Transformer OLTC Optimization
Transformer OLTC Optimization
Optimizing On-Load Tap Changers typically involves assessing different tap settings under varying
load conditions to minimize energy losses, improve system efficiency, and maintain voltage
stability. This process often includes simulation studies and analysis.
We want to consider the following general steps:
Power System Modeling:
Create a detailed model of your power system in ETAP, including transformers with On-Load Tap
Changers.
Evaluate energy losses associated with different tap positions and select settings that minimize
these losses.
Example:
Consider a system with grid voltage of 110 kV is connected to a transformer of 45 MVA,
110/11kV. Assume the grid voltage fluctuates from +10% to -15% and load varies from 12 MW to
35MW.
Objective – To identify OLTC range to regulate the voltage within +/- 5%.
Consider two worst case conditions as
Case 1: Maximum Grid Voltage with Minimum Load and
In case 1 the OLTC on the positive side is set at 2.6% in order to bring the load bus voltage less than
105%.
In case 2 the OLTC on the negative side is set at -21.16% in order to boost the load bus voltage
more than 95%.
Transformer Tap Optimization:
Number of Taps = 1 + [(%Maximum Tap – %Minimum Tap) / %Step]
Maximum Tap = 2.6%
Tap Settings