 ms 1 2 5 4 6 3

Drop delay approx. 20 ms + -


A B A B
J3 J6

Input per channel (hazardous area)


ye ye
Rated voltage to EN 50227, NAMUR A B
J2
A B
J5
No load voltage approx. 7.8 V DC
>1
-
Input resistance approx. 980 Ω gn
Short-circuit current approx. 7.9 mA rd
Switching span 1.2...2.1 mA
J1 J4
Overlap approx. 0.23 mA A B A B

Input pulse length ≥ 500 µs + + – + + –


Input pulse pause ≥ 500 µs 11 14 15 12 13 16

Line break monitoring (relay de-energized) I < 150 mA


Channel 1
Short-circ. monitoring (relay de-energized) R < 100 Ω Channel 2

Explosion protection [EEx ia] IIC 1k 1k

Certificate of conformity PTB 99 ATEX 2119X 1)


J1 / 4

A B
Max. short-circuit current Io = 18 mA 10 k 10 k

J1 / 4
Max. voltage Uo = 10.6 V 2) A B

Max. power Po = 48 mW
Permitted external inductance La = 4 mH 3) J1 / 4

Permitted external capacitance Ca = 545 nF 10 k


A B
10 k
. J1 / 4
4) .
A B

General data .
LED indicator, power “On“ (green) 5) . J1 / 4

A B
LED indicator, “Switching state relay“ (yellow) EEx ia
LED indicator, “Wire break/short-circuit“ (red)
Hazardous area
Max. ambient temperature -20...+60 °C
Isolation
1) Contact with wire break and short-circuit monitoring
Input – output – power supply 2.3 kV 2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
Channel 1 – channel 2 1.35 kV 4) NAMUR transmitter without wire break and short-circuit monitoring
5) Contact without wire break and short-circuit monitoring
Weight 90 g
Power supply Functions of the plug-in jumpers J.:
Rated voltage 19.2...30 V DC Channel 1: J1, J2, J3
Channel 2: J4, J5, J6
Power consumption 0.94 W
J1/J4 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked
J2/J5 Effective direction
A = inverse
B = direct
J3/J6 Relay output
A = NC contact
B = NO contact
The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)

15

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-54
1 channel, 1 x transistor output

■ Switching contacts, proximity detectors


■ Electrical isolation between input, output and
power supply
Contrans I

1
■ Wire break and short-circuit monitoring
■ Reversible signal flow direction
BA
A V17131-54
B

J1 J2
Module size 2
Module fits for:
Output (safe area) Socket Backplane
Rated voltage 8...33 V DC V17111-11 ● V17111-2 _ _ ●
Rated current (limited current) 100 mA V17111-12 ❍ V17111-3 _ _ ●
Residual current < 10 µA V17111-13 ● V17111-6 _ _ ●
Max. switching frequency 1 kHz
Start delay < 500 µs
Drop delay < 500 µs 19.2...30 V DC
Voltage drop < 2.5 V 1 2 4 5

+ - + -
Input (hazardous area)
Rated voltage to EN 50227, NAMUR
No load voltage approx. 7.8 V DC A B ye
J2
Input resistance approx. 980 Ω
Short-circuit current approx. 7.9 mA gn
Switching span 1.2...2.1 mA
rd
Overlap approx. 0.23 mA AB

Input pulse length ≥ 500 µs J1

Input pulse pause ≥ 500 µs


+ + -
Line break monitoring I < 150 mA 11 14 15
(output high-impedance)
Short-circuit monitoring R < 100 Ω
(output high-impedance)
Explosion protection [EEx ia] IIC 1k
J1
Certificate of conformity PTB 99 ATEX 2119X 1) A B
10 k
Max. short-circuit current Io = 18 mA J1

Max. voltage Uo = 10.6 V 2) A B

Max. power Po = 48 mW
Permitted external inductance La = 4 mH 3)
J1

A B
Permitted external capacitance Ca = 545 nF .
10 k
J1
4) . A B

General data .
LED indicator, power “On“ (green) 5) .
J1

A B

LED indicator, “Switching state transistor“ (yellow) EEx ia


LED indicator, “Wire break/short-circuit“ (red)
Max. ambient temperature -20...+60 °C Hazardous area
Isolation
Input – output – power supply 2.3 kV 1) Contact with wire break and short-circuit monitoring
Weight 90 g 2) NAMUR transmitter with wire break and short-circuit monitoring
3) Contact with wire break monitoring
Power supply 4) NAMUR transmitter without wire break and short-circuit monitoring
5) Contact without wire break and short-circuit monitoring
Rated voltage 19.2...30 V DC
Power consumption 0.35 W Functions of the plug-in jumpers J.:
J1 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked

J2 Effective direction
A = inverse
B = direct

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

16

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-55
1 channel, 2 x transistor output

■ Switching contacts, proximity detectors


■ Electrical isolation between input, output and
power supply
Contrans I

1 2
■ Wire break and short-circuit monitoring
■ Reversible signal flow direction
BA
A V17131-55
B

J1 J5 J7 J2
Module size 2
Module fits for:
Output output 1/output 2 (safe area) Socket Backplane
Rated voltage 8...33 V DC V17111-11 ● V17111-2 _ _ ●
Rated current (limited current) 100 mA V17111-12 ❍ V17111-3 _ _ ●
Residual current < 10 µA V17111-13 ● V17111-6 _ _ ●
Max. switching frequency 1 kHz
Channel 1 Channel 2
Start delay < 500 µs
Drop delay < 500 µs 19.2...30 V DC

Voltage drop < 2.5 V 1 2 4 5 3 6

+ - + - + -

Input per channel (hazardous area)


Rated voltage to EN 50227, NAMUR
A B ye B A ye
No load voltage approx. 7.8 V DC J2 J5
J7
Input resistance approx. 980 Ω A
1
gn
Short-circuit current approx. 7.9 mA rd
B

Switching span 1.2...2.1 mA


Overlap approx. 0.23 mA J1
A B
Input pulse length ≥ 500 µs + + –
Input pulse pause ≥ 500 µs 11 14 15

Line break monitoring I < 150 mA


(output high-impedance)
Short-circuit monitoring R < 100 Ω 1k

(output high-impedance) J1
1)
Explosion protection [EEx ia] IIC 10 k
A B

J1
Certificate of conformity PTB 99 ATEX 2119X 2) A B

Max. short-circuit current Io = 18 mA


Max. voltage Uo = 10.6 V 3)
J1

Max. power Po = 48 mW .
10 k
A B

J1
Permitted external inductance La = 4 mH 4) .
A B

Permitted external capacitance Ca = 545 nF .


5) . J1

A B

General data EEx ia

LED indicator, power “On“ (green)


LED indicator, “Switching state transistor“ (yellow) Hazardous area

LED indicator, “Wire break/short-circuit“ (red)


Max. ambient temperature -20...+60 °C 1) Contact with wire break and short-circuit monitoring
2) NAMUR transmitter with wire break and short-circuit monitoring
Isolation 3) Contact with wire break monitoring
4) NAMUR transmitter without wire break and short-circuit monitoring
Input – output – power supply 2.3 kV 5) Contact without wire break and short-circuit monitoring

Channel 1 – channel 2 1.35 kV Functions of the plug-in jumpers J.:


Weight 90 g J1 Wire break monitoring
A = without, jumper plugged
Power supply B = with, jumper parked
Rated voltage 19.2...30 V DC J2 Effective direction output 1
Power consumption 0.48 W A = inverse
B = direct
J5 Effective direction output 2
A = invers
B = direct
J7 Output 2
A = wire break and short-circuit monitoring
A = (J5 set on position A)
B = set (as output 1)
The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)
17

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Amplifier Ex V17131-56
2 channels, 2 x transistor output

■ Switching contacts, proximity detectors


■ Electrical isolation between input, output and
power supply
Contrans I

1 2
■ Wire break and short-circuit monitoring
BA
■ Reversible signal flow direction
BA
A V17131-56
B

J4 J1 J5 J2
Module size 2
Module fits for:
Output per channel (safe area) Socket Backplane
Rated voltage 8...33 V DC V17111-11 ● V17111-2 _ _ ●
Rated current (limited current) 100 mA V17111-12 ❍ V17111-3 _ _ ●
Residual current < 10 µA V17111-13 ● V17111-6 _ _ ●
Max. switching frequency 1 kHz
Start delay < 500 µs
Drop delay < 500 µs 19.2...30 V DC

1 2 4 5
Voltage drop < 2.5 V 3 6

+ - + - + -

Input per channel (hazardous area)


Rated voltage to EN 50227, NAMUR ye ye
A B A B
No load voltage approx. 7.8 V DC J2 J5

Input resistance approx. 980 Ω >1


-
gn
Short-circuit current approx. 7.9 mA
rd
Switching span 1.2...2.1 mA
Overlap approx. 0.23 mA J1 J4
A B A B
Input pulse length ≥ 500 µs
+ + – + + –
Input pulse pause ≥ 500 µs 11 14 15 12 13 16

Line break monitoring I < 150 mA


(output high-impedance) Channel 1 Channel 2
Short-circuit monitoring R < 100 Ω 1k 1k

(output high-impedance) J1 / 4

1)
Explosion protection [EEx ia] IIC 10 k
A B
10 k

J1 / 4
Certificate of conformity PTB 99 ATEX 2119X 2) A B

Max. short-circuit current Io = 18 mA


Max. voltage Uo = 10.6 V J1 / 4
3)
Max. power Po = 48 mW .
10 k
A B
10 k
J1 / 4
Permitted external inductance La = 4 mH 4) .
A B

Permitted external capacitance Ca = 545 nF .


5) . J1 / 4

A B

General data EEx ib


LED indicator, power “On“ (green)
LED indicator, “Switching state transistor“ (yellow) Hazardous area

LED indicator, “Wire break/short-circuit“ (red)


Max. ambient temperature -20...+60 °C 1) Contact with wire break and short-circuit monitoring
2) NAMUR transmitter with wire break and short-circuit monitoring
Isolation 3) Contact with wire break monitoring
4) NAMUR transmitter without wire break and short-circuit monitoring
Input – output – power supply 2.3 kV 5) Contact without wire break and short-circuit monitoring

Channel 1 – channel 2 1.35 kV


Weight 90 g
Functions of the plug-in jumpers J.:
Power supply
Channel 1: J1, J2
Rated voltage 19.2...30 V DC Channel 2: J4, J5
Power consumption 0.62 W
J1/J4 Wire break monitoring
A = without, jumper plugged
B = with, jumper parked

J2/J5 Effective direction


A = inverse
B = direct

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

18

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Binary Modules

Solenoid Drivers

Solenoid Drivers Ex 8/20 V17132-51

Solenoid Drivers Ex 13/45 V17132-52

Solenoid Drivers Ex 15/47 V17132-53

Solenoid Drivers Ex 17.5/36 V17132-54

Solenoid Drivers Ex 19/32 V17132-55

Solenoid Drivers Ex 21/25 V17132-56

12.00 19
Binary Modules

Solenoid driver

V17132-51
V17132-52
V17132-53

V17132-54

V17132-55
V17132-56
Selection table

Input
Control room

Logig/direct x x x x x x

Contact x x x x x x

2nd Output short circuit signal x x x x x x


Output
Solenoid valve x x x x x x
Sensor/actor
Audiple alarms / LED annunciators x x x x x x
Field

Explosion protection [EExia]IIC / [EExib]IIC -/x -/x -/x -/x -/x -/x
Short circuit monitoring x x x x x x
Rated voltage [V] 8 13 15 17,5 19 21
Rated current [mA] 20 45 47 36 32 25
19,2...30VDC x x x x x x
Power supply
20...253VAC/DC o¹ o¹ o¹ o¹ o¹ o¹
Electrical galvanic Output - input /power supply x x x x x x
isolation Input - power supply o² o² o² o² o² o²
General data

Modules fits for:


V17111-11, Socket x x x x x x
V17111-12, Socket with power supply 24/24 x x x x x x
V17111-13, Socket with power supply 230/24 x x x x x x
V17111-2_ _, Backplane 8 way x x x x x x
V17111-3_ _, Backplane 16 way x x x x x x
V17111-6_ _, Backplane 21 way x x x x x x

x = ok; o¹= only with V17111-13; o² = only with V17111-12, -13

20 12.00
Solenoid Driver Ex V17132-51
8 V/20 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V logic/direct
Signal level (output “On“) 19.2...30 V
Contact (terminal 3/4) short-circuit
19.2...30 V DC
Signal level floating signal
1 2 3 4 5 6
Short-circuit signal (terminal 5 /6)
+ - + - +
Voltage H (open collector) 12...30 V
AB
J1
Output (hazardous area)
ye
Rated voltage 8V
Rated current 20 mA
Switching frequency (logic) < 200 Hz rd
Switching frequency (direct) < 10 Hz
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X gn

Max. short-circuit current Io = 32.2 mA


Max. voltage Uo = 10.5 V
Max. power Po = 340 mW
Permitted external inductance La = 4 mH
Permitted external capacitance Ca = 400 nF + -

General data 14 15
8 V, 20 mA
LED indicators, power “On“ (green)
LED indicators, “Switching state“ (yellow)
LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
EEx ib
Weight 90 g Hazardous area
Power supply
Rated voltage 19.2...30 V DC
Power consumption 0.6 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact /logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

21

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Solenoid Driver Ex V17132-52
13 V/45 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V
logic/direct
Signal level (output “On“) 19.2...30 V
Contact (terminal 3/4)
short-circuit
Signal level floating 19.2...30 V DC signal
Short-circuit signal (terminal 5 /6) 1 2 3 4 5 6
Voltage H (open collector) 12...30 V + - + - +
AB
J1
Output (hazardous area)
Rated voltage 13 V ye

Rated current 45 mA
Switching frequency (logic) < 200 Hz
rd
Switching frequency (direct) < 10 Hz
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X gn
Max. short-circuit current Io = 52 mA
Max. voltage Uo = 15.8 V
Max. power Po = 820 mW
Permitted external inductance La = 1.5 mH
Permitted external capacitance Ca = 160 nF
+ -

General data 14 15
LED indicators, power “On“ (green) 13 V, 45 mA

LED indicators, “Switching state“ (yellow)


LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g EEx ib

Power supply Hazardous area

Rated voltage 19.2...30 V DC


Power consumption 1.5 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact /logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

22

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Solenoid Driver Ex V17132-53
15 V/47 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V
Signal level (output “On“) 19.2...30 V logic/direct

Contact (terminal 3/4)


Signal level floating 19.2...30 V DC
short-circuit
signal
Short-circuit signal (terminal 5 /6) 1 2 3 4 5 6
Voltage H (open collector) 12...30 V + - - +
+
AB
Output (hazardous area) J1

Rated voltage 15 V ye
Rated current 47 mA
Switching frequency (logic) < 200 Hz
Switching frequency (direct) < 10 Hz rd
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X
Max. short-circuit current Io = 59.4 mA gn

Max. voltage Uo = 17.5 V


Max. power Po = 1040 mW
Permitted external inductance La = 0.9 mH
Permitted external capacitance Ca = 120 nF
+ -
General data
14 15
LED indicators, power “On“ (green) 15 V, 47 mA
LED indicators, “Switching state“ (yellow)
LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g EEx ib
Power supply Hazardous area
Rated voltage 19.2...30 V DC
Power consumption 1.5 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact/logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

23

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Solenoid Driver Ex V17132-54
17.5 V/36 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V
logic/direct
Signal level (output “On“) 19.2...30 V
Contact (terminal 3/4)
short-circuit
Signal level floating 19.2...30 V DC signal
Short-circuit signal (terminal 5 /6) 1 2 3 4 5 6
Voltage H (open collector) 12...30 V + - + - +
AB
J1
Output (hazardous area)
Rated voltage 17.5 V ye

Rated current 36 mA
Switching frequency (logic) < 200 Hz
rd
Switching frequency (direct) < 10 Hz
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X gn
Max. short-circuit current Io = 45 mA
Max. voltage Uo = 21 V
Max. power Po = 950 mW
Permitted external inductance La = 0.6 mH
Permitted external capacitance Ca = 79 nF
+ -

General data 14 15
17.5 V, 36 mA
LED indicators, power “On“ (green)
LED indicators, “Switching state“ (yellow)
LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
EEx ib
Weight 90 g
Power supply Hazardous area

Rated voltage 19.2...30 V DC


Power consumption 1.5 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact /logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

24

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Solenoid Driver Ex V17132-55
19 V/32 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V
logic/direct
Signal level (output “On“) 19.2...30 V
Contact (terminal 3/4)
Signal level floating short-circuit
19.2...30 V DC signal
Short-circuit signal (terminal 5 /6) 1 2 3 4 5 6
Voltage H (open collector) 12...30 V + - + - +
AB
Output (hazardous area) J1

Rated voltage 19 V ye
Rated current 32 mA
Switching frequency (logic) < 200 Hz
Switching frequency (direct) < 10 Hz rd
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X
gn
Max. short-circuit current Io = 41 mA
Max. voltage Uo = 21 V
Max. power Po = 860 mW
Permitted external inductance La = 0.8 mH
Permitted external capacitance Ca = 76 nF
+ -
General data 14 15
LED indicators, power “On“ (green) 19 V, 32 mA

LED indicators, “Switching state“ (yellow)


LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g EEx ib
Power supply Hazardous area
Rated voltage 19.2...30 V DC
Power consumption 1.5 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact/logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

25

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Solenoid Driver Ex V17132-56
21 V/25 mA

■ Actuation of intrinsically safe solenoid valves,


alarm sounders, LED indicators
■ Logic input
■ With or without additional power supply
■ Electrical isolation input/output

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Logic (terminals 4 /5, jumper J1 = A) V17111-11 ● V17111-2 _ _ ●
Signal level L (output “Off“) 0...3 V V17111-12 ● V17111-3 _ _ ●
Signal level H (output “On“) 12...30 V V17111-13 ● V17111-6 _ _ ●
Direct (terminal 4/5, jumper J1 = B)
Signal level (output “Off“) <3V
Signal level (output “On“) 19.2...30 V logic/direct

Contact (terminal 3/4)


Signal level floating 19.2...30 V DC
short-circuit
signal
Short-circuit signal (terminal 5 /6) 1 2 3 4 5 6
Voltage H (open collector) 12...30 V + - - +
+
AB
Output (hazardous area) J1

Rated voltage 21 V ye
Rated current 25 mA
Switching frequency (logic) < 200 Hz
Switching frequency (direct) < 10 Hz rd
Residual ripple < 200 mV
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 99 ATEX 2118X
gn
Max. short-circuit current Io = 32.2 mA
Max. voltage Uo = 24.2 V
Max. power Po = 780 mW
Permitted external inductance La = 0.5 mH
Permitted external capacitance Ca = 47 nF
+ -
General data
14 15
LED indicators, power “On“ (green) 21 V, 25 mA
LED indicators, “Switching state“ (yellow)
LED indicators, “Short-circuit“ (red)
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g EEx ib
Power supply Hazardous area
Rated voltage 19.2...30 V DC
Power consumption 1.5 W

Functions of the plug-in jumpers J.:

J1 Input circuit
A = contact /logic
B = direct
B = (without additional power supply)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

26

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Binary Modules

Coupling Modules

Optocoupler 2 channels V17133-11

Switch Relay 2 channels V17133-21

Switch Relay Ex 2 channels V17133-510

12.00 27
Optocoupler V17133-11
2 channels

■ Electrical isolation of control signals


■ Matching to various of voltage levels
■ Input with protection against wrong polarity

Module size 2
Module fits for:
Output Socket Backplane
Rated voltage 8...33 V DC V17111-11 ● V17111-2 _ _ ●
Rated current (limited current) < 100 mA V17111-12 ❍ V17111-3 _ _ ●
Residual current < 10 µA V17111-13 ❍ V17111-6 _ _ ●
Switching frequency ≤ 1 kHz
Voltage drop < 2.5 V
Protected against wrong polarity up to ± 80 V 4 5 3 6
+ - + -
Input
Signal level H 12...33 V DC
Signal level L -30...+3 V DC
Input current < 2.8 mA

General data
LED indicator, switching state “transistor“ (yellow)
Isolation per channel
Input – output 3.7 kV
ye ye
Isolation channel 1 – channel 2
Input 1 – input 2 820 V
Output 1 – output 2 2.3 kV
Max. ambient temperature -20...+60 °C + - + -
Weight 90 g 14 15 13 16

Channel 1 Channel 2

28

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Relay V17133-21
2 channels

■ Electrical isolation of control signals


■ Matching to various of voltage levels
■ Level conversion
■ With or without contact protection circuit

Module size 2
Module fits for:
Input Socket Backplane
Signal level H 15...30 V DC V17111-11 ● V17111-2 _ _ ●
Signal level L -30...+3 V DC V17111-12 ❍ V17111-3 _ _ ●
Input current < 24 mA V17111-13 ❍ V17111-6 _ _ ●
Protected against wrong polarity up to ± 80 V

Output
Contact load AC/cosϕ 250 V, 1 A/> 0,7
Contact load DC/resistive load 30 V, 2 A 4 5 3 6
Mech. life expectancy, operating cycles > 3 · 107 + - + -
Contact life frequency,
operating cycles under load > 106
Spark quenching unit 100 Ω /22 nF ge ge
Switching frequency < 20 Hz
Start delay < 10 ms
Drop delay < 10 ms
Contact material AgcdO
P P
A B A B
General data J1 J2

LED indicator, switching state “Relais“ (yellow)


Isolation per channel
Coil – contact 2,3 kV
Isolation channel 1 – channel 2
Contact 1 – contact 2 2.3 kV 14 15 11 13 16 12
Coil 1 – coil 2 820 V
Max. ambient temperature -20...+60 °C
Weight 90 g
Channel 1 Channel 2

Functions of the plug-in jumpers J.:

J1/J2 Spark quenching units


A = with, NO contact channel 1/2
B = with, NC contact channel 1/2
B = without (park position)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

29

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Switch Relay Ex V17133-510
2 channels

■ Electrical isolation of control signals


■ Matching to various of voltage levels
■ Level conversion

Module size 2
Module fits for:
Input Socket Backplane
Signal level H 15...30 V DC V17111-11 ● V17111-2 _ _ ●
Signal level L -30...+3 V DC V17111-12 ❍ V17111-3 _ _ ●
Input current < 24 mA V17111-13 ❍ V17111-6 _ _ ●
Protected against wrong polarity up to ± 80 V

Output
Contact load AC/cosϕ 250 V, 1 A/> 0,7
Contact load DC/resistive load 30 V, 2 A 4 5 3 6
Mech. life expectancy, operating cycles > 3 · 107 + - + -
Contact life frequency,
operating cycles under load > 106
Spark quenching unit 100 Ω /22 nF ye ye
Switching frequency < 20 Hz
Start delay < 10 ms
Drop delay < 10 ms
Contact material AgcdO
Explosion protection [EEx ia] IIC
Certificate of conformity PTB 99 ATEX 2067 X
Max. voltage Ui = 55 V Ui = 40 V Ui = 37 V
Max. current li =800 mA li = 1,5 A li = 2 A

General data
LED indicator, switching state “relay“ (yellow) 14 15 11 13 16 12
Isolation per channel
Coil – contact 2.3 kV
Isolation channel 1 – channel 2
Contact 1 – contact 2 2.3 kV
Coil 1 – coil 2 820 V
Channel 1 Channel 2
Max. ambient temperature -20...+60 °C
Weight 90 g
EEx ia

Hazardous area

30

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Analog Modules

Input Isolators

Power Supply Module 2 channels V17151-100

Loop Powered Supply 1 channel V17151-11

Loop Powered Supply 2 channels V17151-13

Isolating Power Supply 1 channel V17151-21_

Isolating Power Supply 1 channel, HART V17151-22_

Isolating Power Supply 1 channel, HART, FSK bus V17151-320

Isolating Power Supply 1 channel, HART V17151-325

Isolating Power Supply 2 channels, HART, FSK bus V17151-340

Isolating Power Supply 2 outputs, HART, FSK bus V17151-350

Loop Powered Input Isolator 2 channels V17151-413

Input Isolator 1 channel, HART, FSK bus V17151-420

Input Isolator, programmable 1 channel, V, mA V17151-43_

Input Isolator, universal V17151-480

Loop Powered Supply Ex 1 channel V17151-51

Loop Powered Supply Ex 1 channel, HART V17151-52

Isolating Power Supply Ex 1 channel V17151-61_

Isolating Power Supply Ex 1 channel, HART V17151-62_

Isolating Power Supply Ex 1 channel, HART, FSK bus V17151-720

Isolating Power Supply Ex 1 channel, HART V17151-725

Isolating Power Supply Ex 2 channels, HART, FSK bus V17151-740

Isolating Power Supply Ex 2 channels, HART V17151-745

Isolating Power Supply Ex 2 ourputs, HART, FSK bus V17151-750

Isolating Power Supply Ex 2 outputs, HART V17151-755

Input Isolator Ex 1 channel, HART, FSK bus V17151-820

Input Isolator Ex 1 channel, HART V17151-825

Input Isolator Ex 2 channels, HART, FSK bus V17151-840

Input Isolator Ex 2 channels, HART V17151-845

12.00 31
32

Analog Modules
Loop Loop
Input isolator
powered Isolating power supply powered Isolating power supply Ex Input isolator Ex
supply programmable supply Ex

V17151-100

V17151-210

V17151-211

V17151-212

V17151-213

V17151-220

V17151-221

V17151-222

V17151-320

V17151-325

V17151-340

V17151-350

V17151-413

V17151-420

V17151-430

V17151-432

V17151-433

V17151-434

V17151-480

V17151-610

V17151-611

V17151-612

V17151-613

V17151-620

V17151-621

V17151-622

V17151-720

V17151-725

V17151-740

V17151-745

V17151-750

V17151-755

V17151-820

V17151-825

V17151-840

V17151-845
V17151-11

V17151-13

V17151-51

V17151-52
Selection table

Output
0...20mA x x x x x x x
4...20mA x x x x x x x x x x x x x x x x x x x x x x x x x x x
0...5mA x x x x x
Analog signal 0(2)...10V
Control room

x x x x x x
0(1)...5V x x
± 10V x
± 20mA x
Output signal with FSK signal x x x x x x x x x x x x
Output signal free of FSK signal x x x x x x x x x
Multichannel Channels 2 2 2 2 2 2 2 2
2 Outputs x x x
Wire break monitoring x x
Relay output x x x x
Input
0...20mA x x x x x x
4...20mA x x x x x x x x x x x x x x x
4...20mA with supply voltage 20mA,24V
[V] 21,6 18,3 18,3 14 14 14 14 14 14 14 15,5 15,5 15,5 15,5 13,5 13,5 14 14 14 14 14 14 14 15,5 15,5 15,5 15,5 15,5 15,5

FSK(HART) x x x x x x x x x x x x x x x x x x x x x x
0...5mA x x x x x x
0/2...10V x x x x x
Field

Sensor / actor
0/1...5V x x x x x
± 10V x x x x x
± 20mA x
± 25mA x x x x x
± 12,5 V x x x x x
≤=200 V x
≤=100mA x
Explosion protection [EExia]IIC / [EExib]IIC -/x -/x -/x
-/x -/x -/x -/x -/x -/x x/x x/x x/x x/x x/x x/x x/x x/x x/x x/x x/x
Wire break monitoring x x
19,2...30VDC x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
Power supply 95...253VAC o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹ o¹
20...253VAC/DC x
Input - output / power supply x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
Electrical galvanic Output - power supply o² o² o² o² o² o² o² x x x x x o² o² o² o² x x x x x x x x x x x x x x x x x x
isolation Output (4...20mA) -FSK x x x x x x x x x x x x x x x
Channel 1 - channel 2 (output 2) x x x x x x x x x x
via PC-software x x x x
General data

Programmable
via DIP-Schalter x
Kommunikation Point to point (FSK -HART) x x x x x x x x x x x x x x x x x x x x x x
FSK -Bus (HART) x x x x x x x x x
mA x x x x x x x x x x
Test jacks
FSK x x x x x x x x x x x x x x x
Modules fits for:
V17111-11, Socket x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
V17111-12, Socket with power supply 24/24 x x x x x x x x x x x x x x x x x x x
V17111-13, Socket with power supply 230/24 x x x x x x x x x x x x x x x x x x x x
V17111-2_ _, Backplane 8 way x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
V17111-3_ _, Backplane 16 way x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
V17111-6_ _, Backplane 21 way x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

x = ok; o¹= only with V17111-13; o² = only with V17111-12, -13


Power Supply Module V17151-100
2 channels

■ Power supply for loop powered transmitter


■ 2 channels or 1 channel with
FSK connection

Module size 2
Module fits for:
Output Socket Backplane
Output current (short-circuit proof) 0...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ● V17111-3 _ _ ●
V17111-13 ● V17111-6 _ _ ●
Input
Input current 4...20 mA
Supply voltage rated voltage -2.3 V (J1/J2 = A) 19.2...30 V DC 4...20 mA 4...20 mA
(FSK) (FSK)
(Uv = 24 V, Rb = 50 Ω, I = 20 mA) rated voltage -7.1 V (J1/J2 = B)
Short-circuit current 24...35 mA
Overranging > 23.6 mA 1 2 4 5 3 6
+ - + - + -
General data
Voltage drop per channel
(Uv = 24 V, Rb = 0 Ω, I = 20 mA) 1 V (A), 6 V (B) J3
Max. ambient temperature -20...+60 °C gn BA
Weight 90 g
Power supply
Rated voltage 19.2...30 V DC A A
250 Ω 250 Ω
Power consumption 1W B B
J1 J2
Performance under reference conditions
Response time < 50 ms
+ - + -

14 15 13 16

4...20 mA 4...20 mA
(FSK) (FSK)

channel 1 channel 2

Functions of the plug-in jumpers J.:

J1/J2 HART communication


A = without resistance 250 Ω
B = with resistance 250 Ω

J3 Channels
A = 2 channels
B = 1 channel with FSK output
B = (terminal 3/6)

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

33

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Supply V17151-11
1 channel

■ Electrical isolation for current signal


with transmitter power supply

Module size 1
Module fits for:
Output Socket Backplane
Output current (short-circuit proof) 4...20 mA
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ●
Detect. of wire break (input) < 400 µA V17111-12 ❍ V17111-3 _ _ ●
Supply voltage 18.5...30 V V17111-13 ❍ V17111-6 _ _ ●

Input
Input current (short-circuit proof) 4...20 mA 4...20 mA
(18.5...30 V)
Supply voltage ≥ 12.8...24.3 V
Short-circuit current 24...35 mA 4 5
+ -
General data
Voltage drop at 20 mA < 5.7 V
Isolation
Input – output 1.35 kV
Max. ambient temperature -20...+60 °C
Weight 40 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.3 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms

+ -

14 15
4...20 mA
(>12.8...24.3 V)

4...20 mA

P, dP, T

34

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Supply V17151-13
2 channels

■ Electrical isolation for current signal


with transmitter power supply

Module size 2
Module fits for:
Output per channel Socket Backplane
Output current (short-circuit proof) 4...20 mA
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ●
Detect. of wire break (input) < 400 µA V17111-12 ❍ V17111-3 _ _ ●
Supply voltage 18.5...30 V V17111-13 ❍ V17111-6 _ _ ●

Input per channel


Input current (short-circuit proof) 4...20 mA 4...20 mA 4...20 mA
(18.5...30 V) (18.5...30 V)
Supply voltage ≥ 12.8...24.3 V
Short-circuit current 24...35 mA 4+ - 5 3+ - 6

General data
Voltage drop at 20 mA < 5.7 V
Isolation
Input – output 1.35 kV
Channel 1 – channel 2 500 V
Max. ambient temperature -20...+60 °C
Weight 90 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.3 % 14 + - 15 13 + - 16
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 % 4...20 mA 4...20 mA
> 12.8...23.3 V > 12.8...23.3 V
Response time < 50 ms
4...20 mA 4...20 mA
P, dP, T, … P, dP, T, …

Channel 1 Channel 2

35

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
36

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-21_
1 channel

■ Power supply for loop powered transmitters


■ Isolating driver for 4...20 mA
■ Wire break monitoring output overrange/underrange
(Jumper J1)

Module size 2
Module fits for:
Output Socket Backplane
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ●
Residual ripple (peak-to-peak) < 0.25 % V17111-12 ● V17111-3 _ _ ●
Output signal short-circuit proof V17111-13 ● V17111-6 _ _ ●
Type Signal Wire break Short-circuit Load
V17151-210 4...20 mA < 0.1 > 22 mA 23...30 mA 0...600 Ω
V17151-211 0...20 mA 0 > 22 mA 23...30 mA 0...600 Ω 0...05 mA
0...10 V
V17151-212 0...10 V 0 > 11 V – > 10 kΩ 0...20 mA
V17151-213 0... 5 mA 0 > 5.13 mA – 0...2.4 kΩ 19.2...30 V DC 4...20 mA

1 2 4 5 3 6
Input - + -
+
Input current 4...20 mA
Short circuit current 23...30 mA
Residual ripple (peak-to-peak) < 100 mV
Isolating power supply (terminal 14/15)
Supply voltage at 22.7 mA ≥ 14 V
Isolating driver (terminal 13/16) B
Voltage drop <1V A
J1
General data
LED indicators, power “On“ (green) gn
Isolation
Input – output/power supply 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply + - + -
Rated voltage 19.2...30 V DC 14 15 13 16
Power consumption 1.05 W 4...20 mA 4...20 mA
(14 V)
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

Functions of the plug-in jumpers J.:

J1 Wire break monitoring


A = without
B = with

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

37

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-21_
1 channel

Ordering information Catalog No.


Isolating Power supply, 1 channel V17151-21_
Output 4...20 mA 0
0...20 mA 1
0...10 V 2
0...5 mA 3

38

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-22_
1 channel, HART

■ Power supply for loop powered HART transmitters


■ Point to point communication
■ Wire break monitoring output overrange/underrange
(Jumper J1)

Module size 2
Module fits for:
Output Socket Backplane
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ❍
Residual ripple (peak-to-peak) < 0.25 % V17111-12 ● V17111-3 _ _ ●
Output signal short-circuit proof V17111-13 ● V17111-6 _ _ ❍
Type Signal Wire break Short-circuit Load
V17151-220 4...20 mA < 0.1 > 22 mA 23...30 mA 0...600 Ω
0...10 V
V17151-221 0...20 mA 0 > 22 mA 23...30 mA 0...600 Ω 0...20 mA
V17151-222 0...10 V 0 > 11 V – > 10 kΩ 19.2...30 V DC 4...20 mA
Communication FSK* FSK
via terminals 3/6 1 2 4 5 3 6
via mA signal + - + -
Permeable protocol HART
Bandwidth 500 Hz...10 kHz

Input
Input current 4...20 mA
Supply voltage at 22.7 mA ≥ 14 V B
Short circuit current 23...30 mA A
Residual ripple (peak-to-peak) < 100 mV J1

General data gn
LED indicators, power “On“ (green)
Isolation
Input – output/power supply/FSK 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g + -
Power supply 14 15
Rated voltage 19.2...30 V DC
4...20 mA
Power consumption 1.05 W (14 V)
Performance under reference conditions
FSK
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

Functions of the plug-in jumpers J.:

J1 Wire break monitoring


A = without
B = with

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

* FSK only at load ≥ 250 Ω

39

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-22_
1 channel, HART

Ordering information Catalog No.


Isolating Power Supply, 1 channel, HART V17151-22_
Output 4...20 mA 0
0...20 mA 1
0...10 V 2

40

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-320
1 channel, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
Residual ripple (peak-to-peak) < 0.25 % 19.2...30 V DC 4...20 mA
1.7 W
Communication 1 2 4 5 3
FSK
6
FSK (Bus)
7 8
via FSK bus (backplane/FSK bus amplifier) + - + -
via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz


- -
Input
Input current 4...20 mA
Supply voltage at 20/22 mA ≥ 15.5/14.8 V -
Short circuit current 23...28 mA + -

Residual ripple (peak-to-peak) < 100 mV 14 15

General data 4...20 mA


LED indicators, power “On“ (green) (15.5 V)
FSK
Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.7 W
Power dissipation 1.4 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

41

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-325
1 channel, HART

■ Power supply for loop powered HART transmitters


■ Galvanic isolation between input/output/power supply
and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Output Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 1.7 W FSK*

Communication 1 2 4 5 3 6

via mA signal + - + -

via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - -

Input
Input current 4...20 mA
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V
+ -
Short circuit current 23...28 mA
14 15
Residual ripple (peak-to-peak) < 100 mV

General data 4...20 mA


(15.5 V)
LED indicators, power “On“ (green) FSK

Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
* FSK only at load ≥ 250 Ω
Power consumption 1.7 W
Power dissipation 1.4 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

42

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-340
2 channels, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output per channel Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 3.1 W
FSK (Bus) FSK (Bus)
Communication per channel 1 2 4 5 7 8 3 6 9 10
via FSK bus (backplane/FSK bus amplifier) + - + - + -

via jacks 2 x 2 mm (front)


Permeable protocol HART gn
FSK 1 FSK 2

Bandwidth 500 Hz...10 kHz - - -

Input per channel


Input current 4...20 mA 1 2
1
- 2
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V -
+ + -
Short circuit current 23...28 mA
14 15 13 16
Residual ripple (peak-to-peak) < 100 mV

General data 4...20 mA


(15.5 V)
4...20 mA
(15.5 V)
LED indicators, power “On“ (green) FSK FSK

Isolation per channel


Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Channel 1
Isolation channel 1 – channel 2 Channel 2

Input 1 – input 2 500 V


Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 3.1 W
Power dissipation 2.45 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

43

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply V17151-350
2 outputs, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output output 1/output 2 Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 2.6 W FSK (bus)
Communication 1 2 4 5 7 8 3 6
+ - + - + -
via FSK bus (backplane/FSK bus amplifier)
via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - - -

Input
Input current 4...20 mA 1 2
1
- 2
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V
+ -
Short circuit current 23...28 mA
Residual ripple (peak-to-peak) < 100 mV 14 15

General data 4...20 mA


(15.5 V)
LED indicators, power “On“ (green) FSK
Isolation
Input – outp.1/outp. 2/power supply/FSK 2.3 kV
Output 1 – output 2 – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 2.6 W
Power dissipation 2.3 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

44

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Input Isolator V17151-413
2 channels

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ Low voltage drop

Module size 2
Module fits for:
Output per channel Socket Backplane
Output current (short-circuit proof) (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of overranging (input, approx.) > 23.6 mA, max. 40 mA V17111-13 ❍ V17111-6 _ _ ●
Load 0...750 Ω

Input per channel 0(4)...20 mA 0(4)...20 mA


Input current (0)4...20 mA 4 5 3 6
Overranging > 23.6 mA, max. 40 mA + - + -

General data
Voltage drop < 1.5 V
Isolation
Input – output 1.35 kV
Channel 1 – channel 2 500 V
Max. ambient temperature -20...+60 °C
Weight 90 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms
+ - + -

14 15 13 16
0(4)...20 mA 0(4)...20 mA

Channel 1 Channel 2

45

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator V17151-420
1 channel, HART, FSK bus

■ Input isolator for extra powered HART transmitters (Flowmeters)


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of overranging (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC
Residual ripple (peak-to-peak) < 0.25 % 4...20 mA
1.1 W
Communication 1 2 4 5 3
FSK
6
FSK (Bus)
7 8
via FSK bus (backplane/FSK bus amplifier) + - + -
via jacks 2 x 2 mm (front) mA

Permeable protocol HART FSK


gn
Bandwidth 500 Hz...10 kHz
- -
Input
Input current 4...20 mA
Voltage drop in input <3V -
+ -
General data 14 15
LED indicators, power “On“ (green)
Isolation
4...20 mA
Input – output/power supply/FSK 2.3 kV FSK
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

46

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator, parameterizable V17151-43_
1 channel V, mA

■ Input isolator for direct current or direct voltage signals


■ free adjustable measuring ranges
■ Definition of parameters via LCI interface
(does not require an additional power supply)
■ Relay output for alarm

Module size2
Module fits for:
Output (open and short-circuit proof) Socket Backplane
Type Full modulation span Load V17111-11 ● V17111-2 _ _ ●
V17151-430 0/4...20 mA (0/3.8...20,5 mA) 0...600 Ω V17111-12 ● V17111-3 _ _ ●
V17151-432 0/2...10 V (0/1.9...10.25 V) > 100 kΩ V17111-13 ● V17111-6 _ _ ●
V17151-433 0...5 mA (0...5.13 mA) 0...2.4 kΩ
V17151-434 0/1...5 V (0/0.95...5.13 V) > 50 kΩ
Residual ripple < 0.25 % (peak-to-peak) 0/4...20 mA
Damping 0...30 s 0...5 mA
0/2...10 V 250 V AC, 1 A
Binary output 19.2...30 V DC 0/1...5 V 30 V DC, 2 A
Triggering (adjustable via software) alarm set point, wire break 1 2 4 5 3 6 LKS
+ - + -
Relay contact (via jumper J1) 1 x NO/NC J1
Contact ratings 250VAC; 1A; cosϕ >0.7; 560 VA A B

30V DC; 2 A; 60 W
Parameterization via software gn
ro
or customer-specific
J2 µC
Input (open and short-circuit proof) µC
A/D
Sensors V, mA
Measuring ranges full modulat. span/load min. meas. span
-25...+25 mA/5 Ω 0.5 mA + - - +
-12.5...+12.5 V /> 100 kΩ 300 mV 14 15 11 12 16 13
Customer specific (max. tie points) 60
1)
General data +25 ...-25 mA
LED indicator power “On“ (green)
switching state relay (red)
2)
Isolation
Input – output/power supply 2.3 kV -12.5 ...+12.5 V
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply
Connection terminals 1(+); 2(-)
Rated voltage 19.2...30 V DC
Power consumption approx. 1.0 W Functions of the plug-in jumpers J.:

Performance under reference conditions J1 Relay output


A = NC
Linearity deviation < 0.1 % B = NO
Error limit < 0.1 % J2 Parameterization
Temperature effect < 0.1 %/10 K disable
Impedance effect < 0,05 % enable
Response time < 250 ms The positions illustrated on the circuit diagram
represent standard adjustments (delivery status)

47

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator, parameterizable V17151-43_
1 channel V, mA

Ordering information Catalog No.


Input Isolator, 1 channel, V, mA V17151-43_
Output 0/4...20 mA 0
0/2...10 V 2
0...5 mA 3
0/1...5 V 4
Accessories
Programming software (without customer-specified characteristic)* 7957781
LCI adapter 0317135

* with customer-specified characteristic use SMART VISION

48

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator, universal tion V17151-480
p r epara
on

■ Input isolator for direct current or direct


voltage signals
■ Setting of the input and output ranges
with DIP switches
■ Supply voltages from 20...253 V AC/DC

Module size 4
Module fits for:
Output Socket Backplane
Current 20 mA uni-/biploar; 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage 5 V, 10 V uni-/bipolar; V17111-12 ❍ V17111-3 _ _ ●
1...5 V, 2...10 V V17111-13 ❍ V17111-6 _ _ ●
Offset off output span of select -100%, -50%, 0 %, 50 %, 100%
Load at 20 mA ≤ 600 Ω
Load at 10 V ≥=1 kΩ 22...230 V AC/DC mA, V
Offset error < 20 µA/< 10 mV ± 10%
Residual ripple (effective) < 10 mV
1 2 4 5
+ -
Input
Measurement 0.1...100 mA; 20 mV...200 V
Measur. range ≤ 5 mA > 5 mA ≤ 500 mV > 500 mV
Input resistance approx. 100 Ω 5Ω 1 MΩ 1 MΩ gn

Overload ≤100 mA ≤ 300 mA ≤ 20 mA ≤ 3 mA


Adjustment range ZERO pot ± 25 % of the output range -
Adjustment range SPAN pot: 0.3...3.33 from the final value of the input range
Bandwidth < 10 kHz, < 10 Hz, adjustable
General data
LED indicator, power “On“ (green)
Isolation
-
Input – output 2.3 kV + + + -
Output – power supply 2.3 kV
Max. ambient temperature -20...+60 °C 11 12 14 15
Weight 120 g
Power supply
Rated voltage 20...253 V AC/DC > 5 mA
Power consumption 2 VA AC, 48...62 Hz, 0.9 W DC > 500 mV
Characteristics under reference conditions ≤ 500 mV, ≤ 5 mA
Error limit < 0.1 % from final value
Temperature effect < 60 ppm/K from final value
Settings DIP counter:
Output ranges, displacement and limit frequency/damping
Input ranges Output settings ❍ = default ● = on X = not used
Input settings ❍ = default ● = on X = not used Switch S1 S3
Switch S1 S2 Range 1-4 2 3 4 8-10 1 2 3
Range 1 2 3 4 5-10 1 2 3 4 5-10 0...±10 V X X ● ● X
0...±60 mV X ● X 2...10 V X ● X ● ● X
0...±100 mV ● X ● X 0...±5 V X ● X ● ● X
0...±150 mV ● X ● X 1...5 V X ● ● X ● ● X
0...±300 mV ● ● X ● X 0...±20 mA X ● X X
0...±500 mV ● X ● X ❍ 4...20 mA X ● ● X X
0...±1 V ● ● X ● ● X Switch S1 S2
0...±5 V ● ● X ● ● X Offset 1-7 8 9 10 1-3 4 5
0...±10 V ● ● ● X ● ● X ❍ 0% X X X ●
0...±100 V ● X ● ● X -100 % X ● X X ●
0...±0.3 mA ● ● X ● ● X -50 % X ● X X ●
0...±1 mA ● ● X ● ● X +50 % X ● ● X X ●
0...±5 mA ● ● ● X ● ● X +100 % X ● X X ●
0...±10 mA ● ● X ● ● X Variable with ZERO Pot: X X X X X X
0...±20 mA ● ● ● X ● ● X 0...±25% of span
0...±50 mA ● ● ● X ● ● X Switch S3
❍ 0...20 mA ● ● ● ● X ● ● X Bandwidth 1-2 3
Variable with SPAN Pot: X X X X X X X X X ❍ 10 kHz X
30...333% of sel. range 10 Hz X ●
49

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Supply Ex V17151-51
1 channel

■ Electrical isolation for current signals


with transmitter power supply

Module size 2
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 400 µA V17111-13 ❍ V17111-6 _ _ ●
Supply voltage 18.5...30 V

Input (hazardous area) 4...20 mA


(18.5...30 V)
Input current (short-circuit proof) 4...20 mA
4 5
Supply voltage > 13.5 V -
+
Short-circuit current 23...30 mA
Explosion protection [EEx ib] IIC
Certificate of conformity PTB No. 00 ATEX 2017
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 20 V
Max. power Po = 570 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 95 nF

General data
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Performance under reference conditions + -
Linearity deviation < 0.1 % 14 15
Error limit < 0.25 % 4...20 mA
Temperature effect < 0.1 %/10 K (≥ 13.5 V)
Impedance effect < 0.05 %
Response time < 50 ms

EEx ib
Hazardous area

50

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Supply Ex V17151-52
1 channel, HART

■ Electrical isolation for current signals with transmitter power


supply and HART communication
■ Point to point communication

Module size 2
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 400 µA V17111-13 ❍ V17111-6 _ _ ●
Supply voltage 18.5...30 V
Communication
via terminals 3/6 (Jumper J1 = A) 4...20 mA
(18.5...30 V)
via mA signal (Jumper J1 = B)
Permeable protocol HART FSK* FSK
Bandwidth 500 Hz...10 kHz 4 5 3 6
+ - FSK
Input (hazardous area)
Input current (short-circuit proof) 4...20 mA
Supply voltage > 13.2 V A
J1
Short-circuit current 23...30 mA B
Explosion protection [EEx ib] IIC

Certificate of conformity PTB No. 00 ATEX 2017


Max. short-circuit current Io < 28.5 mA
Max. voltage Uo < 20 V
Max. power Po < 570 mW
Permitted external inductance La < 1.3 mH
Permitted external capacitance Ca < 95 nF

General data + -
Isolation 14 15
Input – output/FSK 2.3 kV 4...20 mA
(> 13.2 V)
Max. ambient temperature -20...+60 °C
Weight 90 g FSK
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 % EEx ib
Response time < 50 ms Hazardous area

Functions of the plug-in jumpers J.:

J1 HART communication
A = via terminals 3/6 (delivery status)
B = via terminals 4/5

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

* FSK only at load ≥ 250 Ω

51

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
52

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-61_
1 channel

■ Power supply for loop powered transmitters


■ Isolating driver for 4...20 mA
■ Wire break monitoring output overrange/underrange
(Jumper J1)

Module size 2
Module fits for:
Output (safe area) Socket Backplane
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ●
Residual ripple (peak-to-peak) < 0.25 % V17111-12 ● V17111-3 _ _ ●
Output signal short-circuit proof V17111-13 ● V17111-6 _ _ ●
Type Signal Wire break Short-circuit Load
V17151-610 4...20 mA < 0.1 > 22 mA 23...30 mA 0...600 Ω
V17151-611 0...20 mA 0 > 22 mA 23...30 mA 0...600 Ω 0...05 mA
0...10 V
V17151-612 0...10 V 0 > 11 V – > 10 kΩ 0...20 mA
19.2...30 V DC 4...20 mA
V17151-613 0... 5 mA 0 > 5.13 mA – 0...2.4 kΩ
1 2 4 5 3 6
Input + - + -
(hazardous area)
Input current 4...20 mA
Short circuit current 23...28 mA
Residual ripple (peak-to-peak) < 100 mV
Isolating power supply (terminal 14/15)
Supply voltage at 22.7 mA ≥ 14 V B
Explosion protection [EEx ib] IIC A
Certificate of conformity PTB No. Ex-95.D.2188 X J1
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 20 V gn
Max. power Po = 570 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 95 nF
Isolating driver (terminal 13/16)
+ - + -
Voltage drop <1V
Explosion protection [EEx ib] IIC 14 15 13 16
4...20 mA, 4...20 mA
Max. short-circuit current Io = 28.5 mA (14 V)
Max. voltage Uo = 2.9 V
Max. power Po = 82.6 mW

General data
LED indicators, power “On“ (green)
EEx ib
Isolation
Input – output/power supply 2.3 kV Hazardous area
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.05 W Functions of the plug-in jumpers J.:
Performance under reference conditions J1 wire break monitoring
Linearity deviation < 0.1 % A = without
Error limit < 0.25 % B = with
Temperature effect < 0.1 %/10 K The positions illustrated on the circuit diagram
Impedance effect < 0.05 % represent standard adjustments (delivery status)
Response time < 50 ms

53

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-61_
1 channel

Ordering information Catalog No.


Isolating Power Supply Ex, 1 channel V17151-61_
Output 4...20 mA 0
0...20 mA 1
0...10 V 2
0...5 mA 3

54

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-62_
1 channel, HART

■ Power supply for loop powered HART transmitters


■ Point to point communication
■ Wire break monitoring output overrange/underrange
(Jumper J1)

Module size 2
Module fits for:
Output (safe area) Socket Backplane
Transformation ratio 1:1 V17111-11 ● V17111-2 _ _ ●
Residual ripple (peak-to-peak) < 0.25 % V17111-12 ● V17111-3 _ _ ●
Output signal short-circuit proof V17111-13 ● V17111-6 _ _ ●
Type Signal Wire break Short-circuit Load
V17151-620 4...20 mA < 0.1 > 22 mA 23...30 mA 0...600 Ω
V17151-621 0...20 mA 0 > 22 mA 23...30 mA 0...600 Ω 0...10 V
0...20 mA
V17151-622 0...10 V 0 > 11 V – > 10 kΩ 19.2...30 V DC 4...20 mA
Communication
FSK* FSK
via terminals 3/6
via mA signal 1 2 4 5 3 6
Permeable protocol HART + - + -
Bandwidth 500 Hz...10 kHz

Input (hazardous area)


Input current 4...20 mA
Supply voltage at 22.7 mA ≥ 14 V B
Short circuit current 23...28 mA A
Residual ripple (peak-to-peak) < 100 mV J1
Explosion protection [EEx ib] IIC
Certificate of conformity PTB No. Ex-95.D.2188 X gn
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 20 V
Max. power Po = 570 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 95 nF + -
14 15
General data 4...20 mA
(14 V)
LED indicators, power “On“ (green)
FSK
Isolation
Input – output/power supply/FSK 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply EEx ib

Rated voltage 19.2...30 V DC Hazardous area


Power consumption 1.05 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Functions of the plug-in jumpers J.:
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 % J1 wire break monitoring
Response time < 50 ms A = without
B = with

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)

* FSK only at load ≥ 250 Ω (4...20 mA)

55

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-62_
1 channel, HART

Ordering information Catalog No.


Isolating Power Supply Ex, 1 channel, HART V17151-62_
Output 4...20 mA 0
0...20 mA 1
0...10 V 2

56

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-720
1 channel, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 1.7 W
FSK FSK (Bus)
Communication 1 2 4 5 3 6 7 8

via FSK bus (backplane/FSK bus amplifier) + - + -

via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - -

Input (hazardous area)


Input current 4...20 mA -
Supply voltage at 20/22 mA ≥ 15.5/14.8 V -
+
Short circuit current 23...28 mA
14 15
Residual ripple (peak-to-peak) < 100 mV
Explosion protection [EEx ia] IIC
4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X (15,5 V)
Max. short-circuit current Io = 93 mA FSK

Max. voltage Uo = 26.3 V


Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
EEx ia
Permitted external capacitance Ca = 97 nF
Hazardous area
General data
LED indicators, power “On“ (green)
Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.7 W
Power dissipation 1.4 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

57

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-725
1 channel, HART

■ Power supply for loop powered HART transmitters


■ Galvanic isolation between input/output/power supply
and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 1.7 W FSK*

Communication 1 2 4 5 3 6

via mA signal + - + -

via testjacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - -

Input (hazardous area)


Input current 4...20 mA -
Supply voltage at 20/22 mA ≥ 15.5/14.8 V + -
Short circuit current 23...28 mA
14 15
Residual ripple (peak-to-peak) < 100 mV
Explosion protection [EEx ia] IIC
4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X (15.5 V)
Max. short-circuit current Io = 93 mA FSK

Max. voltage Uo = 26.3 V


Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
EEx ia
Permitted external capacitance Ca = 97 nF
Hazardous area
General data
LED indicators, power “On“ (green)
Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
* FSK only at load ≥ 250 Ω
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.7 W
Power dissipation 1.4 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

58

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-740
2 channels, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output per channel (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 3.1 W
FSK (Bus) FSK (Bus)
Communication per channel 1 2 4 5 7 8 3 6 9 10
+
via FSK bus (backplane/FSK bus amplifier) + - - + -

via jacks 2 x 2 mm (front)


Permeable protocol HART gn
FSK 1 FSK 2

Bandwidth 500 Hz...10 kHz - - -

Input per channel (hazardous area)


1 2
Input current 4...20 mA 1
- 2
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V + - + -
Short circuit current 23...28 mA
14 15 13 16
Residual ripple (peak-to-peak) < 100 mV
Explosion protection [EEx ia] IIC
4...20 mA 4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X (15.5 V) (15.5 V)
FSK
Max. short-circuit current Io = 93 mA FSK

Max. voltage Uo = 26.3 V


Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
EEx ia EEx ia
Permitted external capacitance Ca = 97 nF
Hazardous area Channel 1 Channel 2
General data
LED indicators, power “On“ (green)
Isolation per channel
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Isolation channel 1 – channel 2
Input 1 – input 2 500 V
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 3.1 W
Power dissipation 2.45 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

59

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-745
2 channels, HART

■ Power supply for loop powered HART transmitters


■ Galvanic isolation between input/output/power supply
and HART
■ Jacks for HART communication

Module size 4
Module fits for:
Output per channel (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 3.1 W FSK* FSK*

Communication per channel 1 2 4 5 3 6

via mA signal + - + - + -

via jacks 2 x 2 mm (front)


Permeable protocol HART gn
FSK 1 FSK 2

Bandwidth 500 Hz...10 kHz - - -

Input per channel (hazardous area)


Input current 4...20 mA 1 2
-
1 2
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V
+ - + -
Short circuit current 23...28 mA
14 15 13 16
Residual ripple (peak-to-peak) < 100 mV
Explosion protection [EEx ia] IIC
4...20 mA 4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X (15.5 V) (15.5 V)
Max. short-circuit current Io = 93 mA FSK FSK

Max. voltage Uo = 26.3 V


Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
EEx ia EEx ia
Permitted external capacitance Ca = 97 nF
Hazardous area Channel 1 Channel 2
General data
LED indicators, power “On“ (green)
Isolation per channel
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
* FSK only at load ≥ 250 Ω
Isolation channel 1 – channel 2
Input 1 – input 2 500 V
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 3.1 W
Power dissipation 2.45 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

60

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-750
2 outputs, HART, FSK bus

■ Power supply for loop powered HART transmitters


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output output 1/output 2 (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
Output 1
Residual ripple (peak-to-peak) < 0.25 % 19.2...30 V DC 4...20 mA
Output 2
4...20 mA
Communication 2.6 W
FSK (Bus)
via FSK bus (backplane/FSK bus amplifier) 1 2 4 5 7 8 3 6
+ - + - + -
via jacks 2 x 2 mm (front)
mA
Permeable protocol HART
FSK 1
Bandwidth 500 Hz...10 kHz gn

- - -
Input (hazardous area)
Input current 4...20 mA
1 2
Supply voltage at 20/22 mA ≥ 15.5/14.8 V 1
- 2
-
Short circuit current 23...28 mA + -

Residual ripple (peak-to-peak) < 100 mV 14 15


Explosion protection [EEx ia] IIC
Certificate of conformity PTB 98 ATEX 2183 X 4...20 mA
Max. short-circuit current Io = 93 mA (15.5 V)
FSK
Max. voltage Uo = 26.3 V
Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
Permitted external capacitance Ca = 97 nF EEx ia

General data Hazardous area

LED indicators, power “On“ (green)


Isolation
Input – outp. 1/outp. 2/power supply/FSK 2.3 kV
Output 1 – output 2 – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 2.6 W
Power dissipation 2.3 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

61

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Power Supply Ex V17151-755
2 outputs, HART

■ Power supply for loop powered HART transmitters


■ Galvanic isolation between input/output/power supply
and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Output output 1/output 2 (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 2.6 W FSK* FSK*
Communication 1 2 4 5 3 6
via mA signal + - + - + -

via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - - -

Input (hazardous area)


Input current 4...20 mA 1 2
1
- 2
-
Supply voltage at 20/22 mA ≥ 15.5/14.8 V
+ -
Short circuit current 23...28 mA
14 15
Residual ripple (peak-to-peak) < 100 mV
Explosion protection [EEx ia] IIC
Certificate of conformity PTB 98 ATEX 2183 X 4...20 mA
(15.5 V)
Max. short-circuit current Io = 93 mA FSK

Max. voltage Uo = 26.3 V


Max. power Po = 610 mW
Permitted external inductance La = 4.1 mH
EEx ia
Permitted external capacitance Ca = 97 nF
Hazardous area
General data
LED indicators, power “On“ (green)
Isolation
Input – outp. 1/outp. 2/power supply/FSK 2.3 kV
Output 1 – output 2 – power supply – FSK 500 V
* FSK only at load ≥ 250 Ω
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 2.6 W
Power dissipation 2.3 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

62

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator Ex V17151-820
1 channel, HART, FSK bus

■ Input isolator for extra powered HART transmitters (Flowmeters)


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC
Residual ripple (peak-to-peak) < 0.25 % 1.1 W
4...20 mA

FSK
Communication 1 2 4 5 3 6
FSK (Bus)
7 8
via FSK bus (backplane/FSK bus amplifier) + - + -

via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz - -

Input (hazardous area)


Input current 4...20 mA
-
Voltage drop in input <3V
+ -
Explosion protection [EEx ia] IIC
14 15
Certificate of conformity PTB 98 ATEX 2183 X
Max. short-circuit current Io = 30.5 mA
Max. voltage Uo = 2.9 V 4...20 mA
FSK
Max. power Po = 22.1 mW

General data
LED indicators, power “On“ (green)
EEx ia
Isolation
Input – output/power supply/FSK 2.3 kV Hazardous area
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

63

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator Ex V17151-825
1 channel, HART

■ Input isolator for extra powered HART transmitters


(Flowmeters)
■ Galvanic isolation between input/output/power supply
and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Output (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
Residual ripple (peak-to-peak) < 0.25 % 19.2...30 V DC 4...20 mA
FSK*
1.1 W
Communication 1 2 4 5 3 6
via mA signal + - + -

via jacks 2 x 2 mm (front) mA

Permeable protocol HART gn


FSK

Bandwidth 500 Hz...10 kHz


- -
Input (hazardous area)
Input current 4...20 mA
-
Short circuit current 23...28 mA
+ -
Residual ripple (peak-to-peak) < 100 mV
Voltage drop in input <3V 14 15

Explosion protection [EEx ia] IIC


Certificate of conformity PTB 98 ATEX 2183 X 4...20 mA
FSK
Max. short-circuit current Io = 30.5 mA
Max. voltage Uo = 2.9 V
Max. power Po = 22.1 mW

General data EEx ia

LED indicators, power “On“ (green)


Hazardous area
Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
* FSK only at load ≥ 250 Ω
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

64

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator Ex V17151-840
2 channels, HART, FSK bus

■ Input isolator for extra powered HART transmitters (Flowmeters)


■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication
■ Output signal free of HART signal

Module size 4
Module fits for:
Output per channel (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 1.9 W
FSK (Bus) FSK (Bus)
Communication per channel 1 2 4 5 7 8 3 6 9 10

via FSK bus (backplane/FSK bus amplifier) + - + - + -

via jacks 2 x 2 mm (front)


Permeable protocol HART gn
FSK 1 FSK 2

Bandwidth 500 Hz...10 kHz - - -

Input per channel (hazardous area)


1 2
Input current 4...20 mA 1
- 2
-
Short circuit current 23...28 mA + - -
+
Residual ripple (peak-to-peak) < 100 mV
14 15 13 16
Voltage drop in input <3V
Explosion protection [EEx ia] IIC
4...20 mA 4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X FSK FSK
Max. short-circuit current Io = 30.5 mA
Max. voltage Uo = 2.9 V
Max. power Po = 22.1 mW

General data EEx ia EEx ia

LED indicators, power “On“ (green) Hazardous area Channel 1 Channel 2


Isolation per channel
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Isolation channel 1 – channel 2
Input 1 – input 2 500 V
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.9 W
Power dissipation 1.9 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

65

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Input Isolator Ex V17151-845
2 channels, HART

■ Input isolator for extra powered HART transmitters


(Flowmeters)
■ Galvanic isolation between input/output/power supply
and HART
■ Jacks for HART communication

Module size 4
Module fits for:
Output per channel (safe area) Socket Backplane
Output current (short-circuit proof) 4...20 mA V17111-11 ● V17111-2 _ _ ●
Transformation ratio 1:1 V17111-12 ❍ V17111-3 _ _ ●
Detect. of wire break (input) < 0.1 mA V17111-13 ❍ V17111-6 _ _ ●
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω
19.2...30 V DC 4...20 mA 4...20 mA
Residual ripple (peak-to-peak) < 0.25 % 1.9 W FSK* FSK*

Communication per channel 1 2 4 5 3 6

via mA signal + - + - + -

via jacks 2 x 2 mm (front)


Permeable protocol HART gn
FSK FSK

Bandwidth 500 Hz...10 kHz - - -

Input per channel (hazardous area)


Input current 4...20 mA 1 2
-
1 2
-
Short circuit current 23...28 mA
+ - + -
Residual ripple (peak-to-peak) < 100 mV
14 15 13 16
Voltage drop in input <3V
Explosion protection [EEx ia] IIC
4...20 mA 4...20 mA
Certificate of conformity PTB 98 ATEX 2183 X FSK FSK
Max. short-circuit current Io = 30.5 mA
Max. voltage Uo = 2.9 V
Max. power Po = 22.1 mW

General data EEx ia EEx ia

LED indicators, power “On“ (green) Hazardous area Channel 1 Channel 2


Isolation per channel
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Isolation channel 1 – channel 2
Input 1 – input 2 500 V
* FSK only at load ≥ 250 Ω
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.9 W
Power dissipation 1.9 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

66

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Analog Modules

Transmitter

Intelligent Transmitter 1 channel, LCI V17152-31_

Temperature Transmitter Ex 1 channel, Pt 100 V17152-61_

Intelligent Transmitter Ex 1 channel, LCI V17152-62_

12.00 67
Analog Modules

%
 ",3 ",3
            
            
               
            
            
 
   

        
    
       
    
   
D
          
         
 
 !"#             
 !"$#             
 !"#        
07 
%! &        
'!        
'!        
(         
            
)              
*         
/2
%+%&","-"."/"*""0"%"1        
+ &2        
0             
%& 
"        
,3&&  4,,3566+74,,38566+         
D
98:        
0!          
;"$ +             
)# &&
;$ +             
,    6&  & 7&# &&             
 ' & &# &&             
 )8 )+#        
 3     
D 
 )+#        
    
 <  "0 :             
<  "0 :#!&# &&7             
<  $"0 :#!&# &&$7             
< ==" :&>#             
< $==" :& ?#             
< ?==" :& #             
3@:AB@#! <  $AC@#! <  " $

68 12.00
Intelligent Transmitter V17152-31_
1 channel, LCI

■ Programmable temperature transmitter for resistance


thermometer (RTD) and thermocouples
■ Definition of parameters via LCI interface
(does not require an additional power supply)
■ Relay output for alarm
■ Monitoring of short-circuit, wire break
and internal failure
■ Output at failure under- and overrange, custom
current level
Module size 4
Module fits for:
Output Socket Backplane
Type full modulation span load V17111-11 ● V17111-2 _ _ ●
V17152-310 0/4...20 mA (0/3.8...20.5 mA) 0...600 Ω V17111-12 ● V17111-3 _ _ ●
V17152-312 0/2...10 V (0/1.9...10.25 V) > 100 kΩ V17111-13 ● V17111-6 _ _ ●
V17152-313 0...5 mA (0...5.13 mA) 0...2,4 kΩ 0/4...20 mA
0...5 mA
V17152-314 0/1...5 V (0/0.95...5.13 V) > 50 kΩ 0/2...10 V 250 V AC, 1 A
Output at failure under- and overranging, custom current level 19.2...30 V DC 0/1...5 V 30 V DC, 2 A
1 2 4 5 3 6 LKS
Residual ripple (peak-to-peak) < 0.25 % + - + -
Damping 0...30 s J1
A B
Binary output (relay)
Trigger condition alarm set-point, wire break, short-circuit, gn
device failure (adjustment via software) rt

Relay contact 1 x NO/NC (adj. via jumper J1)


J2 µC
Contact rating: 250VAC; 1A; cosϕ > 0.7; 560 VA; 30V DC; 2 A; 60 W µC
A/D
Parameter setting via software or set by manufacturer
Acc. for parameter setting PC with software
LCI adapter (connection to PC)
14 15 11 12 16 13
Input 1)
ϑ
Sensors Resist. thermometers (2-,3-,4 wire circuit) 2)
Thermocouples with/without ref. junction ϑ
3)
Resistance teletransmitters, Ω, mV inputs ϑ1 ϑ2
Measuring methods Single, differential, average 4)
Measuring ranges full modulation span min. meas. span - + ϑ
5) TC VG
-200...+850 °C (Pt 100) 20 K ϑ
-200...+850 °C (Pt 100 diff.) 40 K - + - +
0...500 Ω; 0...5 kΩ 5 Ω; 50 Ω 6)

±125 mV; -125...+1250 mV 2 mV; 20 mV TC1 TC2


- +
Linearization acc. to DIN IEC RTD - Pt 100, Pt 1000, Ni 100; 7)
TC - B, E, J, K, L, N, R, S, T, U
Customer specific (max. 60 tiepoints) Functions of the plug-in jumpers J.:
J1 Relay output
General data A = NO contact; B = NC contact
LED indicator: Power “On“ (green); “Failure“/“Switching State Relay“ (red) J2 Parameter setting interlock
Isolation closed = inactive
open (parked) = active
Input – output/power supply 2.3 kV The positions illustrated on the circuit diagram
Max. ambient temperature -20...+60 °C represented standard adjustments (delivery status)
Weight 90 g VG Reference junction Catalog No. 0317093
Power supply LKS Local Communication Interface
1) Resistance thermometers, Ω sensor in 4-wire circuit
Rated voltage 19.2...30 V DC 2) Resistance thermometers, Ω sensor in 3-wire circuit
Power consumption approx. 1.0 W 3) Resistance thermometers, Ω sensor in diff./average
4) Resistance thermometers, Ω sensor in 2-wire circuit
Characteristics under reference conditions
5) Thermocouple with internal reference junction
Linearity deviation < 0.1 % 6) Thermocouple, mV sensor in difference/average
Error limit < 0.2 K/< 0.2 % / < 80 mΩ (0...500 Ω) (without reference junction short-circuit to terminals 11/12)
7) mV sensor
< 0.2 K/< 0.2 % / < 0.8 Ω (0...5 kΩ)
< 0.2 K/< 0.2 % / < 10 µV (-125...+125 mV) Standard parameter setting:
(delivery status, if no customer specifications)
< 100 µV/<0.2 % / (-125...+1250 V) Sensor: Pt 100, 3-wire circuit
Additional error through ref. junction: 0.5 K Measuring method: single
Measuring range: 0...100 °C
Temperature effect < 0.1 %/10 K (at < -5 °C 0.25%/10 K) Output: acc. to type 4...20 mA, 0...5 mA, 0...10 V, 0...5 V
Impedance effect < 0.05 % Output at failure: overranging
Response time < 250 ms (TC), < 500 ms (RTD) Binary output: sensor error
69

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Intelligent Transmitter V17152-31_
1 channel, LCI

Ordering information Catalog No.


Intelligent Transmitter, 1 channel, LCI V17152-31_
Output 0/4...20 mA 0
0/2...10 V 2
0...5 mA 3
0/1...5 V 4
Accessories
Internal reference junction (Pt 100) 0317093
Parameter definition software (without customer-specific characteristic)* 7957781
LCI adapter 0317135

Notes:
The internal reference junction is not included and has to be ordered
separately. The termination of the reference junction according to the
connection diagram.

* with customer-specific characteristic use SMART VISION

70

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Temperature Transmitter Ex V17152-61_
Pt 100, 1 channel

■ Connection of resistance thermometer Pt 100


■ Input [EEx ia] IIC
■ Line break monitoring, rise or drop

Module size 2
Module fits for:
Output Socket Backplane
Connection Terminals 4(+); 5(-) V17111-11 ● V17111-2 _ _ ●
Output current 4...20 mA, temperature linear V17111-12 ● V17111-3 _ _ ●
(optional 0...20 mA, 0...10 V)1) V17111-13 ● V17111-6 _ _ ●
Wire break at input > 22 mA/< 3,6 mA (rise/drop)
Load 0...600 Ω
Residual ripple < 0,25 % 19.2...30 VDC 4...20mA
(peak-to-peak – parasitic voltage at input) 1 2 4 5
+ - + -
Output
Connection Terminals 12, 13, 14, 15
for resistance thermometer Pt 100
Input circuit 2-, 3-wire circuit
Line resistance 0 Ω for 2-wire circuit
(10 Ω for ext. line balancing optional)
Measurement start -100 °C
Max. measuring range -100...+850 °C
gn
Min. measuring span 60 °C
Explosion protection [EEx ia] IIC
A B
Certificate of conformity PTB No. Ex-97.D.2030 X J1
J2
Max. short-circuit current Io = 19 mA
Max. voltage Uo = 20 V
Max. capacity Po = 95 mW
Permitted external inductance La = 75 mH
Permitted external capacitance Ca = 140 nF 13 14 12 15 11

General data
Display green LED – power “On“
Test voltage 2.3 kV input – output/power supply
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply
Connection Terminals 1(+); 2(-)
Inputs [EEx ia] IIC
Rated voltage 19.2...30 V DC
Power consumption approx. 1.0 W Hazardous area
Characteristics under reference conditions
Linearity deviation < 0.1 %
Measurement deviation < 0.5 %
Temperature effect < 0.1 %/10 K for -5...+60 °C
Functions of the plug-in jumpers J.:
< 0.2 %/10 K for -20...-5 °C
Load effect < 0.05 % in load range 0...600 Ω J1/J2 Wire break monitoring
A = output signal, rise
Response time < 350 ms B = output signal, drop

The positions illustrated on the circuit diagram


represented standard adjustments (delivery status)

71

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Temperature Transmitter Ex V17152-61_
Pt 100, 1 channel

Ordering information Catalog No.


Temperature Transmitter Ex, Pt 100, 1 channel V17152-61_
Meas. range 0... 60 °C, 3-wire, 4...20 mA 1
0...100 °C, 3-wire, 4...20 mA 2
0...150 °C, 3-wire, 4...20 mA 3
0...200 °C, 3-wire, 4...20 mA 4
.......2) 9
2) Example: 100...200 °C/2-wire/0...20 mA

72

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Intelligent Transmitter Ex V17152-62_
1 channel, LCI

■ Programmable temperature transmitter for resistance


thermometer (RTD) and thermocouples
■ Definition of parameters via LCI interface
(does not require an additional power supply)
■ Relay output for alarm
■ Monitoring of short-circuit, wire break
and internal failure

Module size 4
Output Module fits for:
Type full modulation span load Socket Backplane
V17152-620 0/4...20 mA (0/3.8...20.5 mA) 0...600 Ω V17111-11 ● V17111-2 _ _ ●
V17152-622 0/2...10 V (0/1.9...10.25 V) > 100 kΩ V17111-12 ● V17111-3 _ _ ●
V17152-623 0...5 mA (0...5.13 mA) 0...2,4 kΩ V17111-13 ● V17111-6 _ _ ●
V17152-624 0/1...5 V (0/0.95...5.13 V) > 50 kΩ 0/4...20 mA
0...5 mA
Output at failure under- and overranging, custom current level 0/2...10 V 250 V AC, 1 A
Residual ripple (peak-to-peak) < 0.25 % 19.2...30 V DC 0/1...5 V 30 V DC, 2 A
1 2 4 5 3 6 LKS
Damping 0...30 s + - + -
Binary output (relay) A B
J1

Trigger condition: alarm set-point, wire break, short-circuit, device failure


Relay contact 1 x NO/NC (adj. via jumper J1) gn
Contact rating: 250VAC; 1A; cosϕ > 0.7; 560 VA; 30V DC; 2 A; 60 W rd
Input µC
J2
Sensors Resist. thermometers (2-,3-,4 wire circuit) µC
A/D
Thermocouples with/without ref. junction
Resistance teletransmitters, Ω, mV inputs
Measuring methods Single, differential, average
Measuring ranges full modulation span min. meas. span 14 15 11 12 16 13

-200...+850 °C (Pt 100) 20 K 1)


ϑ
-200...+850 °C (Pt 100 diff.) 40 K 2)
0...500 Ω; 0...5 kΩ 5 Ω; 50 Ω ϑ
3)
±125 mV; -125...+1250 mV 2 mV; 20 mV
ϑ1 ϑ2
Linearization acc. to DIN IEC RTD - Pt 100, Pt 1000, Ni 100; 4)
TC - B, E, J, K, L, N, R, S, T, U - + ϑ

Customer specific (max. 60 tiepoints) 5) TC VG


ϑ
Explosion protection [EEx ia] IIC - + - +
Certificate of conformity PTB 99 ATEX 2013 X 6)
Max. short-circuit current Io = 2 mA TC1 TC2
- +
Max. voltage Uo = 5,4 V 7)
Hazardous area
Max. power Po = 2 mW
Permitted external inductance La = 5 mH Functions of the plug-in jumpers J.:
J1 Relay output
Permitted external capacitance Ca = 1650 nF A = NO contact; B = NC contact
General data J2 Parameter setting interlock
LED indicator: power “On“ (green)/“Failure“/“Switching State Relay“ (red) closed = inactive
open (parked) = active
Isolation The positions illustrated on the circuit diagram
Input – output/power supply/FSK 2.3 kV represented standard adjustments (delivery status)
Max. ambient temperature -20...+60 °C VG Reference junction Catalog No. 0317093
Weight 90 g LKS Local Communication Interface
1) Resistance thermometers, Ω sensor in 4-wire circuit
Power supply 2) Resistance thermometers, Ω sensor in 3-wire circuit
Rated voltage 19.2...30 V DC 3) Resistance thermometers, Ω sensor in diff./average
4) Resistance thermometers, Ω sensor in 2-wire circuit
Power consumption approx. 1.0 W
5) Thermocouple with internal reference junction*
Characteristics under reference conditions 6) Thermocouple, mV sensor in difference/average
Linearity deviation < 0.1 % (without reference junction short-circuit to terminals 11/12)
7) mV sensor
Error limit < 0.2 K/< 0.2 % / < 80 mΩ (0...500 Ω)
(additional error through < 0.2 K/< 0.2 % / < 0.8 Ω (0...5 kΩ) Standard parameter setting:
(delivery status, if no customer specifications)
reference junction: 0.5 K) < 0.2 K/< 0.2 % / < 10 µV (-125...+125 mV) Sensor: Pt 100, 3-wire circuit
< 100 µV/<0.2 % / (-125...+1250 V) Measuring method: single
Measuring range: 0...100 °C
Temperature effect < 0.1 %/10 K (at < -5 °C 0.25%/10 K) Output: acc. to type 4...20 mA, 0...5 mA, 0...10 V, 0...5 V
Impedance effect < 0.05 % Output at failure: overranging
Response time < 250 ms (TC), < 500 ms (RTD) Binary output: sensor error
73

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Intelligent Transmitter Ex V17152-62_
1 channel, LCI

Ordering information Catalog No.


Intelligent Transmitter Ex, 1 channel, LCI V17152-62_
Output 0/4...20 mA 0
0/2...10 V 2
0...5 mA 3
0/1...5 V 4
Accessories
Internal reference junction (Pt 100) 0317093
Parameter definition software (without customer-specific characteristic)* 7957781
LCI adapter 0317135

Note:
The internal reference junction is not included and has to be ordered
separately. The termination of the reference junction according to the
connection diagram.
* with customer-specific characteristic use SMART VISION

74

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Analog Modules

Output Isolators

Loop Powered Isolator 1 channel V17153-11

Loop Powered Isolator 1 channel, bypass V17153-115

Loop Powered Isolator 2 channels V17153-13

Isolating Driver 1 channel V17153-21

Isolating Driver 1 channel, HART V17153-22

Isolating Driver 1 channel, HART, FSK bus V17153-420

Loop Powered Isolator Ex 1 channel V17153-51

Loop Powered Isolator Ex 1 channel, bypass V17153-515

Loop Powered Isolator Ex 1 channel, HART V17153-52

Isolating Driver Ex 1 channel V17153-61

Isolating Driver Ex 1 channel, HART V17153-62

Isolating Driver Ex 1 channel, HART, FSK bus V17153-820

Isolating Driver Ex 1 channel, HART V17153-825

Isolating Driver Ex 2 channels, HART, FSK bus V17153-840

Isolating Driver Ex 2 channels, HART V17153-845

12.00 75
Analog Modules

A 
)   A  @
@ )  @ ?%&
@ ?  %&
 
              
              
                 
              
              
 
       
  
               

              
    
       
   
 
     
                
  * 
 !"#$        
%&      '%%& ())*'%%& +())         
,-./01         
4 
-22/0    
 3  *                 
%  ?  ) 3           
  )  $3     
,3  
 4       3!"#$      
   
 3  !"#$   
    
# >6
       
  
0,5,,,3,,.6               
0,5,,,3,.6    *    
0,5,,,3,/.6    /*    
0,5,,,377.6 8               
0,5,,,3/77.6 ,9               
0,5,,,3977.6 ,               
&:6;<: 0,5,,,3,/;=: 0,5,,,3,.3,/

76 12.00
Loop Powered Isolator V17153-11
1 channel

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ Low voltage drop

Module size 1
Module fits for:
Input Socket Backplane
Input current (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 23.6 mA, max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
V17111-13 ❍ V17111-6 _ _ ●
Output
Output current (short-circuit proof) (0)4...20 mA
Transformation ratio 1:1 0(4)...20 mA

Detect. of overranging (input, approx.) > 23.6 mA, max. 40 mA 4 5


Load 0...750 Ω + -

General data
Voltage drop < 1.5 V
Isolation
Input – output 1.35 kV1)
Max. ambient temperature -20...+60 °C
Weight 40 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms
1) Rating voltage 50 V acc. to DIN EN 61010 + -

14 15
0(4)...20 mA

I
P

77

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Isolator V17153-115
1 channel, bypass

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ At a wire-break in the output signal,
the input signal does not interrupt

Module size 2
Module fits for:
Input Socket Backplane
Input current (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 22 mA, max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
V17111-13 ❍ V17111-6 _ _ ●
Output
Output current (short-circuit proof) (0)4...20 mA 0(4)...20 mA
Transformation ratio 1:1 < 15.8 V (≤ 6.5 V, RB = ∞)
Detect. of overranging (input, approx.) 22...28,5 mA 4 5
Load 0...600 Ω + -

General data
Voltage drop < 3.8 V/< 6.8 V load
160...600/0...160 Ω
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms
+ -

14 15
0(4)...20 mA

I
P

78

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Isolator V17153-13
2 channels

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ Low voltage drop

Module size 2
Module fits for:
Input per channel Socket Backplane
Input current (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 23.6 mA, max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
V17111-13 ❍ V17111-6 _ _ ●
Output per channel
Output current (short-circuit proof) (0)4...20 mA
Transformation ratio 1:1 0(4)...20 mA 0(4)...20 mA
Detect. of overranging (input, approx.) > 23.6 mA, max. 40 mA 4 5 3 6
Load 0...750 Ω + - + -

General data
Voltage drop < 1.5 V
Isolation
Input – output 1.35 kV1)
Channel 1 – channel 2 500 V
Max. ambient temperature -20...+60 °C
Weight 90 g
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms
+ - + -
1) Rating voltage 50 V acc. to DIN EN 61010
14 15 13 16
0(4)...20 mA 0(4)...20 mA

I I
P P
Channel 1 Channel 2

79

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver V17153-21
1 channel

■ Isolating driver for I/P converter


■ Minimal power consumption

Module size 2
Module fits for:
Input Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 1.5 V V17111-12 ● V17111-3 _ _ ●
V17111-13 ● V17111-6 _ _ ●
Output
Output current (short-circuit proof) 4...20 mA
Transformation ratio 1:1 4...20 mA
19.2...30 V DC
Detect. of wire-break (input) < 0.1 mA
Detect. of overranging (input, approx.) 22...30 mA 1 2 4 5 3 6
Load 0...600 Ω + - + -
Residual ripple (peak-to-peak) < 0.25 %

General data
LED indicators, power “On“ (green)
Isolation
Output – input/power supply 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply
Rated voltage 19.2...30 V DC gn
Power consumption 0.7 W
Power dissipation 0.7 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 % + -
Temperature effect < 0.1 %/10 K 14 15
Impedance effect < 0.1 % 4...20 mA
Response time < 50 ms

I
P

80

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver V17153-22
1 channel, HART

■ Isolating driver for I/P converter with HART communication


■ Point to point communication
■ Minimal power consumption

Module size 2
Module fits for:
Input Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 1.5 V; < 6.5 V (if source V17111-12 ● V17111-3 _ _ ●
not HART-kompatible) V17111-13 ● V17111-6 _ _ ●
Communication
via terminals 3/6
via mA signal FSK FSK
Permeable protocol HART 19.2...30 V DC 4...20 mA
Bandwidth 500 Hz...10 kHz 1 2 4 5 3 6
+ - + -
Output
Output current (short-circuit proof) 4...20 mA
J1
Transformation ratio 1:1 A
R B
Detect. of wire-break (input) < 0.1 mA
Detect of overranging (input, approx.) 22...30 mA
Load 0...600 Ω
Residual ripple (peak-to-peak) < 0.25 %

General data
LED indicators, power “On“ (green) gn
Isolation
Output – input/power supply/FSK 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply + -
Rated voltage 19.2...30 V DC
Power consumption 0.7 W 14 15
4...20 mA
Power dissipation 0.7 W
Performance under reference conditions FSK
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K I
Impedance effect < 0.1 % P
Response time < 50 ms

Functions of the plug-in jumpers J.:


J1 Minimum impedance for HHT to terminals 3/6
A = Ui <1.5 V
(Source to terminal 4/5 HART-compatible)
B = Ui < 6.5 V
(Source to terminal 4/5 not HART-compatible)

The positions illustrated on the circuit diagram


represented standard adjustments (delivery status)

81

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver V17153-420
1 channel, HART, FSK bus

■ Isolating driver for I/P converter, positioner with HART-


communication
■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Input Socket Backplane
Input current 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Voltage drop < 6.9 V V17111-12 ❍ V17111-3 _ _ ●
Communication V17111-13 ❍ V17111-6 _ _ ●
via FSK bus (backplane/FSK bus amplifier)
via jacks 2 x 2 mm (front)
19.2...30 V DC 4...20 mA
Permeable protocol HART 1.1 W FSK*
Bandwidth 500 Hz...10 kHz FSK FSK (Bus)
1 2 4 5 3 6 7 8
+ - + -
Output
mA
Output current (short-circuit proof) 4...20 mA
FSK
Transformation ratio 1:1 gn

Detect. of wire break (input) < 0.1 mA - -


Detect. of overranging (input, approx.) 23...29 mA
Load 0...700 Ω
Residual ripple (peak-to-peak) < 0.25 % -
+ -
General data 14 15
LED indicators, power “On“ (green)
Isolation
4...20 mA
Output – input/power supply/FSK 2.3 kV 0...700 Ω
Input – power supply – FSK 500 V FSK

Max. ambient temperature -20...+60 °C


Weight 120 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
* FSK only at load ≥ 250 Ω=for the current source
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

82

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Isolator Ex V17153-51
1 channel

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ Low voltage drop

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Input current (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 22 mA, max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
V17111-13 ❍ V17111-6 _ _ ●
Output (hazardous area)
Output current (short-circuit proof) (0)4...20 mA
Transformation ratio 1:1 0(4)...20 mA
Detect. of overranging (input, approx.) 22...28.5 mA 4 5
Load 0...600 Ω + -
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 00 ATEX 2017 X
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 19 V
Max. power Po = 542 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 110 nF

General data
Voltage drop < 3 V/6 V load
120...600/0...120 Ω
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C + -
Weight 90 g 14 15
Performance under reference conditions 0(4)...20 mA
Linearity deviation < 0.1 %
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 % I
Response time < 50 ms P
EEx ib
Hazardous area

83

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Isolator Ex V17153-515
1 channel, bypass

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ The input signal is not interrupted at break on output
(bypass)

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Input current (0)4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 22 mA, max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
V17111-13 ❍ V17111-6 _ _ ●
Output (hazardous area)
Output current (short-circuit proof) (0)4...20 mA
Transformation ratio 1:1 0(4)...20 mA
Detect. of overranging (input, approx.) 22...28.5 mA < 15.8 V (≤ 6.5 V, RB = ∞)
Load 0...600 Ω 4 5
Explosion protection [EEx ib] IIC + -
Certificate of conformity PTB 00 ATEX 2017 X
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 19 V
Max. power Po = 542 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 110 nF

General data
Voltage drop < 3,8 V/6,8 V load
120...600/0...120 Ω
Isolation
Input – output 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g + -
Performance under reference conditions 14 15
Linearity deviation < 0.1 % 0(4)...20 mA
Error limit < 0.1 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms I
P
EEx ib
Hazardous area

84

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Loop Powered Isolator Ex V17153-52
1 channel, HART

■ Electrical isolation for standard signals 0(4)...20 mA


(I/P converter, positioner)
■ Point to point communication
■ Low voltage drop

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Overranging > 23.6 mA; max. 40 mA V17111-12 ❍ V17111-3 _ _ ●
Communication V17111-13 ❍ V17111-6 _ _ ●
via terminals 3/6
via mA signal 4/5
Permeable protocol HART FSK* FSK
Bandwidth 500 Hz...10 kHz 0(4)...20 mA
4 5 3 6
Output (hazardous area) + -
Output current (short-circuit proof) 0(4)...20 mA
Transformation ratio 1:1
Detect. of overranging (input, approx.) 22...28.5 mA FSK
Load 0...600 Ω
Explosion protection [EEx ib] IIC
Certificate of conformity PTB 00 ATEX 2017 X
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 19 V
Max. power Po = 542 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 110 nF

General data
Voltage drop < 3.5 V/< 6 V at load + -

120...600/0...120 Ω 14 15
Isolation 0(4)...20 mA
Output – input/FSK 2.3 kV FSK

Max. ambient temperature -20...+60 °C


Weight 90 g
Performance under reference conditions I
P
Linearity deviation < 0.1 %
EEx ib
Error limit < 0.1 % Hazardous area
Temperature effect < 0.1 %/10 K
Impedance effect < 0.18 %
Response time < 50 ms

* FSK only at load ≥ 250 Ω=for the current source

85

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-61
1 channel

■ Isolating driver for I/P converter, positioner with


HART-communication
■ Minimal power consumption

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 1.5 V V17111-12 ● V17111-3 _ _ ●
V17111-13 ● V17111-6 _ _ ●
Output (hazardous area)
Output current (short-circuit proof) 4...20 mA
4...20 mA
Transformation ratio 1:1 19.2...30 V DC
Detect. of wire break (input) < 0.1 mA
1 2 4 5 3 6
Detect. of overranging (input, approx.) 22...30 mA
+ - + -
Load 0...600 Ω
Residual ripple (peak-to-peak) < 0.25 %
Explosion protection [EEx ib] IIC
Certificate of conformity PTB No. Ex-95.D.2109 X
Max. short-circuit current Io = 28.5 mA
Max. voltage Uo = 20 V
Max. power Po = 570 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 95 nF
gn
General data
LED indicators, power “On“ (green)
Isolation
Output – input/power supply 2.3 kV
Max. ambient temperature -20...+60 °C + -
Weight 90 g 14 15
Power supply 4...20 mA
Rated voltage 19.2...30 V DC
Power consumption 0.7 W
Power dissipation 0.7 W
Performance under reference conditions I
P
Linearity deviation < 0.1 %
Error limit < 0.25 % EEx ib

Temperature effect < 0.1 %/10 K Hazardous area


Impedance effect < 0.1 %
Response time < 50 ms

86

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-62
1 channel, HART

■ Isolating driver for I/P converter, positioner with


HART-communication
■ Point to point communication
■ Minimal power consumption

Module size 2
Module fits for:
Input (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 1.5 V; < 6.5 V (if source V17111-12 ● V17111-3 _ _ ●
not HART compatible) V17111-13 ● V17111-6 _ _ ●
Communication
via terminals 3/6
via mA signal 4/5 FSK FSK

Permeable protocol HART 4...20 mA


19,2...30 V DC
Bandwidth 500 Hz...10 kHz 1 2 4 5 3 6
+ - + -
Output (hazardous area)
Output current (short-circuit proof) 4...20 mA
J1
Transformation ratio 1:1 A
Detect. of wire break (input) < 0.1 mA R B
Detect. of overranging (input, approx.) 22...30 mA
Load 0...600 Ω
Residual ripple (peak-to-peak) < 0.25 %
Explosion protection [EEx ib] IIC
Certificate of conformity PTB No. Ex-95.D.2190 X
Max. short-circuit current Io = 28.5 mA gn
Max. voltage Uo = 20 V
Max. power Po = 570 mW
Permitted external inductance La = 1.3 mH
Permitted external capacitance Ca = 95 nF
+ -
General data 14 15
LED indicators, power “On“ (green) 4...20 mA
Isolation FSK
Output – input/power supply/FSK 2.3 kV
Max. ambient temperature -20...+60 °C
Weight 90 g I
Power supply P
Rated voltage 19.2...30 V DC EEx ib
Power consumption 0.7 W Hazardous area
Power dissipation 0.7 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K Functions of the plug-in jumpers J.:

Impedance effect < 0.1 % J1 Minimum impedance for HHT to terminals 3/6
A = Ui <1.5 V
Response time < 50 ms (Source to terminal 4/5 HART-compatible)
B = Ui < 6.5 V
(Source to terminal 4/5 not HART-compatible)

The positions illustrated on the circuit diagram


represented standard adjustments (delivery status)

87

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-820
1 channel, HART, FSK bus

■ Isolating driver for I/P converter, positioner with HART-


communication
■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Input (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Voltage drop < 6.9 V V17111-12 ❍ V17111-3 _ _ ●
Communication V17111-13 ❍ V17111-6 _ _ ●
via FSK bus (backplane/FSK bus amplifier)
via jacks 2 x 2 mm (front)
19.2...30 V DC 4...20 mA
Permeable protocol HART 1.1 W FSK*
Bandwidth 500 Hz...10 kHz FSK FSK (Bus)
1 2 4 5 3 6 7 8
+ - + -
Output (hazardous area) mA

Output current (short-circuit proof) 4...20 mA FSK


gn
Transformation ratio 1:1
Detect. of wire break (input) < 0.1 mA - -
Detect. of overranging (input, approx.) 23...29 mA
Load 0...700 Ω
Residual ripple (peak-to-peak) < 0.25 % -
+ -
Explosion protection [EEx ia] IIC
Certificate of conformity PTB 98 ATEX 2183 X 14 15

Max. short-circuit current Io = 93 mA


Max. voltage Uo = 26.3 V 4...20 mA
0...700 Ω
Max. power Po = 610 mW FSK

Permitted external inductance La = 4.1 mH


Permitted external capacitance Ca = 97 nF

General data EEx ia

LED indicators, power “On“ (green) Hazardous area


Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
* FSK only at load ≥ 250 Ω=for the current source
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

88

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-825
1 channel, HART

■ Isolating driver for I/P converter, positioner with


HART-communication
■ Galvanic isolation between input/output/power supply
and HART
■ Testjacks for mA signal
■ Jacks for HART communication

Module size 4
Module fits for:
Input (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 6.9 V V17111-12 ❍ V17111-3 _ _ ●
Communication V17111-13 ❍ V17111-6 _ _ ●
via mA signal
via jacks 2 x 2 mm (front)
19.2...30 V DC 4...20 mA
Permeable protocol HART 1.1 W FSK*

Bandwidth 500 Hz...10 kHz 1 2 4 5 3 6


+ - + -

Output (hazardous area) mA

Output current (short-circuit proof) 4...20 mA gn


FSK

Transformation ratio 1:1 - -


Detect. of wire break (input) < 0.1 mA
Detect. of overranging (input, approx.) 23...29 mA
Load 0...700 Ω -
Residual ripple (peak-to-peak) < 0.25 % -
+
Explosion protection [EEx ia] IIC
14 15
Certificate of conformity PTB 98 ATEX 2183 X
Max. short-circuit current Io = 93 mA
4...20 mA
Max. voltage Uo = 26.3 V 0...700 Ω
Max. power Po = 610 mW FSK

Permitted external inductance La = 4.1 mH


Permitted external capacitance Ca = 97 nF

General data EEx ia

LED indicators, power “On“ (green) Hazardous area


Isolation
Input – output/power supply/FSK 2.3 kV
Output – power supply – FSK 500 V
Max. ambient temperature -20...+60 °C
Weight 120 g
* FSK only at load ≥ 250 Ω=for the current source
Power supply
Rated voltage 19.2...30 V DC
Power consumption 1.1 W
Power dissipation 1.1 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

89

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-840
2 channels, HART, FSK bus

■ Isolating driver for I/P converter, positioner with HART-


communication
■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication

Module size 4
Module fits for:
Input per channel (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ❍ V17111-2 _ _ ●
Voltage drop < 6.9 V V17111-12 ❍ V17111-3 _ _ ●
Communication per channel V17111-13 ❍ V17111-6 _ _ ●
via FSK bus (backplane/FSK bus amplifier)
via jacks 2 x 2 mm (front)
19.2...30 V DC 4...20 mA 4...20 mA
Permeable protocols HART 2.2 W FSK* FSK*

Bandwidth 500 Hz...10 kHz FSK (Bus) FSK (Bus)


1 2 4 5 7 8 3 6 9 10
+ - + - + -
Output per channel (hazardous area)
Output current (short-circuit proof) 4...20 mA gn
FSK 1 FSK 2

Transformation ratio 1:1


- - -
Detect. of wire break (input) < 0.1 mA
Detect. of short-circuit (input, approx.) 23...28 mA
Load 0...600 Ω 1 2
1
- 2
-
Residual ripple (peak-to-peak) < 0.25 %
+ - + -
Overranging in input 23...28 mA
Explosion protection [EEx ia] IIC 14 15 13 16

Certificate of conformity PTB 98 ATEX 2183 X


Max. short-circuit current Io = 93 mA 4...20 mA
0...700 Ω
4...20 mA
0...700 Ω
Max. voltage Uo = 26.3 V FSK FSK

Max. power Po = 610 mW


Permitted external inductance La = 4.1 mH
Permitted external capacitance Ca = 97 nF
EEx ia EEx ia

General data Hazardous area Channel 1 Channel 2


LED indicators, power “On“ (green)
Isolation per channel
Input – output/power supply/FSK 2.3 kV
Output – power supply/FSK 500 V
Isolation channel 1 – channel 2
* FSK only at load ≥ 250 Ω=for the current source
Input 1 – input 2 500 V
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 2,2 W
Power dissipation 2,2 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.1 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

90

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Isolating Driver Ex V17153-845
2 channels, HART

■ Isolating driver for I/P converter, positioner with HART-


communication
■ FSK bus communication via backplanes and FSK bus amplifier
■ Galvanic isolation between input/output/power supply and HART
■ Jacks for HART communication

Module size 4
Module fits for:
Input per channel (safe area) Socket Backplane
Input current 4...20 mA V17111-11 ● V17111-2 _ _ ●
Voltage drop < 6.9 V V17111-12 ❍ V17111-3 _ _ ●
Communication per channel V17111-13 ❍ V17111-6 _ _ ●
via mA signal
via jacks 2 x 2 mm (front)
Permeable protocol HART 19.2...30 V DC
2.2 W
4...20 mA
FSK*
4...20 mA
FSK*
Bandwidth 500 Hz...10 kHz
1 2 4 5 3 6
+ - + - + -
Output per channel (hazardous area)
Output current (short-circuit proof) 4...20 mA FSK 1 FSK 2
gn
Transformation ratio 1:1
Detect. of wire break (input) < 0.1 mA - - -
Detect. of short-circuit (input, approx.) 23...29 mA
Load 0...600 Ω 1 2
Residual ripple (peak-to-peak) < 0.25 %
1
- 2
-
Overranging in input 23...28 mA + - + -

Explosion protection [EEx ia] IIC 14 15 13 16

Certificate of conformity PTB 98 ATEX 2183 X


Max. short-circuit current Io = 93 mA 4...20 mA
0...600 Ω
4...20 mA
0...600 Ω
Max. voltage Uo = 26.3 V FSK FSK

Max. power Po = 610 mW


Permitted external inductance La = 4.1 mH
Permitted external capacitance Ca = 97 nF
EEx ia EEx ia

General data Hazardous area


LED indicators, power “On“ (green)
Isolation per channel
Output – input/power supply/FSK 2.3 kV
Input – power supply – FSK 500 V
Isolation channel 1 – channel 2
* FSK only at load ≥ 250 Ω=for the current source
Input 1 – input 2 500 V
Output 1 – output 2 500 V
Max. ambient temperature -20...+60 °C
Weight 140 g
Power supply
Rated voltage 19.2...30 V DC
Power consumption 2,2 W
Power dissipation 2,2 W
Performance under reference conditions
Linearity deviation < 0.1 %
Error limit < 0.25 %
Temperature effect < 0.01 %/10 K
Impedance effect < 0.05 %
Response time < 50 ms

91

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Monitoring Modules

Trip Amplifier

Trip Amplifier 2 alarms, 2 relays V17171-11

12.00 93
Trip Amplifier V17171-11
2 alarms, 2 relays

■ 1 input 0 (4)...20 mA
■ 2 alarms with one relay each or
■ 1 alarm with 2 relays
■ Operating and quiescent current for each alarm
■ with/without wire-break and short-circuit monitoring
■ Set point adjustment with decade switch

Module size 2
Module fits for:
Output Socket Backplane
Relay contact Rs2/Rs1 NC/NO contacts (via jumpers J1/J2) V17111-11 ● V17111-2 _ _ ●
Contact rating 250 V AC, 1 A, cosϕ > 0.7 V17111-12 ❍ V17111-3 _ _ ●
30 V DC, 2 A, resistive load V17111-13 ● V17111-6 _ _ ●
Mechanical life expectancy > 3 · 107 operations
Contact life expectancy > 106 operations at maximum load
Behavior during wire break Relay drop (only for 4...20 mA,
short-circuit at input (independent of alarm signal) 19.2...30 V DC Rs1 Rs2
jumper J3 = open 1 2 4 5 3 6
+ -
Input
Input current (0)4...20 mA
A B A B
Input resistance 50 Ω J2 J1
Voltage drop ≤1V

Alarm section rd rd
& &
Number of alarms 2 (independent)
Alarm setting 1- and ten-steps gn
A B A B
J7 J4
(behind removable front cover)
1
Adjustment range 0...99 % (0...19.8 mA/4...19.84 mA) 1
J3
Resolution 1% A B
J5
Switch hysterese 0.8 % referred to 0/4...20 mA
Effective direction operating current (relay pick up at X > W) I>2mA

quiescent current (relay pick up at X < W)


independent for both relays W1 W2
J6 x10% x10%
- + X 1%
Ref X 1%
General data
LED display power “On“ (green) + -
LED display switching status relay 14 15
“flooded with current“ (red) 0(4)...20 mA
Spark quenching unit 100 Ω/22 nF (between terminals 4,5 /3,6)
Max. ambient temperature -20...+60 °C
Isolation per channel
Input – power supply 500 V Functions of the plug-in jumpers J.:
Output – power supply/input 2.3 kV J1/J2 Relay output Rs2/Rs1
Weight 90 g A = NO
Power supply B = NC
J3 Line break and short-circuit monitoring
Connection terminals 1(+); 2(–) (4...20 mA)
Rated voltage 19.2...30 V DC closed = inactive
open (parked) = activ
Power consumption approx. 0.7 W
J4/J7 Effective direction
Characteristics under reference conditions B = relay pick up at X > W (operating current)
Temperature effect < 0.1 %/10 K A = relay pick up at X < W (quiescent current)
J5 Relay assignment
Response time ≤ 300 ms A = W1 affects Rs1 and Rs2
A = (1 alarm, 2 relays)
B = W1 affects Rs1, W2 affects Rs2
B = (2 alarms, 2 relays)
J6 Input
closed = 4...20 mA
open (parked) = 0...20 mA

The positions illustrated on the circuit diagram


represent standard adjustments (delivery status)
94

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Sockets, Backplanes

Sockets, Backplanes

Socket V17111-11

Socket with power supply 24/24 V17111-12

Socket with power supply 230/24 V17111-13

Backplane, 8-way V17111-2_ _

Backplane, 16-way V17111-3_ _

Backplane, 21-way V17111-6_ _

Dimensional drawings

12.00 95
Socket V17111-11

■ For mounting the Contrans I modules


■ Standard terminal layout
■ Maintenance-free connection technique
■ For Ex and non-Ex modules
■ Encoding field for module assignment

System connection
Connection terminals 1, 2, 3, 4, 5, 6
Connection technique 6pin double-tiered terminals
(cage clamp spring)
Rated terminal cross-section 0.08...2.5 mm2 / AWG 26...14“
single copper wiring, stranded
with/without wire end ferrule1)

Field connection 1 2 3 4 5 6
Connection terminals 11, 12, 13, 14, 15, 16
Connection technique 6pin double-tiered terminals
(cage clamp spring)
Rated terminal cross-section 0.08...2.5 mm2 / AWG 26...14“
single copper wiring, stranded
1 2 3 4 5 6
with/without wire end ferrule1)

General data
Mounting location can be snap-fitted onto 35 mm
Module slots
standard rail to DIN EN 50022
Protected to DIN 40050 IP 20
Protection class II (to DIN EN 61010)
Test voltage 3.7 kV terminals 1...6 – 11...16 11 12 13 14 15 16
2.3 kV terminals 1, 2 – 4, 5 – 3, 6
1.35 kV terminals 11, 14, 15 – 12, 13, 16
Colour RAL 7035
Material Polycarbonate 11 12 13 14 15 16
Weight 50 g
1) With wire end ferrules max. 1.5 mm2

System connection
1 2 3

1 2 3
4 5 6

4 5 6 Module
jack 1
1 1 2 8
4 5
2 3 6 9
3 10
Legend 12 Encoding
plates 4 13 11 1...14
16
5 12
6 11 13
14
7 15 14
Module
jack 2

14 15 16
14 15 16
11 12 13 11 12 13
Field connection

96

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Socket V17111-12
with power supply unit 24/24

■ For installing Contrans I modules


■ Integrated power supply unit 19...33 V/24 V
■ Electrical isolation to mains
■ Standard terminal layout
■ Maintenance-free connection technique
■ for Ex- and non-Ex modules
■ Encoding field for module assignment

System connection
Power supply
Connection terminals 1, 2
Rated voltage range 19.2...33 V DC
Power consumption appr. 1.5 W for CI module V17151-2X, -6X
appr. 1.1 W for CI module V17153-2X, -6X
Output
Connection power supply for the plugged modules 19,2...33 V DC
Isolation the output is electrically isolated from 1 2 3 4 5 6
the power supply
Rated voltage 24 V ± 10 %
Rated current 83 mA, non short-circuit proof
Terminals 3...6 signal current circuits of the module
(see module description)
1 2 3 4 5 6
Field connection
Terminals 11...16 signal current circuits of the module
(see module description)
Module slots
Safety data
Protection class II (to DIN EN 61010-1)
Overvoltage category II
11 12 13 14 15 16
Pollution degree 2
Type of protection IP 20 (to EN 60 259 /DIN VDE 0470 part 1)
Output functional extra-low voltage to VDE 0100
part 410/IEC 364-4-41 with safe
11 12 13 14 15 16
electrical isolation
Test voltages 2.3 kV power supply – 24 V module supply
2.3 kV power supply – term. 3...6, 11...16
The requirement of the EMC guideline 89/336/EWG and
the low voltage guideline 73/23/EWG are met System connection
1 2 3

General data 1 2 3
4 5 6
Connection technique 6-pin double-tiered terminal
(cage clamp spring) 4 5 6 Module
Rated terminal cross section 0.08...2.5 mm2 /AWG 26...14“, jack 1

single copper wiring, stranded, 1 1 2 8


4 5
with wire end ferrule (max. 1.5 mm2) 2 3 6 9
3 10
Type of mounting can be snap-fitted onto 35 mm Legend 12 Encoding
plates 4 13 11 1...14
standard rail to DIN EN 50022 16
5 12
Mounting location outside the hazardous area 6 11 13
14
(for the supply of Ex-modules, 7 15 14
pay attention to VDE 0165) Module
jack 2
Mounting orientation horizontal or vertical
Ambient conditions 14 15 16
14 15 16
Operating temperature -20...+60 °C for horizontal mounting
11 12 13 11 12 13
-20...+55 °C for vertical mounting
Relative humidity < 85 %, 3K3 to IEC 721, part 3-3, Field connection
no condensation
Weight 80 g 97

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Socket V17111-13
with power supply unit 230/24

■ For installing Contrans I modules


■ Integrated power supply unit 95...253 V/24 V
■ Electrical isolation to mains
■ Standard terminal layout
■ Maintenance-free connection technique
■ for Ex- and non-Ex modules
■ Encoding field for module assignment

System connection
Power supply
Connection terminals 1, 2
Rated voltage range 95...253 V AC/48...62 Hz
Power consumption appr. 1.5 W for CI module V17151-2X, -6X
appr. 1.1 W for CI module V17153-2X, -6X
Fusing Fuse T 0.1 A integr. in power supply unit
Output 95...253 V AC
Connection power supply for the plugged modules 1 2 3 4 5 6
Isolation the output is electrically isolated from
the power supply
Rated voltage 24 V ± 10 %
Rated current 83 mA, non short-circuit proof
Terminals 3...6 signal current circuits of the module
(see module description) 1 2 3 4 5 6
Field connection
Terminals 11...16 signal current circuits of the module
(see module description)
Module slots

Safety data
Protection class II (to DIN EN 61010-1)
Overvoltage category II 11 12 13 14 15 16
Pollution degree 2
Type of protection IP 20 (to EN 60 259 /DIN VDE 0470 part 1)
Output functional extra-low voltage to VDE 0100
part 410/IEC 364-4-41 with safe
11 12 13 14 15 16
electrical isolation
Test voltages 2.3 kV power supply – 24 V module supply
2.3 kV power supply – term. 3...11, 11...16
The requirement of the EMC guideline 89/336/EWG and
the low voltage guideline 73/23/EWG are met System connection
1 2 3

General data 1 2 3
4 5 6
Connection technique 6-pin double-tiered terminal
(cage clamp spring) 4 5 6 Module
jack 1
Rated terminal cross section 0.08...2.5 mm2 /AWG 26...14“,
1 1 2 8
single copper wiring, stranded, 4 5
2 3 6 9
with wire end ferrule (max. 1.5 mm2) 3 10
Legend 12 Encoding
Type of mounting can be snap-fitted onto 35 mm plates 4 13 11 1...14
standard rail to DIN EN 50022 5
16
12
Mounting location outside the hazardous area 6 11 13
14
(for the supply of Ex-modules, 7 15 14
Module
pay attention to VDE 0165) jack 2
Mounting orientation horizontal or vertical
14 15 16
Ambient conditions 14 15 16

Operating temperature -20...+60 °C for horizontal mounting 11 12 13 11 12 13


-20...+55 °C for vertical mounting
Relative humidity < 85 %, 3K3 to IEC 721, part 3-3, Field connection

no condensation
98 Weight 80 g

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-2_ _
8way

■ For installing 8 Contrans I modules


■ Signal processing up to 16 Ex or non Ex signals
■ Separate fusing for modules and 1 2 1 X103

1
2
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
X102
+ -
1 2 2

1
2
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
+ - 5

X104
24VDC 6
X101

signal circuits
5
T1,6A T2,5A 6

1 2 3 4 5 6 7 8

■ Simple design of FSK bus trough pluggable


bus amplifier 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

System connection
Signales X101 /X102 (slot 1...8, terminal 3...6)
Socket/type Pin terminal/SLD 3.5 V/36/90F 3.2 SNOR
Connector/type Female multipoint connector/BL 3.5/18 /FSNOR (for max. 1.5 mm2 wire cross section)
Rated voltage ≤ 30 V AC/DC (functional extra low voltage with safe electrical isolation
to VDE 0100 part 410/IEC 364-4-41)
FSK bus X110 (terminal 5...8)
Socket/type Pin terminal/SLD 3.5 V/4/F 3.2 SNOR
Connector/type Female multipoint connector/BL 3.5/2/FSNOR (for max. 1.5 mm2 wire cross section)
FSK bus amplifier X108 (slot 1...8, terminal 7, 9)
Socket/type 37pin SUB-D
Connector/type FSK bus amplifier V17191-16 (option)
Power supply X1 (terminal 1...4)
Socket/type Screw terminal for max. 2.5 mm2 wire cross section
Rated voltage 19.2...30 V DC (see rated voltage of the CI modules)
Fusing power supply modules T 2.5 A
Fusing power supply signals T 1.6 A

Field connection
Signales Slot 1...21, terminals 11...16
Slot V17111-221 Screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Slot V17111-222 Pluggable screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Connector V17111-222 Type of connector MSTB 2.5/3-ST (for max. 2.5 mm2 wire cross section)
V17111-251 Screw terminals for max. 2.5 mm2 wire cross section (colour blue)
Rated voltage 250 V AC (375 V peak value to EN 50020 for Ex application)

General data
Safe electrical isolation to System connection – field connection, module slot – module slot
EN 61010/EN 50020 (Ex)
Isolation System connection – field connection: 3.7 kV
Module slot – module slot (field connection): 3.7 kV
Per module slot (field connection), terminals 11, 14, 15 – 12, 13, 16: 1.35 kV
Max. ambient temperature -20...+60 °C for horizontal mounting; -20...+55 °C for vertical mounting
Relative humidity < 85 %, 3K3 to IEC 721, part 3-3, no condensation
Type of protect. to EN 60529/ IP 00 (the backplane must be so installed that at least IP 20 is guaranteed)
DIN VDE 0470 part 1
Mounting type can be snapped-fitted onto 35 mm standard rails to DIN EN 50022
Mounting location Outside hazardous area (attention to VDE 0165, IEC 79-14 in case Ex application)
Mounting orientation horizontal or vertical
Weight 369 g

99

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-2_ _
8way

System connection
Signals, slot 1...8

1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
Power supply Slot for

1
2
FSK bus amplifier

1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
1
2
1 2 1 X108

X102
1
2
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
+ -

X1
3 4 2

X101
1
2
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
+ - 5

FSK bus
24VDC

X110
6
7
T1,6A T2,5A 8

1 2 3 4 5 6 7 8

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

Signals, slot 1...8

Field connection

System connection

Power supply slot 1...8, channel 1 slot 1...8, channel 2 FSK bus amplifier FSK bus
X1 X101 X102 X108 X110
+24V 0 V +24V 0 V +24V 0 V +24V 0 V 0 V 0 V +24V

1 2 3 4 1 2 1.4 1.5 2.4 2.5 3.4 3.5 . . . 1 2 1.3 1.6 2.3 2.6 3.3 3.6 . . . 36 37 17 18 19 1 2 3 4 5 . . . 5 6 7 8

T1,6A T2,5A

1 2 4 5 3 6 7 8 9 10

Contrans I
modules

11 12 13 14 15 16

Field connection

connector X101 connector X102


slot 1...8 slot 1...8 X108
X101 X102
channel 1 channel 2 channel 1 channel 2 slot
FSK bus amplifier

0V 0V
+ 24 V + 24 V
slot 1/4(+) slot 1/3(+) slot 1/7 1
20 slot 1/9
slot 1/5(-) slot 2/7 2
slot 1/6(-) slot 3/7
21 slot 2/9
3
slot 2/4(+) 22 slot 3/9
slot 2/3(+) slot 4/7 4
23 slot 4/9
slot 2/5(-) slot 5/7 5
slot 2/6(-) 24 slot 5/9
slot 6/7 6
slot 3/4(+) slot 3/3(+) 25 slot 6/9
slot 7/7 7
26 slot 7/9
slot 3/5(-) slot 3/6(-) slot 8/7 8
27 slot 8/9
slot 4/4(+) 9
slot 4/3(+) 10
28
slot 4/5(-) 29
slot 4/6(-) 11
30
slot 5/4(+) 12
slot 5/3(+) 31
13
slot 5/5(-) slot 5/6(-) 32
14
33
slot 6/4(+) slot 6/3(+) 15
34
16
slot 6/5(-) slot 6/6(-) + 24 V 17
35
36 GND
slot 7/4(+) slot 7/3(+) X 110/6 18
37 GND
X 110/5 19
slot 7/5(-) slot 7/6(-)
slot 8/4(+) slot 8/3(+)
slot 8/5(-) slot 8/6(-)

100

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-3_ _
16way

■ For installing 16 Contrans I modules


■ Signal processing up to 32 Ex or non Ex signals

T2,5A T1,6A

Redundant power supply with signal contact 1 2 1

+ - 24 VDC + -
2 43 44

K101
X101 X102 X108
3 4

FSK
5 6

FSK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

■ Separate fusing for modules and


signal circuits
■ Simple design of FSK bus trough pluggable 14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13
14 15 16

11 12 13

bus amplifier

System connection
Signales X101 /X102 (slot 1...16, terminal 3...6)
Socket/type 37 oin SUB-D
Rated voltage ≤ 30 V AC/DC (functional extra low voltage with safe electrical isolation
to VDE 0100 part 410/IEC 364-4-41)
FSK bus X110 (terminal 5...8)
Socket/type Screw terminals for max. 2.5 mm2 wire cross section
FSK bus amplifier X108 (slot 1...16, terminal 7, 9)
Socket/type 37pin SUB-D
Connector/type FSK bus amplifier V17191-16/-32 (option)
Power supply X1 (terminal 1...4)
Socket/type Screw terminal for max. 2.5 mm2 wire cross section
Rated voltage 19.2...30 V DC (see rated voltage of the CI modules)
Voltage drop through
redundant supply diodes 1.4 V
Wrong polarity protection yes
Fusing power supply modules T 3.15 A
Fusing power supply signals T2A
Fuse monitoring Failure of one or both fuses is signalled by the opening of the relay contact and the
extinction of the LED
Signal contact X105 (terminal 43, 44 – NO contact from relais)
Socket/type Screw terminals for max. 2.5 mm2 wire cross section
Switching capacity ≤ 10 W, 10 VA, cosϕ ≥ 0.7
Switching current ≤ 0.5 A UC
Switching voltage ≤ 50 V UC

Field connection
Signales Slot 1...16, terminals 11...16
V17111-331 Screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Slot V17111-332 Pluggable screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Connector V17111-332 Type of connector MSTB 2.5/3-ST (for max. 2.5 mm2 wire cross section)
V17111-351 Screw terminals for max. 2.5 mm2 wire cross section (colour blue)
Rated voltage 250 V AC (375 V peak value to EN 50020 for Ex application)

General data
Safe electrical isolation to System connection – field connection, module slot – module slot
EN 61010/EN 50020 (Ex)
Isolation System connection – field connection: 3.7 kV
Module slot – module slot (field connection): 3.7 kV
Per module slot (field connection), terminals 11, 14, 15 – 12, 13, 16: 1.35 kV
Max. ambient temperature -20...+60 °C for horizontal mounting; -20...+55 °C for vertical mounting
Relative humidity < 85 %, 3K3 to IEC 721, part 3-3, no condensation
Type of protect. to EN 60529/ IP 00 (the backplane must be so installed that at least IP 20 is guaranteed)
DIN VDE 0470 part 1
Mounting type Mounting in 19“-system
Mounting location Outside hazardous area (attention to VDE 0165, IEC 79-14 in case Ex application)
Mounting orientation horizontal or vertical
Weight 600 g

101

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-3_ _
16way

System connection
Signal Signals, Signals, Slot for
Power supply contact slot 1...16, channel 1 slot 1...16, channel 2 FSK bus amplifier FSK bus
24 V DC T3,15A T2A X105 X101 X102 X108
FSK bus
+ - + -
1 2 3 4 43 44 H101 5 6 7 8

X1 X110
B-Nr:17111-330
Sach-Nr:xxxxxxxx
K101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

Signals, slot 1...21

Field connection

System connection
Power Signal
supply contact slot 1...16, channel 1 slot 1...16, channel 2 FSK bus amplifier FSK bus
X1 X105 X101 X102 X108 X110
+24V 0 V +24V 0 V 0 V 0 V +24V + – + – 0 V 0 V +24V + – + – 0 V 0 V +24V

1 2 3 4 43 44 36 37 17 1 20 2 21 ... 36 37 17 18 19 1 20 2 21 ... 36 37 17 18 19 1 20 2 21 ... 5 6 7 8

T 3,15 A T2A

&

/
K101
H101 1 2 4 5 3 6 7 8 9 10

Contrans I
modules

11 12 13 14 15 16

Field connection

X101 X102 X108


slot 1...16, channel 1 slot 1...16, channel 2 slot
FSK bus amplifier

slot 1/4(+) 1 slot 1/3(+) 1 slot 1/7 1


20 slot 1/5(–) 20 slot 1/6(–) 20 slot 1/9
slotl 2/4(+) 2 slot 2/3(+) 2 slot 2/7 2
21 slot 2/5(–) 21 slot 2/6(–) 21 slot 2/9
slot 3/4(+) 3 slot 3/3(+) 3 slot 3/7 3
22 slot 3/5(–) 22 slot 3/6(–) 22 slot 3/9
slot 4/4(+) 4 slot 4/3(+) 4 slot 4/7 4
23 slot 4/5(–) 23 slot 4/6(–) 23 slot 4/9
slot 5/4(+) 5 slot 5/3(+) 5 slot 5/7 5
24 slot 5/5(–) 24 slot 5/6(–) 24 slot 5/9
slot 6/4(+) 6 slot 6/3(+) 6 slot 6/7 6
25 slot 6/5(–) 25 slot 6/6(–) 25 slot 6/9
slot 7/4(+) 7 slot 7/3(+) 7 slot 7/7 7
26 slot 7/5(–) 26 slot 7/6(–) 26 slot 7/9
slot 8/4(+) 8 slot 8/3(+) 8 slot 8/7 8
27 slot 8/5(–) 27 slot 8/6(–) 27 slot 8/9
slot 9/4(+) 9 slot 9/3(+) 9 slot 9/7 9
28 slot 9/5(–) 28 slot 9/6(–) 28 slot 9/9
slot 10/4(+) 10 slot 10/3(+) 10 slot 10/7 10
29 slot 10/5(–) 29 slot 10/6(–) 29 slot 10/9
slot 11/4(+) 11 slot 11/3(+) 11 slot 11/7 11
30 slot 11/5(–) 30 slot 11/6(–) 30 slot 11/9
slot 12/4(+) 12 slot 12/3(+) 12 slot 12/7 12
31 slot 12/5(–) 31 slot 12/6(–) 31 slot 12/9
slot 13/4(+) 13 slot 13/3(+) 13 slot 13/7 13
32 slot 13/5(–) 32 slot 13/6(–) 32 slot 13/9
slot 14/4(+) 14 slot 14/3(+) 14 slot 14/7 14
33 slot 14/5(–) 33 slot 14/6(–) 33 slot 14/9
slot 15/4(+) 15 slot 15/3(+) 15 slot 15/7 15
34 slot 15/5(–) 34 slot 15/6(–) 34 slot 15/9
slot 16/4(+) 16 slot 16/3(+) 16 slot 16/7 16
35 slot 16/5(–) 35 slot 16/6(–) 35 slot 16/9
+ 24 V 17 + 24 V 17 + 24 V 17
36 GND 36 GND 36 GND
free 18 18 x110/6 18
37 GND 37 GND 37 GND
free 19 19 x110/5 19

102

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-6_ _
21way

■ For installing 21 Contrans I modules


■ Signal processing up to 42 Ex or non Ex signals
■ Redundant power supply with signal contact 24VDC
+ - + - X105
H101 FSK 1...21 FSK 22...42 FSK

10.3
10.6

11.3
11.6
12.3
12.6
13.3
13.6
14.3
14.6
15.3
15.6
16.3
16.6
17.3
17.6
18.3
18.6
19.3
19.6
20.3
20.6
21.3
21.6
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
9.3
9.6
1 2 3 4 43 44

1
2
T2A 5 5 6 6


X103 X104

10.4
10.5

11.4
11.5
12.4
12.5
13.4
13.5
14.4
14.5
15.4
15.5
16.4
16.5
17.4
17.5
18.4
18.5
19.4
19.5
20.4
20.5
21.4
21.5
X106 X107

1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
9.4
9.5
1
2
X301 X302

Separate fusing for modules and


T3,15A X101 X102
K101
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

signal circuits
■ Simple design of FSK bus trough pluggable 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

bus amplifier 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

■ Preference for 19“ racks

System connection
Signales X101 /X102 /X103/X104 (slot 1...21, terminal 3, 4, 5, 6)
Socket/type Pin terminal/SLD 3.5 V/44/90G 3.2 SNOR
Connector/type Female multipoint connector/BL 3.5/2/SNOR (for max. 1.5 mm2 wire cross section)
Rated voltage ≤ 30 V AC/DC (functional extra low voltage with safe electrical isolation
to VDE 0100 part 410/IEC 364-4-41)
FSK bus X110 (terminal 5...8)
Socket/type Screw terminals for max. 2.5 mm2 wire cross section
FSK bus amplifier X108 /X109 (slot 1...21, terminal 7, 9)
Socket/type 37pin SUB-D
Connector/type FSK bus amplifier V17191-21 (option)
Power supply X1 (terminal 1...4)
Socket/type Screw terminal for max. 2.5 mm2 wire cross section
Rated voltage 19.2...30 V DC (see rated voltage of the CI modules)
Voltage drop through 1.4 V
redundant supply diodes
Wrong polarity protection yes
Fusing power supply modules T 3.15 A
Fusing power supply signals T2A
Fuse monitoring Failure of one or both fuses is signalled by the opening of the relay contact and the
extinction of the LED
Signal contact X105 (terminal 43, 44 – NO contact from relais)
Socket/type Screw terminals for max. 2.5 mm2 wire cross section
Switching capacity ≤ 10 W, 10 VA, cosϕ ≥ 0.7
Switching current ≤ 0.5 A UC
Switching voltage ≤ 50 V UC

Field connection
Signales Slot 1...21, terminals 11...16
V17111-621 Screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Slot V17111-622 Pluggable screw terminals for max. 2.5 mm2 wire cross section (colour grey)
Connector V17111-322 Type of connector MSTB 2.5/3-ST (for max. 2.5 mm2 wire cross section)
V17111-651 Screw terminals for max. 2.5 mm2 wire cross section (colour blue)
Rated voltage 250 V AC (375 V peak value to EN 50020 for Ex application)

General data
Safe electrical isolation to System connection – field connection, module slot – module slot
EN 61010/EN 50020 (Ex)
Isolation System connection – field connection: 3.7 kV
Module slot – module slot (field connection): 3.7 kV
Per module slot (field connection), terminals 11, 14, 15 – 12, 13, 16: 1.35 kV
Max. ambient temperature -20...+60 °C for horizontal mounting; -20...+55 °C for vertical mounting
Relative humidity < 85 %, 3K3 to IEC 721, part 3-3, no condensation
Type of protect. to EN 60529/ IP 00 (the backplane must be so installed that at least IP 20 is guaranteed)
DIN VDE 0470 part 1
Mounting type Mounting in 19“-system
Mounting location Outside hazardous area (attention to VDE 0165, IEC 79-14 in case Ex application)
Mounting orientation horizontal or vertical
Weight 1 561 g
103

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Backplane V17111-6_ _
21way

System connection

Signals Signals Slots for


Signal FSK bus amplifier
Power supply slot 1...10, channel 1/2 slot 11...21, channel 1/2 FSK bus
contact

24 V DC X105

X104
+ - + -
X102
H101 FSK 1...21 FSK 22...42 FSK bus

10.3
10.6

12.3
12.6
13.3
13.6
14.3
14.6
15.3
15.6
16.3
16.6
17.3
17.6
18.3
18.6
19.3
19.6
20.3
20.6
21.3
21.6
11.3
11.6
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
9.3
9.6
1 2 3 4 43 44
1
2
T2A 5 7 6 8

X103
X101

X1

10.4
10.5

12.4
12.5
13.4
13.5
14.4
14.5
15.4
15.5
16.4
16.5
17.4
17.5
18.4
X110

18.5
19.4
19.5
20.4
20.5
21.4
21.5
11.4
11.5
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
9.4
9.5
T3,
1
2

X108 X109
15 A
K101

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

Signals, slot 1...21

Field connection

System connection FSK bus amplifier


Power Signal
supply contact slot 1...21, channel 1 slot 1...21, channel 2 slot 1...21, channel 1 slot 1...21, channel 2 FSK bus
X1 X105 X101 / X103 X102 / X104 X108 X109 X110
+24V 0 V +24V 0 V +24V 0 V +24V 0 V 0 V 0 V +24V 0 V 0 V +24V

1 2 3 4 43 44 1 2 1.4 1.5 2.4 2.5 3.4 3.5 . . . 1 2 1.3 1.6 2.3 2.6 3.3 3.6 . . . 36 37 17 18 19 1 2 3 4 5 . . . 36 37 17 18 19 1 2 3 4 5 . . . 5 7 6 8

T3,15 A T2 A

&

K101
/

H101 1 2 4 5 3 6 7 8 9 10

Contrans I
modules

11 12 13 14 15 16

Field connection

X101 X102 X103 X104 X108 X109


channel 1 channel 2 channel 1 channel 2 slot slot
1 1 FSK bus amplifier FSK bus amplifier
0V 0V slot 11/4(+) 11.3 slot 11/3(+)
11.4
+ 24 V 2 2 + 24 V slot 11/5(-) 11.5 11.6 slot 11/6(-)
slot 1/4(+) 1.4 1.3
slot 1/3(+) 12.4 12.3
1.5 1.6
slot 1/5(-) slot 1/6(-) 12.5 12.6
2.4 2.3 slot 1/7 1 slot 1/9 1
13.4 13.3 20 slot 17/7 20 slot 17/9
2.5 2.6 slot 2/7 2 slot 2/9 2
13.5 13.6 slot 3/7 3
21 slot 18/7
slot 3/9 3
21 slot 18/9
3.4 3.3 22 slot 19/7 22 slot 19/9
14.4 14.3 slot 4/7 4 slot 4/9 4
3.5 3.6 23 slot 20/7 23 slot 20/9
14.5 14.6 slot 5/7 5
24 slot 21/7
slot 5/9 5
24 slot 21/9
4.4 4.3 15.3 slot 6/7 6 slot 6/9 6
15.4 25 25
4.5 4.6 15.6
slot 7/7 7 slot 7/9 7
15.5 slot 8/7 8
26
slot 8/9 8
26
5.4 5.3 16.3 27 27
16.4 slot 9/7 9 slot 9/9 9
5.5 5.6 16.6 slot 10/7 28 slot 10/9 28
16.5 10
29
10
29
6.4 6.3 17.3
slot 11/7 11 slot 11/9 11
17.4 slot 12/7 30 slot 12/9 30
6.5 6.6 17.5 17.6
12
31
12
31
slot 13/7 13 slot 13/9 13
7.4 7.3 18.4 18.3 slot 14/7 32 slot 14/9 32
14 14
7.5 7.6 18.5 18.6 slot 15/7 15
33 slot 15/9 15
33
34 34
8.4 8.3 19.4 19.3
slot 16/7 16 slot 16/9 16
35 35
8.5 + 24 V 17 + 24 V 17
8.6 19.5 19.6 36 GND 36 GND
X 110/7 18 X 110/6 18
9.4 9.3 20.4 20.3 X 110/5 19
37 GND
X 110/7 19
37 GND
9.5 9.6 20.5 20.6
10.4 10.3 21.4 21.3
slot 10/4(+) 10.5 10.6 slot 10/3(+) slot 21/4(+) 21.5 21.6 slot 21/3(+)
slot 10/5(-) slot 10/6(-) slot 21/5(+) slot 21/6(+)

104

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Dimensional drawings

Socket V17111-11 Socket V17111-12


Socket V17111-13
20 Mounting rail Mounting rail
to DIN EN 50022 to DIN EN 50022

4 5 6
105

75 (module 1) 100 (module 1)


14 15 16 100 (module 2) 125 (module 2)
11 12 13
145 (module 4)

11
Backplane V17111-2 _ _ 1 2 1
Mounting rail
to DIN EN 50022

1
2
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
+ -
1 2 2

1
2
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
+ - 5
24VDC 6
5
T1,6A T2,5A 6
132.5

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

162 80 (module 1)
105 (module 2)

150 (module 4)

Mounting rail
24VDC T2,5A T1,6A to DIN EN 50022
+ - + -
1 2 3 4 43 44 H101 5 5 6 6

Backplane V17111-3 _ _ B-Nr:17111-330


Sach-Nr:xxxxxxxx

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
132.5

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

323 80 (module 1)
105 (module 2)

150 (module 4)

Backplane V17111-6 _ _
11

24 V DC
+ - + -
10.3
10.6

12.3
12.6
13.3
13.6
14.3
14.6
15.3
15.6
16.3
16.6
17.3
17.6
18.3
18.6
19.3
19.6
20.3
20.6
21.3
21.6
11.3
11.6

1
1.3
1.6
2.3
2.6
3.3
3.6
4.3
4.6
5.3
5.6
6.3
6.6
7.3
7.6
8.3
8.6
9.3
9.6

1 2 3 4 43 44
1
2

T2A 5 5 6 6

2
10.4
10.5

12.4
12.5
13.4
13.5
14.4
14.5
15.4
15.5
16.4
16.5
17.4
17.5
18.4
18.5
19.4
19.5
20.4
20.5
21.4
21.5
11.4
11.5
1.4
1.5
2.4
2.5
3.4
3.5
4.4
4.5
5.4
5.5
6.4
6.5
7.4
7.5
8.4
8.5
9.4
9.5
1
2

T3,15A

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
132.5

57.15

14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16 14 15 16

11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13 11 12 13

425 80 (module 1)
465 105 (module 2)

482.6 150 (module 4)

105

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Accessories

Cross Wiring Module V17191-11

Straight Through Module V17191-12

FSK Bus Amplifier 16, 21, 32 channels V17191-16, -21, -32

Programming Software for Contrans I 7957781

System Cables SUB D connector, single 0336935V

Power Supply V17212-1_0

12.00 107
Cross Wiring Module V17191-11

■ Connection multiplication
■ Various types of cabling
■ Routing of incoming and outgoing lines
■ Separation between intrinsically safe and
non-intrinsically safe circuits

Module size 2
Module fits for:
Input Socket Backplane
Connection Terminals 12, 13, 14, 15, 16 V17111-11 ● V17111-2 _ _ ●
intrinsically safe and V17111-12 ● V17111-3 _ _ ●
non-intrinsically safe circuits V17111-13 ● V17111-6 _ _ ●
Routing DIP switches S11...S17

Output 1 2 3 4 5 6

Connection Terminals 1, 2, 3, 4, 5, 6
S1 S3
non-intrinsically safe circuits
Routing jumpers S1...S7
S2 S5 S4
S6
S7

S17
S16

S12 S15 S14

S11 S13

11 12 13 14 15 16

108

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Straight Through Modules V17191-12

■ Plug-in modules for testing (straight-through)


■ User-specific application through universal
circuit board
■ Not suitable for intrinsically safe
applications

Module size 2
Module fits for:
Input Socket Backplane
Connection Terminals 12, 13, 14, 15, 16 V17111-11 ● V17111-2 _ _ ●
V17111-12 ● V17111-3 _ _ ●
Output V17111-13 ● V17111-6 _ _ ●
Connection Terminals 1, 2, 3, 4, 5, 6

1 2 3 4 5 6

11 12 13 14 15 16

109

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
110

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
FSK Bus Amplifier V17191-16, -21, -32
16, 21, 32 channels

■ FSK bus design Contrans I modules on standard


backplane 20
21

■ Bidirectional transmission of FSK signals 22


23
24

according to HART protocol 25

V17191-32
26
27

■ Cost-effective centralized operation 28


29
30

■ Communication with intelligent field units


31
32
33
34
via IBIS or SMART VISION 35
36
37

Output (FSK bus)


Interconnection per FSK bus max. 100 FSK bus amplifier 19.2...30 V DC FSK bus
(max. 50 FSK bus amplifier
V17191-32) 17 36 37 18 19
Signal level min. 140 mVss...2.0 Vss max. + - -
Line length max. 1000 m

Input FSK
gn
Signal level min. 140 mVss...2.0 Vss max.
Baudrate 1200 bit/s
Line length max. 2 m

General data
Transmission frequency logical 1: 1200 Hz ± 1 %
logical 0: 2200 Hz ± 1 %
Display green LED, power supply „On“
Max. ambient temperature -20...+60 °C
Weight 90 g
Power supply
Connection Terminals 1(+); 2(-)
Rated voltage 19.2...30 V DC
Power consumption approx. 0.8 W
(V17191-16) 1 2 15 16
(V17191-21) 1 2.........16 20.........23 24
Notice:
(V17191-32) 1 2.........16 20.........34 35
The FSK bus is operated with the help of the IBIS or SMART VISION soft-
ware. Field units which are to participated on the FSK bus are addressed via
a bus code. During the first commissioning, it must be ensured that the bus
code has been set to point operation. This means connecting the modem to
the terminals of the respective Contrans I module. For the point to point
operation mode, the connection to the FSK bus must be interrupted (pull out Contrans I modules
the FSK bus amplifier).

Accessories for the FSK bus communication:


– Personal computer with IBIS software of the connected field unit
– FSK modem with connecting cable, Catalog No. 11491-0343705
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
28
10
29
11
30
12
31
13
32
14
33
15
34
16
35
17
36
18
37
19

111

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
FSK Bus Amplifier V17191-16, -21, -32
16, 21, 32 channels

Ordering information Catalog No.


FSK bus amplifier V17191-_ _
16 channels 16
21 channels 21
32 channels 32

112

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Programming Software 7957781
for Contrans I

■ Parameter setting and displaying measured values all


parameters for the devices V17151-43_, V17152-31_, V17152-62_1)
■ All informations on one screen view
■ Online and offline parameterization via PC
and LCI adapter

1) For the definition of all parameters use SMART VISION

Menu-points
Headline: edit file, store file, load datas /save datas from the device,
connection/disconnection to the device, output-simulation,
select COM-port (option), select language (option)
Footline: displayed status informations, green LED
(communication all right), date, time

Device data
All informations which mark the device
(device type, serial number, date of programming,
Measurement tag), max. 32 characters)

Measurement data input window


All datas which descripe the input values of the device:
sensor type (Pt 100), Sensor connection (2-/3-/4-wire),
reference junction for thermocouple (internal, external, without),
measured mode (differential or average)

Measured Value/Status
Online informations:
measured value, unit and percent of output-range
status of the device

Measurement data output window


All datas which descripe the output values of the device:
output range, output at failure (e.g. overranging 22 mA),
output-behaviour at failure (e.g. wire-break),
relays controlled values (alarm limits)

PC requirements (min.)
PC with Intel processor 80486, 66 MHz, 8 MB RAM, 8 MB hard drive
capacity, operating system Windows 3.1x or higher
113

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
System Cables 0336935V
SUB D plug, one-sided

1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
28
10
29
11
30
Cables with shield 20 x 2 x 0,14-SN-GR 12
13
31
32
14
33
15
34
16
35
17
36
18
37
19

L=1m+n

Pinout

Cables ERNI plug Cables ERNI plug

green-black white-grey 9
17 24 V+ channel 9
yellow-black grey-brown 28
36 0V
grey-blue 37 0V
white-pink 10 channel 10
white 1 pink-brown 29
brown channel 1
20
white-blue 11
brown-blue channel 11
green 2 channel 2 30
yellow 21
white-red 12
brown-red channel 12
grey 3 31
pink channel 3
22
white-black 13 channel 13
blue 4 channel 4 brown-black 32
red 23
grey-green 14 channel 14
black 5 yellow-grey 33
channel 5
violet 24
pink-green 15 channel 15
grey-pink 6 yellow-pink 34
channel 6
red-blue 25
green-blue 16
yellow-blue channel 16
white-green 7 35
channel 7
brown-green 26
green-red 18
white-yellow 8 yellow-red 19
channel 8
yellow-brown 27
pink-blue free
grey-red free
Don´t connect shield pink-red free

114

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Power Supply V17212-1_0

■ Power supply for Contrans I modules


■ Termination at front
■ Top-hat rail mounting

Input
Input voltage 115/230 V AC +15 %, -20 %
selectable
Alternating voltage 47...63 Hz; 1.3/0.7 A
Direct voltage 100...375 V DC at 50 % output current
External circuit breaker 10 A (characteristic B proposed)
Internal fuse not reachable

Output
Rated voltage 24 V DC +5 %; -1 % Dimensional drawings (dimensions in mm)
Buffer time
Type output current at 196 V AC 1)

V17212-110 2.5 A > 20 ms


V17212-120 5A > 37 ms
V17212-130 10 A > 20 ms
Tolerance better than 1 %
Residual ripple < 25 mV (peak-to-peak) N L

General data
LED display Power “On“ (green)

84
LED switch off at < 12 V output voltage
Electrical connections Screw terminals at front, input at bottom,
output at top
Type of protection IP 20
Distance between 2 supplies approx. 25 mm
Mounting type at 35 mm DIN rail, acc. DIN EN 50 022
Weight
Type V17212-110 406 g 1) V17212-110 = 50 mm
1) V17212-120 = 65 mm
Type V17212-120 620 g 1)
V17212-130 = 122 mm
Type V17212-130 1050 g
102
Performance under reference conditions
94
Max. ambient temperature -10...+60 °C
62
62

5
4

99

115

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Mounting and Installation Instructions

Safety Instructions

Encoding

12.00 117
Safety Instructions

Correct and safe operation of Contrans I calls for appropriate ■ Before switching on devices of the protection class III, it must
transportation and storage, expert installation and commission- be ascertained that the power source has a functional extra-
ing as well as correct operation and meticulous maintenance. low voltage with an electrical isolation corresponding to the
existing provisions.
Only those persons conversant with the installation, commis-
sioning, operation and maintenance of similar apparatuses and ■ When opening covers or removing parts, except when this is
who posses the necessary qualifications are allowed to work on manually possible, live parts may be exposed.
Contrans I. ■ The apparatus shall be disconnected from all voltage
sources before it is opened for any operations. Operations
Contrans I has been designed and tested in conform with on the opened apparatus under voltage must only be
EN 61010-1 or DIN VDE 0411, Part 1 “Safety requirements for performed by an expert, who is aware of the hazard
electrical process control units, instrumentation and laboratory involved.
devices“, overvoltage category II, pollution class 2 and has been
supplied in a safe condition. ■ Whenever it is likely that the protection has been impaired,
the apparatus shall be made inoperative and be secured
In order to retain this condition and to ensure safe operation, the against any unintended operation.
following safety instructions must be observed. Otherwise,
persons can be endangered and the Contrans I components
themselves as well as other equipment and facilities can be
demaged. Apart from the technical documentation in this catalog, the
following must also be observed:
■ Before plugging the module into the socket, care must be ■ The safety regulations pertaining to the installation and
taken to ensure that the socket circuitry agrees with that of operation of electrical systems,
the connecting diagram. For voltages > 50 V AC or 120 V DC
the terminals must be market with the rated voltage or the ■ the directives and guidelines on explosion protection.
socket must be coded. The coding or marking must corre-
spond th the “Mounting and Installation Instructions“. If the information supplied in this catalog should prove to be
insufficient, the ABB service department will be pleased to
■ For voltages higher than 50 V AC/120 V DC, the insulation provide you with more information.
lengths of terminal wires must be between 5...6 mm. If more
flexible lines are used, the end ferrules used should have
these lengths.

118 12.00
Encoding

Unintentional assignment of wrong functions can be prevented with


Functional diagram for coding (suggestion)
coded modules
Partial view of socket
Encoding pin
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Type group 1 8

> 50 V AC/120 V DC
2 9

Contrans I_remote
3 10
4 11
5 12
Type group
Type group
Type group
Type group
Type group
> 50 V AC/120 V DC 6 13 Type
Contrans I_remote 7 14 Ex

Type
Type
Type
Type
Type
Type
Ex
Binary modules: Switch amplifier
V17131-13 ● ●
V17131-16 ● ● Example of coding (type V17131-1x)
V17131-51 ● ❍ ● ● Encoding star with 4 encoding pins
● ❍ ● ●
(part of supply for socket/backplane)
V17131-52
V17131-53 ● ❍ ● ●
V17131-54 ● ● ●
V17131-55 ● ● ●
V17131-56 ● ● ●
Binary modules: Solenoid drivers
V17132-51 ● ● ●
V17132-52 ● ● ●
break off
V17132-53 ● ● ●
V17132-54 ● ● ●
V17132-55 ● ● ●
V17132-56 ● ● ●
Binary modules: Coupling modules x
1
2
V17133-11 ● ● 3

V17133-21 ● ❍ ● 4
5

V17133-510 ● ● ● plug in 6
7

Analog modules: Input isolators


V17151-100 ● ● ●
V17151-11 ● ●
V17151-13 ● ●
V17151-210 ● ●
V17151-211 ● ● ●
V17151-212 ● ● ●
V17151-213 ● ● ●
V17151-220 ● ●
V17151-221 ● ● ●
V17151-222 ● ● ●
V17151-320 ● ●
V17151-325 ● ●
V17151-340 ● ●
V17151-350 ● ●
V17151-413 ● ●
V17151-420 ● ●
V17151-430 ● ❍ ●
V17151-432 ● ❍ ● ●
V17151-433 ● ❍ ● ●
V17151-434 ● ❍ ● ●
V17151-480 ● ❍ ● ●
V17151-51 ● ● ●
V17151-52 ● ● ●
V17151-610 ● ● ●
V17151-611 ● ● ● ●
V17151-612 ● ● ● ●
V17151-613 ● ● ● ●
V17151-620 ● ● ●
V17151-621 ● ● ● ●

❍ = only when voltages > 50 V AC or 120 V DC are connected


119

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
Encoding

Unintentional assignment of wrong functions can be prevented with


Functional diagram for coding (suggestion)
coded modules
Partial view of socket
Encoding pin
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Type group 1 8

> 50 V AC/120 V DC
2 9

Contrans I_remote
3 10
4 11
5 12
Type group
Type group
Type group
Type group
Type group
> 50 V AC/120 V DC 6 13 Type
Contrans I_remote 7 14 Ex

Type
Type
Type
Type
Type
Type
Ex
Analog modules: Input isolators
V17151-622 ● ● ● ●
V17151-720 ● ● ● Example of coding (type V17131-1x)
● ● ●
Encoding star with 4 encoding pins
V17151-725
(part of supply for socket/backplane)
V17151-740 ● ● ●
V17151-745 ● ● ●
V17151-750 ● ● ●
V17151-755 ● ● ●
V17151-820 ● ● ●
V17151-825 ● ● ●
V17151-840 ● ● ●
V17151-845 ● ● ●
break off
Analog modules: Transmitters
V17152-310 ● ❍ ●
V17152-311 ● ❍ ●
V17152-312 ● ❍ ●
V17152-313 ● ❍ ● x
1


2
V17152-314 ● ● 3

V17152-611 ● ● ● ● 4
5

V17152-612 ● ● ● ● plug in 6
7

V17152-613 ● ● ● ●
V17152-614 ● ● ● ●
V17152-619 ● ● ● ●
V17152-620 ● ❍ ● ●
V17152-621 ● ❍ ● ●
V17152-622 ● ❍ ● ●
V17152-623 ● ❍ ● ●
V17152-624 ● ❍ ● ●
Analog modules: Output isolators
V17153-11 ● ● ●
V17153-115 ● ● ● ●
V17153-13 ● ● ●
V17153-21 ● ● ●
V17153-22 ● ● ●
V17153-420 ● ● ●
V17153-51 ● ● ● ●
V17153-515 ● ● ● ●
V17153-52 ● ● ● ●
V17153-61 ● ● ● ●
V17153-62 ● ● ● ●
V17153-820 ● ● ● ●
V17153-825 ● ● ● ●
V17153-840 ● ● ● ●
V17153-845 ● ● ● ●
Signalling and monitoring modules: Trip ampfifier
V17171-11 ● ● ●

Accessories
V17191-11 ● ● ●
V17191-12 ● ● ●

❍ = only when voltages > 50 V AC or 120 V DC are connected


120

ABB Automation Products GmbH · Borsigstr. 2 · D-63755 Alzenau · Phone +49(0)60 23 - 92 0 · Fax +49(0)60 23 - 92 33 00 · http://www.abb.com/automation
Subject to technical changes. Printed in the Fed. Rep. of Germany 12.00
ABB Automation Products GmbH
Borsigstr. 2, D-63755 Alzenau
Phone +49 (0) 6023 92 0, Fax +49 (0) 6023 92 3430
www.abb.com/automation 04/17.1 EN 11.00