Desigo Automation System With PLlink Device Table
Desigo Automation System With PLlink Device Table
2022-05-11
Copyright
Copyright
Delivery and technical specifications subject to change.
Any form of reproduction, dissemination, copying, disclosure, modification, distribution and/or publication of this
document is strictly prohibited unless permitted expressly. Infringements will lead to compensation. All rights,
including rights created by patent grant or registration of a utility model or design are reserved.
Published by:
Siemens Switzerland Ltd.
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2022-05-11
Document ID: CM110664en_10
2 | 346 CM110664en_10
Table of Contents
CM110664en_10 3 | 346
8 Events and COV reporting .................................................................................................................123
8.1 Sources and causes of system events .................................................................................................123
8.2 Routing system events .........................................................................................................................123
8.3 Sources and causes of COVs ..............................................................................................................124
8.4 COV reporting ......................................................................................................................................124
9 Alarm management............................................................................................................................127
9.1 Alarm sources ......................................................................................................................................127
9.2 Alarm example .....................................................................................................................................129
9.3 Effects of BACnet properties on alarm response ..................................................................................131
9.4 Alarm response of the function blocks ..................................................................................................138
9.5 Alarm functions ....................................................................................................................................145
9.6 Alarm management by notification class...............................................................................................147
9.7 Alarm routing over the network.............................................................................................................151
9.8 Alarm queuing...................................................................................................................................... 153
9.9 Common alarms ..................................................................................................................................155
9.10 Alarm suppression ...............................................................................................................................156
9.11 Alarm message texts............................................................................................................................157
10 Calendars and schedulers .................................................................................................................159
10.1 Schedule .............................................................................................................................................160
10.2 Calendar ..............................................................................................................................................164
10.3 Wildcards .............................................................................................................................................165
10.4 Alarm messages ..................................................................................................................................165
11 Trending .............................................................................................................................................166
11.1 Trend functions ....................................................................................................................................166
11.2 Editing parameters ...............................................................................................................................168
11.3 Processing trend data in Desigo CC .....................................................................................................169
12 Reports ...............................................................................................................................................170
13 Data storage .......................................................................................................................................171
13.1 Data categories....................................................................................................................................171
13.2 Program data .......................................................................................................................................171
13.3 Libraries ...............................................................................................................................................172
13.4 Project data .........................................................................................................................................173
13.5 Plant data ............................................................................................................................................174
13.6 Data transfer processes .......................................................................................................................174
13.7 Texts ...................................................................................................................................................176
14 Network architecture .........................................................................................................................177
14.1 BACnet architecture (MLN & ALN) .......................................................................................................177
14.2 LonWorks architecture (ALN) ...............................................................................................................188
14.3 KNX architecture (ALN)........................................................................................................................190
14.4 KNX PL-Link architecture (FLN) ...........................................................................................................191
14.5 DALI architecture (FLN) .......................................................................................................................192
15 Remote access ...................................................................................................................................194
15.1 Remote access methods ......................................................................................................................194
15.2 Choosing a suitable access technology ................................................................................................195
15.3 Technical details ..................................................................................................................................196
16 Management platform ........................................................................................................................198
4 | 346 CM110664en_10
16.1 User functions ......................................................................................................................................200
16.2 Main components.................................................................................................................................202
16.3 Access and security .............................................................................................................................203
16.4 Event management ..............................................................................................................................204
16.5 Installation, setup and engineering .......................................................................................................205
16.6 Graphics libraries .................................................................................................................................207
16.7 Graphics engineering ...........................................................................................................................208
16.8 Virtual environment ..............................................................................................................................210
17 Desigo Control Point..........................................................................................................................211
17.1 Functions .............................................................................................................................................212
18 Automation stations ..........................................................................................................................216
18.1 Device object .......................................................................................................................................217
18.2 Device info object.................................................................................................................................218
18.3 Error sources and monitoring functions ................................................................................................219
18.4 Operating states...................................................................................................................................220
18.5 Data storage ........................................................................................................................................224
19 Logical I/O blocks ..............................................................................................................................226
19.1 General functions .................................................................................................................................226
19.2 Input blocks..........................................................................................................................................241
19.3 Output blocks .......................................................................................................................................243
19.4 Value objects .......................................................................................................................................246
19.5 Value objects for operation ...................................................................................................................249
19.6 Addressing the I/O blocks ....................................................................................................................249
19.7 Discipline I/Os ......................................................................................................................................258
19.8 Reliability table .....................................................................................................................................259
19.9 Slope [Slpe] and Intercept [Icpt]............................................................................................................260
19.10 Addressing entries for PXC…-U, PTM and P-Bus.................................................................................266
20 Room automation...............................................................................................................................272
20.1 Desigo room automation ......................................................................................................................272
20.1.1 Configurable.............................................................................................................................273
20.1.2 Programmable .........................................................................................................................282
20.1.3 Rooms and room segments......................................................................................................285
20.1.4 Central control functions and grouping......................................................................................286
20.1.5 Desigo room automation and the management level.................................................................287
20.1.6 Desigo room automation and the automation level....................................................................287
20.2 Desigo RXB .........................................................................................................................................287
20.2.1 Product range overview ............................................................................................................288
20.2.2 RXB and the management level ...............................................................................................289
20.2.3 RXB and the automation level ..................................................................................................290
20.2.4 RXB applications ......................................................................................................................290
20.2.5 Mapping RXB in the PX KNX system controller ........................................................................290
21 Desigo Open.......................................................................................................................................291
21.1 Integration on management level .........................................................................................................292
21.2 Integration on automation level.............................................................................................................293
21.3 Integration on field level .......................................................................................................................295
21.4 Integration on room level ......................................................................................................................296
CM110664en_10 5 | 346
22 System configuration ........................................................................................................................297
22.1 Technical limits and limit values ...........................................................................................................299
22.2 Maximum number of elements in a network area..................................................................................300
22.3 Desigo room automation system function group limits ..........................................................................301
22.4 Devices................................................................................................................................................302
22.4.1 PXC..D automation stations / system controllers.......................................................................302
22.4.2 LonWorks system controllers....................................................................................................305
22.4.3 Automation stations with LonWorks integration .........................................................................305
22.4.4 PX Open integration (PXC001.D/-E.D) .....................................................................................306
22.4.5 PX Open integration (PXC001.D/-E.D + PXA40-RS1)............................................................... 306
22.4.6 PX Open integration (PXC001.D/-E.D + PXA40-RS2)............................................................... 306
22.4.7 PX KNX integration (PXC001.D/-E.D).......................................................................................306
22.4.8 TX Open integration (TXI1/2/2-S.OPEN) ..................................................................................306
22.4.9 Number of data points on Desigo room automation stations ..................................................... 307
22.4.10 Number of data points for PXC3 ...............................................................................................309
22.4.11 Number of data points for DXR1...............................................................................................309
22.4.12 Number of data points for DXR2...............................................................................................310
22.4.13 PXM20 operator unit ................................................................................................................311
22.4.14 PXM10 operator unit ................................................................................................................311
22.4.15 Desigo Control Point ................................................................................................................311
22.4.16 PXG3.L and PXG3.M BACnet routers ......................................................................................314
22.4.17 SX OPC ...................................................................................................................................314
22.4.18 Desigo CC ...............................................................................................................................315
22.4.19 Desigo Insight ..........................................................................................................................315
22.4.20 Desigo Xworks Plus (XWP) ......................................................................................................315
22.4.21 Desigo Automation Building Tool (ABT)....................................................................................316
22.5 Applications .........................................................................................................................................316
22.5.1 Peak Demand Limiting (PDL) ...................................................................................................316
23 Compatibility ......................................................................................................................................317
23.1 Desigo version compatibility definition ..................................................................................................317
23.2 Desigo system compatibility basics ......................................................................................................318
23.2.1 Compatibility with BACnet standard ..........................................................................................318
23.2.2 Compatibility with operating systems ........................................................................................319
23.2.3 Compatibility with SQL servers .................................................................................................320
23.2.4 Compatibility with Microsoft Office ............................................................................................320
23.2.5 Compatibility with web browsers ...............................................................................................320
23.2.6 Compatibility with ABT Go ........................................................................................................321
23.2.7 Compatibility with VMware (virtual infrastructure)...................................................................... 321
23.2.8 Compatibility of software/libraries on the same PC ................................................................... 321
23.2.9 Hardware and firmware compatibility ........................................................................................321
23.2.10 Backward compatibility .............................................................................................................322
23.2.11 Engineering compatibility..........................................................................................................322
23.2.12 Compatibility with Desigo Configuration Module (DCM) ............................................................ 322
23.2.13 Compatibility with Desigo PX / Desigo room automation ........................................................... 322
23.2.14 Compatibility with Desigo RX tool .............................................................................................322
23.2.15 Compatibility with TX-I/O ..........................................................................................................323
23.2.16 Compatibility with TX Open ......................................................................................................323
6 | 346 CM110664en_10
23.2.17 KNX PL-Link devices in ABT Site and ABT Pro ........................................................................324
23.3 Desigo Control Point ............................................................................................................................335
23.3.1 Compatibility with earlier systems .............................................................................................335
23.3.2 Compatibility with earlier devices ..............................................................................................335
23.3.3 Supported browsers .................................................................................................................336
23.4 Upgrading to Desigo V6.3 ....................................................................................................................337
23.4.1 Upgrading for Tool and Localization Managers in the Regional Companies (RC) ......................337
23.4.2 Upgrading for Project Engineers ...............................................................................................337
23.4.3 Upgrading restrictions ..............................................................................................................339
23.5 Siemens WEoF clients .........................................................................................................................339
23.6 Migration compatibility ..........................................................................................................................339
23.7 Hardware requirements of Desigo software products ............................................................................340
24 Desigo PXC4 and PXC5 .....................................................................................................................342
25 Compatibility of Desigo V6.3 with PXC4 and PXC5 ..........................................................................343
CM110664en_10 7 | 346
Cyber security disclaimer 1
CM110664en_10 9 | 346
2 Preconditions of this document
Document structure
This document is split into two parts:
● Chapter 3 to 23: Desigo System V6.3
● Chapter 24: Desigo PXC4 and PXC5 range overview and planning overview
● Chapter 25: Compatibility between Desigo System V6.3 and Desigo PXC4 and PXC5
10 | 346 CM110664en_10
System overview 3
Management level
3 System overview
The Desigo building automation and control system has three levels:
● Management level
● Automation level
● Field level
Desigo
Control
Point
BACnet/IP
Room Desigo
automation Room
Automation
Desigo RXB
KNX
CM110664en_10 11 | 346
3 System overview
Management level
Task Activity
Observing the operational status of the plant or Reading current values of all process variables, data objects and parameter
building settings
Receiving and acknowledging alarms
Overview of all pending alarms
Recording and analyzing trends
Observing the operational status of the building Overview of failed automation stations and network interruptions
automation and control system Signaling of anormal hardware or software states in an automation station or in
the associated field devices
Manipulating the operational status of the plant or Modifying parameter settings (e.g., setpoints of control programs)
building Setting values for physical outputs of automation stations
Modifying system and management objects, especially calendars and time
schedules
Management platform
Desigo CC can be installed on one computer, with full server and client functionality, or on several separate
computers. Web Clients, Windows App (ClickOnce) Clients and installed Clients can be added.
12 | 346 CM110664en_10
System overview 3
Management level
Remote management
Desigo CC can operate and monitor the automation level via a public network.
CM110664en_10 13 | 346
3 System overview
Automation level
14 | 346 CM110664en_10
System overview 3
Automation level
CM110664en_10 15 | 346
3 System overview
Room automation
16 | 346 CM110664en_10
System overview 3
Field level
The DXR2.. room automation stations have an integrated web server for IP communication with touch room
operator units. Engineering access is available via the web interface.
Desigo RXB
The RXB room controllers control the room climate in individual rooms and important parameters of the
applications can be configured.
The RXB room controllers communicate via KNX.
The PX KNX system controller connects the room automation devices to Desigo PX and the management level
and assumes coordination functions for room automation (grouping, scheduling, demand signal exchange, peer-
to-peer, etc.).
CM110664en_10 17 | 346
3 System overview
Desigo Open
18 | 346 CM110664en_10
System overview 3
Workflow and tools
Preloaded applications
Some automation stations contain preloaded applications, but are also freely programmable. A comprehensive
library of proven, standardized applications is available and can be used instead of the preloaded applications.
CM110664en_10 19 | 346
3 System overview
Topologies
3.7 Topologies
Small system on BACnet/IP
Web client
Desigo Control Point
@
BACnet/IP Ethernet
iValve Third-party
integration
BACnet/LonTalk
Third-party
integration
20 | 346 CM110664en_10
System overview 3
Topologies
Medium system
Desigo CC
Web client Desigo Control Point
BACnet/IP Ethernet
PXM30/40/50
Touch panel
DXR2.E...
Room automation BACnet/LonTalk KNX
°C
°C
Third-party
integration
Large system
E-Mail
Pager Desigo CC
DSL-
Modem
BACnet/IP Ethernet
PXC12/22/36-E.D PXC50/100/ TXI... PXG3.W100/200-1 PXG3.L PXC001-E.D PXC001-E.D PXG3.M BACnet DXR1
Compact 200-E.D TX Open Web interface Router System controller System controller Router Third-party Sinteso
Modular integration CERBERUS PRO
BACnet/LonTalk
Remote access
DSL modem
BACnet/IP
LONWORKS PXC12/22/36.D PXC50/100/ TX-IO
Third-party Compact 200.D Modules BACnet MS/TP
devices Modular
PXC50/100/
200-E.D
Modular
DALI
Third-party devices
KNX
° C C
° ° C
°C °C °C
PX site
PX site is a means of structuring large PX projects. Desigo room automation stations are not part of a PX site.
In a PX site one PX automation station is defined as the primary server and all other PX automation stations are
defined as backup servers. Every automation station can be defined as the primary server.
The primary server carries out system functions, such as time synchronization, life check and the distribution of
global data:
CM110664en_10 21 | 346
3 System overview
Communication principles
● Time synchronization: The primary server distributes the current time to the backup devices.
● Life check: The backup servers detect the failure of the primary server and the primary server detects the
failure of the backup servers. If a server fails, an alarm message is sent. If the primary server fails, another
automation station must be defined manually as the primary server.
● Distribution of global data: Global objects are available on all PX automation stations. The primary server
synchronizes changes, e.g., calendar object, notification class object, that are made on the primary server to
the backup servers.
BACnet
BACnet (Building Automation and Control Networks) is a communications protocol for building automation and
control networks. BACnet ensures the interoperability between devices from different manufacturers.
See http://en.wikipedia.org/wiki/BACnet.
VendorID
Each BACnet device has a VendorID to identify the manufacturer. The VendorID for the Siemens BACnet
system devices is 7.
Network performance
The performance of the network depends on the following criteria:
● Number of devices on the bus
● Segmentation of the topology via routers (for LonTalk bus)
● Number of simultaneously active clients
● Peer-to-peer communication resulting from distributed PX applications
● Other communications services using the same transmission medium, where, e.g., office communication on
a separate VLAN share the same IP trunk
● Application download on the network
Due to these factors, which can vary widely from project to project, it is not possible to make any generalized
statements about network performance. If the specified product quantities are adhered to, performance is
adequate.
If the network performance is not satisfactory, the following actions may help:
● Use the same automation station for items of equipment with frequent process interaction.
● Divide the network into segments via BACnet router and an Ethernet/IP backbone.
● Isolate the automation station from the network when downloading an application.
22 | 346 CM110664en_10
System overview 3
Communication principles
Client/Server
A BACnet device can assume two different roles within a system, the role as a server and the role as a client.
These roles are defined as follows:
● Client: A system or device which uses another device via a BACnet service (service request) for a specific
purpose. The client (e.g., Desigo CC, operator unit) requests a service from a server.
● Server: A system or device which responds to a given service request. The server (e.g., PXC automation
station, Desigo room automation station) performs a service for a client.
Most system devices in Desigo can act either as a client or as a server, but they normally each carry out their
more typical role. An automation station is normally a BACnet server, which supplies process data to other
system devices. The automation station can also act as a client, when it, e.g., subscribes to a process value
from another automation station.
D-MAP program
Process and
configuration Application
data process
(Visualisation)
BACnet objects
10660Z37_01_en
BACnet protocol
CM110664en_10 23 | 346
3 System overview
Data maintenance
AMEV guideline
Desigo complies with the AMEV guideline BACnet 2011 Version 1.2 with the following profiles:
● Desigo CC: AMEV profile MOU-B
● Desigo PX: AMEV profile AS-B
Desigo RX
The Desigo RXB room automation range communicates via KNX S-Mode (EIB).
24 | 346 CM110664en_10
System overview 3
Data maintenance
Process data and parameter settings can be accessed within the system via BACnet objects, e.g., Present
Value [PrVal] and Status [StaFlg], if the associated mapping is enabled in the engineering phase.
If process data is used by several automation stations, the data origin is the location where the physical variable
is measured (e.g., outdoor temperature) or generated (e.g., the control signal from a time schedule). Copies are
updated on an event-driven basis after a short delay.
Displaying process data and parameter settings
To display process data and parameter settings mapped to BACnet on clients, only one copy of the data
needed for current operation and monitoring is stored. The Desigo system does not store complete copies of
process data or parameter settings. The data (copy) required by a client is normally updated via the BACnet
protocol on an event-driven basis and with a short time delay.
All process data and parameter settings, even those that are not mapped to BACnet objects (engineering
setting), can be monitored and operated in Xworks Plus (XWP). BACnet clients only see what is available via
BACnet.
If several clients modify the same process data, the last change is accepted.
Volatile and non-volatile process data and parameter settings
The majority of the process data is volatile data, which is recalculated when the automation stations are
restarted. However, certain process data is retained even after an automation station restart, e.g., self-adaptive
control parameters, run-time totalizers, etc., which are specifically identified as such in a function block. Even in
the event of a program change, this non-volatile process data remains in memory and can be read back with
XWP.
All parameter settings are non-volatile, that is, they are retained in the event of a power failure.
Readback
All non-volatile PX process data and parameter settings can be read back into XWP. However, parameter
settings in the operator unit cannot be read back into a tool.
Global parameter settings
Some parameter settings are identical in all automation stations, e.g., date and time, calendar function blocks
and Notification Class function blocks. To ensure consistency, they are held in global objects which are
automatically replicated in the system.
Archived data
Setting parameters can be logged and archived. Archived data illustrates the response of process or system
variables or events over a time period, e.g., trend data can be moved from the trend database into archive files.
Archived data are typically lists of one or more of the aforementioned variables and are preferably stored and
processed on the management level. Only small amounts of data are archived at the automation level. Such
data is normally forwarded to the management level.
Ensuring consistency
Archived data only requires a consistency check in cases where it has been moved from one application to
another, e.g., from the automation level to the management level. The data origin is not deleted until a check
has been carried out to ensure that the data has been transferred in full. This data is stored in the non-volatile
memory.
Irregularities in the logging of archived data are recorded in the data itself.
The life of the data is determined either by the user or by a configurable application which automatically
condenses or deletes this archived data.
CM110664en_10 25 | 346
3 System overview
Data maintenance
Metadata
Metadata is project-independent data from standard BACnet objects (e.g., analog input, schedule, etc.) which
needs to be known by a tool or a client, e.g., texts for predefined BACnet enumeration, maximum size of arrays,
data-type information, fixed operating limits, etc. The metadata is loaded into the relevant clients or tools at HQ
and (except texts) cannot be modified after delivery. Text, like the text for BACnet enumeration referred to
above, must be localized (language translation) and distributed to the clients and tools. This is part of the
localization process.
D-MAP program
The D-MAP program is an executable program, and contains instances of the function blocks with the
associated process data and parameter settings, the configuration and description data and the interconnection
and order of processing of function blocks.
The D-MAP program can be modified during operation either by reloading the complete program including any
changes, or by delta (differential) loading. Delta loading only reloads the changes.
The D-MAP program is generated in XWP/ABT from the information in the program charts, compiled and
downloaded into the automation station.
Libraries (LibSet)
The Desigo Library Set (LibSet) is a set of mutually interdependent libraries that belong to a given Desigo
system version.
RXB PX KNX
Firmwareblocks
The library contents are continuously extended. Every LibSet Extension of Desigo (LED) is a comprehensively
tested collection of solutions covering all the necessary parts of the Desigo system.
The LibSet version number defines which LED runs on which system version. The first part of the version
number represents the applicable system version.
A LED includes the latest library per automation station type (PXC, PXC00(-E).D, PXX-L11/12, PXKNX) for the
latest Valid Version Set.
New LEDs are delivered at regular intervals. The individual LEDs are consecutively numbered (LED0 to
LED16).
LibSet version number
26 | 346 CM110664en_10
System overview 3
Data maintenance
DESIGO-LibSet-HQ-230020-02
LED01 PXC: Additional applications for ventilation and heat generation Desigo LibSet-HQ-220031-04 October 2003
and distribution
LED02 All RXC applications for refrigeration generation and distribution Desigo LibSet-HQ-220041-02 December 2004
LED03 PXC: Applications for refrigeration generation and distribution Desigo-Libset-HQ-220041-06 March 2004
RXC: Additional combined applications (INT..)
LED04 PXC: Air quality and domestic hot water applications and recovery Desigo-Libset-HQ-220041-08 June 2004
function after power failure
LED06 PXC: Additional applications for ventilation and domestic hot water Desigo LibSet-HQ-230010-02 January 2005
Desigo Insight: Update to genie library for Visonik, Unigyr and
Integral
LED07 PXC: Additional solutions for ventilation facilities, refrigeration Desigo-Libset-HQ-230010-06 November 2005
plants, heating functions, heating plants and universal functions
LED08 PXC: Like LED07 and compounds for QAX, RX Desigo-Libset-HQ-235040-02 November 2005
DI: Genies for lab management integration
PXR: Compounds for Lab Management integration
LED10 PXC: Heating degree days, three-point actuator, storage Desigo-Libset-HQ-235040-04 July 2006
management, adjustment of humidity control
LED11 Like LED10 and RXB and RXL integration solutions Desigo-Libset-HQ-236040-02 July 2006
LED12 PXC: Solution for combined heating/cooling circuit, room model, Desigo-Libset-HQ-237030-02 February 2007
quality monitoring of control circuits, leakage suppression Desigo-LibSet-HQ-236050-04
PX/KNX: New integration compounds
LED14 PXC: Additional applications for ventilation facilities, Desigo-LibSet-HQ-400210-10 March 2009
heating/refrigeration circuit, heating circuit
Heat storage tank and trend
CM110664en_10 27 | 346
3 System overview
Data maintenance
28 | 346 CM110664en_10
System overview 3
Data maintenance
PXC: CRS03
PXKNX: CAS10
New: Includes enhancements to the existing CAS library &
additional functionality, e.g.:
- Harmonization of CFC charts for better usability
- All plants are equipped now with trends
- 4 new burner & 5 new boiler compounds and a multi-boiler plant
with up to 8 boilers
- New logics in heating & cooling plants for power up/down
- Heating distribution for direct room control
- Improved alarming concept
- Improved plant behavior on sensor disturbance (heating
distribution and domestic hot water)
- Defects solved
NEW LED New: Includes new compound {IngtVlv1} for iValve in the PXC Fits with Desigo V6.2 Update Summer 2019
library
Key
*
The PXC3 room automation station supports several firmware versions independent of the functional content of the application
library.
Desigo CC
The application libraries for Desigo CC are delivered as extension modules for the respective system versions.
For information about compatibility, see Desigo CC System Description (A6V10415500).
CM110664en_10 29 | 346
3 System overview
Views
3.10 Views
There are four views:
● Technical view
● User view
● System view
● Program view
PXM20
10523Z05en_01
Site
BACnet
objects
Technical view
The technical view illustrates the technical building services equipment, such as HVAC systems and associated
elements, in the building automation and control system. The technical view is always present and can be used
as a substitute for the user view if the user does not have his own user designation.
User view
Freely defined and structural user view
The user view is optional in a project. The user view is based on user designations, e.g.:
PL7’FL3’ELE”HEAT.STPT
The structure and syntax of the user designations can be defined for each specific project and customer.
Example of a structure: Installation/building/room/plant element/signal
User view via the User Designation (UD)
Desigo supports different user views, depending on the application:
In Xworks Plus (XWP) a User Designation (UD) can be entered for function blocks or compounds in addition to
the Technical Designation (TD) and description. This entry is carried through in the system and can be
evaluated by clients. The UD allows customers to use their own preferred designations for the plant without
changing the technical structure. The UD can be used in the management platform in addition to the TD. The
detailed view in the PXM20 operator units shows the UD as information.
User Designation for Desigo room automation
You can define the user view for Desigo room automation as follows:
● Define a structure for the user view
● Copy Desigo room automation objects into the user view
● Define UDs that can be used as object names
System view
The system view shows the standard system hierarchy (BACnet view):
30 | 346 CM110664en_10
System overview 3
Views
● Network, topology
● Device and third-party device view
● Flat representation (no hierarchy) of all BACnet objects in one device
The system view provides access to all BACnet devices (including third-party BACnet devices) and all BACnet
objects. A third-party client displays this view of a PX device.
The system view is used in the PXM20 only for third-party devices.
Program view
The engineering and program view corresponds to the XWP/ABT view. The structure is matched to the
automation station. Within an automation station, the view is program oriented: nested CFC charts (compounds)
and function block instances.
Per User Technical view User view System view Program view
1 Operator (without technical Main view Main view No access No access
training)
2 Operator (with technical training) Main view Main view Occasionally No access
3 Engineer (Desigo CC), User Main view Main view Occasionally No access
(PXM...)
CM110664en_10 31 | 346
3 System overview
Views
The FD values and the object name selection are transferred automatically to the automation station or exported
to the management platform during compiling or loading in the CFC.
The CFC Editor checks during compilation if the object name is unique for each automation station under the
following rules:
● The same resulting object name may exist only once per automation station. This also applies to the device
object that must be unique in the BACnet internetwork.
● The resulting object name may not correspond to a TD of another object in a Device. The TD is used to
resolve BACnet references.
Exceptions for object name assignment
Object names cannot be engineered in CFC charts or compounds. These elements always define the TD and
the object name is always the same as the TD.
Special blocks, such as Heatcurve and Discipline I/Os generate reduced value objects in the background whose
object name per default is the TD during compilation.
Free definition of the Device ID
The device ID (the object ID of the device object) can be freely defined. Range: 0…4'194'303
32 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Coverage of the technical process
Main tools
The most important tools are:
● Desigo Configuration Module (DCM): For designing the Desigo system in the sales phase
● Xworks Plus (XWP): For engineering, commissioning and servicing Desigo PX system components
● Automation Building Tool (ABT): For engineering, commissioning and servicing Desigo system components
Special tools
There are also special tools, e.g.:
● Tools for configuring and commissioning specific product families, such as RXT10 for the configuration of
room devices on LON
● Tools for specific tasks, such as the AL Migration Tool for the migration of legacy system components to
Desigo PX
See Automation level migration, Engineering manual (CM110776).
DCM •
XWP • • • •
ABT • • • •
DCM •
ABT • • • •
Apogee tools • • • •
CM110664en_10 33 | 346
4 Desigo workflow, tools and programming
Coverage of the technical process
Sales
DCM supports system design and quantity determination during the sales process. Price calculation, offer
preparation and tracking, and invitation of tenders are supported by country-specific tools.
Planning
The planning tools are country-specific and comprise the following:
● Network planning, design and documentation
● Cable planning and design (network cables, field device cables)
● Texts for equipment plates
● Building planning (system components in the building, room segmentation)
● Plant planning and documentation (plant schematics, function description)
● Planning of the groupings for Desigo room automation
● Order lists
Engineering
Most of the Desigo system components are engineered offline, before they are commissioned. This way you
can verify and document the configuration (e.g., for the uniqueness of addresses), and define work packages for
subcontracting.
XWP and ABT are Desigo engineering tools and allow the following:
● Engineering the primary equipment, room automation, BACnet router
● BACnet references for the integration from/to third party systems
● Interfaces to ElektroCAD, Pharma Validation
● Exports for documentation
● Export for engineering in Desigo CC
The tool export:
● Generates information for illustrating the generic operation (technical hierarchy, User Designation hierarchy)
● Contains information for efficiently generating graphics (mapping functions to symbols and graphic
templates in Desigo CC).
Installation
XWP and ABT allow the following:
● Creating order lists that can be used for ordering the devices
● CAD export for connecting to ElektroCAD for designing control cabinets
● Parallel working of several subcontractors/engineers in a project
● Creating pack and go's for commissioning and the point test for subcontractors
● Loading configurations
● Creating commissioning data point lists
Commissioning
XWP and ABT allow the following:
● Commissioning of the systems (loading programs, program function test)
● Online trending during commissioning
● Diagnostics during commissioning
● Parallel working of several commissioning engineers in the project
Service
XWP and ABT allow the following:
34 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Coverage of the system
● Data access to Branch Office Server (central engineering data management of the regional companies)
● Data security (reading system data in the engineering database)
● Remote engineering and operating, diagnostics and error recovery via an external network connection
BIM Tool
TX Open Tool
Hierarchy Viewer
Report Viewer
DPT Tool
Room Automation
Third-party LNS Tool
RXT10
CM110664en_10 35 | 346
4 Desigo workflow, tools and programming
Main tasks
Network Configurator
Utilities
Point Configurator
CFC
Desigo Configuration Module
Hierarchy Viewer
Report Viewer
ETS
KNX PL-Link
VAV
FNCL
> ABT-SSA for KNX PL-Link
Switch
> ABT-SSA/ETS for KNX S-Mode
Presence
QMX3
KNX S-Mode
DALI
DALI > ABT-SSA for DALI
36 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Main tasks
● Project management: Ordering devices, project planning, claim management, project task planning
● Service management: Service database for devices, network planning, remote service platform
Sales support
Desigo Configuration Module (DCM) supports the calculation of the Desigo configuration for the sales process.
You can verify if:
● The Desigo configuration is technically correct, that is, the solution that was sold can be implemented with
Desigo
● The system limits have been taken into account, that is, the number of possible devices and functions in the
network is verified
● The quantity is correct, that is, correct device types for the automation and room functions, field devices,
accessories and licenses
● Services are correctly calculated
● The design for the review with the customer is well documented
● Prices are correct (regional companies can add their prices to the DCM database)
CM110664en_10 37 | 346
4 Desigo workflow, tools and programming
Main tasks
Level A
You can create solutions with the available options and variants with little prior training and detailed knowledge.
The device is preconfigured and can be configured for the specific project. The functions are predefined. You
can configure the application using options and variants. You can set the function of the application and the
peripheral devices with a configuration tool. The solutions are delivered by HQ as verified and documented
solutions.
Level B
The device can be configured for the specific project. You can assemble the application using library elements.
This is a major advantage of the Desigo application libraries. Even though assembling a solution is relatively
easy, the functions of the solutions are powerful. Using many options and variants, you can customize the
standard solutions to your project requirements.
Level C
The device is preconfigured and can be configured for the specific project. You can assemble the application
using library elements. You can program the application with default function modules with predefined
interfaces. You can program using simple programming functions.
Level D
This level offers full flexibility, but requires detailed knowledge of the application's structure, the programming
tools, BACnet and the Desigo system functions. You can program in CFC (Continuous Function Chart) with
basic function modules. You can use all available programming functions. You must ensure that the programs
you develop fit together regarding execution, priorities, auto-connecting in the tool, interface usage, etc.
Level E
This level offers full flexibility, but requires detailed knowledge of the application's structure and the
programming tools. You must ensure that the functions of the program work. You must ensure that the
programs you develop fit together with all elements in the library and that they are well tested and documented.
You must take care of the compatibility, the versioning and the library packaging.
38 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Tools for different roles
CM110664en_10 39 | 346
4 Desigo workflow, tools and programming
Working with libraries
Design Engineer Can carry out a project. System and room automation
Can select and configure solutions from the library.
Balancer Can balance rooms regarding air and water supply. Room automation
ABT Package XWP ABT ABT ABT Site ABT Site not ABT Site not
licensed licensed
ABT-SSA Access Point Test • • • •
via role and Operate and monitor
password Balancer • • • •
• • • •
ABT-SSA
HQ libraries
There are HQ libraries for every engineering level. HQ libraries:
● Allow you to work efficiently
● Are verified
● Are well documented
● Are based on a text data basis that allows you to switch the language in engineering, that is, the library is
language neutral
40 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Working in parallel and subcontracting
● Are versioned
● Can be installed with the library setup
RC libraries
Based on HQ libraries, you can create country-specific RC libraries that cover country-specific function
requirements.
Project-specific libraries
Project-specific libraries are based on HQ or RC libraries and contain components with the specific settings
needed in the project. This lets you use reuse already configured solutions in the project.
Check-in/Check-out mechanism
The check-in/check-out mechanism ensures that when several users are working in parallel during engineering,
commissioning or service, they cannot make changes to the same automation station. This way no inconsistent
data can be created.
To quickly transfer project data, the data is compressed before it is sent from the computer to the server. The
data is managed on the Branch Office Server. The project creator transfers the data from his local hard disk to
the server.
In large projects the data can be moved in two steps:
1. Step: Part of the project is transferred from the Branch Office Server to a computer in the plant.
2. Step: Parts of the transferred project can be transferred to local computers. This is called a sequential check-
out.
Parts of the project, such as the building or network topology are checked out in read-only mode, so that all
users always have the project overview.
Subcontracting
Project-specific solutions can be developed outside the project organisation and specific tasks, such as
configuration and point test can be outsourced to subcontractors.
CM110664en_10 41 | 346
4 Desigo workflow, tools and programming
Workflow for primary systems
CFC &
Customized Applications (PXC)
Simulation
XWP XWP
XWP Project XWP Report
Network Hierarchy DPT Tool
Manager Manager
Configurator Viewer
XWP Point
Standard Applications (PXC)
Configurator
42 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Workflow for room automation classic
XWP
Create project:
● Create project
● ACP (passwords for accessing the automation stations)
CM110664en_10 43 | 346
4 Desigo workflow, tools and programming
Desigo Configuration Module (DCM)
● Create automation stations, or rooms, based on the project-specific library per floor
● Edit room parameters
Field of application
DCM calculates the required materials for an installation from raw system data, such as data points, panels, and
building and plant structures.
You can use DCM to conduct analysis of variants after defining and completing the installation structure by
generating copies and then subsequently changing the hardware specifications. If prices are stored in DCM, you
can also compare prices to find the best possible device for the money. You can copy the devices calculated in
DCM from the price lists or export them as an Excel file to calculate a bid.
Flexibility
You can enter the data directly into DCM or import it as an Excel file for the automation and Desigo room
automation level.
The structure in DCM is hierarchical, but you can customize the structure according to your requirements.
Management level
The required software licenses for the selected functions, devices, integrations and data points are calculated
on the management level. The licenses are listed and the required software units are calculated.
Calculations can be made for new installations and for upgrades and migration. To calculate upgrades and
migration, you can import existing license keys. The import provides the exact installed basis and explicitly
allows additional, required licenses and software units.
Devices for the Desigo Web Interface are also determined on the management level. The calculation is based
on the number of data points to be integrated in the web interface and by the number of desired touch panels.
Automation level
At the automation level you can calculate the required hardware based on specified data points.
44 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Desigo Xworks Plus (XWP)
You can choose and calculate many variants using presettings. Variants include, e.g., the automation station
type or I/O module type, larger automation stations, or if plants are to be distributed among multiple automation
stations. You can also consider other criteria, such as available panel sizes.
Room automation
You can choose solutions with LON and/or KNX. You can choose predefined solutions with drag & drop and
then equip them with the required field devices. This way you can create a sample room and replicate it as
required.
Third-party devices
You can integrate third-party devices with protocols, such as LON, KNX, ModBus, M-bus or OPC, on all levels.
CM110664en_10 45 | 346
4 Desigo workflow, tools and programming
Desigo Xworks Plus (XWP)
46 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Desigo Xworks Plus (XWP)
The Xworks Hierarchy Viewer shows the technical hierarchy per PX and the technical hierarchy as it is shown,
e.g., in the generic view in Desigo CC.
You can define the user designation (UD) and the free designation (FD). You can define the structure of the
user designation with the field lengths and the separators and assign the data points in the structure of the user
designation. You can verify the consistency of the user designation and free designation in the entire project
and assign the technical designation (TD = default value), the user designation (UD) or the free designation
(FD) to the object name (ON).
CM110664en_10 47 | 346
4 Desigo workflow, tools and programming
Desigo Xworks Plus (XWP)
48 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Desigo Xworks Plus (XWP)
The CFC Classic editor shows all blocks that are used in the program, nested plans, all available CFC block
libraries and the selected plan with the plan interfaces to other plans. This view is available offline for
programming and online for checking the signal flow. The CFC Classic editor lets you compile programs, that is,
create loadable programs.
Additional editors
In addition to the graphic programming, you can configure the programs in the following editors:
● Parameter Editor: Lets you parameterize attributes.
● I/O Address Editor: Shows all I/Os of an automation station.
● Plant Control Editor: Lets you configure the plant controls for ventilation and energy generation.
● Solution Configurator: Lets you configure solutions, that are from the CFC library or have been generated
from the Xworks Project Configurator.
● Simulation: Lets you simulate programs of a modular automation station without hardware on the computer.
● Alarm display: Continuous update and local caching of all alarm status changes during commissioning. Lets
you view, acknowledge and reset alarms.
CM110664en_10 49 | 346
4 Desigo workflow, tools and programming
Desigo Automation Building Tool (ABT)
You can select one or more automation stations for the documentation, per automation station, plant or system
node. You can select document templates and verify reports in a preview.
BIM Tool
The BIM Tool is used for TX-I/O modules that are integrated with a BIM on automation stations. The BIM was
used on old automation stations for integrating I/O modules.
TX Open Tool
The TX Open Tool lets you configure TX Open modules. You can define the TX Open integration and
commission the TX Open modules. To commission TX Open, load a configuration into the modules with the TX
Open Tool.
See TX Open Tool online help (CM111005).
50 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Desigo Automation Building Tool (ABT)
Project data storage in a Desigo project is handled by Xworks Plus (XWP), that is, you can create a customer
project in XWP and check it in to the Branch Office Server (BOS) using Xworks Project Manager. XWP is also
used in the Desigo room automation project to carry out the network check and to create the network
documentation. Some project reports, which also encompass the Desigo room automation stations are created
in XWP.
ABT Pro
In ABT Pro you program automation stations (project-specific solution). Project-specific solutions can be created
in the Center of Competence (CoC) and used as project-specific types in the project in ABT Site.
ABT Pro contains the CFC Plus editor for programming in CFC.
CM110664en_10 51 | 346
4 Desigo workflow, tools and programming
Programming in D-MAP
ABT-SSA
In ABT-SSA (Setup & Service Assistant) you commission I/Os and carry out the point test.
See Desigo TRA - Setup & Service Assistant (CM11105).
In ABT-SSA you can:
● Assign network points (DALI to device), make points available
● Test if the points work
● Define parameters, e.g., time, desired value, default value, etc.
52 | 346 CM110664en_10
Desigo workflow, tools and programming 4
Programming in D-MAP
The following figure shows a simplified P&I diagram of a partial air conditioning system. The heating coil and its
components, including the automation station sequence, are encircled.
XWP
XWP is the programming tool for the PX automation station and incorporates all system elements. XWP shows
the structural view of the system with the plant, partial plant, aggregates, and components, and, e.g., the
compound functional unit for a valve.
CM110664en_10 53 | 346
4 Desigo workflow, tools and programming
Programming in D-MAP
Primary
I/O
PX Prim I/O
Prim
Prim
I/O
Central
Central
Central
I/O
CenGen CenHvac CenLgt CenShd I/O
I/O Reference
PXC3 CenGen
CenGen CenHvac
CenHvac CenLgt
CenLgt CenShd
CenShd I/O
I/O
I/O
room
DXR2 CenGen
CenGen CenHvac
CenHvac CenLgt
CenLgt CenShd
CenShd I/O
I/O
CenGen
CenGen
CenHvac
CenHvac
CenLgt
CenLgt
CenShd
CenShd
I/O
Room
Room
Room
Room
RCoo Room
RHvacCoo
Room RLgtCoo RShdCoo
RCoo RHvacCoo RLgtCoo RShdCoo
RCoo RHvacCoo RLgtCoo RShdCoo
PXC3 RCoo RHvacCoo RLgtCoo RShdCoo
DXR2 RCoo
RCoo
RHvacCoo
RHvacCoo
RLgtCoo
RLgtCoo
RShdCoo
RShdCoo
Scene
Room Segment
Room Segment
Room Segment
Room Segment I/O
Hvac Room Segment Lgt Shd I/O
Hvac Room Segment Lgt Shd I/O
Hvac Room Segment Lgt Shd I/O
Hvac Room Segment Lgt Shd I/O
Hvac RoomSegment
Segment
Lgt Shd I/O
Hvac RoomSegment Lgt Shd I/O
Hvac Room Lgt
Room segment Shd I/O
Hvac Lgt Shd I/O
Hvac Lgt Shd I/O
Hvac Lgt Shd I/O
PXC3 Hvac Lgt Shd I/O
I/O
Hvac Lgt Shd I/O
I/O
DXR2 Lgt
Lgt
Shd
Shd
I/O
Grouping Direct reference
TR Brgt Psc
54 | 346 CM110664en_10
Control concept 5
Programming in D-MAP
5 Control concept
Supply chain model
In building automation and control, media, such as warm water, cold water, warm air, and cold air are generated
using energy, such as oil, gas, and electricity, and distributed to consumers.
Each medium can be assigned a supply chain. The supply chain starts at the generation or handling of the
medium. The distribution system then transports the medium to one or several consumers. A supply chain for
building services systems comprises the following links:
Consumers
The consumer supplies the energy contained in the hot water medium to the room as per the requested demand
(e.g., via a radiator).
Distribution
The distribution system transports the medium from the producer to the consumer and adjusts it to the individual
requirements (minimum losses).
Production
The production consists of a boiler where hot water is treated by means of energy (e.g., heating oil, gas) and
provided to the process.
Supply chains of various media
The following illustration shows a schematic view of the supply chains for the media air, hot water, and cold
water with their respective production (treatment), distribution (e.g., heating circuit, pre-control), and the
consumers.
The supply chain for the medium electricity, which normally begins at supply or at production, if electricity is
produced on-site (e.g., cogeneration plant, photovoltaic) is also shown.
CM110664en_10 55 | 346
5 Control concept
Programming in D-MAP
A tree structure opens to the right for the individual supply chains. In other words, one or more generators
supply multiple primary controllers and each primary controller for its part supplies one or more consumers or
other primary controllers.
From the air supply chain point-of-view, air treatment is a part of production (handling). From the hot water and
cold water point-of-view, air treatment (or air heater/cooler) belongs to consumption.
The air supply chain comprises the central air treatment plant, optionally supplemented by pressurization control
and air posttreatment.
Supply flow
In each supply chain, the medium flows from the producer, through the distribution system to the consumer.
This flow within the supply chain is referred to as the supply flow.
Supply chain structure
A supply chain consists of at least one producer and one consumer. It can also have multiple chain links, that is,
producers, distributors, and consumers, and be structured as follows:
1. One producer with one distributor and one consumer.
2. One producer with two distributors in series and one consumer.
3. One producer with two distributors in parallel and two consumers in parallel.
4. Multiple producers, distributors, and consumers in parallel.
56 | 346 CM110664en_10
Control concept 5
Programming in D-MAP
Producer
In practice, however, there are often multiple producer units, e.g., boilers with the same or similar power, or a
mixture of different units, e.g., boiler combined with a solar plant and cogeneration plant (usually with additional
storage units).
Logical producer
From the distributor and consumer point-of-view, there is only one single producer within the supply chain, the
logical producer, with exactly one supply point as the interface to the distribution network. This logical producer
knows nothing about the structure of the distribution network and the connected consumers. Also, neither the
distributor nor the consumer knows whether the producer consists of one or multiple units.
Distribution components
The distributor or distribution transports the medium within the supply chain. In this process, energy losses and
energy consumption of pumps and fans is to be kept to a minimum.
Conversion
Conversion (transformation) of the medium, e.g., in a heat exchanger, is assigned to a supply chain of
distribution. A change of temperature (e.g., pre-control in the heating circuit) is also seen as conversion. Pre-
controllers can be arranged in series (cascading).
Consumers
The following consumers, e.g., belong to the various supply chains:
CM110664en_10 57 | 346
5 Control concept
Programming in D-MAP
In addition to the three chain links producer, distributor, and consumer, there are the logical links named
coordinator and dispatcher.
Supply chains for a room
You can define different consumer needs for a room, such as heat, refrigeration and fresh air.
Heat demand
The hot water supply chain exists for heat demand. The medium hot water is prepared in hot water generation
and distributed via a heating circuit. The heat is emitted to the room as needed via a heating surface. If air is the
carrier of heat, this is done via pre-control and air posttreatment.
Refrigeration demand
The cold water supply chain exists for refrigeration demand. The medium cold water is prepared in cold water
generation and distributed via a cooling circuit. The refrigeration is emitted to the room as needed via a cooling
surface. If air is the carrier of refrigeration, this is done via pre-control and air posttreatment.
Fresh air demand
The need for fresh air is met by the air supply chain, where the medium is produced by the air treatment plant,
distributed via the ducting, possibly adjusted to differing requirements of the room by an air posttreatment plant,
and transferred to the room via air outlets.
Plant
58 | 346 CM110664en_10
Control concept 5
Programming in D-MAP
A plant consists of partial plants, aggregates, and components, which, as a rule, form a supply chain with the
chain links producer (here: boiler), distributor (pre-control, heating circuit), and consumer (radiator).
Operator interventions
Commands are executed at each link of the chain through operating interventions via HMI commands. The
impact on the plant (or the process) takes place via the corresponding function unit and automation station.
Functional units
Functional units represent the software map of chain links and plant elements. The functional units contain all
control, monitoring, and limiting functions that are necessary for operation.
Information signals
Energy demand information can be passed on implicitly via the medium within the supply chain, e.g., if the hot
water supply temperature falls because of a rise in heat consumption, more heat energy must be produced.
Information can also be represented by an explicit signal and transferred via a signal path (e.g., via a bus). The
following explicit signals have been defined in the Desigo system:
Operating signal Producer to consumer A plant informs the downstream plants about its currently effective operating state.
This signal is only used as an exception and is therefore switched depending on
the situation.
Override signal Producer to consumer The producer demands a certain operating mode from a consumer. Forced
signals are more the exception than the rule and are therefore not implemented in
sample plants. Forced signals are used for solar plants and wood furnaces among
others, where the minimum heat production cannot be controlled.
In addition to the functional units, there are two further elements that belong to the supply chain on the software
side:
● Coordinator: The coordinator combines the demand signals of downstream (to supply flow direction) plants
and delivers a resultant demand signal to the upstream plants. The coordinator also signalizes the operating
state of the upstream plants to the downstream plants.
● Dispatcher: The dispatcher determines the demand signals for the producers on the basis of the resultant
consumer demand signals. It decides which and how many producers must be activated.
CM110664en_10 59 | 346
5 Control concept
Control concept and control blocks
Control functions
The open-loop control functions required for a given element are locally an integral part of the functional unit
(e.g., the increase, after a time delay, in the speed of a multi-stage fan, or the demand-based switch-on of a
boiler). In each functional unit, various possible requirements are prioritized and evaluated. The resulting
operating mode is then passed on to the elements or subordinate functional units. The functional unit already
incorporates the I/Os needed for the physical data points.
60 | 346 CM110664en_10
Control concept 5
Control concept and control blocks
Command control CMD_CTL Superposed control block for sequence control. The block ensures that individual
plant aggregates are switched on or off sequentially in a certain order. The block
monitors aggregates and can send alarms. It is optimized for controlling air
handling plants, but can be used for other applications. The block is used on the
hierarchy level plant/partial plant.
Power control PWR_CTL Superposed control block for power control. The block is used for control and
monitoring of the performance of a number of energy producers (multiple boiler
systems, refrigeration machines). Depending on the request power demand,
energy produces are switch on or off in stages. PWR_CTL is optimized for
controlling heating and refrigeration plants. The block is used on the hierarchy
level plant/partial plant.
I/O blocks with control BO Output blocks implemented per BACnet standard and therefore including a priority
functionality MO mechanism (priority array) that is well suited for control tasks. The priority array
[PrioArr] be used through data flow interconnections and BACnet commanding.
AO Moreover, the block integrate the following control functionality:
- Motor control (pump, burner, etc.), one- to four-speed [BO, MO]
- Fan control, one- to four-speed [BO, MO]
Value blocks with control BVAL Value objects or value blocks are implemented per BACnet standard and
functionality MVAL therefore includes output blocks via the priority mechanism. These blocks are
referred to as data points that can communicate within the system with the I/O
AVAL
modules via BACnet. These blocks are primarily used as the communication
interface between superposed control [CMD_CTL, PWR_CTL] and the
aggregates.
Rotation block ROT_8 The Rotation block switches the operating mode on and off for a maximum of
eight functional units in accordance with a selected mode of rotation (sequence or
hours run). The change of operating mode is based on demand, hours run,
occurrence of a fault or manual intervention (override).
The block is used to process the functional units (e.g., aggregates or components)
as a function of run-time or faults. These blocks are used, e.g., for double pumps,
that are changed over based on runtime.
Control hierarchy
Control hierarchy is the map of the functional assignment and linking of those function blocks included in the
control concept for a plant. The structure of the control hierarchy is subject to certain rules. A distinction is
drawn between higher-level plant control and local control of the functional units.
CM110664en_10 61 | 346
5 Control concept
Control concept and control blocks
Superposed control
Within the hierarchical structure, higher-level control functions are typically assigned to the partial plant level. All
the variables which are influencing factors on the overall plant are weighted and combined to give the effecting
plant operating mode. In respect of each of the possible plant operating modes, a control strategy can be
defined for each underlying functional element. This makes it possible to develop specific plant scenarios, such
as fire control, smoke extraction, frost control, on/off-switch control.
Local control
Within the hierarchical structure, local control of the function elements is typically assigned to the partial plant
level. The main function of local control is to respond to faults. The functional unit itself determines how the
outputs are to be controlled in the event of a fault. Interlocks between functional units (e.g., damper/fan) must be
implemented locally. Local control prevents the risk of damage to plant, in the event that the command control
parameters are set incorrectly.
The control hierarchy in the following figure considers only the example application for ventilation.
62 | 346 CM110664en_10
E,H E,U E,U E,U
O&M
Sched MVAL
OpModMan MI BI BI BI
Cp:BSCHED Cp:MVAL_OP OpModSwi Cp:MI FireDet Cp:BI SmextSu Cp:BI SmextEh Cp:BI
OpMSwiCnv
Ax: DMUX8_BO
CM110664en_10
En En En En En En En En En En En
En DefVal:Off
OpSta OpSta
MI FanSu FanEx
BVAL BVAL ManSwi Cp:Ml DmpShofOa Ag. DmpShof Ag: V(A,C-F) Fan1St DmpShofEh Ag:DmpShof Ag: V(A,C-F) Fan1St
PrVal
PrVal
A-Transport
EnCrit EnCrit
E,H E,H
EnPgm
ValPgm
EnSfty
ValSfty
EnPgm
ValPgm
EnSfty
ValSfty
AO BO AO BO
PrVal
OpSta
Dstb
KickDmp
PrVal
OpSta
Dstb
KickDmp
PrVal
FbVal
PrVal
FbVal
Frost
M
Control concept
Control concept and control blocks
5
are responsible for numerous control and monitoring functions. They enable otherwise complex functions to be
The I/O blocks are the most important blocks in the Desigo system. In addition to controlling the hardware, they
63 | 346
5 Control concept
Control concept and control blocks
64 | 346 CM110664en_10
Control concept 5
Control concept and control blocks
Priority mechanism
Within the Desigo PX system, the BACnet priority mechanism is used for the I/O output blocks and in the value
blocks. This priority mechanism provides a series of prioritized levels at which intervention is possible, for use
with the control functions in HVAC plant and the associated components.
The following priority levels are available with blocks AO, BO, MO (and blocks AO_RED, BO_RED, MO_RED)
and AVAL, BVAL and MVAL.
Operator level Local manual intervention The operator level is where components are overridden manually. Here the
operator unit may be used to force the output of an I/O function block. This
Superposed manual operation overrides all operations at a lower priority level.
intervention
CM110664en_10 65 | 346
5 Control concept
Control concept and control blocks
The following figure illustrates the structure of [PrioArr] and the influence of local and higher-level control.
Priorities 1, 4, 7, 15 Priority 6 Priorities 2, 5, 8, 14, 16
Local control Control within block Higher control
via data flow interconnection via BACnet command
AO BO MVAL
CMD_CTL
3
e.g. anti-icing
ValCrit / EnCrit
protection
Critical value
5
6 Monitoring hours
7 Desigo CC
e.g. local manual Manual operation
switch ValOp / EnOp 8
13
14
Local control Program control
15 ValPgm / EnPgm
PrVal
Local override
The override switch overrides the block's switching value and determines in this way the switching value for the
field device. Local override has priority over an active manual operation at the same time, that is, priority over
local override.
Status monitoring
[AO, BO, MO, AVAL, BVAL, MVAL]
The process is monitored via the feedback signal, and in the case of switching blocks, also via the ramp-up and
ramp-down parameters set in [TbTiDly]. If the feedback value deviates from the present value [PrVal] and the
delay in [TbTiDly] has not yet expired, the process is in a transitional state. The status monitoring function
shows the status at the transient state [TraSta] output. This output can be used to switch on any subsequent
components.
Feedback monitoring
[BO, MO]
Monitoring feedback may be based on a data point or a purely internal to the block based on the feedback time
parameter.
66 | 346 CM110664en_10
Control concept 5
Control concept and control blocks
Reliability monitoring
[AI, AI_RED, AO, AO_RED, AVAL, BI, BI_RED, BO,BO_RED, BVAL, MI, MI_RED, MO, MO_RED, MVAL]
The blocks monitor the reliability of input and output sources and configuration errors. A system alarm is
generated, e.g., when a source no longer communicates and the cause is displayed on output [Rlb]. The
disturbance output [Dstb] changes to yes. This output, e.g., can return to the block for the local disturbance to
achieve a more secure position using a higher priority. Reliability monitoring can be switched off using [OoServ],
which may make sense for defective or faulty hardware.
Reliability monitoring is always active for the RED blocks since no [OaServ] is available. Superposed control
does not distinguish this state and plant safety is not provided under certain circumstances.
Ramp-up/down time
Runtimes for ramp-up and down
[BO, BVAL, MO, MVAL]
The runtime of a damper or the coasting time for a multi-speed motor can be defined in table [TbTiDly] to
display or evaluate a transient state [TraSta]. The time parameter can also influence the switching response
depending on the switch kind [SwiKind] used.
Plant fault
The block independently recognizes faults and reports them to the defined alarm class [AlmCl], which for its part
is responsible for distributing the alarms to alarm receivers. Depending on the alarm function [AlmFnct] set in
the block, you may have to acknowledge the alarm and reset it after eliminating the alarm.
The faulted block on output [Dstb] is reset only after the user action is run. The plant ramps up only after an
alarm reset since both the local control, as a rule, with this output is blocked for a fault and as superposed
control triggered a plant fault.
The alarm reset can be triggered:
CM110664en_10 67 | 346
5 Control concept
Local control design
Temp: AI
OR
100 %
CritActv
TraSta
TraSta
FbVal
FbVal
PrVal
PrVal
Dstb
Dstb
Pu Cp: BO
68 | 346 CM110664en_10
Control concept 5
Local control design
15: ValPgm
14: EnPgm
13. ValCrit
12. EnCrit
Off
Ort
Ax:OR
P15 Pgm P4 Crit
CritActv
PrVal
Dstb
TCtr
PID_CTR
0% On Off
ValCrit
EnCrit
TraSta
FbVal
PrVal
PrVal
Dstb
Dstb
Pu 1St: BO
R/sCtl
Interlocks
The following figure shows a solution where a fan is only enabled after the damper is completely open.
CM110664en_10 69 | 346
5 Control concept
Local control design
[On/Off]
OpMod
Yes
SftyActv
CritActv
TraSta
PrVal
Dstb
Damper Cp:BO
[On/Off]
OpMod
Yes
Off
SftyActv
CritActv
TraSta
PrVal
Dstb
Fan Cp:BO
Local interlocks
A command to ramp-up the plant [OpMod] =On, the damper output changes to [TraSta] = Yes, indicating that a
transient state is now active, in other words, the damper is moving. This information is formed on the one hand
from the parameterized damper run time [TbTiDly] and, on the other hand, from the feedback contact for the
damper's mechanical stop.
The valve is blocked via input [EnSfty] as long as the damper is either blocked or moving, in other words, an
intervention via the operator unit directly on the fan is prevented. When the transient state ends and the damper
is open, the Enable [EnSfty] is cancelled and the fan switched on via the program value [ValPgm]. Enable of the
program value [EnPgm] is a constant in this example.
70 | 346 CM110664en_10
Control concept 5
Superposed plant controls
BACnet Reference
Open
ValCrit
EnCrit
OpSta
DmpShofOa Ag: DmpShof FanSu Ag: Fan1St
OpSta
EnCrit
ValCrit
The operating state [OpSta] for both aggregates are formed within the compounds as illustrated in the previous
example from the AND link for [PrVal] and [TraSta].
Referencing
Referencing is used exclusively for communications by the superposed control blocks with the output and value
blocks in the aggregates to be commanded. The references are derived from the Technical Designation (TD) of
the block. The reference is defined relative to the control block to the command block. The aggregate does not
have to be in the same hierarchy; cross-plant communications is possible.
Example for a reference: B = \...\...\PreHcl’CmdVal
Where CmdVal is the designation for a BVAL object in the PreHcl aggregate. More than one block can be
referenced for each aggregate.
As the project-specific root is not part of the address, the references do not need to be modified if the root
changes. This simplifies project-specific name changes and the copying of library solutions into a project.
The references, that is, the technical designations with relative addresses are resolved in the controller at
runtime. Any addressing errors will therefore only be apparent during runtime. The cause of the error can largely
be eliminated, however, when parameterizing the controls blocks with the help of the Plant Control Editors.
The figure shows that the [PrioArr] can communicate directly with the referenced blocks. You can command
switch and positioning values and enable them. A commanded command remains valid until the priority entry is
enabled again. The control blocks automatically enables all commanded priorities, when the block commands
the aggregates to the new plant operating mode. The entries for the [PrioArr] are deleted in the commanded
blocks when restarting the PX controller, with the exception of local, manual interventions to priority 8.
CM110664en_10 71 | 346
5 Control concept
Superposed plant controls
before plant control as illustrated in the following figure. All potential influences are interconnected, prioritized by
importance on the block and the corresponding required plant operating mode is determined.
Example:
● A fire detector as a high priority (P04) and requires the plant operating mode EmergOff.
● The smoke extraction switch has the highest priority (P01) and demands plant operating mode smoke
extraction.
● The scheduler has a low priority (P11) and demands plant operating modes Stage 1, Stage 2 and Off.
The output [Val] for ENSEL_MS now supplies the CMD_CTL the resulting plant operating mode for additional
processing. It is important that the multistate enumerations for both blocks ENSEL_MS and CMD_CTL are the
same. The multistate values are not text, but rather numbers based.
72 | 346 CM110664en_10
Control concept 5
Superposed plant controls
A-Transport
EnCrit
DmpShofEh Ag:DmpShof
EnCrit
CMD_CTL
On
SmextPrg
SmextEh
OpSta
EnCrit
En
On/P14 Open/P14
E,U
ErcRo DmpShof
EnCrit
On
SmextSu
En
FireDet Cp:BI
E,U
On/P14
EmgOff
En
EmgOff
TSu
On
Frost
En
Sequence table
On
OpModSwi Cp:MI
E,H
Ax: DMUX8_BO
TSu
En
On
Cp:MVAL_OP
OpModMan
TOa
En
O&M
TSu
En
DefVal:Off
Frost
Sched
Cp:BSCHED
TOa
On
En
En
The block CMD_CTL controls and monitors output and value blocks mapped on BACnet. Communications is
based on BACnet referencing rather than interconnections to optimize the costs of engineering. The following
blocks can be used with CMD_CTL: AO, BO, MO and AVAL, BVAL and MVAL.
The sequence is determined in the CMD_CTL in a table. The command for the individual aggregates and the
components can be determined based on the plant operating mode.
CM110664en_10 73 | 346
5 Control concept
Superposed plant controls
The main functionality of the block CMD_CTL is the sequential control of aggregates and components
dependent on the preset plant operating mode [ValPgm]. For this purpose the switch-on sequence is defined by
the order in the function table [FnctTb]. The switch-off sequence is the reverse of the switch-on sequence.
Independent switch-on and switch-off sequences are not implemented in this block.
Switched on block can be monitored for their states. There is no monitoring of the OFF status.
Prior to switching on a block a test is made to see if the conditions for executing a command are given. The
switch-on process is not even available for active switch on delay, minimum switch off times or a switch
command with a higher command (e.g., a maintenance switch). This Look Ahead mechanism is described in
greater detail in this chapter.
This block does not contain interlocks of individual functional units within aggregates. These are implemented
locally via the data flow between the relevant blocks.
The upper part of the dialog box serves primarily to provide a quick online overview of the present plant
operating mode. You can also define exception value which become active as a plant operating mode during a
plant fault.
The upper part of the table configures the sequences. The switch-on sequence of the objects, the monitoring
mode and the switch on and off types for the sequence controllers can be defined here.
The lower part of the table is used to define the plant operating modes. You can define what command at what
priority is command per plant operating mode for each sequence element.
The following priorities for commanding are available:
● Priority 2: Life safety, automatic
● Priority 5: Plant safety, automatic
● Priority 14: Specific command object
● Priority 16: System control
You can enable a command priority with the value Not command for plant operating modes where the local
control is intended to assume control of the aggregate.
[DefVal] applies when the [PrioArr] for the corresponding block is empty, that is, not active recognition set, at
that time.
74 | 346 CM110664en_10
Control concept 5
Superposed plant controls
CM110664en_10 75 | 346
5 Control concept
Superposed plant controls
soon as it reports switched off, that is, the process value of the block [PrVal] = Off. It switches after the timeout
time expires when the shut-down message is not sent.
If a sequence element with a life-safety or plant-safety priority is switched off, the preset delay times will be
ignored.
Switch on aggregates
The following figure shows the switch response and monitoring mechanism for block CMD_CTL.
The system initially checks if the new plant operating mode is an AllLifeSafety mode. The Look Ahead check
takes place in the second step, followed by the check and abort of on-going sequences. The next step is to run
the shut-down series, where objects 8 and 4 are switched off to the extent they have not yet be shut down. The
sequences are then switched on one after the other in the follow-on switch on series.
76 | 346 CM110664en_10
Control concept 5
Superposed plant controls
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Sequence 1
Objects 1, 2 and 3 are switched on in parallel.
Switch-on 1 Switch-on 2 Switch-on 3 As soon as 1 and 3 transmit an On signal
or the 30 sec. timeout expires,
the transition to the next sequence starts.
Timeout 0:30
Sequence 2
in stage X, and is therefore skipped.
(Off)
4 5
Sequence 3
The set time (delay or timeout) marks a switch on or off sequence that may consist of one or more objects. The
times apply for the entire sequence and take effect, when a switch on or step up command or a switch off or
ramp down command is demanded.
Switch on occurs in parallel per sequence. A check of the switch on state occurs only in the switch on type
timeout. The next sequence is only started after either all monitored objects report a switched on state or the
timeout period expires. Operating state monitoring of the objects for monitoring, as depicted in the following
figure, only become active after the step-up process for a sequence is completed.
CM110664en_10 77 | 346
5 Control concept
Superposed plant controls
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Object switch-on:
Switch-on procedure completed: Check if switch-on
State monitoring active state reached
Sequence 3
Operating status monitoring is optional and monitors only blocks in a Switched on state. If a referenced block is
found to be switched off during active operating state monitoring, but that the block should have been in the
state Switched on, a process alarm is generated and the plant operating mode changes to exception value
[EcptVal].
The momentary alarm state is visible from the state flag [StaFlg].
Sequence 1 Sequence 2 Sequence 3
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Monitoring is active from the point when the corresponding sequence successfully completes the switch on
process, that is, the process value for block [PrVal] is not equal to Off and the transient state is completed
[TraSta] = No.
The [PrVal] of the block will be monitored. Hence, only those events which affect [PrVal] can be detected, that
is:
● Local fault shut down using interconnection of fault [Dstb] to enable safety, manual [EnSfty].
● Local shut down of the block in a higher priority application program.
● Switch-off by manual operation of the output module if the I/O module returns the manual setting value.
● Block switched off via HMI operation or manual switch in control panel
Command control is only in a position to recognize fault-related deviations and act accordingly when the
interconnection of all relevant faults [Dstb] occur locally on a monitored output of value block to [EnSfty]. Its
default value [DefVal] becomes the process value [PrVal], if a referenced output or value block is out of service
[OoServ]. The state monitoring of the plant cannot operate correctly, since [PrVal] no longer reflects the actual
state of the aggregate.
78 | 346 CM110664en_10
Control concept 5
Superposed plant controls
To reduce the frequency with which aggregates are switched on and off, it is possible to define a minimum
switch-off time [TiOffMin] in the aggregates. The look-ahead mechanism in the CMD_CTL block prevents the
switching of the whole sequence if the minimum off-time in one aggregate with active state-monitoring has not
yet expired. The output [TraSta] shows the transitional state and [PrVal] remains unchanged, at the last value.
The new plant operating mode will be implemented only when all the aggregates to be enabled in the switching
sequence can actually be enabled.
A minimum off-time should always be set for aggregates incorporating a rotating mass (e.g., fans).
Object nr. 1 2 3 4 5 6 7 8
Operating states
On On
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Sequence 1
Delayed 0:30
Delayed 1:00
Sequence 3
Delayed 2:00
Objects 3 and 2 are switched at the same time as object 5. Object 1 remains switched on.
Alarm management
Block CMD_CTL is alarmable and differentiates process from system alarms.
A process alarm occurs, when:
CM110664en_10 79 | 346
5 Control concept
Superposed plant controls
Out of service
The block can be taken out of commissioning using [OoServ]. The following occurs when switching [OoServ] to
On:
● Immediately abort of switch on and off sequences and monitoring.
● All objects are commanded with a release of the priorities: Life safety (2), plant safety (4), specific command
control (14) and system control (16)
80 | 346 CM110664en_10
Control concept 5
Superposed plant controls
The upper part of the dialog box serves primarily to provide a quick online overview of the block. The maximum
power controlled by the block is set with the maximum power parameter [MaxPwr]. The value must be greater
than 0 kW in order for the block to work. Any changes in this limit value have a direct effect in online mode. If no
limit value is required, the maximum power must be set at an appropriately high value.
The Aggregates tab is used to set the control variables of the aggregates (boiler, refrigeration machine).
● Enable: Activation/deactivation of an entry if they are not released, aggregates in the Profile table will be
ignored.
● Command object reference: Reference (relative addressing) to multistate value blocks [MVAL] of the
relevant energy producer. During the configuration process, all MVAL blocks at the same and at lower
hierarchical levels are displayed.
● Aggregate description: The reference to the value object provides access to (and hence, knowledge of) all
information in a special dialog box via the referenced object in the control command.
● Switch-on delay: Delay time when switching from OFF to Stage 1.
● Switch-off delay: Delay time when switching from Stage n to OFF.
● Step-up delay: Delay time when switching from Stage n up to Stage n+1.
CM110664en_10 81 | 346
5 Control concept
Superposed plant controls
● Step-down delay: Delay time when switching down from Stage n to Stage n–1.
● Switch-on stage power: Power in [kW] at the lowest (that is, first) stage.
● Next power stage: Additional power at the next stage(s) in [kW].
The control sequences for the aggregates (boiler, refrigeration machine) are defined under the Aggregates tab.
Each profile describes the order in which the energy producers are to be switched and the maximum stage in
each case. A total of 8 profiles each with 15 sequence entries can be defined.
The active profile table is defined by entering the profile number [PrfNr] as an input parameter, or by selecting it
from the Profile dropdown list in the Plant Control Editor. This input parameter can be interconnected, so that
the profile can be changed as a function of other events (faults, summer mode, boiler operating hours, etc.). If
the profile is changed during operation, the power output [PrPwr] is switched in accordance with the power
profile in the new profile table.
The profile definition determines the order in which individual aggregates are to be switched on or off. The
following information must be entered for every sequence entry:
● Object: Selected from the previously referenced aggregates.
● Stage limitation: Limit up to which the aggregate may be enabled.
● Control type: Specifies whether the enabled stages are to be switched permanently or released to the
control system.
– Fixed: The total power provided by a given switch stage is switched on or off permanently. This option
can be used, e.g., for a specific base load which is required to be present at all times. The command is
implemented with Priority 14.
– Enable: The power actually required from the released switch stage is determined by local control of the
aggregates. The command is implemented with Priority 16.
For each sequence step, the function block only ever releases the last aggregate marked Release to the control
system. It displays this released object [RlsObj], with the released object stage [RlsObjSt], at the output. All
other aggregates are fixed at the released stage value. If none of the aggregates is marked Release, the
aggregate of the current sequence step is released to the control system.
Out of service
If the PWR_CTL function is taken out of service [OoServ = On], then all referenced aggregates are switched
OFF with Priority 14, without taking account of delay times. The monitoring of the aggregates is disabled.
Demand signals
The current power demand is determined locally in the energy producers. In the event of a power deficit or
surplus, the aggregate will send the appropriate demand signal to the PWR_CTL block. The demand signal
from the aggregate can be generated, e.g., on the basis of the boiler setpoint deviation and the primary flow.
The demand signals of the separate aggregates are combined and transmitted to the [StepUp] or [StepDn] input
of the PWR_CTL block. After expiry of the relevant delay times, the block executes the appropriate sequence
step to increase or reduce the power, as necessary.
82 | 346 CM110664en_10
Control concept 5
Superposed plant controls
When both [StepUp] and [StepDn] demand signals are present simultaneously, [StepDn] takes priority.
Power display
The block has two outputs at which it displays the current total power of the energy producers. This consists
firstly of the controlled power output [CtldPwr]. This output represents the total power switched by the
PWR_CTL block.
The other output, the present power output [PrPwr], shows the additional power output of energy producers that
are not directly switched by PWR_CTL. To do this, PWR_CTL evaluates the priority array [PrioArr] of the MVAL
blocks. In this way it can detect, e.g., that an energy producer has been switched manually [Prio8] to a given
stage.
Configuration error
The entries in the two configuration tables are checked cyclically for validity.
● A fault alarm is generated under the following circumstances:
● Aggregates no longer accessible from PWR_CTL, owing, e.g., to retrospective modifications to the technical
hierarchy, affecting the references of the energy producers
● Retrospective changes to the stage-limit value in the aggregate, making the value configured in the profile
table too high
● No multistate value object
● Reference block no longer available: e.g., deleted with delta download
● Several references to the same block
● Empty profile table
In the event of a fault alarm, all aggregates still accessible by PWR_CTL are switched OFF permanently.
Alarm management
The PWR_CTL block in the system is an alarm-generating block with a configurable alarm class [AlmCl] and
alarm function [AlmFnct].
An Offnormal process alarm is generated:
● When the step-up demand signal [StepUp] persists for longer than the monitoring time deviation
[TiMonDev], and there are no further sequence steps to increase the power.
● When the step-up demand signal [StepUp] persists for longer than the monitoring time deviation [TiMonDev]
plus the step-up delay time of the next sequence step, AND a step-up would cause the maximum power
limit [MaxPwr] to be exceeded.
The process alarm is reset to normal:
● When a sequence step with an increase in power becomes possible again. Another sequence step with an
increase in power becomes possible when the [MaxPwr] limit will no longer be exceeded, or when a further
sequence step with a power increase is present.
● When there is no further [StepUp] demand signal
The text of process alarms can be defined to suit customer requirements.
Switching alternatives
Various switching alternatives can be defined by entries in the profile table. Note that where one or more step-
up sequence steps (intended to increase the power) would, in practice, result in a drop in the power output, all
steps in the step-up sequence are enabled automatically until a sequence entry is reached, at which the power
output actually does increase as required. See also the following example.
CM110664en_10 83 | 346
5 Control concept
Superposed plant controls
The power data in the object table and the sequence entries in the profile table in Figure Example of aggregate
table together give the power profile illustrated in Figure Example of profile entries with a drop in power (Profile
2).
Profile 1
In the main application of the PWR_CTL function, a new energy producer is added for each sequence entry in
the profile table. For this purpose, an aggregate only needs to be entered in the sequence table once.
In the event of a power demand, which the boiler transmits to the PWR_CTL function in the form of the [StepUp]
demand signal, a further boiler stage / sequence step is enabled when the step-up delay has expired. When a
boiler reaches the stage limit, the function switches to the next boiler or boiler stage after expiry of the switch-on
delay. The last-enabled boiler stage is released to local power control, while all other boilers are fixed at their
current power output.
If the power needs to be reduced, this is transmitted to the PWR_CTL function via the [StepDn] demand signal.
The sequence steps are then executed in reverse order, with the defined switch-off and step-down delay times.
84 | 346 CM110664en_10
Control concept 5
Superposed plant controls
Profile 2
Profile 2 shows that the order in which boiler stages are to be enabled has been changed, and that sequences
which will cause a drop in the power output have been defined in the power profile. In the example illustrated,
Boiler 3, which is currently delivering 200 kW, is switched OFF via sequence entry 2. Boiler 1, which could
achieve a power output of 150 kW with its enabled stages, is defined as the next object in the sequence. This
results in a drop in the power output, causing the function block to enable all sequence steps automatically until
an actual increase in power is achieved.
In sequence entry 4, Boiler 2 is enabled up to stage 2, giving a further 150 kW output. Boilers 1 and 2 are thus
enabled simultaneously up to stage 2, to prevent a drop in power. The effective delay time for the simultaneous
switching process is determined the maximum delay time of the boilers concerned. Since it is Boiler 1 which has
the longest delay (15 minutes), the simultaneous switching operation will be delayed for this period of time.
Sequence entry 5 would again result in a drop in performance, because stage 2 of Boiler 2 is no longer enabled.
The block therefore switches straight to sequence entry 6, enabling Boiler 3 to compensate for the power deficit.
In this case the effective switch-on time is based on the switch-on delay for Boiler 3 (10 minutes).
CM110664en_10 85 | 346
5 Control concept
Closed-loop control strategy
Online diagnostics
A diagnostics screen for the PWR_CTL block is available online in Xworks Plus (XWP).
86 | 346 CM110664en_10
Control concept 5
Closed-loop control strategy
Control action
The PID_CTR block can be configured as a P, PI or PID controller. The following parameter settings are used to
define the control action:
● Gain [Gain]
● Integral action time [Tn]
● Derivative action time [Tv]
As an option, the gain [Gain] can be influenced with the [GainFac] input. It can be useful to correct the gain
factor in this way when controlling outside air dampers, e.g., as the effect of the damper positions can depend
on the outside air temperature. The correction factor is defined with the gain scheduling block ADAGAIN.
The actuator runtime can be set. Specifying the actual actuator run-times makes it possible to tune the controller
more accurately to the actuator concerned, so improving the control quality of the control system.
Correcting range
The correcting range is limited by specifying the minimum and maximum output variable. In this process, the
minimum of the two values is always set as the maximum value. In other words, the maximum value may be
below the minimum value; there is no need to update the minimum value.
Neutral zone [Nz]
[Nz] is a zone on either side of the setpoint, within which the controller does not respond. As soon as the
difference between the setpoint [Sp] and the measured value [Xctl] is less than half of the [Nz], the output is
driven for a further 7 cycles, so that the measured value [Xctl] is as close as possible to the middle of the [Nz].
The output signal [Yctr] then remains constant. The output signal is only re-adjusted when the parameters move
outside the [Nz] again.
CM110664en_10 87 | 346
5 Control concept
Closed-loop control strategy
P/PD controller
If the PID_CTR block is configured as a P-controller or PD-controller, a calibration point (Offset) [YctrOfs] can
be specified, e.g., the P-controller can be calibrated so that the set point is maintained with a 50% load.
With a 0% or 100% load, the P-deviation is then half the amplitude of the proportional range [Gain].
Tracking [Track]
[Track] is used, e.g., where the PI(D) controller, operates as a limit controller, e.g., acting on a valve or actuator
via an intermediary minimum or maximum selector block. The tracking input ensures the availability of the
controller during the period in which it is blocked by the minimum or maximum selector block. During this time,
its integrator (and, hence, its output) is maintained at the value of the signal received, so that if the limit
conditions are violated, it is able to respond immediately. [Track] is also used in conjunction with special
actuators with positioning feedback.
Direct/reverse-acting control action [Actg]
[Actg] is a characteristic parameter of the controller and indicates the relationship between the setpoint deviation
and the change in energy flow. A distinction is made between direct action and indirect [Actg].
● Direct control [Actg]: As the controlled variable rises, the controller output increases, and as the controlled
variable falls, so the controller output decreases.
Example: Cooling or dehumidification – as the measured value rises above the setpoint, so the flow of
energy is required to increase.
● Indirect control [Actg]: As the controlled variable decreases, the controller output decreases.
Example: Heating or humidification – as the measured value falls below the setpoint, so the flow of energy is
required to increase.
Inversion [Inv]
[Inv] of the output signal is required, e.g., for air dampers. The outside air and exhaust air damper must close in
response to an increasing heating demand. The inversion of the manipulated variable affects only the output
signal [Yctr] and not the action of the controller.
88 | 346 CM110664en_10
Control concept 5
Closed-loop control strategy
Sequence controller
Sequence controllers are used primarily in ventilation and air conditioning systems to control the temperature
and humidity. Other applications are also possible, e.g., in heating systems.
Each controlled aggregate functional unit incorporates a universal PID controller function block, PID_CTR, as a
sequence-controller element.
The statements made about the universal PID controller also apply to the use of the PID_CTR function block as
a sequence-controller element.
The sequence-controller elements coordinate their own interaction independently. Interaction is coordinated with
coordination signals [FmHigher] and [ToLower], which are mutually exchanged by adjacent sequence-controller
elements. This is the only link between the sequence-controller elements. This process allows the setting of
individual parameters for each individual controller or aggregate, and hence effective optimization of the entire
plant.
CM110664en_10 89 | 346
5 Control concept
Closed-loop control strategy
When the type of operation changes, the neutral zone is defined by the set points (e.g., heating setpoint /
cooling setpoint).
90 | 346 CM110664en_10
Control concept 5
Closed-loop control strategy
SEQLINK connection
With this method, the individual PID_CTL blocks are connected via the SEQLINK block. The sequence linker
block SEQLINK is a wiring block with no function other than that of connecting other blocks.
The connection is made between the pins of block PID_CTL and a location on the SEQLINK block. The order in
which the PID_CTR blocks are connected must be the same as that of the sequence. The connections to the
SEQLINK block need not be continuous: connected pins and unused pins may be interspersed.
For example, 1 = Re-heater, 2 = Pre-heater, 3 = Dampers, 6 = Cooling coil.
This method of connection is used to interconnect PID_CTR blocks on different charts, or in cases where
individual project-specific sequence-controller elements or aggregates are to be deleted from an off-the-shelf
solution (CAS library).
Communication between one sequence controller element and another flows via the pins [ToLower] →
[FmHigher] and [ToHigher] → [FmLower].
The block recognizes configuration errors and shows these at the Token State output [TknSta]. If, e.g., the
control action [Actg] of an individual sequence-controller element is incorrectly set, the associated sequence
controller element is disabled and an error message is displayed.
CM110664en_10 91 | 346
5 Control concept
Closed-loop control strategy
Example: Output from elements 4 and 6 [TknSta] = HEL_CSEQ Output from elements 3 and 5 [TknSta] =
CEL_HSEQ:
In all the examples illustrated, several aggregates are deactivated. This is a precaution, as the sequence
elements cannot determine which of the aggregates has incorrectly set parameters. For this reason, the
aggregates are disabled one after the other until there is a clear transition to the next sequence.
Cascade control
The CAS_CTR block integrated into the Desigo system is a PI master controller for room supply air cascade
control. It delivers three supply air set points on the basis of the difference between the measured room
temperature and the room setpoint.
Compared with control without a cascade, e.g., cascade control improves the dynamics of the control process.
If the temperature in a ventilated room is below the setpoint, e.g., the supply air temperature must be increased,
at least for a brief period, in order to raise the temperature to the room setpoint. This can be achieved by
measuring and controlling not only the room temperature, (that is, the value which actually concerns the user),
but also the supply air temperature, whose setpoint depends on the difference between the room setpoint and
the room temperature.
92 | 346 CM110664en_10
Control concept 5
Closed-loop control strategy
If the room temperature is lower than the room setpoint, the supply air setpoint is adjusted in proportion to the
room control differential, and the supply air temperature is increased via the supply air control loop.
The master controller generates the setpoint for the auxiliary variable (e.g., the supply air temperature) on the
basis of the difference between the primary setpoint and the primary controlled variable (e.g., the room setpoint
and the room temperature).
The master controller must include an integrator function (I component), because even under static conditions
(that is, when the measured value and the setpoint are equal) there is generally a negligible control deviation,
which means that the controller output must be at a different operating point. For improved control dynamics, a
P-component should be connected in parallel with the integrator. This is why the master controller in this case
has a PI control structure.
Even when the primary controlled variable (room temperature) is identical to its setpoint, the auxiliary controlled
variable (supply air temperature) must generally be at a value other than 0, (that is, setpoint ≠ 0). This is only
possible if the output of the master controller is not equal to 0, even if the P component = 0. In other words, the
master controller must have an I-component which remains constant when the control differential = 0. This is
why the master controller has a proportional and an integral component. It is a numerical PI controller for use as
a master controller in a room/supply air cascade.
To save energy in the ventilation plant, various room set points are selected for different types of air handling
(heating/cooling and humidification/dehumidification). The master controller in the cascade must therefore be
able to generate different supply air set points, depending on how the kind of air treatment (heating/cooling or
humidification/dehumidification).
The supply air controller must determine whether the heating or cooling sequence is to be activated and the
decision-making strategy does not affect the calculation of the two supply air set points. Within the cascade
control loop, the supply air set points always move parallel to each other, and their offset is determined by the
integral component.
If the air handling plant includes an energy recovery aggregate, this aggregate may be either reverse-acting
(e.g., heating) or direct-acting (e.g., cooling) depending on the relationship between the condition of the outside
air and the condition of the exhaust air.
To avoid external calculation of the energy recovery setpoint, this, too, is done by the master cascade controller,
and made available to the energy recovery aggregate, if there is one, at a separate output pin:
In a humidity control system with various physical control variables, the initial value of the integrator should be
predefined.
Example:
If the humidity of the supply air is measured with an absolute humidity value [g/kg], while the room air humidity
is measured in terms of relative humidity [%Hu], an initial value must be defined for the I-component, otherwise
the mean value from [SpLoR] and [SpHiR] will be used as the initial value. If the room set points are expressed
in terms of relative humidity, then the initial value for the integrator will start at a numerically high value, and
decrease as a function of the preset integral action time [Tn]. The result of this can be that even if the room
needs to be dehumidified, the humidifier is enabled in the controller start-up phase until the integrator reaches
its correct value.
To prevent this, the current measured supply air humidity value is linked to the initial value of the integrator, or a
fixed parameter value is defined for the integrator.
If control accuracy is critical (e.g., no deadband or zero-energy control zone), then the current measured value
is linked to the initial value of the integrator, or a fixed parameter value is defined for the integrator.
CM110664en_10 93 | 346
5 Control concept
Desigo room automation
3 3
2
1
HVAC zone
The room typically is considered 1 HVAC zone influenced via a common automation and control strategy
regardless of number and type of installed HVAC plant components (e.g., radiator, chilled ceiling, fan coil unit).
Lighting zone
All lamps operated/automated together are grouped into a lighting zone regardless of number and type of the
installed lamps. A room typically has one or several lighting zones.
Shading zone
All shading products (blinds) operated/automated together are grouped into a shading zone regardless of
number and type of the installed shading products. A room typically has one or several shading zones.
94 | 346 CM110664en_10
Control concept 5
Desigo room automation
● Cross-technical installation coordination to ensure smooth functional interplay of the various installations
● Centralized, room-wide access point to operate and monitor a room
Cross-technical installation coordination
The application functions of the individual technical installations contain functionality required for technical
installation-specific control. Additional functionality assuming coordination with other technical installations is
part of room coordination. As a result, project-specific Desigo room automation requests and changes can be
carried out without changes to technical installation-specific application functions.
Examples for coordination functions are coordination of HVAC and shading functions and coordination of
shading and lighting functions.
Centralized, room-wide access point
Room coordination offers a centralized, room-wide access point to operate and monitor a room. This allows
users to enter common data for several technical installations only once and retrieve them as a group.
Examples:
● Predefinition of the room operating mode (across all technical installations)
● Predefinition of a scene for the entire room
● Queries for general occupancy
● Common alarm for system alarms
The room coordination default solution influences the following functions:
Room operating mode
Various sources influence and determine the room operating mode:
● Centralized commands from scheduler programs or manual intervention
● Local commands from presence detectors or scheduler program override
Room coordination offers a centralized, room-wide access point to operate and monitor a room operating mode.
The individual technical installations separately acquire all relevant information.
Scene
Scenes are defined to command several or all technical installations in a room via one single command, e.g.,
brightness of a lighting zone, or blinds positions in each shading zone can be defined for each scene. Room
coordination:
● Controls a scene as per the predefined values
● Changes the predefined values
Both are carried out by the room user.
Thermal room load analysis
Room coordination supports room temperature control via blinds control. The various HVAC data is analyzed to
determine the thermal room load and the associated signal definition for blinds control:
● Load if energy must be supplied to the room via the blinds position
● Unload if no additional energy must be supplied to the room via the blinds position
Blinds control determines the optimal blinds position in dependence of room occupancy and solar position
(thermal radiation and glare).
Green Leaf (RoomOptiControl)
Manual room user manipulations (e.g., manual lighting and shading commands, or manual changes to the room
temperature setpoint) can result in inefficient energy operation. Each zone and each technical installation is
checked for inefficient definitions to be pointed out to the room user. Room coordination then summarizes the
results and visualizes them on the room operator unit. The room user can then reset all manual entries (which
lead to inefficient plant operation) by one single pressure of a button.
Room common alarm
One common alarm is set up for each room to keep down the number of set up system alarms. To this end,
room coordination acquires status information (normal/alarm) for each zone and each technical installation, and
determines the room-wide alarm state as a common alarm.
CM110664en_10 95 | 346
5 Control concept
Desigo room automation
96 | 346 CM110664en_10
Control concept 5
Desigo room automation
Room Coordination
Functions
User Request
WndCont PscDet
Below is an illustration of the temperature control sequence for a more complex HVAC plant in the room. The
charts show the segregation of heating and cooling control sequences and associated setpoints and sequencing
of heat convection by fan air flow or associated switching stages.
CM110664en_10 97 | 346
5 Control concept
Desigo room automation
100%
0% TREff
Speed 3
Speed 2
Speed 1
FanSpdMin=Off TREff
SpH SpC
Individual temperature sequence controllers are assigned to each heating and cooling element. They
intercommunicate to achieve required sequencing.
Open-loop control
Additional interactions between HVAC devices implemented via open-loop control functions are required in an
HVAC plant in the room. The open-loop control functions feature two basic interactions:
● Support: Heating coil and cooling coil require the fan to run on the stage/speed required for their operation.
● Lock: The electric heating coil is locked to ensure that it cannot be operated without air flow.
Open-loop control and sequence controller are used together to implement the above, typical control sequence.
The following image shows the connection between controller and actuating devices (this does not correspond
to the actual program structure).
FanDevMod=Mod
HclDevMod=Mod CclDevMod=Mod
AND AND
Max
Operating modes
The HVAC plants in the room adapt to the room's comfort requirements, e.g., ventilation is:
Active while the room is occupied
Off, as soon as the room no longer is occupied
The following illustrations show sequence control for an HVAC plant in the room for operating modes Comfort
and Economy. Sequence control acts on heating and cooling equipment and a multi-speed fan.
Control sequences in the Comfort operating mode:
98 | 346 CM110664en_10
Control concept 5
Desigo room automation
100%
VlvPos VlvPos
0% TREff
HclHw01 CclChw01
AirFlReqHeat AirFlReqCool
Speed 3
Speed 2
FanSpd
Speed 1
FanSpdMin=Off TREff
FanMultiSpd01
SpH SpC
100%
VlvPos VlvPos
0%
HclHw01 CclChw01
AirFlReqHeat AirFlReqCool
Speed 3
Speed 2
FanSpd
Speed 1
FanSpdMin=Off TREff
FanMultiSpd01
SpH SpC
The available operating modes determine both operation and basic control strategy in the automation and
control system at three different levels:
● The room operating modes determine the operation of HVAC equipment in a room in terms of current use
by the user. The room operating modes defined for the room are available in all HVAC control applications
in the room.
● The HVAC plant operating modes determine the operation the HVAC plant in the room with regard to
existing, physical plant processes. The HVAC plant operating modes are defined specifically for 1 HVAC
plant in the room.
● The device operating modes determine the operation of the HVAC devices in a room by predefining their
tasks and implementation method. The device operating modes are defined specifically for each individual
HVAC device.
Plant and device operating modes of a plant with heating coil, cooling coil, and fan
Project-specific adaptations of both plant and device operating modes can be implemented by adapting the
operating mode table.
Plant operating mode Fan operating mode Heating coil operating mode Cooling coil operating mode
Off Off Off Off
CM110664en_10 99 | 346
5 Control concept
Desigo room automation
In addition, setpoints and setpoint limits define room and device operating modes. They can vary depending on
the selected HVAC plant operating mode. Four different setpoints are provided for heating and cooling in the
room.
SpC
SpH
t
RClmOpMod Eco Cmf Eco
00:00 06:00 18:00 24:00
The HVAC control applications in the room dynamically enable and disable the setpoints to achieve the desired
combination of energy-saving Economy and demand-based Comfort operating mode.
Command priorities
An HVAC control application simultaneously achieves several goals. Functions with different objects may
conflict when they are implemented. In this case, the command priority determines which command value has
priority in the priority array of the BACnet objects.
HVAC control applications in a room are programmed to accept commands at many different levels, including
operating mode variable level. As a result, HVAC control applications control the controlled output objects at a
priority commensurate with the active priority of the operating mode variable. The following figure shows how
commands and priorities are passed in the application.
Fire Detector
16 15 14 13 ... 8 7 6 5 4 3 2 1 RClmOpMod
FcuPltMod01
Off
C ... 8 7 6 5 4 3 2 1
16 15 14 13 PltOpMod
The BACnet objects in the system support 16 priority levels. The HVAC control applications apply these levels
as follows:
Emergency mode 2 Automatic commands related to personal safety Propagated response to Emergency
mode commands
Protection mode 5 Automatic commands to avoid damage to equipment Programmed response to equipment
safety conditions
Automatic control 9 Unassigned - commands for comfort and energy conservation None
Automatic control 10 Unassigned - commands for comfort and energy conservation None
Automatic control 11 Unassigned - commands for comfort and energy conservation None
Automatic control 12 Unassigned - commands for comfort and energy conservation None
Manual operating 13 Manual commands through room unit Programmed response to inputs from
occupants
Automatic control 14 Unassigned - commands for comfort and energy conservation None
Automatic control 15 Typical automatic commands for comfort and energy Typical automatic commands
conservation
Automatic control 16 Unassigned - commands for comfort and energy conservation None
TEx
TR
TSu
FanMulti01 HclHw01 CclChw01
TOa
DmpOa01 Fan1Spd01 HclHw02 CclChw02
FanVarSpd01 HclEl01
Often, more must be done than merely adding or removing components (CFCs). If, an HVAC device, e.g., is to
be added, the following must be added or removed:
Shading control
Products and requirements
Suitable façade products and intelligent control allow for optimum satisfaction of various requirements for
shading.
Façade products and their control required to protect against environmental influences or to make use of the
same are the primary issue:
● Shading to protect against glare
● Using daylight
● Using solar energy for heating
● Shading to protect against overheating
● Protection against rain
Other requirements may be:
● Intrusion protection
● Protection of privacy
Façade product control in addition must protect persons and equipment against the façade products
themselves. Examples:
● Drive up blinds in case of fire to open an escape route
● Protect against collision (e.g., in the event of outward-opening doors)
Façade control protects the façade products and their functionality against environmental damages caused,
e.g., by rain, wind, or frost.
The market knows many different façade products such as roller shutters, blinds, awnings, etc. to satisfy the
various requirements. The different properties of the products are included in the respective control functions.
The following figure shows a few typical façade products (from left to right):
● Horizontal blinds
● Roller shutter
● Vertical blinds
● Drop-arm awning
● Vertical awning
● Sliding-arm awning
Color key:
● Gray: Complete building
● Blue: Façade or part of a facade
● Green: Rooms of a renter, e.g., one floor
● Orange, red: Local, manual operation
The functions are grouped into local and central functions depending on whether the function acts on one or
multiple blinds in a room, or on an entire group of blinds, e.g., on all blinds of a facade.
Grouping by local and central functions for the examples from the figure above
Local manual operation Automatic shading Wind speed monitoring Scheduler program
Central function n/a Determination of optimal Measuring of wind speed Commanding of a position
shading position in Monitoring of wind speed in dependence of daytime
dependence of sun
position Commanding of wind
protection position
Local function Commanding of manual Decision on which position Positioning of blinds Positioning of blinds
position is commanded
Positioning of blinds automatically
Positioning of blinds
Control concept
The control concept is based on the following:
● Grouping into autonomous functions determining a set position for the blinds
● Priority assignment to individual functions
● Evaluation of all functions and decision in favor of specific blinds position based on priorities
Function Description
Automatic shading Automatic determination of optimum blinds position based on current room use, solar
radiation, outdoor brightness, solar position, and HVAC status. In simple terms, this
function prevents glare in occupied rooms and uses solar energy for heating in
unoccupied rooms, or protects the building against undesired heat-up.
Manual operation (room, central) Manual operation allows users to themselves determine the blinds position via buttons. If
manual operation overrides a lower-priority function, a scheduler program or local
presence information will reactivate the function.
Presence-based influence Locking of automatic operation upon entering a room, and activation of automatic
(room) operation upon leaving a room. The presence-based function generally acts on the same
priority as manual operation.
Scheduler program A scheduler program opens, closes blinds at specific times, or commands them to a
specific shading position. Furthermore, automatic operation can be activated or
deactivated via scheduler program. Another priority may need to be commanded
depending on purpose. If, e.g., automatic operation should be activated at noon, manual
operation must be overridden by allowing the scheduler program to act on the priority for
manual operation. If the blinds are to be closed at night without allowing for manual
operation, a higher priority must be commanded.
Automatic shading at high priority For example, to prevent overheating it may be necessary to use automatic shading at
higher priority, which limits or prevents manual operation in certain situations.
Manual operation at high priority Manual operation at high priority allows for positioning blinds and overriding low-priority
(room, central) functions. For example, local operation can be overridden during, e.g., a presentation. Or
it can be ensured that neither automatic shading nor a scheduler will drive the blinds up or
down at an undesired time.
Product protection, local Risks impacting a blind only, e.g., protection against collision with a service door opening
outward, are included in local product protection.
Product protection, central Environmental influences impacting a group of blinds are included in the central functions
for product protection. A common function in this category is protection of blinds against
damage from strong winds.
Maintenance position, central For maintenance or cleaning, blinds are commanded or blocked to a specific position at
high priority enabling staff to carry out all required work without risking injury due to
moving blinds.
Protection, central Blinds can be moved/driven up to provide escape or access routes for emergency
personnel in the event of a fire.
A very simple control contains just one or two functions; a complex plant may use many or all available
functions. In addition, the response of individual functions may require parameterization depending on the
requirements. The following figure shows an example of a plant including all functions.
Maintenance position
(blinds maintenance, window cleaning)
Product protection local (avoiding
collisions)
Product protection central
(wind, rain, frost)
Selection of priority
(button)
Execute
Manual operation at high priority (btton,
resulting drive
management station)
command
Scheduler program
Manual operation
(button, management station)
Presence-induced activation/
deactivation of automatic mode
Lighting control
Products and requirements
Suitable lighting products and intelligent control allow for optimum satisfaction of various requirements.
Lighting products and their control are the primary means to create optimum lighting conditions for building
users:
● Optimum workspace conditions (bright or darkened rooms)
● Optimum lecturing/teaching conditions (presentation)
● Comfort in living spaces
● Mood lighting in entertainment spaces (restaurants, bars, etc.)
Other requirements may be:
● Energy savings
● Lighting of objects, products
● Façade lighting
● Intrusion protection
Lighting products control in addition must ensure the safety of persons. Examples:
Lighting product positioning in a building, room purpose, and allocation of rooms to an organizational unit
determine the type of information acting on lamp control. Example:
● A fire alarm acts on the entire building
● A scheduler program acts on all rooms of a renter
● Local manual operation acts on all lighting of a room, or on individual lamps
Gray: Complete building
Green/yellow: Rooms of a renter, e.g., one floor
Orange: Local, manual operation
The functions are grouped into local and central functions depending on whether the function acts on one or
multiple lamps in a room, or on an entire group of lamps, e.g., on all lamps of a renter.
Grouping by local and central functions for the examples from the figure above
Local manual operation Fir alarm Scheduler program
Central function n/a Fire alarm reception Commanding of On/Off command in
Commanding of On-command dependence of time
Local function Commanding of manual brightness Switching on lighting Switch on/off lighting
Adapting lighting
Control concept
The control concept is based on the following:
● Grouping into autonomous functions determining a command for lighting
● Priority assignment to individual functions
● Evaluation of all functions and decision on the state of lighting based on priorities
Function Description
Automatic control Automatic switch-on/switch-off based on brightness, constant lighting control.
In simply terms, this function achieves optimum lighting conditions automatically in
occupied rooms, and switches off lighting when rooms are unoccupied.
Manual operation (room, central) Manual operation allows users to themselves determine brightness via buttons. If manual
operation overrides a lower-priority function, a scheduler program or local presence
information will reactivate the function.
Presence-based influence (room) Automatic switch-on when dark upon entering a room, and automatic switch-off when
leaving a room. The presence-based function generally acts on the same priority as
manual operation.
Scheduler program Lighting can be switched on/off at specific times using a scheduler program. Furthermore,
automatic control can be activated or deactivated via scheduler program. Another priority
may need to be commanded depending on purpose. If, e.g., automatic control should be
activated at noon, manual operation must be overridden by allowing the scheduler
program to act on the priority for manual operation. If lighting is to be switched off at night
without allowing for manual operation, a higher priority must be commanded.
Manual operation at high priority (room, Manual operation at high priority allows for influencing lighting blinds and overriding low-
central) priority functions. For example, this function allows for ensuring that neither motion
detectors nor scheduler programs can switch on/off lighting at the wrong time during a
lecture/presentation.
Maintenance, central For maintenance or cleaning, lighting is switched on/off at high priority enabling staff to
carry out all required work without risk of injury or being interrupted.
Protection, central Lighting can be switched on in the event of a fire alarm to light escape routes or support
emergency crew access.
A very simple control contains just one or two functions, A complex plant may use many or all available
functions. In addition, the response of individual functions may require parameterization depending on the
requirements. The following figure shows an example of a plant including all functions.
Central function Local function
Maintenance
Selection of priority
(button)
Execution of
Manual operation at high priority (button, resulting lighting
management station) command
Scheduler program
Manual operation
(button, management station)
Presence-induced influence
Automatic control
6 Technical view
The technical view illustrates the technical building services equipment, such as HVAC systems and associated
elements, in the building automation and control system.
Area Gubelstrasse
Burner
Sensor
KNG:ABdb6'AHU3Fl'FanSu
The technical view helps organize measured and controlled physical variables from specific, technical
installations in a building. The technical view is modeled with structure objects. The structure of the technical
view represents the hierarchy of the technical installations. Objects representing variables, such as setpoints or
operating modes supplement the view.
Plant types
The technical view contains all the conceptual objects in the system. The following plant types have been
defined for descriptions and categories:
● Primary plant: All physical plants that are directly controlled from the automation level, e.g., heating
systems, ventilation systems, etc.
● Room automation: Individual room controls.
● Global objects: Data objects which exist simultaneously in several automation stations at the automation
level, e.g., an exception calendar for the time schedules of all plants. These objects are combined as a
virtual plant in a global area and can be invoked as such (global data).
The technical view can be used for other disciplines integrated via PX Open. The technical view and the
associated technical designations can be set up in the compounds library.
Site
Plant
Partial plant,
Aggregate,
Component
Total max. 6
recursions (max. 7
levels)
Elements
Site: A site is a self-contained area in terms of location, function and organization, usually a building or a group
of buildings (facility). A site can comprise several plants. Example: Building 6
Plant: A plant consists of partial plants, aggregates and components. A plant can comprise several partial
plants. Aggregates and components can be directly subordinate to a plant. Example: Ventilation system, heating
system
Partial plant: A partial plant can comprise various aggregates. Components can be directly subordinate to a
partial plant. Example: Central supply air treatment, air distribution, hot water supply (one or more boilers)
Aggregate: An aggregate can comprise various components. Example: Exhaust air fan
Component: A component can comprise several components, which can comprise several components
themselves. Example: Pumps (motors), dampers, valves, sensors, detectors, limit switches, contactors, selector
switches, remote/local switches
Engineering model BACnet/System model
Site Site
1
n n
Element type:
Hierarchy element Hierarchy object Element type:
auxil. element
plant
plant (primary) Element type area
area CFC Editor: Compound
subarea
subarea
section
section Element type
1 1 Structured view object
Total max. 6 Element type
Assignable to PX recursions
(nesting)
n n
Element type:
Function element Block object Element type:
auxil. element
partial plant
partial plant Element type
CFC Editor: Compound aggregate
aggregate
Function block component
component
Function room
room
Element type Standard BACnet object
1 Element type
Element type: auxiliary element, plant, partial plant, aggregate, component, area, subarea, section, room
Global objects
Structure
Site
Global area
Component
Elements
Site: A site is a self-contained area in terms of location, function and organization, usually a building or a group
of buildings (facility). Example: Building 6
Global area: The global area contains all the global components of the site. There is one global area per site.
Global objects are data objects which exist simultaneously in several automation stations at the automation
level, e.g., an exception calendar for the time schedules of all plants. These objects are combined as a virtual
system in a global area and can be invoked as such.
Component: A global area may contain several components, such as 3 calendars, 18 notification classes for
alarm distribution. Each component is present on all automation stations of the site. For operation, however,
each component is visible only once.
Site
Area, Subarea,
Section
Room
Elements
Site: A site is a self-contained area in terms of location, function and organization, usually a building or a group
of buildings (facility). A site can comprise several plants. Example: Building 6
Area: An area is typically a building, and can comprise subareas, sections, components and subcomponents.
Example: Building
Subarea: A subarea is typically the wing of a building and can comprise several sections. Rooms can be directly
subordinate to a subarea. Example: Building wing, staircase
Section: A section is typically a floor in a building and can contain various rooms. Example: Floor
Software objects, which need to be displayed and operated even though they do not exist as physical elements
in a real building, are also treated both as sections (e.g., via grouping criteria, such as east facade or
emergency group 12) and as components (e.g., group object for distribution of centrally determined control
variables to several rooms).
Room: A room is a section of a building that is delimited by walls, ceilings, floors, windows and doors. Example:
Individual room, hall
Building
Floor
Room
Room segment
Functional unit
Component
Elements
Building: A building is a locally, functionally and organizationally defined area. Example: Building 6
Floor: A floor in a building can contain various rooms. Example: Floor
Room: A room is a section of a building that is delimited by walls, ceilings, floors, windows and doors. Example:
Individual room, hall
Room segment: A room segment is a subdivision of a room. A room can contain several room segments.
Functional unit: A functional unit is a logical component representing an encapsulated application unit which
may be independently deployed to an arbitrary automation device. Example: Fan coil
Component: A functional unit can contain several components. Example: Awning
Each element of the TD is called ShortName. A ShortName is a designation for an individual plant element
within the automation station. A ShortName is always linked to a description. This pair is called the
Name&Description_Pair.
TD rules
Item Rule
Address structure Comprises at least one hierarchical object and one function object
Has a variable length (site + 1..8 hierarchy and function objects + pin name)
Is independent of the automation station, that is, does not contain a designation for an
automation station
Must be unique for each site
Syntax Site designation Consists of upper and lower case letters, and numbers (must start with a letter): [a..z,
A..Z, 0..9].
Is case insensitive, e.g., Imax and IMAx are treated the same.
Other partial designations Consist of upper and lower case letters ([A..Z] and [a..z]) and/or numbers 0 to 9.
Is case insensitive, e.g., Imax and IMAx are treated the same.
Desigo CC PXM30/40/50
10664Z03en_07
Life check The primary server monitors the backup servers and the third-party BACnet devices of a site.
The primary server can monitor the Desigo room automation server.
Time synchronization The primary server synchronizes the time of the backup servers and the third-party BACnet devices of
the site.
The primary server can synchronize the Desigo room automation server time.
Replication The primary server replicates the global objects and properties (device object) to the backup servers
of a site. A backup server accepts changes of global objects only from the primary server.
Life check The backup servers monitor the primary server of the site.
Backup servers can monitor Desigo room automation servers.
Time synchronization The backup server can synchronize the time of the Desigo room automation server and of the third-
party BACnet devices.
The role of the Desigo room automation server and third-party BACnet device
Server/Function Function and description
Desigo room automation server / The Desigo room automation server acts like a standard BACnet device.
Third-party BACnet device
Life check The Desigo room automation server / third-party BACnet device is monitored by the primary server or
the backup server.
Locked Locked
Reset Reset Reset
DESIGO PX
Reasons for replication: Keeping the setting parameters consistent for all automation stations of a site when
modifications occur (adding or deleting configured recipients from recipient list, changing priorities).
Desigo CC PXM20
10664Z05en_07
The number of global Notification Class objects is limited to 18 (six alarm classes each with three possible alarm
functions).
Calendar object
There are global and local calendar objects.
Desigo CC
10664Z06en_07
Global calendar object: A logical object at site level. It exists in identical form (as a replicated object) on each
automation station of a site.
Local calendar object: Individual (unique) object that exists only on a particular automation station.
Local processing: Schedule objects in an automation station may reference the replicated calendar objects in
the device. A client may read the global calendar objects from any automation station.
Reasons for replication: Global exceptions (bank holidays, general holidays, etc.) can be modified centrally in
one location for the entire site. Ensures continuity of operation if the master fails.
10664Z07en_07
BACnet Device Info Object The BACnet Device Info Object detects the causes of system events which apply to the automation
station as a whole. The following causes are detected:
- Change of operating state (start and stop the program)
- Restart after a power-up
- Primary server has found a new backup server on the network
- Backup server has found the primary server
System events cannot be acknowledged or reset. A Confirmed Event Notification message is sent to all alarm
recipients. The Notify_Type data field in the message defines that the event is a system event and not an alarm.
Each alarm recipient that receives the Confirmed Event Notification is required to respond with a SimpleAck. If
the SimpleAck is not received, the same mechanism comes into operation as for alarms.
SimpleAck
SimpleAck
t t t
Event texts
Each system event has a message text assigned to it. For the system events related to the operating hours
counter, a user-specific text can be set up in Xworks Plus (XWP). Predefined system texts are available for the
other system events.
COV
Client
Automation level
COV
Client PXM20
Block A Block Z
COV
Client
COV
Server
Block V
COV
Server
10664Z46en_07
Block B Block Q
The local PXM10 operator unit is not a BACnet client and cannot, therefore, be used as a COV client.
See PXM10 operator unit: User's guide (CM110397).
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
t t
The BACnet client subscribes to the COV server as a COV client using the BACnet service SubscribeCOV. The
server sends a SimpleAck acknowledgement. Immediately after the acknowledgement, the COV server
transmits an initial ConfirmedCOVNotification. The COV client acknowledges receipt of the value with a
SimpleAck acknowledgement. The COV connection between the COV server and COV client is now
established, and ConfirmedCOVNotifications are sent whenever a trigger for the subscribed COV occurs.
The BACnet service SubscribeCOV includes a time limit for the COV connection. However, the COV client re-
registers with the COV server before this limit expires, thus ensuring that the connection is maintained. A COV
connection ends when the subscription period expires and is not renewed, or when the COV client can no
longer be contacted, causing the COV server to stop sending notifications.
In addition to the SubscribeCOV service, a SubscribeCOV Property service is implemented, e.g., for the
operation of plant graphics in Desigo CC. This enables the system to respond with appropriate speed to
changes in the high or low limit.
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
t t
When an automation station connects, the BACnet service WhoHas searches the entire network for the object
referred to in the COV client. The automation station concerned responds to the COV client with the BACnet
service IHave. If the COV client cannot find the COV server, it repeats the WhoHas request after the time period
defined in the BACnet Device Info Object Property Name resolution interval [NamRI] until the COV server is
found.
The COV client registers for a limited period as a COV client with the COV server using the BACnet service
SubscribeCOV. The server sends a SimpleAck acknowledgement. The value is then sent to the COV client for
the first time by the COV server, using the BACnet service ConfirmedCOVNotification. The COV client
acknowledges receipt of the value with a SimpleAck acknowledgement. The COV connection between the COV
server and the COV client is established from this point on. According to the global property COV renewal
interval CovRI of the BACnet Device Info Object, the COVsubscription is renewed. The lifetime used for
SubcribeCOV is twice the COV renewal interval CovRI. The COV connection ends when the subscription period
expires and is not renewed, or when the COV client can no longer be contacted, causing the COV server to stop
sending notifications.
9 Alarm management
Alarms indicate faults in the HVAC plant and building automation and control system, and let you initiate
corrective action, where appropriate. The management of alarms (generation, signaling, acknowledgement) is in
compliance with the BACnet standard.
There are two alarm types:
● OFFNORMAL
● FAULT
OFFNORMAL
OFFNORMAL alarms (process alarms) occur when a process variable assumes an inadmissible value. What is
inadmissible is determined during engineering. The relevant parameters are stored in all alarm-generating
objects. An OFFNORMAL alarm always indicates a fault in a plant, while the automation system itself works
properly.
Examples of OFFNORMAL alarms:
● Temperature in HTHW circuit is too high or too low
● Alarm generated by fire detection system
● A damper-motor feedback signal has not been received
● A time schedule cannot execute a command
FAULT
FAULT alarms are faults in the automation system itself (internal alarms). You cannot define the cause of a
FAULT alarm during engineering. Nor is it possible for the user to suppress or otherwise influence the
monitoring of FAULT alarms. FAULT alarms are intrinsically linked to the system. A FAULT alarm always takes
precedence over an OFFNORMAL alarm from the same alarm source, because in the case of a FAULT alarm,
there is some uncertainty about the reliability of the alarm source.
Examples of FAULT alarms:
● Faulty sensor (open circuit, short circuit, etc.)
● Buffer for storage of non-volatile data full
● Access to an I/O module failed
● Bus open circuit (RX integration)
Only these alarm sources incorporate intrinsic reporting, and can thus generate their own alarms. If any other
value of a function block needs to be monitored for an alarm (e.g., the control signal for a controller block), an
Event Enrollment object must be added.
Alarm-generating function blocks include a range of interface variables which can be set as parameters to
determine the alarm response (Input Property) or to supply the relevant alarm state information (Output
Property). These interface variables are described further below. Some of the interface variables are common to
all alarm-generating block types, while others are specific to certain types of alarm-generating blocks.
TO_NORMAL1 The current OFFNORMAL alarm condition has disappeared, and there is NORMAL
no other alarm condition present.
TO_NORMAL2 The current FAULT alarm condition has disappeared, and there is NORMAL
currently no other alarm condition.
System events may also occur within each alarm state. These message functions do not affect the alarm state.
Because FAULT alarms take priority over OFFNORMAL alarms, the state transition from FAULT to
OFFNORMAL only occurs under very special circumstances.
If, while in the OFFNORMAL state, a FAULT alarm condition occurs, there is then a state transition TO_FAULT
(because as stated above, FAULT takes priority over OFFNORMAL).
Zustandsmaschine 1
RefVal 3 4
? PrVal disturbed Belt
PrVal
2
3 7 disturbance
appears
OR 6
Pop Up Desigo CC
Txt:........................
3 ACK
RESE 5
Auto
ON Pop Up
OFF
Txt:........................
9 ACK
RESE
Key
Ⓐ State machine
Ⓑ CFC program
Ⓓ Desigo CC popup
Ⓔ PXM… Values (in a PXM10 alarm handling is only possible for connected PXCs or PXRs)
Ⓕ PXM… Popup (in a PXM10 alarm handling is only possible for connected PXCs or PXRs)
up time is allowed to expire, that is, DPMon.RefVal is held at 1 during the transient state. Only after expiry of
the ramp up time does DPMon.RefVal revert to 0.
7. The ventilation system is already running (from step 6 on), that is, the fan blades start rotating, the pressure
builds up and the differential pressure monitor detects delta p = X again, that is, DPMon.PrVal → 1. The
alarm monitoring function is active again. After expiry of the time [TiMonDvn], this determines that there is
no alarm condition present, because [DPMon.PrVal(0) <> DPMon.RefVal (1)]. The system then operates
100% correctly as described under step 1 above.
To simplify the time chart shown above, the connection to DPMon.EnAlm has not been included.
Event state EvtSta Event state Event_State Discipline I/O1 I/O/V I/O/V I/O/V
1
Group
Pulse Converter
Trend Logs
Device-Info1
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
Out of service OoServ Out of order Out_of_Service Device-Info1 I/O/V I/O/V I/O/V
1
Discipline I/O
Group1
Pulse Converter
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
State flag StaFlg State flag Status_Flags Device-Info I/O/V I/O/V I/O/V
Pulse Converter
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
Event time stamp TiStmEvt Event time stamp Event_Time_Sta Device-Info1 I/O/V I/O/V I/O/V
mps Discipline I/O1
Group1
Pulse Converter
Trend Logs
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
Key
1
Only in Desigo PX.
Hi limit [HiLm]
This parameter (data type Real) determines the high alarm limit. If [PrVal] exceeds the high limit value [HiLm] for
longer than the period defined under [TiMonDvn], an OFFNORMAL alarm condition prevails, namely:
HIGH_LIMIT.
The definitions of the set point and the measured value depend on the object type:
Examples
The following example shows the use of the three time periods [TiMonDvn], [TiMonOn], [TiMonOff]. For another
example, see Alarm Example.
It is assumed that a fire damper has two separate feedback mechanisms (end switches). This means that the
damper is commanded via the commands Open and Close. The first end switch, the Open switch delivers the
signals Fully open or Not fully open. The second end switch, the Closed switch delivers the signals Fully closed
or Not fully closed. The following is an example of how to connect the BO (binary output for commanding and
integrating the Open switch) and BI (the binary output for the closed switch):
Given the feedback signal [FbVal] Fully open, the Open and Close commands follow the time sequence shown
below, making use of all three deviation monitoring times [TiMonDvn].
Since the BO block can handle the feedback of two different addresses, the fire-protection damper solution can
be further simplified by direct connection of the Closed switch (Addr. 1) and Open switch (Addr. 2). In cases
where both end switches are simultaneously On or simultaneously Off, the BO block treats the [FbVal] as
invalid. Throughout this period, therefore, the alarm monitoring function will return the value Alarm =
OFFNORMAL. The circuit and time sequence for normal and error conditions are as follows:
Circuit and time sequence for normal and error conditions:
Reliability [Rlb]
The value under [PrVal] is only plausible if [Rlb] = NO_FAULT_DETECTED.
When [Rlb] <> NO_FAULT_DETECTED, this is precisely the condition for a FAULT alarm.
The BACnet Device Info Object is an exception. The value of [Rlb] for the BACnet device object is
NO_FAULT_DETECTED, except in the case of the fault FLASH_FULL (FAULT condition). This is equivalent to
the standard BACnet property Reliability.
Name Value
State 1 STEP 1
State 2 STEP 2
State 3 STEP 4
In this example, an incoming OFFNORMAL alarm will be detected if [PrVal] = STEP 1, STEP 2 or STEP 4 after
expiry of the period defined by [TiMonDvn].
A recipient name (e.g., the configured recipient of an alarm) could not be resolved, because, e.g., the network
connection to the recipient was interrupted. This causes an alarm to be generated. The alarm is cleared as soon
as the subsequent name resolution process succeeds.
Notif. Class ref. missing
Each alarm-generating block includes a reference to a Notification Class block. If the referenced Notification
Class block does not exist, the BACnet Device Object generates an alarm.
Life check error
While the life check is in progress, the primary server finds that it is unable to communicate with one or more of
its backup servers (e.g., owing to a network failure). This causes an alarm to be generated. The alarm is cleared
when, during a subsequent life check, all the backup servers are found again.
Primary server not found
This bit is set when the backup server detects that the primary server is no longer connected to the network. At
the same time a notification (data-type STRING) is sent, defining the source, target and reason. The bit is reset
as soon as the backup server detects the primary server on the network again.
FAULT alarms
The condition described below causes a FAULT alarm to be generated in the BACnet Device Object:
Flash is full
The automation station checks periodically whether there is at least one free page (64 kB) in the flash memory.
This bit is set if the flash memory falls below this value. The bit is reset when the flash memory contains at least
one free page again.
Alarm response of the BACnet Device Object is also parameterized or depicted by the number of variables, but
the display differs: The BACnet Device Object is not displayed by a D-MAP function block, but rather only visible
via BACnet. The variables described are therefore only accessible as properties of the BACnet Device Object.
Binary Output
The alarm handling process in the binary output function block is essentially different from that of the binary
input and binary value blocks.
● An OFFNORMAL alarm occurs when the current values of the variables [PrVal] and [FbVal] differ from each
other for a time period at least equivalent to the delay time specified in [TiMonDvn], [TiMonOff] or
[TiMonOn].
● An existing OFFNORMAL alarm will disappear when the current [PrVal] und [FbVal] are again identical and
remain so for a period at least equivalent to the time specified in the variable [TiMonDvn].
● A FAULT alarm is generated when the [Rlb] property of the function block assumes any value other than
NO_FAULT_DETECTED. In particular, this is the case when the [Rlb] property changes from a value not
equal to NO_FAULT_DETECTED to another value not equal to NO_FAULT_DETECTED.
In the case of the binary output, [Rlb] errors may originate both from the [PrVal] (or associated physical
output) and from the [FbVal] (or associated physical input).
● A FAULT alarm will disappear as soon as the variable [Rlb] changes from a value not equal to
NO_FAULT_DETECTED back to the value NO_FAULT_DETECTED.
Command Control
An OFFNORMAL alarm is generated:
● A monitored, referenced object is not enabled
● A referenced object cannot be enabled
A FAULT alarm is generated when:
● A referenced object is not found
● A referenced object is not a commandable object (output object or value object)
● Invalid priorities are used for the referenced object (valid priorities are Priority 2, 5, 14 and 16)
● ProgramValue or ExceptionValue are outside the permissible range
● The referenced objects have a different number of operating modes
● The function table is empty
● Address conflict:
The subsystem fails to recognize the device defined in the [IOAddress] parameter. This alarm is issued by
the associated function block.
● Communications error:
The subsystem indicates a communications failure. This can be due to a bus open circuit or a faulty device,
or, very rarely, to a communications overload on the bus. These alarms are indicated by the shared function
block.
The subsystem indicates an inadmissible response from a device e.g. in the case of faulty QAX… room unit.
These alarms are indicated by the shared function block.
Multistate output
The alarm handling procedure for the Multistate Output function block is different from the alarm handling
procedure for the Multistate Input and Multistate Value function blocks, but follows the same principles as for the
Binary Output block:
● An OFFNORMAL alarm occurs when the current values of the variables [RwVal] and [FbVal] differ from
each other for a time period at least equivalent to the delay time specified in [TiMonDvn].
● An existing OFFNORMAL alarm will disappear when the current [PrVal] und [FbVal] are again identical and
remain so for a period at least equivalent to the time specified in the variable [TiMonDvn].
● A FAULT alarm is generated when the [Rlb] property of the function block assumes any value other than
NO_FAULT_DETECTED. In particular, this is the case when the [Rlb] property changes from a value not
equal to NO_FAULT_DETECTED to another value not equal to NO_FAULT_DETECTED. In the case of the
multistate output block, [Rlb] errors may originate both from the [PrVal] (or associated physical output) and
from [FbVal] (or associated physical input).
● A FAULT alarm will disappear as soon as [Rlb] changes from a value not equal to NO_FAULT_DETECTED
back to the value NO_FAULT_DETECTED.
Power Control
An OFFNORMAL alarm is generated:
● The UP command is issued but the maximum stage has already been reached
● The UP command causes MaxPower to be exceeded
● Table_No is set outside the admissible range
A FAULT alarm is generated when:
● A referenced object is not found
● A referenced object is not a multistate value object
● Object_No. is outside the admissible range
● StepLimit is outside the range of the referenced object
● The function table is empty
Pulse Converter
Alarm response
An OFFNORMAL alarm is generated, when [PrVal]:
● [PrVal] has remained above the high alarm limit specified by the [HiLm] variable for a period of time longer
than the period specified in [TiMonDvn] (HIGH_LIMIT)
● or [PrVal] has remained below the low alarm limit specified by the [LoLm] variable for a period of time longer
than the period specified in [TiMonDvn] (LOW_LIMIT)
An existing OFFNORMAL (HIGH_LIMIT) alarm will disappear when [PrVal] has remained below the value
([HiLm] + [Nz]) for longer than the time specified in the variable [TiMonDvn]
An existing OFFNORMAL (LOW_LIMIT) alarm will disappear when [PrVal] has remained below the value
([HiLm] + [Nz]) for longer than the time specified in the variable [TiMonDvn]
● A FAULT alarm is generated as soon as the [Rlb] property of the function block assumes any value other
than NO_FAULT_DETECTED. In particular, this is the case when [Rlb] changes from a value not equal to
NO_FAULT_DETECTED to another value not equal to NO_FAULT_DETECTED.
● A FAULT alarm will disappear as soon as the [Rlb] property of the function block changes from a value not
equal to NO_FAULT_DETECTED back to the value NO_FAULT_DETECTED.
Trend Log
Alarm response
The Trend Log function has an intrinsic reporting mechanism, but does not issue OFFNORMAL alarms.
● A FAULT alarm is generated as soon as the [Rlb] property of the function block assumes any value other
than NO_FAULT_DETECTED. In particular, this is the case when [Rlb] changes from a value not equal to
NO_FAULT_DETECTED to another value not equal to NO_FAULT_DETECTED.
● A FAULT alarm will disappear as soon as the [Rlb] property of the function block changes from a value not
equal to NO_FAULT_DETECTED back to the value NO_FAULT_DETECTED.
Event message
An event is generated when:
● The record count exceeds the record count value [RecCnt] set via the notification threshold [NotifThd], that
is, the local non-volatile trend memory is overflowing.
Event enrollment
The event enrollment object monitors referenced BACnet properties in other objects. The referenced property
can be located in the local device or in another device.
Event algorithms
Monitoring details for a property value are defined by means of event algorithms. An event algorithm has a
specific parameter. Event algorithms are the same as for intrinsic reporting. Intrinsic reporting uses a subset of
the possible event algorithms of event enrollment.
Event notification
An event enrollment object also monitors the status flag property of an object with referenced property. If the
FAULT flag of the referenced object is set, the event enrollment object generates a Fault alarm.
Loop object
Alarm response
The Loop object contains intrinsic reporting.
An OFFNORMAL alarm occurs when:
● [XCtr] exceeds the limit (SetPoint + ErrorLimit) longer than the specified time (HIGH_LIMIT) defined in
variable [TiMonDvn]
● [XCtr] drops below the limit (SetPoint – ErrorLimit) longer than the specified time (LOW_LIMIT) defined in
variable [TiMonDvn]
An existing OFFNORMAL alarm (HIGH_LIMIT) disappears again when [XCtr] drops below the value (SetPoint +
ErrorLimit – Deadband) longer than the specified time defined in variable [TiMonDvn].
An existing OFFNORMAL alarm (LOW_LIMIT) disappears again when [XCtr] exceeds the value (SetPoint –
ErrorLimit + Deadband) longer than the specified time defined in variable [TiMonDvn].
FAULT alarm:
● A FAULT alarm occurs immediately as soon as [Rlb] of the function block has a value other than
NO_FAULT_DETECTED. This is true in particular when [Rlb] changes from a value that is not equal to
NO_FAULT_DETECTED to another value that is not equal to NO_FAULT_DETECTED.
● A FAULT alarm disappears immediately as soon as [Rlb] of the function block changes again from a value
that is unequal to NO_FAULT_DETECTED to the value NO_FAULT_DETECTED.
Standard pattern
There are three standard categories of alarm, or alarm functions, reflecting the type of acknowledgement
required:
● Simple alarm
● Basic alarm
● Extended alarm
Each alarm source is assigned (via a Notification Class, see further below) to one alarm function only. No
further distinction is made at this stage between OFFNORMAL and FAULT alarms.
Simple alarm
Neither incoming alarms (disturbance appears) nor disappearing alarms (disturbance disappears) require
acknowledgement.
Basic alarm
Acknowledgment is required for incoming alarms only, but not for alarms that have been cleared (that is,
acknowledgement required but not reset).
Extended alarm
Locking alarm with acknowledgement of incoming alarms (disturbance appears) and cleared alarms
(disturbance disappears). Alarms in this category require both acknowledgement and reset.
While testing the system, it may not be possible to reset an alarm. The reason is that an Extended Alarm is not
reset until it has been acknowledged, and the time delay has expired.
The alarm remains locked until the fault has disappeared and has been acknowledged and a reset has been
carried out, e.g.:
The burner system is restarted when the service engineer has acknowledged the alarm, cleared the fault and
reset the alarm. The alarm state of every alarm-generating object is managed within the object itself. The state
machines above illustrate this for each of the alarm functions.
Simple message
The alarm function simple message is the same function as the simple alarm. State transitions, however, are
not indicated as events, but alarms.
For HVAC applications and response in the system, the functionality is identical to simple alarm: Simple alarm
without acknowledgement of incoming and outgoing faults. The only difference is EventNotification as alarm or
event.
Customized alarm
Any alarm function under BACnet can be used. The following behavior can be defined for customized alarms:
● EventNotification can occur as either event or alarm
● Acknowledgement: For each change of state (TO-OFFNORMAL, TO-NORMAL, and TO-FAULT) can be
defined whether or not an acknowledgement is required.
[AckTra] Acknowledged transitions
This feature is used to represent the acknowledgement status, or to handle information about which state
transitions currently still require acknowledgement. The value of [AckTra] is based on the alarm function, the
current [EvtSta] and the monitoring of acknowledgements already received.
[AckTra] consists of three flags, one each for TO-OFFNORMAL, TO-NORMAL and TO-FAULT. The flags have
the following meanings:
● The flag is always FALSE when there has been a relevant state transition and an acknowledgement is
required, because this is a requirement of the alarm function and no acknowledgement has yet taken place.
● The flag is TRUE when no acknowledgement of the state transition is required. This may be the case
because the alarm function does not require acknowledgement, or because no state transition has occurred,
or because a state transition that has occurred has already been acknowledged.
[TiAck] Time of acknowledgement
Time of the last acknowledgement (time stamp).
Each alarm-generating object is assigned one notification class [NotifCl] only, but one notification class can be
used by more than one alarm-generating object. This makes it possible to create a Notification Class object for
each group of alarms (e.g., HVAC alarms, fire alarms etc.). Each alarm source in a given alarm group is
assigned to the [NotifCl] for that group.
There are global and local notification class objects:
● Global notification class: One set of max. 18 global notification class objects per site. Global notification
classes are replicated and thus exist on all Desigo PX of a site in identical form.
● Local notification class: On Desigo PX, local notification classes can be engineered, but are NOT replicated.
● Desigo room automation supports exclusively local notification classes.
Interface definition
The notification class function block [NotifCl] is the means by which functionality is transferred from the BACnet
standard into the CFC environment.
This function block contains the instance number of the Notification Class (an integer). which must be identical
to the value entered in the subordinate alarm sources. This makes it possible to create a unique reference.
The number must not be modified online.
Notification class number
There are 18 predefined global notification classes. The notification class is identified with the two independent
variables AlarmFunction and AlarmClass, and referenced in the alarm source:
● AlarmFunction [Simple(1), Basic(2), Extended Alarm(3)]
● AlarmClass [UrgentAlarm (1), HighPrioAlarm (2), NormalAlarm (3), LowPrioAlarm (4), UserDefinedAlarm (5)
and OffLineTrend (6)]
Formula
The notification class number is calculated as follows:
NotificationClass# := 10 * AlarmClass + AlarmFunction
This gives the following notification classes:
UrgentAlarm Simple 1, 1, 5 11
UrgentAlarm Basic 1, 1, 5 12
UrgentAlarm Extended 1, 1, 5 13
Critical alarms
HighPrioAlarm Basic 2, 2, 6 22
HighPrioAlarm Extended 2, 2, 6 23
Normal alarms
NormalAlarm Simple 3, 3, 7 31
NormalAlarm Basic 3, 3, 7 32
NormalAlarm Extended 3, 3, 7 33
Non-critical alarms
LowPrioAlarm Simple 4, 4, 8 41
LowPrioAlarm Basic 4, 4, 8 42
LowPrioAlarm Extended 4, 4, 8 43
UserDefinedAlarm Simple 5, 5, 9 51
UserDefinedAlarm Basic 5, 5, 9 52
UserDefinedAlarm Extended 5, 5, 9 53
Offline trends
The To-Normal priority must
be such that it is less than or
equal to the Alarm Priority
Limit of the device object (for
Remote Mgmt)
OffLineTrend Simple 2, 2, 2 61
OffLineTrend Basic 2, 2, 2 62
OffLineTrend Extended 2, 2, 2 63
Project-specific notification classes can be defined in addition to predefined ones. Alarm classes 7...16 are
intended for this purpose. The associated calculation of a notification class number is identical to calculation of
predefined notification class numbers.
Customized alarms can be engineered in Desigo PX. In this case, the value for a notification class number can
be defined without restrictions.
Priority [Prio]
This defines the alarm priority on the basis of which alarm and system events are to be transmitted to the
receivers. Every transition can be described individually with this BACnet property, data type ARRAY of
INTEGERS [TO_OFFNORMAL; TO_FAULT; TO_NORMAL]. Priority levels can range in value from 0 to 255.
The lower the value, the higher the priority. In Desigo only priorities 1 to 9 are used.
Alarmfunction [AlmFnct]
Alarm function types: Simple, Basic or Extended. [AlmFnct] is only supported by Desigo PX.
Destination list [RecpList]
The configured (permanent) alarm recipients, the week days, and the time window in which the alarm recipient
is operated, are entered here. [RecpList] is equivalent to the standard BACnet property Recipient_List.
Destination list [DestLi]
This is where the configured (permanent) alarm receivers are entered, together with the days of the week and
the time-window in which the alarm receiver is operated. [DestLi] is only supported by Desigo PX.
Site "Muri"
BACnet PTP
BACnet PTP
Router
Operator units:
● Permanently connected operator units (and hence, alarm receivers) are addressed by their Device Name.
● Operator units (and hence alarm receivers) with a point-to-point connection (PTP connection) are addressed
with a Remote Area Site identifier and their Device Name. For example:
B=fff for permanent connection
B=kkk:aa for point-to-point connection (PTP connection)
● Adjustments are required during the addressing process so that there is no conflict between the names of
operator units and the plant or room management designations.
Permanent and point-to-point connections:
● For alarm receivers, the address syntax (see further below) indicates the type of connection: permanent or
PTP connections.
● Desigo PX automation stations with half-routers must know the Remote Area Site designators of their
remote alarm receivers to enable an PX automation station to resolve the remote alarm receiver designator.
B=
Permanently
DeviceIdentifier connected
alarm receiver
Not case-sensitive
A..Z
a..z
0..9
Element Description
DeviceName Device name. In plain text so that the user can understand it.
Example: CC 01
DeviceIdentifier Device Identifier. Alternative syntax for the alarm receiver of a third-party manufacturer. If the
alarm receiver has a special address range or if DeviceName does not work.
Example: [13456]
RemoteAreaSiteName Remote area site name. In plain text so that the user can understand it.
Example: Chur
If an automation station cannot transfer an alarm message to a temporary alarm receiver (e.g., because it is no
longer connected to the network), the address of the receiver concerned will be removed from the [RecpList]. All
alarm messages destined for that receiver will then be deleted.
Preconfigured alarm receivers
The preconfigured alarm receivers are entered in the notification class object:
● In the [DestList] for Desigo PX
● In the [RecpList] for Desigo room automation
SimpleAck
SimpleAck
t t t
This procedure is carried out for every change in alarm state on an alarm server: TO_OFFNORMAL,
TO_FAULT und TO_NORMAL. The data record Confirmed Event Notification contains the following information:
● BACnet address of the alarm server
● Object ID of the alarm-generating object
● Time stamp
● Alarm priority
● Initial and final state of the transmitted state transition (this is used to determine whether the state transition
is TO_OFFNORMAL, TO_FAULT or TO_NORMAL)
● Acknowledgement required [AckReq]: Does the notified state transition require acknowledgement or not?
● Alarm text
● Other technical details
Based on this information, the alarm client can present the alarm in a comprehensible way; it may also read
additional information automatically from the alarm server, and if required, return any acknowledgement to the
correct address.
If a temporary alarm receiver does not confirm receipt with a SimpleAck message (via the Confirmed Event
Notification input), the alarm server will try three times more to transmit the alarm to the relevant alarm receiver.
The message for this alarm client will then be lost and its reference will be deleted from the [RecpList] of the
BACnet device object.
Alarm acknowledgement over the network
This process is performed for all acknowledgements made on an alarm client.
SimpleAck
SimpleAck
t t t
SimpleAck
SimpleAck
t t t
• • • • (F, F, F) suppressed
Longer messages are divided into segments with forward slashes // so that the client can display the message
over several lines. Each segment may contain a maximum of 70 characters, with a maximum of three segments
separated by // for any one message.
Non-configured message texts
System alarms and events of the BACnet Device Info Object use text messages which cannot be configured,
e.g., Battery low.
Predefined, language-dependent text
System alarms and events of the BACnet Device Info Object use non-configured text messages whose contents
are language-dependent. These language-dependent texts are organized into text groups with a predefined
server system text scope, and can be translated. The translated text groups are loaded into the automation
station via BACnet description information.
10.1 Schedule
Weekly schedule [WeekSchd]
The weekly schedule [WeekSchd] consists of seven 24-hour profiles, one for each day of the week. By default,
the priority level assigned to the weekly schedule is 16 (the lowest priority). The weekly schedule is active
unless there is an exception schedule.
For system limits, see chapter System Configuration.
24-hour profiles
A 24-hour profile is a list of time-and-value pairs. The present value remains at the [PrVal] output until the
processing of the next time-and-value pair causes a new value to be written to the output.
If there is no schedule entry with a switch time of 00:00 in the daily profile, the default value determines the
resulting Present_Value (=Rule schedule default value).
If the daily profile encompasses an empty list of schedule entries, the default value [DefVal] determines the
resulting Present_Value (=Rule schedule default value).
The evaluation of the exception schedule, weekly schedule, and [DefVal] is as follows:
Start of the day:
● Exception schedule with switch value at 00:00:
The exception schedule determines the resulting Present_Value if an active switch value exists at 00:00.
The day begins with this exception value (=Rule switch value exception schedule).
● Empty daily profile:
If the daily profile encompasses an empty list, the default value [DefVal] determines the resulting
Present_Value (=Rule schedule default value).
● Daily profile with switch value at 0:00.
If a schedule entry with switch time 00:00 and active switch value is available in the daily profile, the switch
value determines the resulting Present_Value. The day begins with the daily profile value (=Rule Switch
value daily profile).
Course of the day:
● Switch value exception schedule:
If an active switch value exists for a specific time, the exception schedule determines the resulting
Present_Value.
● Daily profile switch value:
If an active switch value from a daily profile exists for a specific time, the daily profile determines the
resulting Present_Value.
● Default value switch value:
If no active switch value from the exception schedule and the daily profile exists at a specific time of day, the
default value determines the resulting Present_Value.
Key
① An exception profile applies to more than one day. On the second day, the exception profile is inactive, because another profile with
a higher priority is active for the whole day.
② An exception program without the entry NULL. This exception profile is active for the whole day and ends automatically in the
automation station at 24:00 hours by the NULL entry.
③ Several exceptions with the same priority on the same day, but without overlapping times. The exception profiles do not interfere
with each other as an exception begins with the first time entry and ends with NULL.
④ Several exception profiles with the same priority on the same day with overlapping times. These exception profiles affect each
other, as several exceptions with the same priority level are active simultaneously. In such cases, the rule is that if the switch
commands are the same, the first time-entry applies (in this example 13:00 to NULL). With non-identical switch commands, the
latest time-entry applies.
Output signals
[PrVal] [NxVal] [NxTi]
The scheduler sends the following output signals:
● [PrVal]
● [NxVal]
● [NxTi]
The [NxVal] und [NxTi] output signals support the optimum start/stop control of the plant. When determining
[NxVal] and [NxTi] in the time schedule, the current day and the next two days are taken into account. This
results in a time window of 48 to 72 hours, depending on the current time and the next switch entry. If there is
no change in [PrVal] within the time window, then [NxVal] is the same as [PrVal] and [NxTi] is equivalent to the
current date plus 3 days (00:00h).
[DefVal]
This default value [DefVal] appears at the [PrVal] output when there is no active entry in the time schedule, or
when the entries are all NIL, or when the time period is outside the active period.
[EnDef]
The [EnDef] variable enables or disables the [DefVal] variable.
The function block variables [DefVal] and [EnDef] are mapped to the Schedule_Default property. The property
Schedule_Default can have the value [DefVal] or NIL.
The NIL value in the Schedule_Default property is the release value for the active priority of the object controlled
by the scheduler. Do not confuse it with the NIL value in the exception schedule used to prioritize the time
entries.
Schd (PX and Desigo room automation) Boolean / Unsigned / Real / Enumerated
The switching value is output to [PrVal] and to the objects to be switched (commanded objects list). A schedule
block can only contain switching values of the same data type (binary or analog or multistate or boolean or
unsigned or real or enumerated). It is therefore not possible to switch two different data types in sequence.
In Desigo PX the CAL (calender) and SCHED (schedule) function blocks can be created online.
Commanded objects
The schedule can influence other commandable objects, irrespective of whether or not they are in the same
automation station.
The schedule is thus a grouping object and contains a list of group members, in the form of a list of name
references [NamrList]. These group members are the commanded objects, that is, the objects to be switched.
The list can contain up to five entries.
Referencing
The referencing of group members is resolved at runtime.
Information flow
The grouping and the information flow only go in one direction (forward referencing).
The information flows inside one automation station or across several automation stations. The scheduler object
recognizes the flow of information and knows where to send information and what data type is required by the
group members. The information transmitted covers only the present value [PrVal] or the values for the
Optimum Start/Stop functions [PrVal], [NxVal] and [NxTi].
Heartbeat [Hrtbt]
In Desigo PX the function block variable Heartbeat [Hrtbt] determines the period measured in seconds at which
the current value (Present_Value) is written.
Enable_Repeat_
Command [EnRptCmd]
In Desigo PX the function block variable Enable_Repeat_Command [EnRptCmd] defines if the switching action
is executed if the Present_Value does not change:
● EnRptCmd = TRUE: Switching action is executed if Present_Value does not change.
● EnRptCmd = FALSE: Switching action is NOT executed if Present_Value does not change.
Time resolution
The smallest unit in the scheduler program is one minute and in the calendar one day. The schedule may be
dependent on the calendar. In the PX automation stations, the calendar function block is automatically
processed before the scheduler function block. The superposed cycle for processing the calendar and
scheduler begins at the start of the new minute of the system time.
A PX automation station incorporates an automatic load shedding mechanism. The result is that a switch
command at time x is executed within a time-period defined by time x + 1 minute.
System time
Schedules and calendars are based on the same global time. This ensures that all automation stations on a site
have the same time base.
10.2 Calendar
Function block Calendar
The calendar object is a function block from the firmware library. It contains a list of dates [DateList] with, e.g., a
date or a date range.
The date list [DateList] uses Boolean logic to control the calendar outputs. [PrVal] activates an exception profile
if the calendar object is referenced by a schedule object. The outputs tomorrow [Tmw] and day after tomorrow
[DayAfTmw] support the optimum start/stop control of the plant.
Standard BACnet object Calendar
The SCHED (schedule) and CAL (calender) function blocks in the firmware library correspond to the SCHED
and CAL standard BACnet objects. Standard BACnet object can be operated via the BACnet clients.
The calendar and schedule can be linked at the BACnet level by references. There is no data flow link between
the calendar and schedule function blocks in the CFC chart.
10.3 Wildcards
A wildcard character (*) generates a repetition and is an abbreviated way of listing individual entries, e.g., writing
3.* is a short way of representing 3.1., 3.2., 3.3., 3.4., 3.5., etc.
All data structures of the scheduler or calendar objects support dates with wildcards. Date ranges and time
specifications do not support wildcards. Invalid weekdays are ignored.
23.April.2001 /* 23.April.2001
23.April.* /Monday Each April 23rd, each year if the weekday is a Monday
*.April.* /Tuesday Each day in April of each year if the weekday is a Tuesday
31.*.* /* Each January 31, March 31, May 31, … of each year
or each February 28/ 29, April 30,... of each year
If a date contains a wildcard in the month or year, the last day of the month is used for the day, if the value of
the day is greater than the maximum number of days in the month.
11 Trending
Trend data provide important information about the processes in a building automation and control system, e.g.:
● Monitoring of the control system for optimization purposes
● Logging the room temperature in association with the set temperature
● Logging of temperature and humidity trends for the pharmaceutical industry
Offline/Online trend
There are two types of trend data:
● Offline trend:
The recorded trend data are saved in the automation station and uploaded to Desigo CC periodically or as
needed. The data can be analyzed in Desigo CC.
A connection is needed only during the data upload. Trend objects are needed in the automation station.
Offline trend is mostly used for long term data logging.
● Online trend:
Arbitrary data points can be saved as online trends.
A permanent connection is needed. No trend objects are needed in the automation station.
Online trend is mostly used for temporary data logging.
Trend Log Objects
The trend data is saved in the buffer of the Trend Log and Trend Log Multiple objects in the automation station.
The Trend Log object can only record one value of a data point. The Trend Log Multiple object can record up to
six different values of a data point.
The Trend Log object cannot be set up online, but must be set up in advance, offline in the application. A
Technical Designation (TD) determines (BACnet reference) which object is to be logged. This presupposes that
the referenced object is visible via BACnet (not No Element). The reference and the parameters can be defined
and modified online or offline.
When the number of trend log entries reaches a definable threshold (Notification Threshold [NotifThd]), the
Trend Log object generates an event. The Trend Log object sends out an alarm which is defined in a notification
class specified for Trend Log.
The trend log data acquired can only be read, and if necessary, archived, with a BACnet Client configured for
this purpose, e.g., Desigo CC. The status of a Trend Log object is not affected by reading out trend log data. It
is not possible to reload sampled data into Xworks Plus (XWP).
A BACnet client cannot reserve a Trend Log object. Every BACnet client can access the Trend Log object. In
the case of access or modifications undertaken by several clients, the rule is that the most recent one always
takes priority.
Single Run
The trend data is saved until the available memory area is full. You can define the buffer size [BufSize] within
the range 2 to 5,000 entries. You can define the Single Run function with the parameter Stop when full.
Logging Type
The parameter Logging Type [LogTyp] defines the logging type. The values are:
● POLLED: Periodic Sampling
● COV: COV Sampling
● TRIGGERED: Triggered Sampling
By setting the parameters accordingly, you can define combinations of Continuous Run / Single Run and
Periodic Sampling / COV Sampling / Triggered Sampling.
Periodic Sampling
In Periodic Sampling data is acquired by sampling and storing values in a regular cycle. Periodic Sampling is
supported by the trend log object and the trend log multiple object.
COV Sampling
In COV Sampling data is stored based on a change of value (COV) of the referenced parameter. A COV
subscription can be applied to all supported data types (analog, Boolean and multistate). The amount of change
required to initiate a COV is set as a parameter in the object to be referenced. COV Sampling is supported only
by the Trendlog object.
Triggered Sampling
In Triggered Sampling an application (e.g., via data flow interconnection) determines when values are
acquired/logged and saved. Triggered Sampling is supported by the Trendlog object and the Trendlog Multiple
object.
12 Reports
You can create reports in Desigo CC about the functioning of the building automation and control system.
You can configure:
● The elements in the report (such as tables, plots, logos, form controls, text and so on), and their layout.
● Filters (such as name, condition, time, and/or row) to populate the elements of the report with information,
e.g., if you want a report on a room's activity data over the past month, you could define a name filter and a
time filter in an activities table.
● The formatting of the report elements and the page layout.
● The output type (PDF or XLS) and the output destination (file, email, or printer).
You can save your report definition for later use, run it, or schedule the report to be run at a specified time.
You can use reports as a reference or as a troubleshooting mechanism. Reports are helpful during system
operation.
For example, you can:
● View a mixed report containing:
– A table displaying details of all active events for a floor of a building
– A table displaying a history report of events
– A trends plot displaying the temperature variations gathered from temperature sensors
● Export trend data for statistical analysis to:
– An XLS file
– A CSV file (according to the EMC requirement)
● Schedule production of a report using macros and reactions
● Send a report by email, print it or save it as a PDF
You can export and import report definitions and logos.
You can also create and configure reports for operating procedures. These reports are used during assisted
treatment to enter information about how the alarm or event is being handled.
13 Data storage
Large volumes of data are created in the Desigo system during engineering, commissioning and plant
operation. The data is processed, saved, and archived as needed in accordance with type, generation, and
meaning in the various system components.
Setting parameters Values that affect the program elements. Setpoints, default values, limit values,
address settings
Configuration parameters Data in the form of defined constants, or data that Description data, templates, profile,
influences the appearance or operability of the plant. metadata
Process data Physical process variables of the plant during operation. Measured values, state variables,
History or saved process data are plant data. calculated values
Data ownership
Data ownership is based on the practical allocation of data to its owner. The owner, usually an organizational
entity, a person, or a group of people, checks the data and is responsible for its scope and content. Data
ownership shows in which Desigo system product the data is located and which tools are available for its
management. Data ownership is divided in four groups.
The following table shows the four data ownership groups.
Libraries Collection of predefined, specific, and tested Library manager (HQ/RC) Project/Library engineer
program elements.
Libraries can be copied and customized.
Project data All data for the customer project or customer Contractor Plant operator
plant. Project engineer
Plant data Data from the customer plant saved Plant operator Customer
permanently following commissioning.
13.3 Libraries
Libraries are needed during engineering. You can create loadable applications using libraries. Library elements
are compiled from system basic components, e.g., the Desigo CC graphic library contains default graphics for
visualizing plants during engineering.
You can copy and customize or extend libraries. Every engineering level has a library. Libraries can cover many
combinations.
DXR2 automation stations are delivered with preloaded applications and only need to be configured.
There are three library types:
● HQ libraries are tested, well documented and delivered with the system version. Every new Desigo version
contains new libraries.
● RC libraries are tested, well documented and contain country-specific characteristics. They are optional,
independent or an addendum to the HQ library. Not all RCs offer comprehensive libraries.
● Project-specific libraries are not tested and documented.
Application libraries
Application libraries contain plant-specific functions (heating, cooling, control of electrical equipment, etc.) or
templates for subsystem bindings. You can set up and manage libraries with the Xworks Plus (XWP) and
Automation Building Tool (ABT) engineering tools.
PX libraries
The functional units of the PX application libraries are defined by compounds. You can copy, change and
extend the compounds of the PX library.
Application libraries for PX are designed using the same application principles and are provided via Xworks Plus
during project engineering.
PXC3/DXR2 libraries
The functional units of the PXC3/DXR2 application libraries are defined by application functions. You can copy,
change and extend the application functions of the PXC3/DXR2 library.
Parameterization
The library elements have plant-specific or function-specific setting and configuration parameters:
● Setting parameters: The default values are defined by the application and usually do not require adjustment.
● Configuration parameters: The default values can be adapted as needed.
Graphics libraries
Graphics libraries contain graphics that represent the operating elements of the firmware and application
libraries. The graphics are used in Desigo CC to visualize and operate plants. The elements of the graphics
libraries depend on the elements of the application libraries. Any changes to the application libraries must
therefore also be made to the graphics libraries.
The graphics libraries for Desigo PX and PXC3/DXR2 are identical.
Offline generation
Full code generation
Full code generation:
● Checks the overall application consistency (limits, identifiers)
● Converts the application into loadable units
● Generates the appropriate description data for configuration
You must compile the code to get the required performance. You cannot engineer a compiled program.
Delta generation
Delta generation (converts only the modifications):
● Improves performance
● Is faster than full code generation
Online loading
Full download
The full download transfers all loadable units into the automation station.
Delta download
The delta download:
Online readback
During readback of non-volatile process values and parameter settings the data in the automation station is
aligned with the project data in the tool.
Readback comprises two steps:
1. Current parameter settings and non-volatile process values in the PX/PXC3 automation station are read
from the automation station and copied to the data storage.
2. The values are updated in the CFC data storage or PXC3 program and configuration data storage.
The following data can be read back from PX/PXC3 to the project data storage in the XWP/ABT tools:
● Setting parameters changed in the PX/PXC3 automation station
● Changed, non-volatile process values or configuration data
Advantages
Reading back data has the following advantages:
● Outdated data in XWP/ABT is overwritten by current data and thus is available again for reloading programs
in the PX/PXC3 automation station.
● During online changes of background variables (e.g., calendar), data between CFC and XWP/ABT and the
automation station is retained.
● Current setting parameters and non-volatile process values (e.g., operating hours) are saved.
● The newest configuration is saved offline and can be used for, e.g., reports.
Runtime data cannot be read back. Only offline data can be read back. Only objects (not individual properties)
can be read back. If a property is changed, the entire object (e.g., data point), that is, the last change on the
object is read back. The last change per object is always valid.
Workflows for changes
There are two workflows for changes:
Workflow 1 (ideal workflow):
1. Perform readback before the changes
2. Perform changes offline
3. Download
Workflow 2:
1. Perform changes offline
2. Perform readback
3. Compile
4. Download
Offline import
You can import configuration and description data for the plant into Desigo CC. This is the same as the data
downloaded to the automation station.
13.7 Texts
If you work with HQ or RC libraries, the texts are from a text database. These texts can be automatically
translated, because they have a unique ID. Project-specific texts that are not from the text database cannot be
automatically translated.
14 Network architecture
The Desigo system is divided into three network levels:
● Management Level Network (MLN)
● Automation Level Network (ALN)
● Field Level Network (FLN)
BACnet Internetwork
Field Level
IP Segment 8
IP segment 9
Network
PXC3/DXR2 #1 PXC3/DXR2 #2
RXB #1 RXB #2
This classification is based on the functions performed at a given level, rather than on the communications
protocol or medium. The MLN and ALN use the BACnet protocol. The transport protocol (Data Link Layer) is
LonTalk or IP. The FLN uses LonWorks, KNX and MS/TP technology.
Key
Internetwork
In BACnet, the BACnet internetwork is defined as the largest BACnet unit. It consists of one or more BACnet
networks. Only one active connection can exist between any two BACnet devices in a BACnet internetwork.
All bus subscribers from the ALN and MLN, including BACnet third-party devices, are part of the BACnet
internetwork. The devices in the FLN are part of the Desigo system but not part of the BACnet internetwork,
because they do not communicate via BACnet.
Network
Desigo devices use LonTalk (BACnet/LonTalk), IP (BACnet/IP) or MS/TP (BACnet MS/TP) as their transport
protocol. If different transport protocols are used, different physical networks are created, which must be
connected to the PXG3 router. BACnet routers connect networks on the BACnet network layer and transmit
messages via the network number.
If the transport protocol changes, the BACnet network also changes, e.g., BACnet devices that use LonTalk as
their transport protocol are always located in a different network than devices that use IP as their transport
protocol. This also applies to PTP connections.
Desigo devices use LonTalk (BACnet/LonTalk) or IP (BACnet/IP) as their transport protocol and MS/TP
(BACnet MS/TP) to integrate third-party devices. If different transport protocols are used, different BACnet
networks are automatically created, which must be connected to the PXG3 BACnet router. Multiple BACnet
internetworks can be created on an IP segment by using different UDP port numbers.
Desigo establishes PTP connections only between operator units and a network. Operator units duplicate a
virtual network since PTP connections demand a network at both ends.
Desigo CC does not use PTP.
Segment
Large networks are structured, that is, divided into several (logical) network segments for reasons of security,
performance, size and (limited) address range of network devices. The segments must then be connected to
routers of the corresponding transport protocol (e.g., LonWorks router, IP router).
In most cases it is not necessary to divide a BACnet/LonTalk network into several LonWorks segments (ALN).
However, if it does prove necessary, it is not possible to use a LonWorks router, because this limits the length of
the data packets. An L-switch (Loytec) can be used as a router on the ALN.
BACnet MS/TP networks cannot be segmented, because there are no associated routers.
With BACnet/IP some IP segments may be connected by IP routers. Since the IP router prevents broadcasting,
the connection must be activated with the BACnet Broadcast Management Device (BBMD).
Physical segment
Physically, (cable) networks cannot be expanded as desired. Depending on electrical transmission properties
and the data link layer based on it, repeaters must be added at specific cable lengths to amplify the signal. This
divides the network into multiple, physical segments. A repeater does not impact the transmission protocol; it
merely electrically connects two physical networks.
Dividing up the network into several physical segments may be necessary in LonWorks technology.
The physical segments are connected with physical or logical repeaters. Due to the limited buffer size of logical
repeaters, only physical repeaters may be used on the ALN. Only one physical repeater may be located
between any two nodes.
MS/TP is transmitted on a two-wire cable as per EIA-485/RS-485*. The length of the physical segment can be
max. 1,200 m and can be extended with EIA-485 repeaters.
*TIA standard (Telecommunications Industry Association): TIA-485-A Electrical Characteristics of Generators
and Receivers for Use in Balanced Digital Multipoint Systems (ANSI/TIA/EIA-485-A-98) (R2003)
Desigo site
A site is an independent and self-contained logical entity within the building automation and control system. This
type of structuring is not defined by BACnet, and is therefore largely independent of the BACnet network
topology. The BACnet devices bound to a site can therefore be placed anywhere within a BACnet internetwork.
A site cannot extend across a PTP connection. Communication occurs only within the site, but data can be
exchanged with any device on the BACnet internetwork.
Only automation stations (PXC/PXC3) and LonWorks system controllers (PXC...D+PXX-L11/12)) are assigned
to the sites, by special structuring of the Device ID and Device Name. These products are considered third-party
devices for the purposes of a site.
VMAC
BVLL BZLL
BVLLv6
ISO8802-2 Type 1 LonTalk
MS/TP PTP
Data Link Layer UDP/IP UDP/IPv6 (IEEE802.2) (EIA 709.1)
ZigBee
ISO8802-2 Type 1
(IEEE802.2)
Ethernet Ethernet
Physical Layer IEEE TP/FT 10
ISO8802-3 ISO8802-3 ARCNET EIA-485 EIA-232
802.15.4 (EIA-709.1)
(IEEE802.3) (IEEE802.3)
Application layer
The BACnet application layer defines services, objects and their characteristics. From the network viewpoint,
the Device object is important. The object ID and the object name must be unique within the BACnet
internetwork.
Application Layer
Network Layer
Device ID
The Device ID is the object ID of the BACnet device object.
The device ID is divided into the following categories:
Device name
The device name is the object name of the BACnet device object.
Guidelines
Different rules for object names apply for configuring TD (Technical Designation), UD (User Designation), or FD
(Free Designation):
● The TD is generated from predefined partial names, separated by an apostrophe ('), that show the technical
hierarchy with plant, partial plant, and component. The TD is supplemented by site name and pin name.
● The names may consist of upper- and lowercase letters and numbers 0 to 9. The site name is separated by
a colon (:) and the pin name by a period (.). The maximum total length is 30 characters.
● The UD is formed similar to the TD based on partial names. However, users determine the partial names,
structure, and separators. The names consist of upper- and lowercase letters, numbers 0 to 9, and
separators, such as _-;=’, etc. The maximum total length (including site name and pin name) is 80
characters.
● The FD is a freely assigned name consisting of letters, numbers and a few special characters, limited within
the system only by uniqueness and length. The maximum total length is 80 characters, ten of which, plus
one separator, are reserved for the site name.
Class B1 Meaningful text for the user (this text is used as a reference
for the alarm recipient)
Class B2 Model name + device ID Model name + “ “ + 8 character device ID (hexadecimal). The
device name for temporary devices is generated
automatically.
Class C Site name + automation station name Site name + “:“ + automation station name
B2 – 15 0x02100401 – – PXM20TMP0210040f
Designation Description
Max APDU Length Accepted Maximum length of application message (Application Protocol Data Unit) supported for this
device. The length depends on the transport medium used, and the capacity of the device
buffer. The length of the APDU must always be less than the length of the smallest NPDU
(Network Protocol Data Unit) between the different bus subscribers.
Beispiel There are two IP networks linked by a PTP connection. The two IP bus subscribers could have
a maximum APDU length of 1476 octets. However, since the maximum NPDU length of the
PTP connection is 500 octets, the maximum APDU length of both devices must be set to 480
octets.
Range: 1000...5000 ms
APDU Timeout Timeout for an acknowledged message. This value must be identical throughout the
internetwork.
Range: 1000...5000 ms
Designation Description
Number of APDU Retries Number of retries in the event of an APDU or APDU segment timeout. This value must be
identical throughout the internetwork.
Range: 1...5
Default value: 3
Window size
To transfer large data packs, BACnet uses the windowing algorithm. Windowing means that instead of
acknowledging individual segments separately, the acknowledgement applies to a specific number of segments,
referred to as a window.
Definitions for Desigo
The window size is permanently set to four for all Desigo devices, so that for segmented messages, only every
fourth segment is acknowledged.
Network layer
The most important information in the network layer is the network number of the BACnet network.
Application Layer
Network Layer
Network number
The network number is the unique identification of the BACnet network. There are stationary and temporary
networks:
● Stationary networks are defined during commissioning and then remain unchanged.
● Temporary networks are created when a tool (e.g., XWP/ABT) dials into a network via PTP.
Range/Value Description
0 Reserved for applications with only one BACnet network in a BACnet internetwork, that is, where there are
no BACnet routers.
1...65280 Network number for stationary BACnet networks. You can select any network number in this range.
We recommend that you form categories, e.g.:
65281...65534 Reserved for temporary BACnet networks. Not yet used in Desigo.
Router parameters
The router parameters are written to the BACnet router during commissioning. The following information is
required for each port (logical connection to network):
Designation Description
Network Number Network number of the directly connected network.
Max NPDU Length Max. message length supported in this network. This value depends on the transport medium
used.
Default: 228
Default: 501
Designation Description
Default: 1497
Hop counter
Every BACnet that is routed to another BACnet network has a hop counter. The counter reading is reduced by
one with each pass of the BACnet router. When the counter reads 0, the message will not be routed further.
This prevents continuously circulating messages.
Definitions for Desigo
For Desigo the hop counter is initialized with a fixed value of 5. This means that a message can pass through a
maximum of four BACnet routers.
Application Layer
Network Layer
Domain ID: The domain ID is the highest unit in the LonWorks addressing system. Data can only be exchanged
within a domain. A gateway is required for inter-domain communication. The domain ID can be 0, 1, 3 or 6
octets in length. A domain can consist of up to 255 subnets.
Subnet ID: The subnet is a logical collection of up to 127 nodes within a domain. The bus traffic within a subnet
can be kept local by using BACnet routers. Subnets must never be defined across a router.
Node ID: Unique identifier within the subnet. Each node can be addressed uniquely within a domain by the
subnet ID and the node ID.
Group ID: The group address is a type of addressing. The group address is not used in BACnet.
On the ALN, the following rules apply to Desigo:
Subnet ID 1…255 The subnet ID is a consecutive number that starts with one. The subnet ID
is incremented by one when a subnet is full (no free node IDs).
Node ID 1…100 This range is for automation stations (PXC), system controllers (PXC...)
and system devices (BACnet routers).
Application Layer
Network Layer
Below the BVLL, BACnet relies on UDP (User Datagram Protocol). Unlike TCP (Transmission Control Protocol),
UDP supports broadcast messages. The connection monitoring (carried out by TCP) is resolved in the
Application Layer.
All media, such as ethernet, are available if supported by IP as physical layers.
For detailed information on the IPv6 data link layer, see Ethernet, TCP/IP, MS/TP and BACnet basics
(CM110666).
IP addresses
The IP address of stationary and temporary operator units can be set automatically via DHCP (Dynamic Host
Configuration Protocol) provided that there is a DHCP server in the network. The use of DHCP is not
recommended with automation stations and BACnet routers. DHCPv6 is currently not supported for IPv6.
DHCP is not allowed for devices using integrated BBMD functionality.
The IP addresses must be agreed upon with the IT department.
RFC1918 defines three specific address areas for private networks. IP addresses within these ranges are not
routed:
10.0.0.0 - 10.255.255.255 Subnet mask: 255.0.0.0
172.16.0.0 - 172.31.255.255 Subnet mask: 255.240.0.0
192.168.0.0 - 192.168.255.255 Subnet mask: 255.255.0.0
For IPv6, IP addresses and private address ranges are defined differently. See Ethernet, TCP/IP, MS/TP and
BACnet basics (CM110666).
IP address: Host address of the network subscriber.
Subnet mask: Subnet mask of the IP segment in which the device is located. This value must be aligned with
the other IP devices.
The subnet mask is required for the identification of broadcast messages and for communication across IP
segments. The subnet mask and target IP address enable the transmitting IP device to decide whether the data
packet can be delivered directly to the target device or if it must be forwarded via the default gateway.
For IPv6, the subnet mask corresponds to the network prefix. See Ethernet, TCP/IP, MS/TP and BACnet basics
(CM110666).
Default gateway: IP address of the IP router. This value is relevant for communication across IP segments.
UDP port number
For BACnet/IP to use UDP, a UDP port number must be defined. Only devices with the same UDP port number
can communicate with each other.
Port numbers are divided into the following classes by the IANA (Internet Assigned Numbers Authority):
● Well Known Port Numbers: Fixed port numbers assigned by IANA (0… 1023)
● Registered Port Numbers: Numbers registered with IANA (1024…48151)
● Dynamic and/or Private Ports Dynamically assigned or privately used port numbers (49152…65535)
For BACnet, port number 47808 (0xBAC0) is registered with IANA.
If there are several BACnet internetworks on an IP network, they can be separated by different port numbers.
Using several internetworks can be helpful in very large projects, for migration, and to encapsulate sections of a
plant with different reliability criteria. Since Desigo CC communicates simultaneously with multiple
internetworks, the operation is not restricted.
However, only one port number is registered for BACnet with the IANA. If additional UDP port numbers are
required, we recommend the use of port numbers 47809 to 47823 (0xBAC1...0xBACF). This does not comply
with IANA regulations. This range is reserved for future applications and should not be used. There is only a
very small chance that these ports might be used elsewhere. To avoid clashes, do not use any port numbers
from the range of dynamic or private ports. See www.iana.org/assignments/port-numbers.
BACnet Broadcast Management Device (BBMD)
The BBMD is required as soon as IP routers are used in a BACnet network. IP routers limit broadcast messages
to the local IP segment, that is, they do not allow any broadcast messages to pass through. In order to distribute
BACnet broadcast messages across IP segments irrespective of this limitation, a BBMD is required in the
relevant IP segments. If a BBMD receives a broadcast message, e.g., within the local IP segment, it transmits
this as a unicast message to all other BBMDs. The BBMDs then transmit the received message to their own
local IP segments. BACnet refers to this as two-hop distribution:
1. Hop: BBMD sends a unicast message to all other BBMDs.
2. Hop: They then distribute the message to all BACnet devices in the local IP segment.
One-hop distribution can be implemented with Direct Broadcasts. In this case the BBMD sends a direct
broadcast to all remote IP segments. This broadcast is received by all IP bus subscribers in the relevant
segment. Not all IP routers support Direct Broadcasts.
IPv6 (BVLLv6) only supports two-hop BBMD. Broadcasts are implemented via IPv6 mutlicasts. See Ethernet,
TCP/IP, MS/TP and BACnet basics (CM110666).
BBMDs ensure that broadcast messages are distributed in a BACnet network. They are grouped by BACnet
network. A maximum of one BBMD is allowed in any one IP segment.
BACnet network #100 is separated by IP routers. The Internet also contains IP routers. This is why different
segments are shown before and after the Internet cloud. BBMDs are required so that BACnet broadcast
messages are available in all IP segments.
BBMD parameters
The BBMD parameters are written to the BBMD or (for Desigo) to the BACnet router during commissioning. The
following information is required for each BBMD in the BACnet network:
Designation Description
IP address IP address of the BBMD.
Broadcast mask If the BBMD is to be addressed via direct broadcast (one-hop distribution) the subnet mask of the
BBMD must be specified. Since not all IP routers support this mechanism, direct broadcasts are
not supported by default. Two-hop-distribution is always possible. The broadcast mask is then
255.255.255.255.
Not required for IPv6.
Foreign device
A foreign device is a (remote) BACnet device in a remote IP segment. It registers with a BBMD in order to send
or receive broadcast messages. Registration with a BBMD involves making an entry in its Foreign Device Table
(FDT). The registration must be renewed at regular intervals.
The foreign device does not send broadcast messages, but passes them as unicast messages to the BBMD for
distribution. The BBMD in turn passes incoming broadcast messages as unicast messages to the foreign
devices in its FDT.
In the Desigo system, Desigo CC, XWP/ABT, and PXM30/40/50-E can be operated as foreign devices. IPv6
does not support foreign devices
Examples from the Desigo topology
● IP Segment 1: Desigo CC 1 does not have to be configured as a foreign device, because this IP segment
contains a BBMD.
● IP Segment 2: Desigo CC 3 does not have to be configured as foreign device, because this IP segment
contains a BBMD.
● IP Segment 3: This segment only contains Desigo CC 2. To enable Desigo CC 2 to receive and send
broadcast messages, it must register with a BBMD as a foreign device. It does not matter with which BBMD
it registers.
Foreign device parameters
If a BACnet device operates as a foreign device, the IP address and UDP port number of the BBMD must be
specified.
Designation Description
IP Address of BBMD IP address of the BBMD with which the foreign device registers.
UDP Port of BBMD UDP port number of the BBMD with which the foreign device is registered. The default is 0xBAC0.
The recording interval (Time-To-Live) for Desigo products is set at 300 seconds (= 5 minutes).
Application Layer
Network Layer
PTP connections are only possible between Desigo CC, XWP/ABT und PX. PTP connections between PXs are
not permitted.
PX devices which can be reached via PTP always belong to a separate site. With reference to the topology at
the beginning of the chapter, the site named Baar must not be combined with the sites named Zug or Cham.
Several PXs per site can be used as half routers. When establishing a communication, the best-performing
connection is always selected. Redundancy is not allowed, that is, several simultaneously active connections in
a given BACnet network are not allowed.
With Desigo CC, a separate, independent, internal BACnet internetwork is created for each Data Link Layer
type. Routing between LonTalk, IP or PTP is therefore not possible.
The following parameters are required for each half router:
Designation Description
Local network number The BACnet network number to which the half router belongs.
With PX, the local network number is the same as the device's own network number.
Desigo CC supports all three different Data Link Layers (IP, LonTalk and PTP). They are handled
internally as independent BACnet internetworks. This means that routing between the different
Data Link Layers is not possible. Therefore, the local network number can be allocated to IP
and/or LonTalk independently of the networks. However the local network number must be unique
among all networks which could possibly be reached from Desigo CC via a PTP connection.
Recommendation:
If Desigo CC has an additional Data Link Layer (IP and/or LonTalk), the local network number of
this network should be used (example in the beginning of the chapter: For Desigo CC 2, the local
network number of BACnet network #4 should be adopted).
In Desigo CC with only one PTP connection, the local network number must be in the range 1000
to 1099. (Example: Desigo CC 3 -> #1000).
COM parameter For the PX half router, the COM port to which a modem or null modem is connected must be
specified.
Modem parameters The modem parameters contain individual settings for the relevant modem types. Predefined
parameter sets are available for the PX half router.
The following parameters are required for each PTP connection starting from a PX half router:
Designation Description
Remote network number This network number determines the BACnet network in which the remote partner device is
located. In the Desigo system this is the local network number of Desigo CC.
Designation Description
Remote area name The remote area name stands for a peer-to-peer remote network number of the network
containing Desigo CC.
During configuration, the remote area number lets you assign a clear name to the (remote) alarm
recipient rather than a network number.
Telephone number The telephone number for access to the remote device.
Performance index The performance index refers to the quality of the router data connection. If multiple PX half-
routers are available in a PX site, and if a connection to a remote network is to be established, the
router with the best performance index is selected. If no connection is established, the router with
the next best performance index automatically tries to connect.
For each PTP connection in Desigo CC, only the telephone number needs to be defined.
Network Layer
10664Z42_06
MS/TP ...
Router
PXG3
DXR2 DXR2 DXR2 DXR2
Due to relatively difficult, electrical conditions imposed by EIA-485 wiring and limited data transmission capacity,
we recommend using BACnet MS/TP only for devices with low data volumes that are geographically far apart.
For devices with larger data volumes and shorter distances to the Desigo automation station, integration in
Desigo primarily should be carried out via TX Open or PX Open.
System devices
PXG3 is a BACnet router that routes BACnet telegrams between BACnet networks and different data link
layers. It is available in two versions:
● PXG3.L: (triangle router) Simultaneous routing between Ethernet/IP, LonTalk, and MS/TP
● PXG3.M: Routing between Ethernet/IP and MS/TP
See BACnet router for BACnet/Ethernet/IP, BACnet/LonTalk, BACnet MS/TP PXG3.L, PXG3.M (CM1N9270).
An individual BACnet IPv6 data link can be used as an option for the router. As a result, the PXG3.M is turned
into a triangle router and the PXG3.L to a square router. The router can be configured either via XWP or the
integrated web server.
BACnet address
Every BACnet device in the BACnet internetwork can be accessed via its BACnet address.
The BACnet address is defined by the BACnet standard and comprises the following elements:
Designation Description
Network number Network number of the BACnet network in which the device is located. The network number is
only parameterized on devices with BACnet router functionality (including half router) and is
implicitly valid for all BACnet devices in the BACnet network.
BACnet MAC address Address specific to the transport protocol. This address is written to the device in the
commissioning phase.
BACnet MAC address for:
Designation Description
Device ID Object identifier of the BACnet device object. The device ID is unique within the BACnet
internetwork.
Device name The object name of the BACnet device object. The device name is unique within the BACnet
internetwork.
For information about the direct addressing of BACnet references to objects in other networks and media, see
Desigo Ethernet, TCP/IP, MS/TP and BACnet (CM110666).
Structure
The following figure shows the structure of a Lon network in the FLN
Key
System devices
Gateway
The gateway links trunks. It operates on the application layer of the ISO/OSI layer model. The following
LonWorks gateways are available:
The RXZ03.1 point coupler provides a fixed number and type of LonTalk network variables (NV). Each side of
the point coupler belongs to a trunk or LonWorks project. The point coupler can be used to implement time-
critical connections between two trunks. The point coupler integrates third-party devices that have been
engineered with a different tool.
Loytec L-Proxy and Sysmic XFM-LL are freely programmable point couplers. The XFM-LL device may be used,
when depicted like a standard third-party device (configuration via its own tool).
The PXX-L.. extension modules let you connect LonWorks devices to the PXC..D modular series.
Router
The LonWorks router operates on the network layer of the LonWorks protocol. It filters data packets based on
their subnet ID or group ID. Subnets or groups must never be defined across a router, that is, the subnet IDs
and group IDs at each end of the router must never be the same. Routers are used where there is heavy local
network traffic. They allow the unloading of unaffected devices from the network traffic. In Desigo there are no
large LonWorks networks, as the FLN is divided into trunks. Routers are only required in exception cases.
L-Switch (Loytec)
The L-Switch filters the package on the basis of the subnet/node ID or group ID. It automatically learns the
topology and forwards the data packets accordingly. The L-switch does not have to be configured. Unlike the
router, there is no need to take account of any addressing limits (allocation of Subnet ID or Group ID).
Physical repeater
LonWorks has physical and logical repeaters. The physical LonWorks repeater does not filter the data packets.
It regenerates the electrical signal. One physical LonWorks repeater can be used in the path between any two
devices within a segment.
In logical repeaters, the data packet is processed by the neuron chip. This enables several logical repeaters to
be connected in series. The disadvantage is that the logical repeater must be configured, and that owing to the
limited size of the buffer, it cannot be used for large data packets, that is, for BACnet/LonTalk.
Structure
The following figure shows the structure of the KNX network:
● KNX: KNX devices, e.g., third-party KNX
● PX KNX: Automation station PXC001.D or PXC001-E.D and PX KNX firmware
Backbone line
Area 1 Area 3
EIB EIB
PX KNX
(3.1.y)
EIB EIB
EIB EIB
Line 1 Line 2
Line
A KNX network consists of lines. Up to 64 devices can be connected to each line.
Area
Up to 15 lines can be connected to a main line via line couplers (LC). This is called an area.
Backbone line
The topology can be expanded by means of a backbone line. Up to 15 areas can be connected to the backbone
line via backbone couplers (BC). Technically, these are the same devices as line couplers.
Line/Backbone couplers
Couplers separate the areas and lines. Couplers keep the bus traffic within bounds. Datagrams that are only
needed on one line should not create a load on the entire network and hence have to be confined to that line.
Respective filter tables are created (ETS) when setting up the project/network.
Engineering Tool Software (ETS)
The KNX Engineering Tool Software (ETS) is used to create KNX projects. A bus interface is required to
commission the devices with ETS.
For a detailed description of the KNX topology, see
http://www.knx.org/fileadmin/template/documents/downloads_support_menu/KNX_tutor_seminar_page/basic_d
ocumentation/Topology_E1212c.pdf.
System Devices
PX KNX
The PX KNX system controller maps KNX devices to BACnet objects. PX KNX also supports different system
functions, such as grouping, scheduling, alarming, trending, etc.
The system controller must be positioned correctly in relation to the topology and the load on the bus caused by
the devices and connections (group addresses).
Bus power supply
Each line and each area must include a bus power supply.
Structure
The following figure shows an example of a logical network topology with KNX PL-Link devices, a room
automation station and several rooms.
BAC network
Automation
station
Automation station
PSU
System devices
Third-party KNX devices can be integrated in KNX PL-Link networks via KNX S-mode. The KNX Engineering
Tool Software (ETS) is necessary to engineer and commission these devices.
DXR2.M.. automation stations cannot integrate KNX S-Mode devices.
Structure
A DALI system can be made up of control gear, control devices and bus power supplies.
Control gear
Control gear usually contains the power control circuit to drive lamps, or some other type of output, such as
on/off switching or 1 to 10 V analog signals.
Control devices
Control devices can provide information to other control devices, such as light intensity information, and can
send commands to control gear. Input devices are a type or a part of a control device that provides some
information to the system, such as a button press or movement detection. DALI application controllers are also
control devices, e.g., they can send commands to control gear to modify the lighting.
Bus power supplies
At least one bus power supply must be present in a DALI system. This is necessary to allow both
communications on the bus, and to power any bus-powered devices. The bus power supply does not need to be
a separate unit – it could be part of another device such as a LED driver or a sensor.
Bus wires
A DALI system also includes the bus wires that are used to connect the DALI terminals of the various devices in
the system.
Addressing
DALI allows the flexible addressing of devices.
At the simplest level, all devices are addressed simultaneously by broadcast commands. This allows the control
of lighting in a similar manner to 1 to 10 V analog control, without requiring any configuration of the individual
devices. If a level (Direct Arc Power Command) is broadcast, then all control gear will act upon that command,
changing their output to the same new level.
With simple configuration, DALI devices can be given one of 64 short-addresses. This allows individual control,
configuration and querying of any single device in the system.
DALI devices can also be group addressed, e.g., a DALI LED driver could be programmed to be in any
combination of the 16 available groups. When a command is sent to a group, only devices that are in that group
are addressed.
System devices
PXC3...A
The PXC3…A automation stations have a DALI bus for connecting up to 64 DALI ballasts/drivers.
PXC3.E16A
The PXC3.E16A room automation station is optimized for lighting applications. It has an onboard DALI interface
for connecting up to 64 electronic ballasts or LED drivers
15 Remote access
The remote access is an access to resources via the internet or a point-to-point connection.
The remote access is used to:
● Connect a remote location to Desigo CC, e.g., for on-call service, managing different locations or support by
a specialist
● Remotely access Desigo CC
● Make a change, create an extension or search for errors using an engineering tool
● Forward alarms as text messages or emails from Desigo Control Point or Desigo CC
10664Z45en_02
Metro ethernet
Modem
TV cabel
Mobile phone
BACnet/IP
Web interface
Automation station
The following access networks can be used for the remote access:
● Telephone network
● TV cable network
● Other cable-based networks, such as metro ethernet
● Mobile networks
● Other RF-based access networks
TV cable-based access
● This access is similar to DSL. You can access the system remotely via a cable modem provided by the
cable network operator.
I want to use the remote access for... DSL LTE & GPRS TV cable Metro RF-based
UMTS ethernet
Remote access to Desigo CC o/+ o/+ - + + o/+
Alarm forwarding + + + + + +
Key
+ Good
The different access technologies are available with different bandwidth, e.g., DSL (o/+) can be fast or relatively
slow.
Costs
The costs are divided into monthly basic costs and usage costs. To optimize costs, analyze your usage profile,
that is, how many times per month do you use it and how much data do you exchange per use.
A data flat rate ensures that the costs are capped. Choosing an inappropriate rate plan for a mobile subscription
could result in high costs.
Availability
RF-based links and all mobile network-based transmission standards can suffer from transmission problems
due to bad weather especially at the cell border. The bandwidth that can effectively be used in the project can
vary over the day, because the bandwidth is shared by all users. The bandwidth variations for cable-based
technologies are lower.
Recommendations
To ensure a reliable remote access, use cable-based technologies even if the cost is slightly higher. Use mobile
networks or RF-based systems only if no alternative is available. If you require a high availability remote access,
you can additionally establish a mobile network-based link as a fallback solution. To do this, use a router that
offers both a DSL and a GPRS/UMTS/LTE modem.
Every remote access can be attacked. Note the safety measures in the document IT Security in Desigo
Installations (CM110663).
Access to the PXC..D/-U automation stations via Xworks Plus (XWP) can be protected with a password
(password property for remote access [RemAcpwd]). You can enter the password in the Device Property dialog
in XWP.
Migrating from an analog modem-based method
Analog modems should not be used in new installations and are not future-proof due to the migration of the
networks to Voice over Internet Protocol (VoIP).
ISDN also is not a future-proof technology and should therefore not be used.
If DSL is available, use DSL. Otherwise, use other cable-based internet access networks. If you cannot use
such a network, use a mobile network or an RF-based access.
If a project is based on LON, use the PXG3.L router, to connect the remote access on the IP side of the router.
TV cable-based method
The operator provides the modem. Sometimes, you have to configure the modem. Usually, the cable operator
provides a preconfigured modem or the modem configures itself automatically when you connect it for the first
time. The modem has an RJ45 connector to connect it to the IP network (the router) or a built-in router. The
router must be configured. Sometimes you need to enter an access code received from the operator.
A separate DSL splitter for splitting TV and data signals is not necessary.
Metro Ethernet
Metro ethernet is usually not implemented in a BACS project and is therefore not described in this document.
The antenna cable between the modem and the antenna must be short, otherwise the signal is too weak.
Observe the manufacturer's information on the cable type and maximum length. Antenna cables may not be
bent or pinched too severely. The mobile modem must be placed near the optimum antenna location. The
length of the cable to the IP network is not that critical.
The mobile network operator provides the SIM card. SIM cards come in various sizes, depending on the
modem. Choose the correct SIM card.
The modem is connected to the IP network. The safety measures depend on the modem.
GPRS modems with an RS-232 connection can be connected to some PX controllers using a USB-RS-232
converter.
16 Management platform
A building automation and control system encompasses all control functions of one or more buildings.
In addition to typical HVAC systems, there is a need to integrate other areas of the building, such as lighting and
blind control systems, fire alarm systems and access systems.
At completion the system comprises one or more superordinate management platforms that let you centrally
operate and monitor the individual plants, while each plant's technical building equipment still continues to work
autonomously.
Functions
Desigo CC has the following functions:
● Central operation of HVAC processes and related areas of a building
● Visualization, storing and interpretation of data from underlying levels
● Control of superordinate functions (time catalogs, external process reactions)
● Interface for external communication (alarm messages, etc.)
● Data exchange between DDC controllers (automation level)
Requirements
Modern building automation and control systems need to fulfill the following requirements:
● User friendliness
● Integration capability
● Expandability
● Remote operability
● Cost effectiveness
Advantages
Under the brand name Desigo™, Siemens offers a system family of complementary automation modules and
management platforms for buildings and infrastructures of all types and sizes.
Desigo CC has the following advantages:
● A uniform interface for all connected areas from heating, ventilation and air-conditioning through fire alarm
systems, video solutions and intrusion alarms to access control systems.
● Cost-effective solutions in every expansion phase through the broad scalability of the number of data points,
functions, and broad integration of subsystems.
● A state-of-the-art graphical user interface.
● PC- or server-based management platform based on the current Microsoft operating system.
For more information on the Desigo CC management platform, see Desigo CC System Description
(A6V10415500).
Architecture
The Desigo CC management platform presents a single point of entry for users to operate, monitor and optimize
building automation, fire safety and security systems or a combination thereof.
Desigo CC is a flexible, full client-server architecture allowing scalability from small and medium to large and
complex systems. The platform provides customizable and market-specific distributions.
Desigo CC can be installed on one single computer, with full server and client functionality. Furthermore,
Installed, Web, and Windows App Clients can also be added on separate hardware. Additional system
connections can be made through systems installed with Desigo CC Front End Processors (FEP)
configurations. Web interfaces provide the customer an increased flexibility for operation and future extensions,
e.g. mobile applications for tablets and smart phones.
Main server
The main server contains the project database and the software that monitors and commands the system
network. Clients connect to this server to monitor and control the facility. If the same computer runs Microsoft
IIS, the installation provides web clients with access to the facility. The Desigo CC server installation always
includes an installed client with a user interface for monitoring and controlling the facility. The main server has
interface connections to the field (either directly or using FEP) and provides a centralized database and other
services to the connected clients. The main server can support a number of clients that are connected using a
network (LAN) or Intranet (WAN).
Installed client
The Installed Client is typically used for operators who are focused entirely on monitoring and managing building
systems. In this configuration, software components used for event management are locked in place and cannot
be moved or covered by other applications. This ensures that critical events are never missed or hidden.
Installed Clients can optionally be configured to run in a closed mode where only Desigo CC and other
specifically identified applications are allowed to run. In closed mode, the workstation is dedicated to running
Desigo CC, with access to the Start menu or other operating system and customer applications available only to
administrative users.
Web client (browser client)
The web client is deployed on the intranet with full trust and allows access to local resources. The system runs
in the Internet Explorer browser (using HTTP or HTTPS as communication protocol) and is downloaded on
demand each time the user launches the system as web application. When working in a browser, you can have
the same capabilities as those working on an Installed Client, or can be restricted to have different access when
connected remotely.
As web clients require low latency and high network bandwidth, they are appropriate for intranet use. We do not
recommend it for internet use.
See Desigo CC Installing the Web Client Application Certificate (A6V10415479).
Windows app client (ClickOnce)
The Desigo CC Windows App Client looks like the standard system software, but is a light application that can
be downloaded from the Desigo CC server when connecting through a browser. When the Windows App Client
is downloaded, it runs like any other Windows application on the desktop. It can be launched from the Start
menu, desktop icon, quick-launch toolbar, and so on. This deployment does not require administrative
privileges. The Windows App Client runs in its own pane, without the overhead of the internet browser
application and menus.
Web server
To use the Desigo CC Web and Windows App Clients, you must install the web server. To install the web
server, you must first install Microsoft IIS on the web server computer. Usually the web server is on the Desigo
CC server. It might be located on a separate computer, if the customer's IT department requires the web server
to be installed in a separate controlled environment, or if it is preferred not to use the resources of the system
server for the Microsoft IIS tasks.
The web server lets you to access the system using the intranet and a web browser. You can add only one web
server. It lets you download all files required for the Web Client and Windows App Client environments. It
provides a system web page to access the Web Client, the Windows App Client, and the system documentation
in the Internet Explorer browser. It also represents the endpoint of the communication with the system server.
Front End Processor
A Front End Processor (FEP) is a computer that provides additional connections between building level devices
(such as field panels) and Desigo CC. By providing additional connections to the building level network, an FEP
enables load balancing for the network-based processing for a Desigo CC system.
System Dimensioning Guide
Desigo CC covers a wide variety of solutions so that it is impossible to define simple rules for determining the
size. Therefore, a system dimensioning tool is available that estimates the system size and disk storage space
on the basis of information available at the time of the offer, e.g., the number and type of physical points and the
expected history data base contents.
Scheduling
The Scheduler allows you to schedule events for Desigo CC and field panels at your facility. You can create
daily or weekly schedules for Desigo CC and BACnet devices. You can fully configure and monitor standard
BACnet schedules, calendars, command objects, and workstation-based schedules that can be used to support
systems without built-in scheduling capabilities. Schedules are automatically associated with systems they
control, so you can quickly navigate to the schedules of any selected object. A Timeline Viewer lets you view the
details of multiple Desigo CCs and field panel schedules simultaneously, spanning a range of time.
Reports
The Desigo CC reporting tool includes standard reporting templates and lets you create fully configurable
reports with custom logos, headers, footers, and layouts that include tabular and graphical system information.
You can schedule reports and save them in CSV or PDF formats.
Event management
Event management allows you to manage events throughout the system. You can monitor and manage the
progress of each event from initiation through resolution. The full history of each event issue is recorded, and
you can generate event-related reports that you can view, save, and print.
Log Viewer
The Log Viewer application provides an historic log of all user and system events and activities that have
occurred. You can retrieve these historic events and activities for further analysis and investigation using sorting
and filtering. Log views can be saved and exported if required.
Detailed log
The detailed log allows users to view the most recent records for any selected object. The same content filtering
and sorting functionality available in the Log Viewer is possible in the detailed log.
Remote notification
You can configure Desigo CC to automatically or manually send email or SMS messages to specific recipients.
You can specify:
● What events the recipients should be notified for and when
● How notifications are escalated from one recipient to another until a notification message is responded to
● If a message is periodically sent to the operators stating that the system is running normally
● Which devices are used for the notification
Macros
Macros are predefined lists of commands that enable a user to send out a group of commands to specified
devices with a single action. Some macros can be started manually while others may be part of schedules
defined for time-based functions or automatic reactions. Macros are also used by the system to perform multiple
command actions. These predefined system macros are applied to specific control actions, such as block
commands to fire control panels and system backup functions.
Reaction Processor
Reactions are automations programmed in the system, so that when a specific situation occurs on site, a
command or a series of commands is automatically executed.
You can define actions to be executed automatically when specific conditions are verified. Conditions can be
based on time, on events, on a change of values, or on a combination of some or all. When conditions are met,
the Reaction Processor executes a pre-configured list of commands.
Document management
Desigo CC can handle the different types of document templates used in the project. You can configure
document templates in PDF, RTF, TXT, XLS, and HTML format.
System Browser
The System Browser displays objects in the building control system through various views. You can search and
filter objects, display object names and descriptions, and drag objects into Trends, Schedules, and Reports.
History Database (HDB)
Historical data is stored in an access-controlled MS SQL Server database. The System Management Console
lets you create a project History Database (HDB) and link it to the active Desigo CC project on the main server.
The history database is used to log a wide range of user and system activities, such as:
● User and system activities
● Alarms and their treatment
● Faults that have occurred and are handled as batch messaging
● Values that are logged as trends
Project database
The runtime data (process image) and the engineering data are stored in a file-based database in a
subdirectory of the project directory. The data is unencrypted and database access can only be prevented by
restricting access to the database files. The project directory needs to get shared when deploying installed
clients. It is therefore important to restrict access on the db folder in the project directory to the Windows
account running the Desigo CC main server.
Microsoft SQL Server
Desigo CC uses the Microsoft SQL database software. Microsoft SQL Express is included on the product
installation DVD (Microsoft SQL Server 2008 R2 Service Pack 2, Express Edition, version 10.50.4000.0).
Alternately, you can use an existing Microsoft SQL Server installation (same version 10.50.4000.0). In this case,
the Desigo CC Installer will skip the Microsoft SQL Server installation. In both cases, Microsoft SQL must first
be installed and running on the computer where the Desigo CC main server will be installed.
Microsoft IIS server
A Microsoft Internet Information Services (IIS) server for Web Clients and Windows App Clients can be installed
on the Desigo CC server or on a separate installation (web server).
License Manager
Licensing ensures the operation of the system within the agreed system limits. Only the system is allowed to
change license data.
If a license becomes temporarily unavailable (e.g., due to network connection issues) the system continues to
run fully operational for a grace period. The system continues to check for the license and shuts down at the
end of the grace period, if none of the license checks succeed.
Exceeding the limits of the license (e.g., by integrating more field system data points than stated in the license)
puts the system into courtesy mode. Phases of courtesy mode accumulate until a total duration of 30 days is
exceeded, then the server shuts down. Unless new licenses are made available, after a manual restart the
system again goes into courtesy-mode exceeding and shut down.
Any unauthorized attempt to modify system license data directly in the database (e.g., changing the remaining
time of a specific license mode) shuts down the system.
Scopes
Scope is the general term for specific object access in Desigo CC. A scope segments and implements certain
rules for the user role in the project. A user only sees the area of the building assigned to him, e.g., pumps,
receives only alarms from this area in the event of an emergency and can only acknowledge those alarms. If an
emergency occurs in an area that is not in the scope of this user, e.g., ventilators, the user does not receive an
alarm about this event.
Communication security
In general, communication channels are non-encrypted due to performance reasons. Exceptions are
communication channels for file transfer using web and video transfer. Sensitive data (passwords during
authentication or user management configuration) is transferred as encrypted message content.
Wireless input devices (especially keyboards) use radio transmission that is often not or inadequately
cryptographically protected. Even from greater distances, it is possible to listen in or even plant external data in
the system.
We recommend that you do not use wireless input devices. If you must use wireless input devices, use only
devices with proven encryption.
Communication ports and protocols
Which ports are used depends on the actual deployment and subsystem integration of the whole system.
See Desigo CC System Description (A6V10415500).
Event Bar
When using profiles for critical event management, you can collapse the Event List into a condensed list of
event buttons in an area called the Event Bar, that remains docked on the desktop for easy access. This lets
you keep an eye on the current situation at all times.
Client profiles
To ensure the correct level of event management support for users in any situation, a workstation and/or users
can be easily assigned predefined profiles supporting casual, intermediate, or dedicated event notification and
management.
Fast treatment
From the Event List or Event Bar, you can quickly select an event and perform all the commands (e.g.,
Acknowledge, Reset, Close or Suspend) from the Event Detail Bar and Event List, without looking at treatment
steps, viewing live video or a map of the alarmed area, etc. The event descriptor (visible when the Event List is
expanded) contains a short description of the next action (which command to select).
When event treatment is in progress, you can send the available commands to the source object causing the
event or suspend treatment.
Investigative treatment
From the Event List or Event Bar, operators can quickly open the System Manager with focus on the source of
the event, and all information (live video, recent history, schedules, etc.) related to the event source.
Operating procedures
Operating procedures consist of a sequence of steps or actions, which the operator must, or is suggested to
perform with the assisted treatment. For each step of a procedure, the system provides instructions and
operating tools. With appropriate permissions, you can create, view, edit, or delete operating procedures.
Assisted treatment
From the Event List or Event Bar, operators can quickly open the assisted treatment to guide the operator
through pre-configured operating procedures. Each operating procedure is composed of steps - some of which
may be mandatory - for the user to complete (e.g., to see the graphic of the object in alarm, fill-in a treatment
form, or automatically print the information of the event).
Subsystem integration
Representative data points in Desigo CC can be created manually, imported through data exchange files, or
uploaded through a selective auto-discovery mechanism depending on the type of system being connected. A
unique, extensible object modeling approach allows Desigo CC to normalize information brought in through any
interface, and to provide the same look, feel, and operation through a common set of applications, without
concern for the source of the data.
Desigo CC lets you configure connected subsystems directly and perform typical automation station functions,
such as scheduling and event generation, at the management platform for connected systems that do not
support those functions directly.
Desigo CC supports the following subsystems:
● Desigo building automation system
● Desigo room automation system
● Siclimat-X
● Sinteso Fire Safety System
● Sinteso Fire Safety System
● Intrunet Intrusion System
● Video through Milestone Video Management System
● Mass Notification System (see MNS documentation)
● Third-party Building Automation and Fire Safety systems based on BACnet/IP
● Third-party subsystems through OPC
● Third-party subsystems through Modbus/IP
● Integration through SNMP
● APOGEE Building Automation system
● XNET FireFinder XLS and MXL fire safety systems
● Desigo Fire Safety FS20 UL systems
Auto discovery
Auto discovery lets you discover and import devices, which are already on the network, into Desigo CC. You
can set filters and detect your devices on the network, which then display in the System Browser. You would
typically use this method for existing jobs, where field panels are already installed and online.
OPC server
OLE for Process Control (OPC) is a widely accepted industrial communication standard that enables the
exchange of data between multi-vendor devices and control applications without any proprietary restrictions.
OPC is a client-server technology and Desigo CC can acts as the server providing data to third party clients.
Web services
Using RESTful technology, Desigo CC provides alarm, object and time series data via web based services to
supervision management platforms or other third-party external applications.
Language packs
The Desigo CC software is delivered in English and can be extended with additional languages. The following
software language packs are supported:
● Arabic
● Chinese (simplified)
● Chinese (traditional)
● Czech
● Danish
● Dutch
● English (default)
● Finnish
● French
● German
● Italian
● Korean
● Norwegian
● Polish
● Portuguese
● Russian
● Spanish
● Swedish
● Turkish
You can install 3 languages simultaneously. Every user can define his user interface language.
Project and HDB backup
Backing up Desigo CC requires saving independent parts on different servers or PCs. We recommend that you
save the backups of your project data to a different machine from where they originally reside.
Two parts must be backed up:
● The entire customer project data, including all libraries, configurations, object data (project backup).
● The historic data collected in the history databases (HDB backup).
Backups can be done either manually or by applying a macro in combination with a management platform
scheduler.
See Desigo CC System Management Console (A6V10415497).
See Desigo CC Getting Started (A6V10415475) and Desigo CC User Guide (A6V10415471).
Operable systems
● Desigo primary plants
● Desigo room automation
● BACnet third-party devices and systems
Topology
Touch panels Standard Web Browser
PXM50.E PXM50-1
PXM40.E PXM40-1
PXM30.E PXM30-1
BACnet/IP
Desigo automation station Desigo room automation station PXG3.Wx00-2 Standard BACnet devices
17.1 Functions
User management
● User logon function to protect access.
● Automatic logoff function (can be disabled as an option).
● Online user management: Create, edit, and delete user accounts.
● Data point access based on user rights.
Alarming
● Event list for the generic display of alarms and events, regardless of whether they are included in a user
view.
● Trend and display historical, confirmed alarms and events.
● Forward alarm messages to multiple e-mail or SMS recipients. An SMS gateway on the Internet is used for
alarming via SMS.
● Alarms are forwarded pursuant to a configurable schedule and based on alarm priority.
● The email subject line with alarm message can be configured.
Trend
● Graphic display of multiple trend objects on a trend graph on two Y-axes.
● Trend objects can be read from remote Desigo PX automation stations (offline trend) or created during
runtime on the device, dynamically (online trend).
● Highly flexible configuration and modification to trend view.
● Manual export of trend data via CSV file.
● Automatic transmission of trend data via email or save to an FTP server, pursuant to a schedule.
Schedulers
● Operate BACnet schedulers and calendar programs.
● Supported scheduler program objects: Analog, binary, and multistate.
● Operate local and global calendars on Desigo PX automation stations.
● Create and copy efficient exception programs easily.
Reports
● Filter data points by alarm state, operating state, or object type.
● Manually export reports via CSV file.
● Transmission of reports via email or saving to an FTP server.
Heating curve
● Heating curve as a graphical background image with the most important operating parameters.
● List displays for complete operation of all heating curve parameters.
Plant graphics
● Animate 2D and 2D+ symbol.
● Look & feel follows Desigo CC style.
Energy dashboards
● Standard template to display and compare energy consumption.
● Comprehensive selection of graphic, configurable controls.
Northbound integration
● External access to IT application on BACnet objects of a Desigo system via Haystack tagging or Haystack
REST API.
● Project Haystack is an initiative to simplify handling data from the Internet of Things (IoT) and to optimize it
for building automation and control (http://project-haystack.org/).
● Application examples: Data access to third-party devices with HTML5.0 Browser, customized apps, SAP
systems, etc.
Engineering
● Graphics editor is integrated in ABT Site.
● Flexible and efficient creation of customized user interface: Page layout, navigation, texts, colors, operating
elements (list, buttons, hyperlinks, etc.).
● Efficiently take advantage of existing graphics.
● Simulated preview of graphics in the tool during creation.
● All functions available for editing and creating graphics via a standard web browser, no additional tool
required.
● Graphics library with a large selection of symbols and templates:
– 2D and 2D+ symbols for plant graphics
– Templates for technical primary plants and rooms, meeting and office environments, energy dashboards
– RC-specific localization possible
18 Automation stations
The Desigo PX range is based on freely programmable automation stations. They provide the infrastructure to
accommodate and process system-specific and application-specific functions. The PX range of automation
stations comprises the compact and modular series.
See Desigo PX - Automation system for HVAC and building services - System overview (CM110756).
See Automation stations modular series PXC..D, PXC..-E.D, PXA40-.. (CM1N9222).
See Automation stations compact model PXC..D (CM1N9215).
Control Functions
The D-MAP programming language lets you program and parameterize plants, using function blocks and
compounds. The graphics-based data-flow programming in Xworks Plus (XWP) lets you implement all the
necessary control strategies for optimum operation.
System Functions
The distributed functions, which ensure the overall functioning and inter-operation of all plants, are described in
the following chapters and documents:
● For alarm strategy, see chapter Alarm Management.
● For time scheduling, see chapter Calendars and Schedulers.
● For access rights and user designations, see IT Security in Desigo Installations (CM110663).
● For emergency operation and forced control, see chapter Control Concept.
● For wiring tests with Desigo Point Test Tool, see chapter Desigo Workflow, Tools and Programming.
Cyclical Processing
One PX automation station contains one downloaded D-MAP program. A D-MAP program cannot run on two
automation stations, that is, there are no overlapping programs across automation stations. A downloaded D-
MAP program does not run automatically. It must be started explicitly and is executed in accordance with the
cyclical processing principle, that is, all D-MAP blocks in an automation station are processed in a repeating
cycle.
Cycle time
A minimum and maximum cycle time is defined for each automation station. If the processing of all blocks is:
● Shorter than the minimum cycle time, the next processing cycle is delayed until the minimum cycle time has
elapsed.
● Longer than the maximum cycle time, the next processing cycle starts as soon as possible.
The processing order of the individual blocks:
● Does not depend on their arrangement on the plan (D-MAP program)
● Can be set explicitly when creating the D-MAP program
Process image
The values at the physical inputs and outputs are displayed in the automation station via the process image.
There are two instances of the process image:
● The frozen process image does not change during a processing cycle. D MAP programs only read from or
write to this instance of the process image.
● The active process image is continuously connected to the real plant.
AI AO
Read Write
Frozen values
Process image
buffer
Current values
I/O scan
Values read in cycle 1 are processed in cycle 2. Output values calculated in cycle 1 are transferred to the
peripherals in cycle 2.
The serial number in the row Serial number SN=150120C61487 consists of:
● 15 = Year
● 01 = Month
● 20 = Day
● C = Hardware version
● 61487 = Consecutive number
Error Effect
Memory error, e.g., faulty flash memory Desigo PX stops working.
Failure of backup server recognized by primary server Desigo PX recognizes the fault and transmits the relevant alarm.
Mains OFF
BACnet: Download
required
14: Load
BACnet: Operational
12: Reanimation
COMA 13: Master reset
4: RUN Cmd 15: Delta loading
BACnet: Operational
5: STOP Cmd
Operating states
Mains off
● No power supply
STOP
● I/O scan active
● Ready for wiring test (only possible without D-MAP program loaded) (PXM20, for PTM modules only)
● D-MAP program processing stopped
● Communication with XWP: Master reset, complete loading and delta loading allowed
● BACnet communication with Desigo CC and PXM20: ReadProperty, WriteProperty, Who-Has, COVs,
EventNotification, AcknowledgeAlarm GetEventInformation
● COVs: For values changed by the operator, values cannot be changed by the program
● Alarming: Alarm monitoring inactive, no new alarms or events are generated (the device info object can still
generate alarms and system events). Notification of saved alarms and events is possible if recipient lists are
set up. GetEventInformation and AcknowledgeAlarm possible.
● Primary server in the STOP state: Primary server is not active, that is, no life check, no time synchronization
and no replication of global objects
● Backup server in the STOP state: The backup server is not active, that is, no time synchronization and no
replication of global objects by primary server. The backup server will not accept changes to global objects
by a client.
RUN
● I/O scan active
● Wiring test not allowed
● D-MAP program processing active
● Communication with XWP: Master reset and complete loading not allowed, delta loading allowed
● BACnet communication with Desigo CC and PXM20: ReadProperty, WriteProperty, Who-Has, COVs,
EventNotification, AcknowledgeAlarm GetEventInformation.
● COVs: For values changed by the program and operator
● Alarming: Alarm monitoring active, notification of alarms and events, GetEventInformation and
AcknowledgeAlarm
● Primary server in the RUN state: Primary server is active, that is, life check, time synchronization and
replication of global objects
● Backup server in RUN state: The backup server is active, that is, time synchronization and replication of
global objects by primary server. The backup server does not accept changes of global objects by a client.
COMA
● I/O scan not active
● Communication with XWP not active
● BACnet communication not active
● Wiring test not possible
● D-MAP program processing stopped
Transitions
1 Power failure
Power failure
2 Power restoration STOP
Power restoration. Operating state before power failure was STOP.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold-start variable function blocks: Volatile variables are initialized with initial value. Non-volatile variables
retain their last value.
The STOP state is reached when the I/O scan is finished.
3 Power restoration RUN
Power restoration. Operational status before power failure was RUN.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold-start variable function blocks: Volatile variables are initialized with initial value. Non-volatile variables
retain their last value.
● System event: Power restoration.
D-MAP processing starts when the first I/O scan is finished.
4 RUN Cmd
Explicit command via dialog in XWP or BACnet (DeviceObject, Out of service property [OoServ])
Actions (warm start action):
● Implicit warm start I/O scan: I/O scan continues to run
● Implicit warm-start variables function blocks: All variables retain their last value
● System event: Change to operating state
D-MAP processing starts.
5 STOP Cmd
Explicit command via dialog in XWP or BACnet (DeviceObject, Out of service property [OoServ])
Actions:
● System Event: Change to operating state
● Stop D-MAP processing at the end of current cycle
I/O scan continues.
6 Restart
Restart of the automation station due to software error.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold start function block variables: Volatile variables are initialized with initial value. Non-volatile variables
retain their last value.
The STOP state is reached when the I/O scan is finished.
7 Restart
Restart of the automation station due to software error.
Summary
Every time the automation station restarts (Powerfail, Reset) a cold start is carried out.
The operating state is stored as a non-volatile variable.
The operating state is mapped as follows to the system status [SysSta] property of the device object:
PXM20
XWP
D-MAP Communication
Application
Flash RAM
Input blocks Output blocks Value blocks Value blocks for operation
Analog Input (AI, AI RED) Analog Output (AO, AO RED) Analog Input (AVAL) Analog Input (AVAL_OP)
Binary Input (BI, BI RED) Binary Output (BO, BO RED) Binary (BVAL) Binary (BVAL_OP)
Multistate Input (MI, MI RED) Multistate Output (MO, MO RED) Multistate (MVAL) Multistate (MVAL_OP)
Discipline I/O
Priority mechanism
Basic function
In order to evaluate the various defined setpoints received from the BACnet command system and via the data
flow connections, the AO, BO, MO, AVAL, BVAL and MVAL blocks each incorporate a priority array [PrioArr].
All external sources write their defined setpoint and information bit (enable signal) into this [PrioArr]. The block
then evaluates these entries continuously, in order to determine the valid present value [PrVal].
The [PrioArr] holds up to 16 different entries, each consisting of a setpoint definition and the associated
information bit (enable signal). The input number also indicates the priority of the entry, where 1 is the highest
and 16 the lowest priority. Each priority level has a predefined meaning.
Determining [PrVal]
The block continuously evaluates the valid present value at the output [PrVal]. It selects the value that has the
highest priority of those whose information bit (enable signal) is also set. If none of the information bits is set,
the default value [DefVal] is processed.
Structure of the Priority Array [PrioArr]
Each priority level has a predefined meaning.
In the [PrioArr], two adjacent priority levels each are reserved for life safety, manual operation and plant
operation.
● The higher priority (lower number) of each pair is reserved for local control and monitoring, close to the plant
(priority 1, 4, 7 and 15).
● The lower priority (higher number) of each pair is reserved for higher level control and monitoring (priority 2,
5, 8 and 16).
● Priority level 6 is specifically designed for switch-on and switch-off delays and to maintain minimum ON and
OFF times.
This ensures that, e.g., an on-site EMERGENCY OFF command, initiated at the plant level, takes priority over a
safety function from a higher-level subsystem.
AO BO MVAL
CMD_CTL
3
e.g. anti-icing
ValCrit / EnCrit
protection
Critical value
5
6 Monitoring hours
7 Desigo CC
e.g. local manual Manual operation
switch ValOp / EnOp 8
13
14
Local control Program control
15 ValPgm / EnPgm
PrVal
Priority 6
Priority entry 6 is used to forward the switch commands resulting from [PrioArr] to the [PrVal] output after a
delay. This enables you to implement both switch-on and switch-off delays and minimum ON and OFF times.
For this purpose, the internal block logic imports the Present value [PrVal] into the priority 6 entry. While the
delay times referred to above are running, priority 6 is set to active and so takes priority over priority levels
7…16. Outside these delay times, priority 6 is always inactive.
Locating this function in the [PrioArr] between priorities 1…5 and 7…16 has the following consequences:
● Commands with a priority level of 1…5 are always executed immediately, irrespective of any currently active
delay times.
● Commands with a priority level of 7…16 are always overridden by any currently active delay times.
Unlike all the other entries in [PrioArr], the commands and information bit for priority 6 are generated exclusively
by the BO, MO, BVAL and MVAL blocks. A priority 6 entry cannot be written from an external source.
The switch-on and switch-off delay
As soon as one of the commands with a priority of 7…16 determines the [PrVal] which will therefore cause the
present state of [PrVal] to change, the entry for priority 6 is set up as follows:
If the switch-on delay [DlyOn] or switch-off delay [DlyOff] is greater than 0:
1. Priority 6 adopts the still unchanged present value [PrVal].
2. Priority 6 is set to active.
3. The switch-on or switch-off delay timer starts.
4. After expiry of [TiOnMin] or [TiOffMin], priority 6 is set to inactive.
If the delay times [DlyOn] or [DlyOff] are equal to 0, no action is taken.
If the new value which determines [PrVal] is the same as the current [PrVal], then, here too, no action is taken.
The minimum on/off time
For each change at the output [PrVal] from OFF to Stage n or from Stage n to OFF, the entry for priority 6 is set
up as follows:
If the minimum ON-time [TiOnMin] or OFF-time [TiOffMin] is greater than 0:
4 Critical value (plant protection) Local monitoring of critical plant states, Data flow interconnection via pins:
Reserved for monitoring critical plant e.g.: [ValCrit] und [EnCrit].
states. - Frost protection (protection from excess Normally, [ValCrit] is a constant and
If priority 4 or 5 becomes the determining cooling) [EnCrit] is enabled/disabled.
value for [PrVal], then the value - Interlock of aggregates
concerned is transmitted immediately to - Icing protection
the [PrVal] output. It is not subject to the
5 delay times defined for priority 6. Higher-level monitoring of critical plant BACnet command system.
states: Access via the CMD_CTL block.
- Frost in ventilation system (close
dampers, stop fans, switch pump on and
open valve)
Can be used to ensure that run-on delay times are implemented. The timer periods [TiOnMin], [TiOffMin],
[DlyOn] and [DlyOff] can be configured in
blocks BO, MO, BVAL and MVAL.
14 Program value Superposed control and monitoring of the BACnet command system. Access is via
Reserved for normal plant operation with plant. blocks:
monitoring and control. - CMD_CTL
- PWR_CTL (if control enable signal =
Fixed)
17 Default value [DefVal] The influence of [DefVal] depends on the BACnet command system. Access via:
If none of priorities 1…16 is active, then state of the block concerned: - CFC
the default value [DefVal] is processed Out-of-service [OoServ=False]: - PXM20
instead. [DefVal], like the values of priorities - Web client
7…16, is subject to the delay times of
priority 6.
[OoServ=True]:
[DefVal] is transmitted immediately to the
[PrVal] output.
Prio Use
1 Prio 7…16 Assumption: The effective switch command from priority (7…16) is Off and is set to active.
2 Prio 7…16 The effective switch command from priority (7…16) switches from Off to Stage 2.
Prio 6 Priority 6 adopts the (still unchanged) present value [PrVal=Off] and is set to active.
At the same time, the switch-on delay [DlyOn] starts. Throughout the delay time, priority 6 remains active –
the associated value remains Off.
[PrVal] Since priority 6 overrides the effective switch command from priority (7…16), the [PrVal] output remains
Off.
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
[PrVal] When priority 6 ceases to take effect, the [PrVal] output is once again determined by the effective switch
command from priority (7…16).
[PrVal] remains at Stage 2.
5 Prio 7…16 None of the information bits for priorities (7…16) is active.
The resulting switch command is therefore determined by the default value [DefVal].
[PrVal] Since priority 6 overrides the effective switch command [DefVal], the [PrVal] output remains at Stage 2.
Prio Use
Prio 6 1. After expiry of the switch-off delay [DlyOff], priority 6 is released.
2. The effective switch command Off from [DefVal] is transmitted to [PrVal].
3. Priority 6 adopts the new value of [PrVal] and is set to active again. At the same time, the minimum
switch-off time [TiOffMin] is started. Priority 6 remains active throughout this monitoring time.
Prio 6 The minimum switch-off time [TiOffMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any of the information bits for priority entries (7…16) is active, the effective
switch command is determined by [DefVal].
The output value [PrVal] remains at Off.
8 Prio 7…16 At least one of the information bits for priorities (7…16) is active again.
The effective switch command from priority (7…16) is Stage 1.
Prio 6 Priority 6 adopts the (still unchanged) present value [PrVal=Off] and is set to active.
At the same time, the switch-on delay [DlyOn] starts. Throughout the delay time, priority 6 remains active –
the associated value remains Off.
[PrVal] Since priority 6 overrides the effective switch command from priority (7…16), the [PrVal] output remains
Off.
10 Prio 7…16 The effective switch command from priority (7…16) switches from Stage 1 to Stage 2.
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
[PrVal] When priority 6 ceases to take effect, the [PrVal] output is once again determined by the effective switch
command from priority (7…16).
The [PrVal] output remains at Stage 2.
Prio Use
1 Prio 1…5 Assumption: All information bits for priorities 1…5 are inactive.
2 Prio 1…5 At least one of the information bits for priorities (1…5) is active again. The effective switch command from
priority (1…5) is Off.
Prio 6 Since the effective switch command for priority (1...5) does not cause a change in the [PrVal] output,
priority 6 remains inactive.
3 Prio 1…5 The effective switch command from priority (1…5) switches from Off to Stage 1.
Prio 6 Priority 6 adopts the new present value [PrVal=Stage 1] and is set to active. At the same time, the
minimum switch-on time [TiOnMin] starts without waiting for the delay time [DlyOn].
Note: Entries for priorities (1…5) initialize only the minimum switch-on or switch-off times [TiOnMin] and
[TiOffMin] respectively, but not the switch-on and switch-off delays.
[TiOnMin] and [TiOffMin] times for which the timer has already started only take effect when all priorities
(1…5) are inactive, that is, when the [PrVal] will be determined by one of priorities (7…16).
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Off to Stage 1.
4 Prio 1…5 None of the information bits for priority entries (1…5) is active.
Prio 6 The minimum switch-on time [TiOnMin] is still active. Priority 6 adopts the new target value from priority
(7…16).
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any entries for priorities (1…5) are active, the output [PrVal] is now again
determined by the effective switch command from priorities (7…16).
The [PrVal] output remains at Stage 2.
Note: Switching from Stage 1 to Stage 2 does not re-start the minimum switch-on time [TiOnMin].
6 Prio 1…5 Assumption: All information bits for priorities 1…5 are inactive.
Prio Use
7 Prio 1…5 At least one of the information bits for priorities (1…5) is active again. The effective switch command from
priority (1…5) is Off.
Prio 6 Since the effective switch command for priority (1...5) does not cause a change in the [PrVal] output,
priority 6 remains inactive.
8 Prio 1…5 The effective switch command from priority (1…5) switches from Off to Stage 2.
Prio 6 Priority 6 adopts the new present value, [PrVal=Stage 2] and is set to active. At the same time, the
minimum switch-on time [TiOnMin] starts without waiting for the delay time [DlyOn].
Note: Entries for priorities (1…5) initialize only the minimum switch-on or switch-off times [TiOnMin] and
[TiOffMin] respectively, but not the switch-on and switch-off delays.
[TiOnMin] and [TiOffMin] times for which the timer is already running only take effect when all priorities
(1…5) are inactive, that is, when the [PrVal] will be determined by one of priorities (7…16).
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
the switch state and of any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Off to Stage 2.
9 Prio 1…5 The effective switch command from priority (1…5) switches from Stage 2 to Off.
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
the switch state and of any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Stage 2 to Off.
10 Prio 1…5 All information bits for priorities 1…5 are inactive.
Prio 6 The minimum switch-off time [TiOffMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any entries for priorities (1…5) are active, the output [PrVal] is now again
determined by the effective switch command from priorities (7…16).
The output value [PrVal] remains at Off.
Motor •
Switch • •
Release •
Normal
Normal handling of the process values in the [PrioArr]. The configured runtimes are active. The outputs can be
switched directly or in stages.
Motor
The Motor setting is used when there is a need to allow for ramp-up and ramp-down times due to a rotating
centrifugal mass. The programmed times in this setting can be used, e.g., to avoid overloading the fan belt
when starting a fan motor.
When the motor is switched down, the system checks on the basis of the ramp-up time whether or not the
current motor speed has been reached. The switch-down command is not executed until the motor speed is
stable. During the ramp-down period, the effective command to the hardware is Off. When the ramp-down time
has elapsed, the new command is transmitted to the hardware.
Trigger
In the Trigger setting, the source of the last command takes precedence. The valid value is written from the
[PrioArr] to the [DefVal] and transmitted to the output. The priority is then released again.
In this setting, Priorities 7…16 are treated equally; Priorities 1…5 have a blocking effect.
The trigger function is used, e.g., for the integration of LON data points. Owing to the event mechanism, this
function is not used for P-bus objects.
Switch
The Switch setting is used to generate an ON or OFF pulse of a predefined duration. A command via BACnet,
or the activation of an Enable signal in one of Priorities 7…16 via the data flow connection initiates an
associated pulse (event). The minimum switch-on time [TiOnMin] and/or minimum switch-off time [TiOffMin]
must be set. Setting both times can prevent fast switching operations. Priorities 1…5 have a blocking effect.
Pushbutton with delay (time extension)
The Pushbutton with delay function is like the Switch function, except an active pulse can be extended by
another pulse at any time.
● Switch-on/off delay
● Minimum switch-on/off time
● Ramp-up/-down time
Monitoring periods:
● Feedback time with switch-on/off
● Feedback signal deviation during operation
Runtimes
Switch-on/off delay
Blocks: BO, MO, BVAL, MVAL
The switch-on/off delay when applied to the switching I/O blocks causes a delayed output if the switch
command was written via Priority 7…16. The delay time affects Priority 6 as described. Switch commands via
Priorities 1…5 are executed without a delay.
Minimum switch-on/off time
When applied to the switching I/O blocks, the minimum switch-on/switch-off time causes the output to be
blocked for a period of time if the switch command was written via Priority 7…16. The minimum switch-on/off
time affects Priority 6 as already described in Section 24.2.1.3. However, switch commands via Priorities 1…5
are executed immediately irrespective of the minimum switch-on/off time.
Ramp-up/down time
The ramp-up/down times (run-up/-down times) can be defined in a table for each stage. These times apply to
the two switch types [SwiKind] Normal and Motor.
The ramp-up time is the time taken by a motor when changing from a lower speed to the next higher speed, to
reach the new speed. This limits the current consumption of the motor.
The ramp-down time is the time taken by the motor when switching down from a higher speed, to reach the
lower speed. This prevents feedback to the mains supply network and protects the fan belt and the motor.
As a rule, the ramp-up and ramp-down times depend on the centrifugal mass involved, and must be determined
separately for each project.
Especially with single-speed motors, the times can be used as Open/Close runtimes (e.g., damper actuator from
0…100%). A moving damper can thus be mapped in the system and the transition signal can, if required, be
used for control purposes.
Monitoring periods
Feedback monitoring / process value monitoring
Blocks: BI, MI, BO, MO, BVAL, MVAL
The I/O objects have a monitoring function. The output objects monitor the feedback signal from the plant. For
this purpose, an address string must be entered for the [FbAddr] feedback parameter [FbAddr] and the alarm
function must be enabled.
The input and value objects can monitor reference values. For this purpose, the relevant reference values must
be configured and the alarm function must be enabled.
Deviation monitoring
If the feedback value deviates from the output value [PrVal], a deviation alarm is generated after a configurable
time period, and the block status changes to In Alarm. When the two values match again, and the configured
time period has expired, the alarm and status are reset. There is otherwise no automatic block reaction, that is,
if a switch response in the plant is required as a reaction to this alarm, this response must be programmed in
CFC via the Disturbance output [Dstb].
Switch-on/off feedback monitoring
It is also possible to configure the time period during which the maximum deviation of the feedback signal may
occur after a switch-on/off operation. If the deviation persists after the monitoring time has expired, an alarm is
generated and the status of the block changes to In alarm. When the two values match again, and the
configured time period has expired, the alarm and status are reset. There is otherwise no automatic block
reaction, that is, if a switch response in the plant is required as a reaction to this alarm, this response must be
programmed in CFC via the Disturbance output [Dstb].
No feedback monitoring
If no feedback monitoring is required, and the address string is left blank, the monitoring periods are used by the
block for the internal generation of the transient state [TraSta]. This means that the transient state signal for the
switch-on/off operation is set for the preset period of time. This is how a moving actuator, e.g., a damper, is
displayed in the system.
Limit monitoring
Blocks: AI, AO, AVAL
In the case of the analog I/O blocks, the present value [PrVal] can be monitored for a high/low limit. If the alarm
monitoring feature is enabled, a deviation alarm is generated after a configurable time period, and the block
status changes to In Alarm. When the present value is within the limits again and the configured time period has
expired, the alarm and status are reset. There is otherwise no automatic block reaction, that is, if a switch
response in the plant is required as a reaction to this alarm, this response must be programmed in Xworks Plus
(XWP) via the disturbance output [Dstb].
PXM20 PXM30/40/50
Input objects are overridden by setting the out-of-service parameter [OoServ] and writing the desired present
value [PrVal]. The default value [DefVal] is automatically set to the same value as [PrVal]. (You can also
overwrite [DefVal], in which case [PrVal] is automatically used instead).
There is no need to follow these rules when using the PXM20 to override a value, as the operator unit observes
them automatically.
Overridden input objects are not reset automatically. To do this, reset [OoServ] first. [DefVal] remains at the last
overridden value and [PrVal] is again derived from the physical input.
2. Override via online test mode in CFC:
Overrides with CFC are carried out via a proprietary service.
Outputs of a block cannot be overwritten.
To overwrite [PrVal] the out of service state in [OoServ] must be set to TRUE, after which the default value
[DefVal] can be modified. This value is then adopted (or applied) as the present value and is made available
under [PrVal].
User override of an output value
BACnet clients
[PrioArr]
[OoServ] [PRVal]
[DefVal] [StaFlg]
[EnOp] [Rlb]
[ValOp]
[EnPgm]
Online test mode
[ValPgm]
in PX Design
Runtime totals
Runtime totalization can be implemented in the binary input, binary output and multistate input and output
blocks (BI, BO, MI and MO). Part of the overall range of functions is defined by the BACnet standard. In order to
provide the complete range of runtime totalizing functions required in the field of building automation and
control, certain proprietary enhancements have been added here.
Function
With a binary input object, the operating hours are determined on the basis of the ON state of [PrVal] (that is, by
measuring the time for which this value is active). For multistate blocks, you can configure how many states are
to be totalized. These are combined and added in a totalizer (the various states cannot be evaluated
individually). In contrast to the input object, the output objects of the ON state for [FbVal] is logged (not [PrVal])
to operating hours message of the output objects.
There are two separate totalizers for runtime totalization:
● Runtime totalizer
● Overall runtime totalizer
Release
Runtime totalization can be enabled via the [EnOph] pin (Enable operating hours count). This is a binary value
for binary objects, for multistate objects a list of values released for counting.
Runtime totalizer
Maintenance messages (events) are generated via the runtime totalizers. These are typically reset when the
maintenance has been carried out. The present operating hours [PrOph] output can be used to connect the
runtime totalization feature for further use in the program (e.g., for changeover of pumps or boilers based on
operating hours).
Resetting the runtime total
The operating hours [Oph] input is used to reset the current runtime total. In online test mode in Xworks Plus
(XWP) via a BACnet client the present value can be reset by overwriting it with a new value (usually 0). This
reset does not affect the total operating hours count (pins [OphTot] and [PrOphTot], total operating hours and
present total operating hours respectively).
Overall runtime totalizer
The total operating hours count records the total hours run by an aggregate. It is only reset when the aggregate
is replaced. The [PrOphTot] output is available for further interconnection in the program.
Resetting the operating hours total
The [OphTot] input is used to reset the total operating hours. In online test mode in Xworks Plus (XWP) or via a
BACnet client, the present value can be reset by overwriting it with a new value (usually 0). This reset procedure
simultaneously sets the runtime totalizer (pins [Oph] and [PrOph]) to the same value.
This is necessary, e.g., for an aggregate which is installed as a replacement item, but which has previously
been in operation elsewhere for some time.
Maintenance message
A maintenance message (event) can be generated either after a specified period of operation or on a specified
date. The operating hours limit value and the maintenance date [OphLm]/[MntnDate] can be configured for this
purpose. An event message is generated when the limit value is exceeded or at 13:00 hours on the preset date.
At the same time, the binary output [MntnInd] (maintenance indication) is set to active for further use in the
program. After the operating hours reset, this output reverts to inactive. At the same time, the time stamp of the
last reset is stored in the time stamp operating hours reset pin [TiStmOph].
Feedback value
The following applies to output blocks: When a feedback is configured, operating hours count is done based on
the feedback value and not based on present value.
The maintenance interval can be further connected via the output present total operating hours limit [PrOphLm].
Value range for run time totalizing
The hours run are registered in 32-bit format, giving a maximum value of 4,294,967,296. With a resolution in
seconds, this gives a value range of over 49,000 days (more than 136 years).
Reliability [Rlb]
The reliability of the present value and of the physical input/output is represented by the reliability pin [Rlb]. This
makes it possible to detect and signal faults and errors, such as addressing errors, sensor problems (short-
circuit or open circuit) and module faults (missing or incorrect modules). See Reliability Table.
The Pulse Converter object can be used in two different manners: Counting or metering. The type of application
is parameterized using the FnctMod parameter.
The referenced object, e.g., an external device provides the pulse value:
● Present_Value for the pulse converter object represent the pulse count of the referenced object: The
difference to the last read value is added for each record.
● Present_Value can be set via the system.
● After start-up, the pulse converter object encompasses the last stored counter value:
● After a change in counter, the pulse converter object encompasses a false counter value.
● Typical application: On-board I/O with pulse logging.
The referenced object, e.g., an external device provides the absolute pulse value:
● Present_Value from the pulse converter object represents the absolute counter value of the referenced
object.
● Under no circumstance may the Present_Value be set via the system.
● After start-up or a change in counter, the pulse converter object after includes the correct counter value.
● Typical applications:
– Access to an accumulator or pulse converter object is another BACnet device
– I/O Open module or M-bus with counter value integration
– Integration of a device via LON
● Incorrect applications: I/O module with pulse recording
● Switch-command delays
● Process monitoring [StaFlg]
● Runtime totalization and maintenance messages
Analog Output
[PrioArr]
[PrVal]
[FbVal]
[FbVal] :=
Feedback Raw Value *Feedback Slope+ Feedback Intercept
If
[FbAddr]
Feedback_Raw_Value
The value [PrVal] from the program is converted into the physical positioning value by use of a conversion
curve. This present value is then available at [PrVal] for further processing in the program while at the same
time, the raw data is transmitted to the associated I/O system, where it is converted into an electrical signal to
drive the field device.
The conversion curve is a linear function which takes the following form:
Raw Value [RwVal] = [PrVal] * Slope + Intercept
The values for slope [Slpe] and intercept [Icpt] must be defined specifically for the application concerned in
accordance with the I/O system in use and the signal type.
For slope [Slpe] and intercept [Icpt] values for SBT products, see Slope [Slpe] and Intercept [Icpt].
OpMSwiCnv
Ax: DMUX8_BO
CM110664en_10
En En En En En En En En En En En
En DefVal:Off
On On
TOa
TSu
SpErcTSu
TSu
EnCrit
EnCrit
OpSta OpSta
MI FanSu FanEx
BVAL BVAL ManSwi Cp:Ml DmpShofOa Ag. DmpShof Ag: V(A,C-F) Fan1St DmpShofEh Ag:DmpShof Ag: V(A,C-F) Fan1St
PrVal
PrVal
A-Transport
EnCrit EnCrit
E,H E,H
EnPgm
ValPgm
EnSfty
ValSfty
EnPgm
ValPgm
EnSfty
ValSfty
AO BO AO BO
PrVal
OpSta
Dstb
KickDmp
PrVal
OpSta
Dstb
KickDmp
PrVal
FbVal
PrVal
FbVal
Frost
can be used, e.g., as a simple way of enabling the user to operate setpoints and switch commands.
Value objects
Logical I/O blocks
determine and monitor operating hours. The value objects designed specially for operation via BACnet client
19
Furthermore, the value objects can be used for alarm monitoring (reference values or high/low limit value), or to
247 | 346
19 Logical I/O blocks
Value objects
I/O systems
To enable the process value of the logical I/O block to be allocated to the appropriate physical I/O, the relevant
address must be assigned. The address is assigned as follows:
● Via automated assignment by the Point Configurator to the CFC
● Direct allocation to the I/O block in Xworks Plus (XWP)
The logical I/O blocks are designed for universal use in various I/O systems. The specific address structures
and hardware definitions are determined by the I/O system, e.g., the failsafe control value for the island bus.
In Desigo, they are as follows:
● Physical I/Os
● Values in a Desigo room unit, accessible via the PPS2 interface
● Data in the same or in another automation station, referenced by its Technical Designation and accessed
without a connection, peer-to-peer via BACnet services.
Address prefix
The addressing syntax indicates the origin of the raw value. The syntax must correlate with the actual physical
inputs.
The prefixes for the various subsystems are as follows:
● "T=" for TX-I/O modules on an island bus-capable automation station PXC....D
● "C=" for on-board I/Os of the Desigo PX compact automation stations
● "B=" for referencing to BACnet objects
● "Q=" for QAX room units
● "L=" for LonWorks addressing
● "M=" for PX-OPEN addressing
● "D=" for PX Open Diagnostic Addressing
For addressing with "P=", see Addressing Entries for PXC…-U, PTM and P-Bus.
For addressing with "S=", "M=" and "D=", see the corresponding expert documentation.
For more information on TX-I/O, see TX-I/O Assortment overview (CM2N8170) and TX-I/O Functions and
operation (CM110561).
Required address entries when using the modular series automation station in
conjunction with TX-I/O-I/O modules
Signal types shown in italics are used to map virtual modules for use with TX OPEN at module level. Signal
types AIS, AOS, DIS and DOS deliver a 16 bit value with status information, while signal types AISL, AOSL,
DISL and DOSL deliver a 32 bit value with status information. All other signal types deliver a 16/32 bit value
without status information.
While all the module types listed may be connected to any island bus addresses, not all module types have 16
points.
PX Info LED 8 1
Parameter values
Parameters are entered in the I/O address editor.
See Automation stations modular series PXC..D, PXC..-E.D, PXA40.. (CM1N9222).
DO1
HMI / TOOL
Block
AI
I/O module Island bus
T
R
10664-24z 02en
AI
Island bus
If you wire it as in the figure above, Xworks Plus (XWP) determines multiple use and generates an error
message.
For the multiple use of output blocks, the plant will malfunction, because there will then be two or more sources
acting on one switching command. The effective switching command (at the output) is the last one received
(determined by the rule "the last command takes precedence"). In other words, the order of processing
determines which source or origin will be linked to the output.
In CFC the same address can be allocated to two or more input or output blocks. This multiple address
allocation goes undetected when the program is compiled; the automation station also fails to recognize the
error (a reliability error is generated and an error message is transmitted only in the case of multiple address
allocation with two different signal types).
Solution 1
Many systems include a requirement for the multiple use of sensors. A typical example of this is an outdoor air
temperature sensor shared across systems. The following example illustrates the simplest form of the multiple
use of sensors:
In CFC the current value is transmitted for further use in the program by interconnecting the blocks. The logical
I/O block (Analog Input, {AI}) occurs in the program once only, and its hardware-specific parameters only need
to be set once.
10664-24z03en
Block
I/O module
Analog input
Solution 2
The multiple use function can be implemented with a BACnet reference to the first analog input block (Partial
plant 1). In other words, the first block will receive the island bus address at the [IOAddr] pin. The second analog
input block (Partial plant 2) references the first AI (B=…) via the technical designation.
● Q-M1: T=1.1
● Q-M2: T=1.1
● Q-M3: T=1.1
● Q-M4: T=1.1
● Q250-P3: T=10.1
● DOS: T=24.7
Values with up to four stages can be processed. The signals to be registered, which are addressed via
Module.Channel, must always be of the same hardware signal type. In the case of a multistate output on the
hardware side, there is one address only (this is only possible with PXC modular automation stations).
Error handling
If an automation station does not support a given address (e.g., incorrect syntax) or a given I/O system, this will
lead to a reliability error, which will be displayed at the [Rlb] pin.
Advanced mapping (Multistate Input)
The manual switch can be encoded on the PX Compact in various ways, e.g.:
● (Auto/Off/On) or (Off/Auto/On)
● (Auto/Off/S1/S2) or (Off/Auto/S1/S2)
So avoid having to keep adapting the data types and text groups in the system, the manual switch must always
be represented in the same way within the system:
● (Auto/Off/On)
● (Auto/Off/S1/S2)
A prerequisite for this approach is that it must be possible in the multistate input block to configure the hardware
coding and mapping to the standardized manual switch. This is made possible with parameters in the address.
1_n-Mapping (Multistate Input and Output)
Syntax:
T = Module.channel
C=Module.channel;Module.channel;Module.channel;Module.channel (signal type, a,b,c,d,e)
a represents [PrVal] for HW-I/O (0,0,0,0)
b represents [PrVal] for HW-I/O (1,0,0,0)
c represents [PrVal] for HW-I/O (0,1,0,0)
d represents [PrVal] for HW-I/O (0,0,1,0)
e represents [PrVal] for HW-I/O (0,0,0,1)
Example: T=2.1
For the TX I/O addressing no additional information in the address string is added. All information (signal type,
mapping table, mapping rules, e.g., up-down, etc.) is configured in the I/O Address Editor and loaded in the
automation station with the IOC file.
Example: C=2.1;2.2;2.3;2.4 (D20, 2, 1, 3, 4, 5)
1 1 0 0 0 Auto
3 0 1 0 0 Stage 1
4 0 0 1 0 Stage 2
5 0 0 0 1 Stage 3
1 1 0 0 0 Off
5 0 1 0 0 Comfort
9 0 0 0 1 StandBy
2 1 0 0 0 Stage 1
3 1 1 0 0 Stage 2
4 1 1 1 0 Stage 3
5 1 1 1 1 Stage 4
With Up/Down mapping, more than one hardware input or output may be active.
Binary Mapping (Multistate Input and Output)
Application: Output of an integer in binary form.
Example: Binary electric heating coil.
Syntax: C=Module.channel;Module.channel;Module.channel;Module.channel (signal type, BINARY)
Example: C=5.1;5.2;5.3;5.4(Q250,BINARY)
Example: C=2.1;2.2;2.3;2.4(D20,BINARY)
2 1 0 0 0 Stage 1
3 0 1 0 0 Stage 2
4 1 1 0 0 Stage 3
5 0 0 1 0 Stage 4
6 1 0 1 0 Stage 5
...
16 1 1 1 1 Stage 15
With binary mapping, more than one hardware input or output may be active.
BACnet addressing
Peer-to-peer communication
Data can be exchanged via peer-to-peer communication.
The exchange takes place using the BACnet services defined in the BACnet standard. The process employs
mechanisms engineered in CFC which can be tracked in online test mode, but which are based on BACnet
objects and BACnet services.
Engineering
When engineering the exchange of data in CFC, it is important to take note of the following:
● Addressing is via [IOAddr].
● Data is exchanged only between BACnet objects. The attributes of the I/O blocks and pins must be defined
appropriately, and the information must also be made available in the form of a BACnet object. For this
purpose, the attributes of this block or I/O must be defined correctly.
● In BACnet terminology, the I/O block is a client which fetches the required value from an object defined as
the server. This process is carried out using services defined by BACnet, e.g.: The client subscribes to the
relevant object (the server) using the SubscribeCOV service. The server then supplies the value via the
BACnet service COVReporting whenever it changes by the programmed value, COVIncrement.
ReadProperty (polling) is another BACnet service. Here, the value is read at regular predefinable intervals.
● Addressing is carried out via the Technical Designation (TD). Note, however, that this Technical Designation
must first be made known to the client in the form of a reference address.
● The data is exchanged both within a given automation stations, and across automation stations.
Address syntax
Addressing takes place via the input/output address [IOAddr] and always starts with the prefix "B=".
The BACnet reference address is the same as the Technical Designation (TD) of the value. The BACnet
addressing syntax is as follows:
B=BACnetReference (BACnetConfig)
Example: B=Geb6'Lft3'FanSu'Mot'MntnSwi.PrVal(0)
Polling or COV procedure
The FB variable PollCyc is used instead of the prior BACnetConfig parameter in the I/O address syntax, to
distinguish between COV or polling:
FB variable IOAddr. FB variable PollCyc
BACnetConfig = 0 -> COV (Change of Value)
BACnetConfig = 1…65535 -> Polling in seconds
In an automation station operating as a BACnet device, the maximum number of simultaneously supported COV
subscriptions is limited to 400.
The BACnet Device as BACnet Server supports a maximum of 400 subscriptions from BACnet clients or from
other BACnet devices via the BACnetReference.
A BACnet device operating as a BACnet client can also accommodate a maximum of 100 subscriptions to other
values via the BACnetReference.
If the COV procedure is selected, COVIncrement is used for analog objects to define the value by which the
present value must change to initiate a COV event.
Data output using WriteProperty
Output objects can write their Present_Value to the properties of other objects or command other value or
output object.
Write without priority: Optional address string-Par(P=Number) no available.
Command with priority: Optional address string-Par(P=Number) available.
COV across sites
The value subscribed to must be available in the same BACnet network. Avoid a COV across sites.
The DeviceID is used to access and subscribe freely to values in different BACnet devices (especially in the
case of third-party integration). The syntax is as follows:
B=[DeviceID]Objectname – where the object name can be any string required. The DeviceID is entered in
decimal (instance number or entire ObjectID).
PPS2 addressing
A PPS2 address is required when values are to be transmitted via the PPS2 interface. Addressing takes place
via the input/output address [IOAddr] and always starts with the prefix "Q=".
Address syntax
Up to five room units can be connected to one Desigo PX automation station and addressed via the PPS2
interface. The addressing syntax is as follows:
Q=RoomUnitNumber.Object(Profile)
Example: Q=1.40 (1)
The functions available in the room unit are mapped directly to the I/O blocks. The following elements of the
address are predefined:
Type (standard BACnet objects) Room unit Object Object description Profile1 Example
number
Analog input 1…5 24 Setpoint correction – Q=1.24
Key
1
The Profile relates to the configuration number shown in the next table.
The room unit is configured with this configuration number and appended to the Room temperature object.
Other objects are not assigned a configuration number. Only the relevant operating and process values are
mapped in the I/O blocks, rather than all objects of a room unit.
Six profiles have been defined to keep both the memory requirements and the demands placed upon the user in
practice to a reasonable level. If no profile information is supplied, the predefined device-specific default value
[DefVal] is used. As an exception in the case of the QAX units, Profile No. 5 is used.
Configuration Profile
1 2 3 4 5 6
StandBy ON ON ON ON ON ON
Auto ON ON ON ON ON ON
Fan1 ON ON ON ON ON ON
KonfLCD
Symbol Standby ON ON ON ON ON ON
Symbol Auto ON ON ON ON ON ON
Symbol Fan1 ON ON ON ON ON ON
TempUnit °C °F °C °F °C °F
This profile (or configuration number) is always valid for one room unit only. It is used to configure the objects
ConfigLCD and EnableOperatingMode and to define how the room unit is to operate (e.g., °C or °F).
In principle, the profile can be attached to any other object.
This configuration applies only to the QAX33.1 and QAX34.1 room units.
Configuration of the object ConfigLCD is only relevant in the case of the QAX34.1, as this is the only unit with a
display in °C or °F.
The configuration of the object EnableOperatingMode is only relevant in the case of the QAX33.1 or QAX34.1,
as only these two room units have the option of selecting Fan1, Fan2 or Fan3.
Where QAX units without an address switch are still in use, only one room unit per automation station can be
integrated. The room unit number in such cases is then "1".
LonWorks addressing
There are two ways to integrate data points from LonWorks devices:
● via Discipline I/O
● via standard inputs/outputs (the latter approach is only sensible with a small number of data points to be
integrated, e.g., from third-party devices)
Address syntax
The block registers the control variables and output variables of the RX devices (outside the CFC chart) in
accordance with the information in the [IOAddr] property (Input/output address).
Addressing starts with the prefix "L=".
Addressing via discipline I/O
L=DeviceType DeviceNo. GroupIndex(MappingTableNo.)
● DeviceType: M (Master), S (Slave)
● DeviceNo: Field device identification number
● GroupIndex: Group identification: Up to 4 similar groups of an application unit may exist in the field device
(e.g., lighting or window-blind groups). The group index number is optional.
● MappingTableNo: Number of the mapping table which is valid for that Discipline I/O.
More than one device can be specified for each [IOAddr] string. The devices are separated with a semicolon.
However, the maximum [IOAddr] string length of 60 characters must not be exceeded.
Addressing via standard I/O
L= DeviceType DeviceNo.GroupIndex(3RD[NVIndex.FieldIndex])
● DeviceType: M (Master). There are no slaves (S) with third-party devices There is only ever one device.
● DeviceNo: Field device identification number
● GroupIndex: Group identification: Up to 4 similar groups of an application unit may exist in the field device
(e.g., lighting or window-blind groups). The group index number is optional.
● ObjectType: Constant for third-party devices: 3RD.
● NVIndex: Network variable referenced in the third-party device.
● FieldIndex: Element number, if the network variable is structured
KNX addressing
You can integrate data points from KNX devices as follows:
● See PX KNX, RXB integration - S-Mode (CM1Y9775)
● See PX KNX, RXB/RXL integration - Individual addressing (CM1Y9776)
● Address Info LED for PX KNX: D=1001
This input value is the logical image, or memory map, of an analog positioning command and describes its
properties. Within the program, the Present Value is made available to the block as a program value. The block
transfers the program value to the subsystem, from where it is transmitted to the field device.
Writing to this value acts as a trigger. This makes it possible, e.g., to generate the output of the same value
(e.g., Lighting 100%, followed later by 100% again). In this case the subsystem registers the trigger value and
transmits the value to the devices. This capability is required when the same variable can be modified from
several sources (e.g., when Desigo CC writes 100.0%, the local operator unit writes 0.0% and the Desigo CC
user wants to rewrite the value of 100.0%). The sources can be BACnet clients or system function blocks.
Only analog trigger values may be used.
Commandable value
The input value is the logical image, or memory map, of an analog positioning command and describes its
properties. Within the program, the Present Value is made available to the block as a program value. The block
transfers the program value to the subsystem, from where it is transmitted to the field device.
The commandable value is based on the BACnet priority-mechanism (which is the same as for the output
blocks – refer to Section 0). A commandable value can be operated from various sources. Each source has its
own priority. The sources are mutually exclusive (interlock). The source with the highest priority prevails, e.g.,
Emergency = Priority 1, Façade control = Priority 6, Operator = Priority = 8). The sources can be BACnet
operator units or system function blocks (grouping function).
Only analog commandable values can be used.
1 No sensor.
4 Continuous loop.
5 Short circuit.
6 No output.
7 Unreliable other.
8 Process error
9 Multistate fault.
84 Memory full.
89 Reliable participant.
Siemens Building Technologies field devices: XWP automatically enters the combined values [Slpe] and [Icpt]
(for the signal type, the field device and its measurement or positioning range) on the I/O block.
Third-party field devices: You can calculate the value [Slpe] and [Icpt] using the Intercept Calculator.
Signal type Description Standard Resolution on the Value range on the [Slpe] [Icpt]
measurement measuring range bus bus
R1K LG-Ni 1000 -50 … 150 °C 1/100 °C -5000 ... 15000 0.01 0
Pt100_4 Pt100 -50 ... 600 °C 1/100 °C -5000 ... 40000 0.01 0
T1 PTC sensor -50 ... 150 °C 1/100 °C -5000 ... 15000 0.01 0
Ni1K LG-Ni 1000 -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K375 Pt1000 (NA) -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K385 Pt1000 (EU) -50 ... 600°C 1/100 °C -5000 ... 60000 0.01 0
NTC10K NTC sensor -40 ... 115 °C 1/100 °C -5000 ... 11500 0.01 0
NTC100K NTC sensor -40 ... 125 °C 1/100 °C -5000 ... 12500 0.01 0
Signal type Description Standard Resolution on the Value range on the [Slpe] [Icpt]
measurement measuring range bus bus
I25/020 (Shunt 100 DC 0 ... 25mA 0 … 10 mA 1/500 V 0 ... 5000 0.002 0
Ohm)
I25/020 TX-I/O* DC 0 ... 20mA*) 0 ... 20 mA* 1/1000 mA 0 ... 20000 0.001* 0
U10 (Shunt 400 DC 0 ... 25mA*) 0 ... 25 mA* 1/1000 V 0 ... 10000 0.0025* 0
Ohm) TX-I/O*
Key
*
TX-I/O modules support only 0 ... 20 mA. For a range of 0 ... 25 mA, use the shunt for 400 Ohm (0.1%, 1 W) and measure the
voltage with U10.
BACnet referencing
Reference to a value in another BACnet object. As the referenced value is already available as a converted or
resulting value, no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as 0.
PPS2 interface
The measured value from a room unit connected via the PPS2 interface. In the analog input block, only Objects
24 (setpoint correction) and 40 (room temperature) may be used. As the value is already available as a
converted or referenced value, no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as 0.
Key
*
Value [Slpe] for Y250T is not a physical value, but rather a special code controlling output of the AO to two relay outputs. This code
differs between P-bus and island bus.
PPS2 interface
Transfer of an analog control command to a room unit connected via the PPS2 interface. Only Object 195 (=
Room temperature display) can be used in the analog output block. As the value is already available as a
converted or referenced value, no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as 0.
P1K (Pt1000)
R2K5
P1K (0...2500 Ohm)
0 Ohm 0.1 1 0 1
Default = 1 Ohm 0.1 0 0 0
2 Ohm 0.1 -1 0 -1
3 Ohm 0.1 -2 0 -2
R250
0 Ohm 0.01 1 0 1
Default = 1 Ohm 0.01 0 0 0
2 Ohm 0.01 -1 0 -1
3 Ohm 0.01 -2 0 -2
R250
P100 (0...250 Ohm)*
0 Ohm 0.01 0 0 0
Default = 1 Ohm 0.01 -1 0 -1
2 Ohm 0.01 -2 0 -2
3 Ohm 0.01 -3 0 -3
Key
*
PT-I/O modules P100 is a four-wire type Default line resistance = 0 Ohm
Line resistance not compensated
TX-I/O modules with island bus Pt100_4 is a four-wire type Default line resistance = 0 Ohm
integration Line resistance not compensated
TX-I/O modules with BIM Pt100_4 is a four-wire type Default line resistance = 0 Ohm
integration Line resistance not compensated
Ni1K 5 0.2
Pt100_4
BSG61
0 ... 5 V
10563A22
Zener diode Voltage divider Active setpoint adjuster BSG61
(Datasheet CE1N1992)
Address entries required when using the modular series automation station in
conjunction with TX-I/O modules
Type Module addressing I/O point or channels
Desigo TX-I/O 1...120 1...16
PX Info LED 8 1
1:n - Mapping
1:n - Mapping
Signal types shown in italics are used to map virtual modules for use with I/O OPEN at module level. Signal
types AIS, AOS, DIS and DOS deliver a 16 bit value with status information, while signal types AISL, AOSL,
DISL and DOSL deliver a 32 bit value with status information. All other signal types deliver a 16/32 bit value
without status information.
While all the module types listed may be connected to any P-bus addresses, not all module types have 16
channels.
Parameter values
Parameter values for the analog output, binary output and multistate output blocks:
Y10S
Failsafe function (emergency control function) if the transfer of data over the P-bus fails (for longer than 4
seconds) or in the event of a power failure. (an operating voltage of AC 24 V must be available).
NO -> Module output signal goes to 0 V.
KEEP -> Module output signal remains at previous value.
0...30 -> Module output signal 0 = 0 V, 1 = 0.33 V, etc. , … 30 = 10 V.
Y250T
1…13, 1…13 Runtime ranges for On/Off signals (the ranges do not need to be the same for On/Off). Values
1…13 correspond to the following runtimes:
1 = 8.5 ...13 seconds
2 = 13 ... 18 seconds
3 = 18 ...25 seconds
4 = 25 ...35 seconds
5 = 35 ... 48 seconds
6 = 48 ... 66 seconds
7 = 1.1 ... 1.6 minutes
Key
1
For PXC10-TL the two Alarm1/2 buttons and the DIL switches1/2 are mapped to the modules with the Address 3.
2
The manual switch can only be loaded into the application if the DIL switches (in the cover of the PXC36-S) are set correctly.
3
Syntax for PPS-2 signal: Q=Romm device number.Object number (profile number). Up to five devices can be connected.
4
The current UI and AO can all be configured as AI, DI, CI, or AO.
Signal type if no application is loaded (wiring test): X1...X16 = Y10S, Y1...Y8 = R1K.
Module 4
For Module 4, the universal outputs (UO for AO and DO) not only control proportional actuators (AO), but can
also be used as binary switch commands (DO).
● Analog Output = 0…10 V
● Binary Output = DC 0 or 24 V, max. 22 mA with the use of an additional external relay.
Layout of PXC52 housing with address ranges
D1..D4
MD002
GND
GND
GND
GND
X10
X12
D1
CP+
CP -
X11
D2
D3
D4
D5
D6
D7
D8
X1..16 D5..D16
AC24V
26VA MD001 MD003
GND
GND
GND
GND
X13
X14
X15
X16
D9
Simple mapping
Syntax: P=Module.Channel;Module.Channel;Module.Channel;Module.Channel (Signal type)
Examples:
● P=1.1 (D20)
● P=1.1;1.2 (D20)
● P=1.1;1.2;1.3 (D20)
● P=1.1;1.2;1.3;1.4 (D20)
● P=10.3 (DIS)
Up to four binary status values (e.g., Off/St1/St2/St3/St4) can be registered. The signals to be registered, which
are addressed via Module.Channel, must always be of the same hardware signal type. With the simple mapping
procedure, to enable the multistate input to interpret the current binary signals correctly, only one binary signal
may be present at any one time. If several binary signals are present at once, this is displayed as an error at the
[Rlb] pin.
The examples below show a possible application for multistate input blocks in conjunction with the physical I/O
modules. The example on the left of the diagram is a multiple I/O module, while the one on the right shows the
mapping of several individual I/O modules in one multistate input block.
Multistate output
The multistate value from the program is converted in the Multistate Output block into a switching command.
Addressing is via [IOAddr]. For PX modular, the syntax is as follows:
Syntax: P=Module.Channel;Module.Channel;Module.Channel;Module.Channel (signal type, parameter)
Examples:
● P=1.1 (Q250)
● P=1.1;1.2 (Q250)
● P=1.1;1.2;1.3 (Q250)
● P=1.1;1.2;1.3;1.4 (Q250)
● P=10.1 (Q250-P3,120)
● P=24.7 (DOS)
Values with up to four stages can be processed. The signals to be registered, which are addressed via
Module.Channel, must always be of the same hardware signal type. In the case of a multistate output on the
hardware side, there is one address only (this is only possible with PXC modular automation stations).
Error handling
If an automation station does not support a given address (e.g., incorrect syntax) or a given I/O system, this will
lead to a reliability error, which will be displayed at the [Rlb] pin.
3 1 0 0 0 Stage 1
2 0 1 0 0 Off
4 0 0 1 0 Stage 2
5 0 0 0 1 Stage 3
20 Room automation
Desigo room automation
Desigo room automation offers solutions with greater functionality and flexibility allowing for energy-optimized
plant operation without loss of comfort (efficiency class A).
The DXR1 and DXR2 room automation stations are perfectly suited to exclusively automate heating, ventilation,
and air conditioning in a room. In addition, the DXR2 can be extended with lighting and shading functions by
adding devices with KNX PL- Link.
The PXC3 modular room automation stations are used in buildings with multiple disciplines for room automation
(HVAC, lighting, blinds) all combined in one system.
Desigo RX
Desigo RX is a proven room automation product range featuring comprehensive communications and
application functions for individual rooms. The product range consists of a series of communicating room
controllers RXB with operator units and predefined applications for HVAC, lighting, and blinds. Desigo RX room
automation is capable of autonomous operation. Integration of LonWorks or KNX network via the system
controllers provides for additional functionality.
Communication with room units KNX PL-Link KNX PL-Link KNX PL-Link KNX PL-Link
3 3
Room units QMX3.. QMX3.. QMX3.. QMX3..
QMX1.. 4 QMX1.. 4
Key
1
DXR1.E..: Applicable for some variants only.
2
Not applicable for DXR1.M...
3
Only for DXR2...
4
Only for DXR1...
KNX PL-Link
KNX PL-Link (Peripheral Link) connects communicating room and field devices (room devices, sensors, actors)
with the room automation station.
DALI
DALI (Digital Addressable Lighting Interface) helps control lighting.
20.1.1 Configurable
DXR2.. can automate up to two rooms for heating, ventilation, air conditioning, shading, and lighting, whereas
DXR1 can automate one room and heating, ventilation, and air conditioning only.
The stations communicate with each other and other system components, depending on the type, via
BACnet/IP (DXR1.E../DXR2.E..) or BACnet MS/TP (DXR1.M../DXR2.M..). The room automation stations have a
set number of I/O data points and an onboard interface to KNX to connect field devices. The automation
stations are delivered with preloaded applications and only need to be configured.
A comprehensive library of proven, standardized applications is also available and can be used instead of the
preloaded applications. Buttons, sensors, and actuators for lighting and shading are connected to the room
automation stations via the KNX PL-Link.
The preloaded and proven standardized applications in the library are configured using ABT Site and offer a
great deal of flexibility since the inputs and outputs of the DXR1../DXR2.. can also be configured in addition to
the functions.
See Desigo Configurable Room Automation (BACnet) – Product Range Description (A6V10866237).
BACnet/IP Ethernet
PXC..-E.D
KNX PL-Link
KNX PL-Link
°C °C
°C °C
BACnet/IP Ethernet
PXG3.M PXC..-E.D
Router
KNX PL-Link
KNX PL-Link
°C °C
°C °C
Applications
The tables below show the functions of the different applications of the DXR2 room automation stations.
Preloaded applications
Application
Application
control
● Internal flow controller and velocity sensor for damper actuator control
● Chilled water cooling coil
● Heating/Cooling coil
● Hot water heating coil
● Electric heating coil modulating, single stage or two stage
● Room temperature control by two-pipe system with change-over
● Room temperature control by four-pipe system
● Supply air temperature cascade control
● Air flow tracking for under/overpressure
● Room dehumidification control
● Room air quality control
● Rapid ventilation
● Green leaf
Application
● Multi group constant light control
● LED support on push buttons
● Green Leaf - RoomOptiControl
● Burn-in & operating hours function
Application
Application
from the rooms to optimize the fan speed
– Extract VAV flow saturation evaluation (air flow control loop cannot get
enough air to reach setpoint) evaluates the extract VAV saturation signals
from the rooms to optimize the fan speed
– Supply VAV setpoint evaluation with the summed setpoints of the supply VAV
the fan's speed can be set for an optimized fan speed when VAV positions
and VAV flow rates are not known
– Extract VAV setpoint evaluation with the summed setpoints of the extract
VAV the fan's speed can be set for an optimized fan speed when VAV
positions and VAV flow rates are not known
Application
Central functions ● 2x VAV supply fire emergency group with off, extract, pressurization or purge
● 1x Central weather station with:
– Outside temperature
– Outside brightness
– Outside solar radiation
– Outside wind speed
– Outside precipitation
● 2x Light manual central operation group
● 1x Light central control group for emergency situations
● 4x Shading central facade functions with:
– Central weather station brightness calculation supports facade automatic
function
– Glare protection function calculates the glare protection state by central
weather station for all facade
– Annual shading calculates the glare protection state for all facade by in-
formation from annual shading computer
– Thermal protection for unoccupied rooms by central global radiation sensor
on weather station
– Three delayed distribution groups for central blind commands for big
buildings
● 2x Shading manual central operation with 3 delayed distribution groups for big
buildings
● 1x Shading service ensures central commanding of blind group with high priority
● 1x Shading central protection for all blinds with:
– Wind protection
– Precipitation protection
– Frost protection
– Three delayed distribution groups for big buildings
Communication
BACnet/IP DXR2.E DXR2.E DXR2.E DXR2.E DXR2.E DXR2.E DXR2.E DXR2.E DXR2.E
09- 09T- 10- 10PL- 10PLX- 12P- 12PX- 18- 18-
101A 101A 101A 102B 102B 102A 102B 101A 102A
BACnet DXR2. DXR2. DXR2. DXR2. DXR2. DXR2. DXR2. DXR2. DXR2. DXR2.
MS/TP1 M09- M09T- M10- M10PL- M10PL M11- M12P- M12PX- M18- M18-
101A 101A 101A 102B X-102B 101A 102A 102B 101A 102A
Applications
Room • • • • • • • • • •
operating
Heated / • • • • • • • • • •
Chilled ceiling
radiator
VAV system • • • • •
Lighting • • • • • • • • • •
Shading • • • • • • • • • •
Central • •
functions1
Housing
DIN • • • • •
Flat • • • •2 •2
Operating voltage
230V • • •
24V • • • • • • •
Digital inputs 1 1 1 1 1 1 1 1 2 2
Universal 2 2 2 2 2 2 2 2 4 4
inputs
Relay outputs 3 1 3
Triac outputs 4 4 4 4 6 6 6 8 8
Analog 3 1 1 1 2 2 2 4 4
outputs (DC
0...10 V)3
Pressure 1 1 1 1
sensor
Maximum configuration
Number of I/O 30 30 30 30 60 30 30 60 60 60
data points4
Integrated 50 50 50 50 50 50 50 50 50 50
power supply
for KNX (mA)
Key
1
Cannot be combined with other applications.
2
Mounting via damper shaft.
3
Cannot be extended by KNX PL-Link inputs and outputs.
4
Total number of data point used by TX-I/O, KNX PL-Link and DALI. For details, see chapter System Configuration.
See Compact room automation stations, BACnet/IP, 230 V DXR2.E10.., DXR2.E09.., DXR2.E09T.. (N9204).
See Compact room automation stations, BACnet/IP, 24 V DXR2.E18.., DXR2.E12P.. (N9205).
See Compact room automation stations, BACnet MS/TP, 230 V DXR2.M10.., DXR2.M09.., DXR2.M09T..
(N9206).
See Compact room automation stations, BACnet MS/TP, 24 V DXR2.M11.., DXR2.M12P.., DXR2.M18..
(N9207).
DXR1 compact room automation stations
Communication
Applications
Room operating • • • •
VAV system • • • • •
Central functions1
Housing
DIN
Flat •2 •2 •2 •2 •2
Operating voltage
230V
24V • • • • •
Digital inputs 1 1
Universal inputs 2 2 2 2
Relay outputs
Triac outputs 4 4 4 4
Pressure sensor 1 1 1 1 1
Maximum configuration
Key
1
Cannot be combined with other applications.
2
Mounting via damper shaft.
3
Cannot be extended by KNX PL-Link inputs and outputs.
4
Total number of data point used by TX-I/O, KNX PL-Link and DALI. For details, see chapter System Configuration.
Accessory device
See Compact actuating room automation stations, BACnet/IP, AC 24 V (Actuating DXR) DXR1.E09PDZ-112,
DXR1.E09PLZ-112, DXR1.E09PDZ-113 (A6V11393931)
See Compact actuating room automation stations, BACnet/IP, AC 24 V (Actuating DXR) DXR1.E10PL-112,
DXR1.E10PL-113 (A6V11393933)
See Compact actuating room automation stations, BACnet MS/TP, AC 24 V (Actuating DXR) DXR1.M09PDZ-
112, DXR1.M09PLZ-112, DXR1.M09PDZ-113 (A6V11393929)
Fan powered box ● Fan powered box with series fan and staged electric reheater
● Supply air volume control with integrated damper actuator (5 Nm / 10 Nm)
● Room temperature control
● Air quality control
● Relative humidity monitor
● Fan powered box with variable speed fan and staged electric reheater
● Room temperature and rapid ventilation operation via KNX PL-Link room operator unit with
temperature, air quality & relative humidity measurement
Component
Accessory device
20.1.2 Programmable
The DXR2.. and PXC3.. room automation stations are programmable, based on proven application blocks.
Thus, solutions can be tailored to specific needs and can achieve maximum efficiency and comfort.
See Range Description Desigo Room Automation (BACnet), Programmable Room Automation - Emergency
Lighting (A6V10640596), Programmable Room Automation - Room Operation (A6V10640597), Programmable
Room Automation - Distributed Functions and Scenes (A6V10640598) and Programmable Room Automation -
Lighting Controls and DALI (A6V10640599).
Topology
Desigo CC
BACnet/IP Ethernet
PXG3.L
BACnet MS/TP Router
DALI
Third-party °C °C C
° C
°
C
°
C
°
devices
°C °C C
° C
°
KNX
iValve
Push button Push button Push button Push button Push
button
QMX3... QMX3... QMX3... QMX3... QMX3...
Room operator units DALI Room operator units Room operator units Room operator units Room operator units
Touch operator units
Third-party devices
AQR25.. Detector AQR25.. Detector AQR25.. Detector AQR25.. Detector AQR25.. Detector
Room sensor Room sensor Room sensor Room sensor Room sensor
Applications
A comprehensive block library for room automation is provided as part the scope of delivery. The library
contains predefined application functions for room climate, lighting, shading, and superimposed room functions.
The applications can be combined with operating and display functions as required. The individual application
functions can be adapted to customer needs and are programmable. The application functions do not depend
on the selected field devices.
See Application Catalog.
Configuration of application functions
Many application functions are preconfigured and available in the library. Retroactive configuration during
engineering or commissioning is possible. Your own configured application functions and entire rooms can be
stored in a project library.
Configuration of field devices
The application architecture does not depend on the field device interface. Field devices can be connected
directly to the PXC3 room automation station (via TX-I/O modules) or via bus (KNX or DALI) or IP
communication.
Many field devices are preconfigured and available in the library. Retroactive configuration during engineering or
commissioning is possible. Project-specific field devices configured accordingly can be saved in a project
library.
QMX3 • • • •
QMX7 • • • • •
Programming • • • • •
Peripheral bus
DALI • • •
Maximum configuration
DALI ballasts 64 64 64
Key
1
Dedicated devices with KNX PL-Link.
2
Total number of data points used by TX-I/O, KNX PL-Link and DALI. For details, see chapter System Configuration.
TX-I/O modules
TX-I/O modules (TXM1) help connect field devices to the PXC3 room automation station. Bus supply and
interface modules (TXS1, TXA1) are available as an accessory.
The following TX-I/O modules can be used with the PXC3 room automation station:
● TXM1.8T: Triac module with 8 outputs (AC 24 V) to control thermal and motorized valve actuators (AC 24 V)
for up to 4 actuators (3-point output) or 8 actuators (permanent contact or pulse width modulation).
● TXM1.6RL: Bistable relay module to switch lighting for up to 6 data points.
● TXM1.8RB: Relay module to control blind motors for up to 2 motors (3 end switches) or 4 motors (2 end
switches).
● TXM1.16D: Digital input modules for up to 16 data points.
● TXM1.8D: Digital input modules for up to 8 data points.
● TXM1.6R: Relay module for up to 6 data points.
● TXM1.8U: Universal module for up to 8 data points.
See TX-I/O Assortment overview (CM2N8170).
Housing
DIN • • •
Flat • • •
Operating voltage
230V • • •
24V • • •
Digital inputs 1 1 1 1 1 2
Universal inputs 2 2 2 2 2 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 8
Pressure sensor 1
Maximum configuration
Key
1
Total number of data points used by TX-I/O, KNX PL-Link and DALI. For details, see chapter System Configuration.
A room segment is the smallest indivisible element. A room comprises at least one or several adjacent room
segments. A room segment is defined and created only once. Room segments are typically combined several
times to rooms over the course of a building's lifecycle.
Various sources are available for forming these central superposed functions:
● External system or third-party device
● System user via BACnet client
● Building user via BACnet client or local operator unit
● Scheduler or reaction program
● Superposed office based on grouping function
They are distributing after evaluating signals and commands via a Grouping function.
One group master exists for each of the various categories which then forwards the resulting information to all
assigned group member (rooms). A group master can for its part be a group member of a superposed group
master.
Desigo CC
PXM20
BACnet/IP
TX-I/O
T
T
KNX/EIB Controller
Common functions:
● Window contact, occupancy sensor, four operating modes
● Manual fan control with room unit
● Automatic fan control (three speeds)
● Options with two-pipe systems: Heating only, cooling or changeover via KNX/EIB bus
Application groups
Similar application types are grouped into application groups. These differ from each other in terms of how the
functions are implemented. Thus chilled ceiling with radiator (CLC02) and chilled ceiling and electric radiator
(CLC03) are two different applications within the CLC group. The first of these two applications uses water for
heating, while the second uses electrical energy. The difference between applications in the other groups
follows a similar pattern.
The following application groups are available for RXB:
● CLC Chilled ceiling applications (not for Synco)
● FNC Fancoil applications
● VAV Variable air volume applications (not for Synco)
Individual applications
The individual application is designed for typical HVAC systems as commonly used in practice in individual
rooms.
Configuring applications
Each application has a defined number of configuration parameters with which the application can be
programmed for a specific project. These parameters consist both of general values (e.g., temperature
setpoints, etc.) and of specific values for the application concerned (e.g., changeover configuration, electric
reheater, etc.).
21 Desigo Open
Desigo Open lets you integrate devices and systems from different manufacturers into the Desigo system.
Integration with Desigo Open offers:
● Standardized automated functions, operating and monitoring of the entire building
● Single-station operation, common view and display. Simplified multidisciplinary operation, common reporting
and common alarm management.
● Peer-to-peer interaction, communication on the automation level, automated interactions and data exchange
● Comfort combined with lower energy consumption. New opportunities to save energy with systems that
communicate among themselves. Improved performance, efficiency evaluation, flexibility and ability to
modify system operation and configuration without re-cabling or new hardware.
● Engineering of integrated solutions in Xworks Plus (XWP)
● Reduced risk thanks to standard solutions. Clear functions that cover the most important standard protocols.
Topology
Third-party devices and systems can be integrated with Desigo on all levels.
Desigo CC
Management level
BACnet/LonTalk or BACnet/IP
Automation level
System conroller
PXC001..D PXC001..D
RS232
RS485
KNX S-Mode / EIB or Bus
Adapter
RXZ97.1/KNX
LONWORKS KNX/EIB Third-party system
Third-party system RXB Third-party system
Room controller
Room level (Desigo room automation and RX) DALI, KNX, EnOcean, LonWorks
SDKs
If a solution is not supported by HQ and RCs need a specific solution, HQ offers Software Development Kits
(SDKs) for experts. The regional companies can develop their own solutions using Software Development Kits
(SDKs).
The following SDKs are available:
● PX Open platform SDK
● TX Open platform SDK
Desigo CC
BACnet
BACnet is a widely used communication protocol for building automation and control networks. It defines a
number of objects, services and data link layers. It is an essential part of Desigo CC's openness for integrating
any third-party devices, using the BACnet/IP protocol. An online auto-discovery and alternatively an offline EDE
import are available for integrating third-party devices.
See BACnet 3rd party Integration Guide (A6V10446271).
BTL
For more information about compliance and interoperability of Desigo products, go to
http://www.bacnetinternational.net/btl and search for Desigo.
Modbus-TCP
A native Modbus-TCP driver lets you integrate a Modbus TCP server and subsequent Modbus RTU devices via
a protocol converter. An offline importer supports the engineering workflow for integrating Modbus data points.
See Modbus Integration Guide (A6V10438039).
OPC
OLE for Process Control (OPC) is a communication standard for exchanging data between windows based
software applications and process control hardware without any proprietary restrictions. It is a client/server
technology, where one application acts as the server providing data, and another acts as a client using data.
The most common specification Data Access (DA) defines a set of objects, interfaces and method to facilitate
the interoperability. OPC has been extended to become a cross-platform communication standard, named OPC
Unified Architecture (OPC UA).
For more information about OPC, see the documentation by the OPC Foundation (www.opcfoundation.org) and
the OPC Training Institute (www.opcti.com).
OPC DA client
An OPC client interface lets you integrate any OPC server, using the Data Access specification. An offline
Importer supports the engineering workflow to integrate OPC items.
See OPC Server Integration Guide (A6V10415483).
OPC DA server
An OPC server option provides a freely configurable set of data points for integration in any enterprise system,
using the OPC DA standard. Each data point (object) is represented by several OPC items, providing the
relevant readable and writable object property information.
See OPC DA Server Manual (A6V10415485).
The Desigo CC OPC server is officially tested and certified by the OPC foundation
(https://opcfoundation.org/products/view/251).
OPC UA server
OPC Unified Architecture (OPC UA) clients can connect to the Desigo CC OPC DA server using the OPC
DA/UA wrapper, provided with the Desigo CC setup. The UA wrapper meets the security model of mutual
authentication for a trusted connection between the OPC UA server and the OPC UA client.
See OPC DA Server Manual (A6V10415485).
SNMP
Simple Network Management Protocol (SNMP) is a data communication protocol for monitoring devices and
applications on a network. It is an Ethernet based protocol for retrieving management data from networked
devices, and exposing this data as properties.
SNMP gives you the capability to monitor a device, e.g., a printer or UPS, which is not directly configured on a
computer, but can be reached through a network link.
Device monitoring capabilities are provided by device manufacturers via a Management Information Base (MIB)
text file, which describes the structure of the device management data. MIB files use a hierarchical namespace
containing object identifiers (OID). Each OID identifies a property that can be read or written via SNMP.
Desigo CC has an SNMP Manager feature for reading and writing information from SNMP agents.
See SNMP Application Guide (A6V10455382).
Web services
Using RESTful technology, Desigo CC provides alarm, object and time series data via web based services for
supervising management platforms or other third-party external applications.
The platform for integrating LonWorks compatible third-party devices consists of:
● System controller PXC00.D and automation station PXC50.D, PXC100.D or PXC200.D for integrating
LonWorks devices via BACnet/LonTalk
● System controller PXC00-E.D and automation station PXC50-E.D, PXC100-E.D or PXC200-E.D for
integrating LonWorks devices via BACnet/IP
● PXX-L11 and PXX-L12 expansion modules for 60 and 120 LonWorks devices
PX KNX
PX KNX connects KNX networks with Desigo and maps the group addresses to BACnet datapoints. PX KNX
can handle the following main tasks:
● Data compression on the automation level (group functions)
● Time control
● Alarming, device monitoring
● Trend storage
● Mapping the Desigo RXB applications to BACnet for operating and monitoring
PX KNX supports the integration of:
● KNX S mode third-party devices
● RDF, RDG and RDU room thermostats
● RXB room automation stations
The PXC001.D system controller can integrate KNX via BACnet/LonTalk. The PXC001-E.D system controller
can integrate KNX via BACnet/IP. PX KNX is preinstalled on PXC001..D controllers.
PX Modbus
PX Modbus connects Modbus devices or networks supporting the Modbus protocol to the Desigo system and
maps their data points to BACnet data points. PX Modbus is particularly suitable for integrating industrial
controls or chillers and linking them to the automation process.
The PXC001.D system controller can integrate Modbus via BACnet/LonTalk. The PXC001-E.D system
controller can integrate Modbus via BACnet/IP. The PXA40-RS1 and PXA40-RS2 option modules support
additional data points.
See PX Modbus (CA2N9772).
PX M-Bus
PX M-Bus connects the M-Bus consumption meters to the Desigo system and maps meter readings and device-
related meter information to BACnet data points. PX M-Bus handles the following main activities:
● Measurement of consumption data and remote monitoring of max. 250 consumption and heat meters
● Compression of data from consumption and heat meters at the automation level
● Alarm handling, device monitoring
● Trend storage to record meter readings
The PXC001.D system controller can integrate M-Bus via BACnet/LonTalk. The PXC001-E.D system controller
can integrate M-Bus via BACnet/IP. The PXA40-RS1 and PXA40-RS2 option modules support additional data
points.
See PX M-Bus (CM2N9774).
PX SCL
PX SCL lets you quickly develop simple protocol solutions. The script control language from XWP is used with
an interpretable environment and lets engineers create a solution. The solution cannot be used for complex
protocols and solutions. It is used to develop other applications, such as local serial printer driver and pager
applications.
The PXC001.D system controller can integrate SCL via BACnet/LonTalk. The PXC001-E.D system controller
can integrate SCL via BACnet/IP. The PXA40-RS1 and PXA40-RS2 option modules support additional data
points.
The regional companies develop the necessary protocols themselves.
The hotel management system Fidelio can be integrated into Desigo via PX SCL.
See PX SCL (CA2N9773).
PX LON
PX LON connects LonWorks networks to Desigo and maps Standard Network Variables (SNVT) to BACnet data
points. The main functions of PX LON are:
● Higher-level control and optimization functions, such as room and zone-based groups, time control, and
system functions, such as changeover, summer/winter compensation, etc.
● Alarm handling, device monitoring
● Trend storage
The PXC00.D system controller and the PXC50.D, PXC100.D and PXC200D automation stations can integrate
LonWorks devices via BACnet/LonTalk. The PXC00-E.D system controller and the PXC50-E.D, PXC100-E.D
and PXC200-E.D automation stations can integrate LonWorks devices via BACnet/IP. With the PXX-L11 and
PXX-L12 expansion modules you can connect 60 and 120 devices.
PX Open Platform SDK
HQ provides the PX Open Platform Software Development Kit (SDK) for experts in the regional companies.
22 System configuration
System overview
Desigo CC
Internet
BACnet/IP
PX Site PX Site
System System-
PXC..D PXC..D function function
group group
PXC3 PXC3
DXR2 DXR2
BACnet/IPv4
BACnet/IPv6
PX Site
PXG3.Wxxx-1 PXG3.L
BACnet MS/TP
BACnet/LonTalk
(remote)
PX Site
PXG3.Wxxx-1
Desigo system
Covers all the devices on the MLN (Management Level Network), ALN (Automation Level Network) and FLN
(Field Level Network).
One Desigo system may comprise several BACnet internetworks. These are connected into a system with
Desigo CC. In this case, Desigo CC appears as a BACnet device in several BACnet internetworks.
BACnet internetwork
A BACnet internetwork consists of one or several BACnet networks. Individual BACnet networks are connected
to BACnet routers.
Each BACnet device can communicate with another BACnet device in the internetwork. A BACnet device in one
internetwork cannot communicate with a device in another internetwork.
A Desigo management station can be used to integrate the operation of several BACnet internetworks and other
systems (see Desigo system).
When defining the system configuration, FLN integrations (LonWorks, KNX) are also added to the BACnet
internetwork. In this way, the Desigo system can be seen as a combination of several BACnet internetworks.
Technically, the individual FLN devices are not BACnet devices. They do not communicate via the BACnet
protocol.
BACnet network
A quantity of BACnet devices connected within an IP or LonTalk or MS/TP network with specific (that means,
the devices are in the same BACnet Broadcast Domain) limits. In the case of the LonTalk or MS/TP network,
the limit is physical. In the case of an IP network, the network can be physically the same, but the limit is
determined by different UDP ports.
Local communication between two BACnet devices in a BACnet network is not visible in another BACnet
network.
IP segment
Sub-area of an IP network. IP segments are connected by IP routers.
In order to ensure that BACnet communications (Broadcasts) can always take place across IP routers, BBMDs
(BACnet Broadcast Management Devices) are required. PXG3.L/M and PXC…-E.D over IP can be configured
as BBMDs. Individual BACnet devices in an IP segment can register with a BBMD as foreign devices.
PX KNX integration
Comprises the integration of KNX devices that are connected on the FLN side of the PXC001.D/-E.D.
PX site
A Desigo PX automation system site.
The PX BACnet devices which control the plant in a PX site are interconnected via the global objects and the
primary copy procedure.
A PX site is independent of the limits affecting the BACnet network. A site can extend over several BACnet
networks. One BACnet network may include several sites. All the associated limits must be maintained
simultaneously.
A PX site cannot be extended beyond the limits of a BACnet internetwork. This is particularly important in the
case of BACnet PTP internetworks.
PX plant
A PX plant is part of a PX site and generally comprises several partial plants (plant structure).
A PX plant can be distributed over several PX BACnet devices. In principle PX BACnet devices can be
distributed to different BACnet networks. However, owing to the communications load between partial plants,
this is not recommended.
The plant structure is mapped to BACnet by means of hierarchy objects. Operator units with generic operation
automatically read this structure.
BACnet MS/TP
A BACnet MS/TP network is a BACnet network that is physically based on EIA-485 and operated using a
BACnet-specific MasterSlave/TokenPassing data link protocol (see BACnet standard clause 9). An MS/TP
network is linked via a BACnet router to a BACnet/IP or BACnet/LonTalk network.
PX system functions
A PXC.. of a PX site as PX system function can assume Desigo room automation subsystem functions such as
scheduling, life check, time synchronization for a Desigo room automation system function group for BACnet
devices for room automation.
BACnet internetwork 200 n/a n/a n/a n/a n/a n/a n/a
18
BACnet PTP internetwork 1 n/a n/a n/a n/a n/a n/a n/a
19
BACnet/IP network n/a 10 [50*] [1] n/a n/a n/a n/a [total 20]
BACnet MS/TP network n/a [50] n/a 8 n/a n/a n/a n/a
PXG3.M/L (BACnet router) n/a [100] [30] [100] 1 1 n/a n/a n/a
IP segment n/a 10 [50*] 6 [50*] 6 10 [50*] 6 n/a n/a n/a n/a n/a
LonWorks segment (ALN) n/a [100] [30] n/a n/a 1 n/a n/a n/a
PX plant [4,000] [2,000] [60] n/a n/a n/a n/a n/a 100
LonWorks trunk (FLN) [200] [100] [30] n/a n/a n/a n/a [50]
LonWorks segment (FLN) n/a n/a n/a n/a n/a n/a [5] n/a [250]
PX KNX integration [200] [100] [30] n/a n/a n/a n/a [50]
Desigo devices
PX… without DXR2/PXC315 [2,000] [1,000]9 [30] [200]8 n/a 30 n/a n/a 50/10017
PXC3.E (Desigo room (10,000)16 [1,500] n/a 25023 n/a n/a n/a n/a n/a15
automation) (2,500) [500]24
DXR214 (Desigo room (10,000)16 [1,500] n/a 25023 6421 n/a n/a n/a n/a15
automation) (2,500) [500]24
DXR1 (Desigo room (10,000)16 [1,500] n/a 10023 6421 n/a n/a n/a n/a15
automation) (2,500) [500]24
Desigo Xworks Plus (XWP) n/a [10] [10] [10] n/a [5] n/a n/a total 1510
(commissioning)12
Total LonWorks nodes [40,000] [20,000] [6,000] n/a n/a n/a 3002 n/a [10,000]
4
RXB [8,000] [2,000] [1,200] n/a n/a n/a n/a 45 [2,000]
Physical data points [100,000] [100,000] [3,000] [20,000] n/a n/a n/a n/a [6,000]
Total BACnet objects [500,000] [100,000] [30,000] [100,000] [3,000] [30,000] n/a n/a [50,000]
Trendlog object [30,000] [2,500] [200] [2,500] [540] [600] n/a n/a [1,000]
Key
n/a
Not applicable.
–
No restrictions.
2
Not the same as the number of integrated devices ( PXC00.D/-E.D + PXX-L…).
3
LonWorks routers must not be used at the automation level.
4
Limit applies only if this device type is used exclusively.
6
For higher performance use a PXG3 instead of a PXC-E.D for the BBMD function.
7a
Limit for PXC00.D/-E.D + PXX-L11.
7b
Limit for PXC00.D/-E.D + PXX-L12.
8
Limit for PX devices without Desigo room automation. Do not exceed the number of PXC devices per site.
9
The limit on the number of PX automation stations per internetwork can only be maintained if no PX clients are used. PX clients
limit the permissible number of PX per internetwork. The values can be obtained by reference to the relevant automation station
columns. The restricted view option does not affect the system configuration of PX clients.
10
The number of temporary alarm receivers in a PX is a technical limit. The recommended limit is lower. This takes account of the
fact that additional devices may be connected for service purposes.
11
The number of temporary alarm receivers in a PX is a technical limit. The recommended limit is lower. This takes account of the
fact that additional alarm receivers (third-party) may have entries in this list.
12
Parallel engineering (commissioning ) is possible subject to the following restrictions:
- Node setup: Only one XWP per LonTalk/IP segment.
- Download and online operation: only one XWP for each automation station.
14
In pressurized rooms with or without fume hood, all automation stations of a room must be connected to a switch in a starlike
manner to ensure high availability.
15
Desigo room automation stations do not belong to a PX site (no primary copy function).
16
For the system configurations of the Desigo CC management platform, see Desigo CC System Description (A6V10415500).
17
50: If Lon PX exists in the PX site. 100: If no Lon PX exist in the PX site (only IP PX).
18
These limits in the Desigo system refer in particular to Desigo Insight. The limits may be significantly lower due to the PTP
connection(s) outside the Desigo system and their technical limitations. Examples of such limitations outside the Desigo system
can include available bandwidth for the PTP link or available modem speeds.
19
This limit can be exceeded if all BACnet devices are located within the same IP subnetwork, or if no communication between the
various BACnet/IP networks is required.
20
These limits apply only to IP-based DXR2 devices.
21
These limits apply to MS/TP-based DXR2 devices.
23
Multiple IP segments per BACnet internetwork.
24
One IP segment per BACnet internetwork.
For more information about networks, see Application Guide for IP Networks in Building Automation Systems
(CM110668).
Number of external BACnet references 500 Maximum number of external BACnet references that support a
Desigo room automation system function PX. The Desigo room
automation system function PX requires external references for the
life check and for scheduler functions. Examples of objects with
external references:
- EventEnrollment: 1reference
- Schedule: 1-5 references
Event enrollment per Desigo room automation 1 Number of event enrollment objects required on the Desigo room
station automation system functions PX for the life check per Desigo room
automation station.
Sample number of Desigo room automation 250 Desigo room automation system function PX with maximum scheduler
stations per Desigo room automation system functions.
function group The limit designates the maximum number of Desigo room automation
stations in the Desigo room automation system function group. In this
example, it is assumed that the following scheduler objects are
available on the Desigo room automation system function PX:
- Maximum number of scheduler objects
- Per scheduler object, maximum number of external references
Sample number of Desigo room automation 500 Desigo room automation system function PX without scheduler
stations per Desigo room automation system functions.
function group The limit designates the maximum number of Desigo room automation
stations on the Desigo room automation system function group. In this
example, it is assumed that no scheduler objects are available on the
Desigo room automation system function PX.
22.4 Devices
Total BACnet [4,000] [4,000] [4,000] [4,000] [4,000] [4,000] [4,000] [4,000]
objects
Trend log5 100 100 100 200 350 200 600 100
Trend log 20 20 20 20 20 20 20 20
multiple19
Calendar14 10 10 50 50 50 50 50 50
PXM10 1 1 1 1 1 1 1 n/a
Physical data n/a n/a 52* 200* 15 (350)15 n/a n/a n/a
points TX-I/O +
PTM
Total number of n/a 400* 400* 600* 15 (1,000)15 n/a n/a n/a
data points
onboard + TX-
I/O + PTM + TX
Open
Dynamic event 50* 50* 50* 50* 50* 50* 50* 50*
enrollment
objects20
Dynamic trend 100* 100* 100* 100* 100* 100* 100* 100*
log objects20
Dynamic trend 20* 20* 20* 20* 20* 20* 20* 20*
log multiple
objects20
Key
1
PXM20, PX-Web and XWP are temporary alarm receivers.
2
Desigo CC is a configured alarm receiver. The number of entries in the notification class is limited to 20. The total number of
different configured alarm receivers across all notification classes is limited to 30.
3
Max. number of BACnet references, COV servers: SubscribeCOV requests which can be accepted. Example: 1400: 1 client and
1400 values or 2 clients and 700 values.
4
Max. number of BACnet references, COV client resources, i.e. values read from or written to (commanded) your own automation
station or a remote automation station.
BACnet client references are used in Input, Output, Scheduler, Trendlog and Group objects (all NameRef_Type inputs with
AddrKind = B). The configured alarm receivers of the Notification Class objects do NOT require any BACnet client references.
The available number of BACnet client references shall address not more than 50 different remote automation stations. If this value
is exceeded the number of BACnet broadcast messages on the network will increase.
Example: 400: 1 client and 400 values or 2 clients and 200 values.
5
Every active Trendlog object needs a BACnet reference.
Trends need 12 bytes per entry (irrespective of data type). Max. 64 KB can be allocated to the log buffer (approx. 5,000 entries) for
each Trendlog object. These log buffers are assigned in D-MAP RAM. If the log buffer size is changed and there is insufficient D-
MAP RAM available, the Reliability property of the Trendlog object is set to Memory limit reached.
8
The address of the PPS-2 devices QAX84.1 and RXZ90.1 is always 1 (no address selection).
9
PX KNX = PXC001.D / PXC001-E.D and loaded PX KNX firmware.
10
PX Open = PXC001.D / PXC001-E.D with option module PXA40-RS1/RS2 and loaded PX Open firmware.
14
Maximum 30 calendar entries.
15
The number of physical data points influences the reaction time of the application. If minimum reaction times are specified, the
number of physical data points may have to be reduced.
The following relationship between reaction times and the number of physical data points can be assumed:
- up to 150 physical data points = Reaction times < 1s
- up to 250 physical data points = Reaction times 1…2 s
- up to 350 physical data points = Reaction times 2…3 s
17
Number of switching times per day: 10; max. 5 BACnet references.
18
Number of switching times per day: 20; max. 5 BACnet references.
19
Every active trendlog multiple object needs a BACnet reference per logged value.
5 logged values are assumed for the number of trendlog multiple objects (number of Trendlog / 5).
Trends need 12 bytes per entry (irrespective of data type).
Max. 64 KB can be allocated to the log buffer (approx. 5,000 entries) for each trendlog object.
These log buffers are assigned in D-MAP RAM.
If the log buffer size is changed and there is insufficient D-MAP RAM available, the Reliability property of the Trendlog object is set
to Memory limit reached.
20
Dynamic objects are counted the same as non-dynamic objects for total limits.
21
Limits of the PXX-PBUS extension module:
- DB (Function blocks instances): 1500
- Trends: 100
- Local BACnet references. 100
22
To prevent high cycle times of the PXX-PBUS extension module:
- Only use PXC100-(E).D controllers together with PXX-PBUS; Do not use PXC 200 controllers.
- Do not connect PXX-L11 or PXX-L12 or PX Web modules (WO-W2) together with PXX-PBUS on the same controller.
- Do not use WebServer functionality on PXC, when using PXX-PBUS.
- Do not extend existing applications from PXC128-U or PXC64-U with new functionality.
D-MAP RAM
If the whole D-MAP RAM is taken up with trendlog objects, a delta (differential) download will no longer be
possible.
The overall size of the free and used D-MAP RAM can be viewed with XWP, Desigo CC or PXM20. The
information concerned is stored in the device object under the memory statistics property [MemStc].
Item Limit
LonWorks devices:
PXX-L11 60* (e.g.: 5 Group Members are defined, that means 5 x 12 = 60 COV resources are needed)
PXX-L12 120*
Max. number of integrated LonWorks devices covers third-party LonWorks devices.
Group members Cross-disciplinary groups can have more than 5 destinations. The number of cross-disciplinary groups
depends on the COV client resources (max. 250). A different number of COVs is required, depending
on the group type. These must be multiplied by the number of destinations.
Calculation basis:
Reaction times depending on number Without LonWorks devices Up to 5 LonWorks devices 5 to 20 LonWorks devices
of physical data points
Max. 150 data points < 1s 1-2s 3-4s
SCL data points [250*] Max. number of data points per PX SCL.
M-bus data points [250*] Max. number of data points per PX M-bus.
SCL data points [800*] Max. number of data points per PX SCL.
M-bus data points [800*] Max. number of data points per PX M-bus.
SCL data points [1,000*] Max. number of data points per PX SCL.
M-bus data points [2,000*] Max. number of data points per PX M-bus.
RXB 45 Max. number of RXB devices per KNX (approx. 50 KNX data points
per RXB, depending on the application).
TXM1.8RB 8 I/O blinds modules max. 8 Used TX-I/Os are counted (1 data point per
relay).
TXM1.8U 8 I/O universal modules (DI, AI, AO) max. 8 Used TX-I/Os are counted.
TXM1.8D 8 I/O digital input modules max. 8 Used TX-I/Os are counted.
TXM1.16D 16 I/O digital input modules max. 16 Used TX-I/Os are counted.
AQR253… Flush-mounted room sensor with: 1-3 Fixed count, 1 data point per measured value
AQR257… Front module (optional potential-free, passive NTC sensors
are not counted)
Base module
ASN Physical TX-I/O data points used Total I/O data points (TX-I/O, DALI, KNX PL-Link)
PXC3.E16A n/a 64
PXC3.E72 72 140
PXC3.E72A 72 140
Templates with standard background pictures2 6 Maximum number of different templates which are using the default
background pictures.
Customized background pictures2 1.5 MB Maximum total size of all customized background pictures (the PNG
file format is used as a reference).
Key
1
Restriction: When using standard web clients (web browser on PCs, smart phones, tablets, etc.), the screen display and operation
(touch or mouse) are neither modified nor tested for the available browsers.
2
Valid values when using 8 room applications at the boundary of maximum system limits.
DXR1.E02PLZ- 2 n/a
112
DXR1.M04PDZ- n/a 2 UI
112
Key
a1
Total Number of PL-Link data points (under unconfigured status): 36
a2
Activate all selectable PL-Link devices, then check the maximum number of PL-Link data points: 12
b1
Total Number of PL-Link data points (under unconfigured status): 28
b2
Activate all selectable PL-Link devices, then check the maximum number of PL-Link data points: 9
Templates with standard background pictures2 2 Maximum number of different templates which are using the default
background pictures.
Customized background pictures2 1.5 MB Maximum total size of all customized background pictures (the PNG
file format is used as a reference).
Key
1
Restriction: When using standard web clients (web browser on PCs, smart phones, tablets, etc.), the screen display and operation
(touch or mouse) are neither modified nor tested for the available browsers.
2
Valid values when using 8 room applications at the boundary of maximum system limits.
Alarm administration Only the alarms from the site where the user is logged on are
displayed (PXM20 self-registers as temporary alarm recipient for all
devices of a site).
BACnet objects in alarm per site 50* Maximum number of BACnet objects per site.
The administration of the number of BACnet objects in alarm per site
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
Alarm History 50* Maximum number of entries in the Alarm History. The oldest entries
are deleted when this limit is exceeded.
Alarm administration Management of the alarms of the PXC to which the PXM10 is
connected.
BACnet objects in alarm per PXC 25* Max. number of BACnet objects in alarm per PXC.
The management of the number of BACnet objects in alarm per PXC
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
Online trends 20 20 20 50
Memory requirements
Max. number of plant graphics at 300 kB each 6,000 kB 6,000 kB 6,000 kB 15,000 kB
(20 graphics) (20 graphics) (20 graphics) (50 graphics)
Alarm history - 10,000 entries 5,000 kB 5,000 kB 5,000 kB 5,000 kB
PXG3.W200-2 800 60 20
PXM30.E 200 15 5
PXM40.E 400 30 10
PXM50.E 400 30 10
* The selection of integrated data points can be optimized and individually customized with the Advanced Tool in the data point
integration function.
** Primary plants: Per hardware I/O some 2.5 BACnet objects are integrated on average.
Trend export: Max. number of entries per trend 10,000 10,000 10,000
*) see specific MSTP and LonWorks section for more specific limitations
1
5 is the recommended number. More clients can be connected, but performance deteriorates when the same operations are
performed simultaneously. Example: Simultaneous load of the same plant graphic to 10 clients.
2
Trend data management must be configured according as part of the online trend configuration.
10,000 trend entries can be recorded from:
● 1 trend entry daily over a minimum of 25 years
● 1 trend entry every hour over a minimum of 1 year
● 1 trend entry every 15 minutes over a minimum of 3 months
3
The time to read a BACnet trendlog object depends on the number of entries and the data link.
Desigo Control Point is optimized for BACnet/IP devices which are supporting COV communication. The objects
of an assigned device will automatically be polled if the device does not support COV. Polling causes a higher
network communication load. This can decrease the overall performance of the Desigo Control Point device,
depending on the BACnet device and on the type of communication (MS/TP, LonWorks). Such topologies must
be tested individually and project specifically.
The following limits and constraints must be considered if the MS/TP devices do not support COV, i.e. only
polling:
● Disable the list view core function (user profile setting in ABT Site)
● Limit to one concurrent operating client (limit your network topology)
● Set baud rate to 38400 or higher
FDT (Foreign Device Table) [50*] Maximum number of foreign devices which can register with the
BACnet router.
Desigo CC in a remote IP segment counts as a foreign device.
Ethernet bit rate 10/100 Mbit/s The router supports 10/100 Mbps.
MS/TP telegrams [100 - 140] pkt/s The BACnet router integrates BACnet MS/TP not as a field bus in the
@115,200 bps network. The router operates transparently and routes all data traffic
[-120] pkt/s addressed to the subnet. This is why global broadcast telegrams
@76,800 bps negatively impact transmission performance of the router and end
devices.
Max. [~4,5] KB/s
Recommendation: Do not carry out time and security-critical process
controls using BACnet MS/TP.
Depends on baudrate, number of nodes and maximum number of
data frames (N max_info_frames).
BACnet/LonTalk [100 - 120] pkt/s The BACnet router integrates one (1) BACnet/LonTalk network. The
@78 KB/s router operates transparently. The same restrictions apply to global
Max. [~4,5] KB/s broadcast telegrams as for MS/TP.
BACnet/IPv4 [~2500] pkt/s The BACnet router can route between two BACnet/IP networks. The
Max. [~500] KB/s BACnet/IP networks have different UDP ports.
BACnet/IPv6 1 The BACnet router integrates one (1) BACnet/IPv6 network. The
router works transparent, but when connection ports for BACnet/IPv4
and BACnet/IPv6 are used simultaneously, make sure that no
unintentional ethernet loops are created on the IT side.
22.4.17 SX OPC
Item Limit Description
SX OPC applications 1 SX OPC application per PC. The performance depends on the PC
hardware.
OPC server [10] Max. number; OPC data access 2.x or 3.0 specification.
Alarm-generating objects [2,000] Alarm-generating objects (of total 20,000 BACnet objects).
1
SX BACnet references client resources [1,000]
Key
1
Max. number of BACnet client connections (COF or polling), that is, values read from or written to (commanded) the own
automation station or a remote automation station.
BACnet client connections are used in Input, Output, Scheduler, Trendlog and Group objects (all NameRef_Type inputs with
AddrKind = B). The configured alarm receivers of the Notification Class objects do NOT require any BACnet client references.
The available number of BACnet client references does not address more than 50 different remote automation stations.
22.4.18 Desigo CC
For the system configurations of the Desigo CC management platform, see Desigo CC System Description
(A6V10415500).
Number of XWP per BACnet internetwork 10 Parallel engineering is possible under the following limitations:
(parallel engineering) Node setup: Only one XWP per LonWorks/IP segment.
Download and online operation: Only one XWP per automation
station.
Number of I/O function block instance per 200 The number of I/O function block instances are limited per plan
plan (compound). Mapping of function blocks on BACnet sets the limit. The
limit is lower for other function blocks mapped to BACnet.
22.5 Applications
Cycle time [ms] 500 Minimum cycle time required to ensure the functioning of the PDL
application.
To guarantee the cycle time, use a PX modular automation station
(PXC 100/200…D, PXC12/22/36…D).
Do not use the the automation station with the PDL application to
control any other plant.
The PDL application must be confined to one automation station only.
Limit control is binary only (enabled/disabled). Step control (Stage1,
Stage2, Stage3) or modulating control (0…100%) is not possible.
Commissioning and operation are only possible with XWP.
There is no provision for backward compatibility with future PDL
applications.
23 Compatibility
For information on the system compatibility of the Desigo CC management platform, see Desigo CC System
Description (A6V10415500).
For information on the system compatibility of the Desigo Insight management station V6.0 SP2, see Desigo
Building Automation System 6.0 SP, Technical Principles (CM110664 / 2016-09-20).
For the current state of the Valid Version Set (VVS), see the document Desigo_VVS_6.10.48x.pdf.
Glossary
Term Description
Project data Desigo engineering and project data required to create runtime systems, but that are no longer
needed for operation (offline data).
Runtime system Firmware (loaded) installed on the hardware of the customer plant or software with compiled
project data including libraries (online data).
New New Desigo customer project with no Desigo runtime system and project data.
Extension Existing plant or installation (existing Desigo runtime system with project data) that is being
expanded or extended (e.g., additional buildings).
Migration Replacement of existing plant or installation (existing Desigo / Visonik / Unigyr / Integral runtime
system with project data) by new technology with a change of software and/or hardware.
Upgrade Functional improvement to existing plant or installation (existing Desigo runtime system with
project data) by deploying developments for a new Desigo system version.
Update Existing plant or installation (existing Desigo runtime system with project data) is updated within
the same version (e.g., to eliminate errors with a service pack).
Project data conversion Online Desigo project data from earlier Desigo versions are migrated to the current ABT/XWP
version when opened in ABT/XWP.
During conversion, the existing database structure and/or associated tool landscape is migrated to
the latest version. A conversion always impacts all project data of a tool project.
The project data and libraries remain unchanged. The runtime system (online project data) does
not change, that is, the original version status remains as is.
● Desigo V5.1
● Desigo V6.0
● Desigo V6.1
● Desigo V6.2
● Desigo V6.2 Update
● Desigo V6.2 Update 2
● Desigo V6.2 Update 3
● Desigo V6.2 Update 4
3
2
Key
① Desigo CC
Properties from earlier BACnet protocol revisions can be read by a BACnet device even if the device supports a higher BACnet
protocol revision than Desigo CC.
New properties from a BACnet protocol revision higher than Desigo CC cannot be read or changed, because they are not
recognized by Desigo CC.
The BACnet client ensures the backwards compatibility. Desigo CC should thus have a BACnet revision that is
at least the same as all of its connected BACnet servers.
Usually, BACnet devices of a specific BACnet protocol revision fully support earlier revision functions. However,
since this is not true in all cases, we recommend that you verify the compatibility in each case.
For an overview of the BACnet functions supported in Desigo, see BACnet Protocol Implementation
Conformance Statement (PICS) (CM110665).
Compatibility Desigo CC
For information on the system compatibility of the Desigo CC management platform, see Desigo CC System
Description (A6V10415500).
64-bit
XWP Yes*
ABT Site / ABT Pro Yes*
RXT10.5 Yes*
Unlisted Microsoft server operating systems/editions are not supported. They can, however, be used for stand-
alone SQL servers and file hosts.
Note
Windows Server 2012 and 2012 R2 support
Microsoft has officially announced the end of support for Windows Server 2012 and 2012 R2 for October 10th
2023. Therefore, tools on Windows Server 2012 and 2012 R2 will no longer be supported after that date. We
recommend using Windows Server 2016 or any of the other compatible operating systems instead.
Key
1
Support of of HTML5-capable browsers with native SVG format.
Desigo CC
For notes on Desigo CC web client running in a browser shell, see Desigo CC System Description
(A6V10415500).
* Do not minimize ABT Go and make sure the device remains unlocked for longer running tasks such as
generating a report.
For Android devices download ABT Go from the Google Play Store:
https://play.google.com/store/apps/details?id=com.siemens.abtgo&hl=en
For iOS devices download ABT Go from the Apple Store:
https://itunes.apple.com/app/abt-go/id1293043551?l=en&ls=1&mt=8
Restrictions
As soon as an automation station or a system controller with the newest Desigo firmware is used in a runtime
system, all operating clients and Desigo Control Point must be upgraded to the same version. Otherwise, only
limited operation is available.
Not all Desigo PX devices in the field can be upgraded to the newest firmware version.
For information on the hardware and firmware compatibility of the Desigo CC management platform, see Desigo
CC System Description (A6V1041550).
TX-I/O
A firmware update or upgrade from TX-I/O modules is not possible (except for TXI1.OPEN, TXI2.OPEN, and
TXI2-S.OPEN).
To load firmware, protocol applications, and the configuration to the TX Open modules, use the TX Open Tool,
which is available as a part of XWP.
See Desigo Xworks Plus Online Help (CM111006).
Restrictions
After upgrading Desigo project data for a Desigo software product to the newest version, the data can only be
accessed or processed with the appropriate software/LibSets for the newest version.
Key
1
Directly switched lighting applications (by the user) are not supported by the PXC..D automation stations. For this reason, the
configured button function of the digital input modules is not available together with the PXC…D automation stations.
23
23.2.17 KNX PL-Link devices in ABT Site and ABT Pro
Compatibility
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Acvatix Valve actuator GDB111.9E/K 6-way valve 5 mA 1 V4.0 V4.0 V4.0 V4.0 No No
N actuator (5 Nm
non-spring
return)
return)
Desigo I/O block RXM39.1 PL-Link I/O 5 mA 5 V4.0 V4.0 V4.0 V4.0 No No
blocks for fan
coil units
Desigo Room unit QMX2.P33 QMX2 wall 10 mA 3 V4.0 V4.0 V4.0 V4.0 No V4.1
with display &
T: without
Green Leaf
CM110664en_10
and KNX S-
Mode
CM110664en_10
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Desigo Room unit QMX2.P43 QMX2 wall 10 mA 4 V4.0 V4.0 V4.0 V4.0 No V4.1
with display &
T, rH: without
Green Leaf
and KNX S-
Mode
Desigo Room unit QMX3.P02 QMX3 wall 8 mA 5 V4.0 V4.0 V4.0 V4.0 No No
with switches
Compatibility
operator unit,
wall-mounted
lighting,
shading
23
326 | 346
23
Supported workflows
Room automation (without Critical Environment) Critical Environment
Compatibility
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Desigo Room unit QMX3.P40 Room operator 8 mA 2 V4.0 V4.0 V4.0 V4.0 No No
unit without
display, with
temperature
and humidity
sensor
configurable
operator unit,
wall-mounted
Desigo Room unit QMX3.P87 Freely 8 mA 3 V4.0 V4.0 N/A N/A V4.0 V4.0
configurable
operator unit,
wall-mounted
(fume hood)
Desigo Room unit QMX3.P88 Freely 8 mA 3 V4.0 V4.0 N/A N/A V4.0 V4.0
configurable
operator unit,
flush-mounted
CM110664en_10
(fume hood)
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Blind actuator N 543D31 Blind actuator: N/A 4 V4.1 V4.1 No No No No
4 channels
actuator, 6A,
AC 230V
Gamma Input JB 260C23 4-fold binary N/A N/A V4.0 V4.0 V4.0 V4.0 No No
input,
AC/DC12...230
V
Gamma Input RL 260/23 4-fold binary N/A 4 V4.0 V4.0 V4.0 V4.0 No No
input,
Compatibility
AC/DC12...230
V
dimmer,
1x125VA
23
(AC120V)
328 | 346
23
Supported workflows
Room automation (without Critical Environment) Critical Environment
Compatibility
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Light dim JB 526C23 2 channel 10 mA 2 V4.0 V4.0 V4.0 V4.0 No No
actuator 1...10V
dimmer with
relay output
2x DALI,
broadcast
Gamma Light dim N 528C01 DIN rail 2- N/A N/A V4.0 V4.0 V4.0 V4.0 No No
actuator channel
universal
lighting
dimmer (incl.
LED dimming),
UL
Gamma Light dim N 528D01 Universal N/A 2 V4.0 V4.0 V4.0 V4.0 No No
actuator dimmer, 2 x
300 VA, AC
230 V
1...10V
dimmer with
relay output
CM110664en_10
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Light dim N 536D51 Switching/Dim N/A 8 V4.0 V4.1.1 No No No No
actuator ming actuator
8 channel,
1...10V
dimmer with
relay output
Gamma Light dim N 554D31 Universal 7.5 mA 4 V3.2 V4.0 V4.0 V4.0 No No
actuator dimmer, 4 x
300 VA / 1x
1000 VA, AC
230 V
Compatibility
actuator light. dimmer,
1x 250VA, AC
230V
2x10A (AC
120V/AC
23
277V)
330 | 346
23
Supported workflows
Room automation (without Critical Environment) Critical Environment
Compatibility
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Light switch JB 512C23 1x light 10 mA 1 V4.0 V4.0 V4.0 V4.0 No No
actuator switching
actuator,
1x20A or
1x15A (AC
120V / AC
277V or AC
347V)
120V / AC
277V)
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Light switch UP 510/13 2x lights 10 mA 2 V4.0 V4.0 V4.0 V4.0 No No
switching
actuator,
2x10A, AC
230V
(quadruple)
Gamma Push button UP 22x Delta i-system 9 mA 2, 4, 6 V4.0 V4.0 V4.0 V4.0 No Partially from
push button: Desigo Room
Compatibility
UP 221 Automation
(single), UP
222 (double),
UP 223 (triple)
331 | 346
23
332 | 346
23
Supported workflows
Room automation (without Critical Environment) Critical Environment
Compatibility
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Push button UP 28x Delta style 9 mA 2, 4, 8 V4.0 V4.0 V4.0 V4.0 No Partially from
push button: Desigo Room
UP 285 Automation
(single), UP
286 (double),
UP 287
(quadruple)
detector &
brightness
sensor
(product phase
out at the end
of 2016)
Gamma Sensor UP 258D12 Presence N/A N/A V4.0 V4.0 V4.0 V4.0 V4.0 V4.0
detector &
brightness
sensor,
successor of
UP258D11
Supported workflows
Room automation (without Critical Environment) Critical Environment
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
Gamma Sensor UP 258D51 Presence 30 mA 5 V4.0 V4.0 No No No No
detector,
brightness, T,
rH., CO2
sensor WIDE
multi
Compatibility
Gamma Switch N 53xD Switching N/A 4, 8, 12 V3.2 V4.0 V4.0 V4.0 No No
actuator actuator 9
types: 4 / 8 /
12 channels
333 | 346
23
334 | 346
23
Supported workflows
Room automation (without Critical Environment) Critical Environment
Compatibility
ABT Pro version or higher ABT Site ABT Pro ABT Site
version or version or version or
higher higher higher
Product Product ASN Description PL-Link Data points Hardware As one Fully In application Fully Application
portfolio group power catalog instance in integrated in types integrated in types
consumption application application application
library library library
OpenAir Damper GDB111.1E/K Damper 5 mA 2 V4.0 V4.1 No No No No
actuator N actuator 5 Nm,
non-spring
return, AC 24
V, 150s
spring return,
AC 24 V, 150s
base module
Compatibility 23
Desigo Control Point
PXM20-E PXM30.E
PXM40 PXM40-1
PXM50 PXM50-1
PXM20-E
PXM20-E PXM30.E
● The dimensions for the cut out are the same as for mounting in the panel.
● Supply voltage AC/DC 24 V.
● Ethernet connection for communication.
● No Power over Ethernet (PoE) connection on PXM30.E.
PX web
PXA40-W0
PXA40-W1 PXG3.Wx00-2
PXA40-W2
● PX web graphics are not compatible with graphics for the new web interfaces PXG3.Wx00-1 and -2.
● No workflow is currently available to automate migration of PX web graphics.
● New graphics can be efficiently created, based on templates or existing graphics.
PXG3.W100 PXG3.Wx00-2
FW Update
① Same dimensions for the cut out as for mounting in the panel
Supply voltage AC/DC 24 V
Ethernet connection
Similar look and feel
② PXM40-1 and PXM50-1 panels are backward compatible with PXG3.W100 (PXG3.W100 FW updated required).
③ Existing PXM40 and PXM50 panels are not compatible with the PXG3.Wx00-1 and PXG3.Wx00-2 devices.
④ Engineering data, including graphics are not compatible with the new web interface.
Grade C Firefox
Partially compatible standard Internet Explorer 11
web browsers.
All web browsers on iOS devices
● Minimally tested browsers.
● Not supported with Desigo Control Point.
● Access to the web server is possible in principle.
* Chrome remains automatically on https when visiting an HTTPS page. It must be manually switched back to http to work with
Desigo Control Point.
Desigo software
All Desigo software programs and LibSets (LED) operate on the Siemens WEoF client.
Permanent Open User Desigo Xworks Plus (XWP) including PX firmware library (FW), Automation Building
Tool (ABT) and additional tools
Permanent Open User Headquarter (HQ) and Regional Company (RC) libraries
Migration of Unigyr
Described in Requirements
CM110496 Unigyr tools V7.61 with Unigyr automation level V7.64
Migration of Integral
Described in Requirements
CM110499 NCRS from V3.1 (only automation level)
For replacing Integral RS modules (NRUA, NRUB, NRUC, and NRUD) with PXC automation stations and PXC-
NRUD modules, Desigo supports the use of PXC-NRUD modules with PXC100/200(-E).D and PXC50(-E).D.
Migration of Visonik
Described in Requirements
CM110497 DCS from V22.16 Patch 195 or V24.16 Patch 195 (server with automation level)
Desigo Xworks Plus (and all other Compatible with > 2.0 GHz 8 GB RAM 50 GB HD* with Monitor: 1366x768
utilities) incl. ABT Site/Pro on the Intel and AMD (> 3 GHz (> 16 GB good performance DVD
same computer technology recommended) RAM (HDD at very fast
access times) (SSD drive)
recommende
d) (USB port for SSA to
Discovery Network
Tool (DNT) as
alternative to ethernet
connection)
Multiple core
processors, e.g., for
VMware
Branch Office Server (BOS) Compatible with > 1.6 GHz (2.5 8 GB RAM HD size
Intel and AMD GHz) recommende depending on
technology d project data
volume
Key
*
Desigo Xworks Plus (XWP) requires ca. 1.4 GB memory. Automation Building Tool (ABT) requires ca. 1-2 GB memory.
Uncompressed project data requires an additional 0.5 MB memory per data point (reference value). The performance depends on
available memory.
The indicated values apply to a host installation. For stable and reliable operation of VMware, CPU and RAM
requirements are higher.
The recommended values allow for larger projects (up to 12 PXC3 with 8 rooms each per ABT project). For
details, see chapter Compatibility with Operating Systems.
Configure SSDs for a long life. See Microsoft documentation.
ABT projects require ca. 2.5 times more memory per PXC3 room automation station compared to PXC
automation stations.
Parallel port or USB port for license dongle.
For online functions you need:
● LonWorks interface card or LonWorks dongle
● Ethernet interface
● Connection cable for automation stations
● USB port for P-bus BIM and SSA Discovery Network Tool (DNT) connection
The following software is required:
● Operating system: See chapter Compatibility with Operating Systems
● Microsoft Office: See chapter Compatibility with Microsoft Office
● Acrobat Reader 6.0 or higher (optional installation with tool installation)
● WinZIP
● .NET Framework >= V3.5 (version 3.5 is available on the tool DVD)
Prerequisites for extending Desigo V6.3 (XWP project) with PXC4 and PXC5
● Upgrade the management platform Desigo CC to V5.0.
● Make sure all PXC00...200..D primary controllers and room automation products adhere to the Desigo V6.3
compatibility.
● You are using Desigo Xworks Plus (XWP) V6.3.
● You are using ABT Site V4.3.
Desigo CC Desigo CC
BBMD
IP Subnet
Floor Scope: Flexible Rooms
BBMD
IP Subnet
Floor Scope: Flexible Rooms
BBMD
IP Subnet
Plant Scope: Primary Plants with Desigo PX00..200..D
BBMD
IP Subnet
Plant Scope: Primary Plants with Desigo PXC4 & 5
BBMD
IP Subnet 192.168.100.x
For more information, see Application Guide for BACnet Networks in Building Automation (A6V11159798).
Engineering and commissioning of Desigo PXC4 and PXC5
Engineer and commission the Desigo PXC4 and PXC5 subsystem with ABT site V4.3 and export/import it into
the Desigo CC management platform.
For more information on the system compatibility of the Desigo CC management platform, see Desigo CC
System Description (A6V10415500).
Engineering and commissioning of Desigo V6.3
Engineer enhancements and adaptations in Desigo V6.3 with XWP V6.3 (ABT Site) and export/import it into the
Desigo CC management platform.
For more information on the system compatibility of the Desigo CC management platform, see Desigo CC
System Description (A6V10415500).
Data exchange between Desigo V6.3 and Desigo PXC4 and PXC5 on automation level
Similar to the integration of third-party systems via BACnet references into the Desigo V6.3 system engineered
via XWP V6.3.
For more information, see XWP Online Help.
CM110664en_10