HERZ Valve Actuator: Dimensions in MM
HERZ Valve Actuator: Dimensions in MM
0510480003, 0510480004
RD BN BK GN GY VT HERZ Actuators
RD = red/rot
HERZ Valve actuator
BN = brown/braun
BK = black/schwarz
GN = green/grün
GY = grey/grau
Datasheet 7712 28, 29, Issue 0620
VT = violet/violett
Dimensions in mm
62.7
79.1
70 145.5
Models
1 7712 28 Valve actuator
Actuating Power 500 N, Voltage AC 230 V, Control: 2-/3-point
Running time: 7,5 s/mm, Power consumption: 3,2 W, 7 VA / 2 W, 5 VA
Technical Data
Weight 1 kg
Housing Lower section black, Upper section red
Page 28
HERZ Actuators
1 7712 28:
Supply voltage 230 V~ ±15%, 50...60 Hz
Power consumption 2 W; 5 VA
Control 2-/3-point
CE conformity according to
EMV-directive 2014/30/EU EN 61000-6-1, EN 61000-6-2
EN 61000-6-3, EN 61000-6-4
Low-Voltage Directive EN 60730-1, EN 60730-2-14 2014/35/EU
Over-voltage category III
Degree of contamination II
Mach. directive 2006/42/EG EN ISO 12100 (according to appendix IIB)
1 7712 29:
Power supply
Supply voltage 24 V~ ±20%, 50...60 Hz
Supply voltage 24 V= -10%...20%
Power consumption 3,5 W, 6,6 VA; 2,7 W, 5,3 VA
Positioner
Control signal y 0...10 V, Ri > 100 kΩ
Positional feedback signal 0...10 V, load > 10 kΩ
Starting point U0 0 V or 10 V
Control Span ΔU 10 V
Switching range Xsh 200 mV
CE conformity according to
EMC-directive 2014/30/EU EN 61000-6-1, EN 61000-6-3, EN 61000-6-4
Page 29
HERZ Actuators
Description of operation
1 7712 28:
When voltage is applied to the cable, the control unit to be activated is moved to any desired position by
means of the coupling rod.
Direction of the stroke for 2-point control (there is always voltage on the black cable 02):
• The coupling rod moves out and the valve opens when the actuator is connected to the voltage via the
blue (MM/N) and brown (01) cables.
• The coupling rod moves in and the valve closes when the actuator is connected to the voltage via the blue
(MM/N) cable, and the brown (01) cable is not connected to the voltage. In the end positions (limit stop in
valve or maximum stroke reached) or in the case of an overload, the magnetic coupling is activated. The
electronic cut-out switches off the positioning signal after approx. 3 minutes.
The manual adjustment is performed in the load-free state by releasing the gear unit (slide switch beside
the connection cable) and simultaneously turning it with the hexagon key on the top part of the actuator.
20 mm stroke is achieved with 4 turns. The actuator position can be determined by looking at the actuator
bracket or the indicator knob on the top part of the actuator.
1 7712 29:
This valve actuator is used to control valves and may only be used for this purpose.
Depending on the type of connection (see connection diagram), the actuator can be used as a continuous
0...10 V, 2-point (OPEN/CLOSE) or 3-point actuator (OPEN/STOP/CLOSE) with an intermediate position.
2 running times are available for selection.
Switch S3 can be used to select the equal-percentage or linear characteristic. The 1 7712 29 is combined
with valves that have an equal-percentage basic characteristic. The 1 7712 29 can be mounted on a valve
with a linear characteristic, but the position of the coding switch must be considered.
The manual adjustment is performed in the load-free state by releasing the gear unit (slide switch beside
the connection cable) and simultaneously turning it with the hex spanner on the top part of the
actuator. 20 mm stroke is achieved with 4 turns.
Attention!
Damage to device!
►After the manual adjustment, the slide switch must be put back into its original position. (Engage gear
unit)
Description of operation
1 7712 28:
The upper section of the housing with the cover and indicator knob contains the synchronous motor with
capacitor. The lower section of the housing contains the maintenance-free gear unit and the gear-release
knob.
Page 30
Type Running time [s/mm] Status Active power P [W] Apparent power S
AVM215F120 7.5 Operation 2.0 5.0
Connection
Connection diagram diagram
1 7712 28
2pt 3pt
F..0 = 230 V~ F..0 = 230 V~
MM/N 01 02 MM/N 01 02
A10763
Accessories
Connection diagram 1 7712 29
Connection as 2-point actuator
0510480003, 0510480004
This OPEN/CLOSE activation can be performed via 2 cables. The actuator is connected to the voltage via
the blue and brown RD cables. The control passage of the valve is opened by connecting the voltage to the
BN BK GN GY VT
black cable. After this voltage is switched off, the actuator moves to the opposite end position and closes
the valve.
The unused red and grey wires must not be connected or come into contact with other cables. We
recommend that you insulate these.
RD = red
BN = brown
Connection as 3-point
BK =control
black unit
When voltage is applied to the cable (brown or black), the valve is moved to any desired position. The
GN = green
coupling rod movesGY
out and opens the valve when voltage is applied to the black cable. It moves in and
= grey
closes the valve when
VT = the
violetelectrical circuit is closed via the blue and brown cables. In the end positions
(limit stop in valve or maximum stroke reached) or in the case of an overload, the electronic motor cut-off is
activated (no limit switches). Direction of the stroke changed by transposing the connections (BN/BK). The
unused red and grey wires must not be connected or come into contact with other cables. We recommend
that you insulate these.
Page 31
HERZ Actuators
Product data sheet 1.1
Thanks to the electronics, no steps can be lost, and the actuator does not require periodic re-adjustment.
After the power supply is connected, the stepping motor moves to the lower limit stop, makes the con-
It is possible to operate multiple
nection with actuators
the valve of the to
spindle, moves same typelimit
the upper in parallel.
stop and The feedback
thus defines signal position.
the closing y0 = 0...10 V
corresponds to the effective stroke.
After this, every stroke between 0 and 20 mm can be achieved, depending on the control voltage.
When control signal Thanks0…10
to theVelectronics,
is interrupted andcan
no steps direction of operation
be lost, and the actuator1does
is connected, the valve
not require periodic is closed
re-adjust-
completely (0% position).
ment. It is possible to operate multiple actuators of the same type in parallel. The feedback signal y0
The coding switch canVbe
= 0...10 used to toselect
corresponds the characteristic
the effective stroke. of the valve. Characteristics can only be
When control signal 0…10
generated when the actuator is used as a continuous
Product data sheet V is interrupted andactuator.
direction
1.1 of operation 1 is connected, the valve is
The running times can be selected with 51.383
Power consumption
Type Running time [s/mm] Status Active power P [W] Apparent power S [VA]
AVM215SF132R 7.5 / 15 Operation 3.5 / 2.7 6.6 / 5.3
Standstill 0.35 0.75
Accessories
0510480003, 0510480004
RD BN BK GN GY VT
RD = red/rot
BN = brown/braun
BK = black/schwarz
GN = green/grün
GY = grey/grau
Connection diagram 1 7712 29
VT = violet/violett
Condensate, dripping water, etc. must be prevented from entering the actuator along the valve spindle.
Hanging position (fitting upside down) is not admissible.
The coupling of the valve spindle with the actuator spindle is performed semi-automatically using the
manual adjuster.
Dimension drawing
When dismantling, first the actuator and valve spindles are released, then unscrewed. The concept of
synchronous motor and magnetic coupling enables parallel operation of multiple valve actuators of the
same type.
79.1
62.7
79.1
The auxiliary contacts accessory is screwed onto the side of the device.
Caution!
When the housing is opened there is a risk of injury through electric shock.
Opening the
70
housing can damage the device. 145.5
Page 32