Sr No.

System P&ID reference Description


1 Steam V1916-P- Steam supply
54_P&ID control valve -
Sewage existing will be
System used

2 Steam V1916-P- Local control panel


54_P&ID with temperature
Sewage controller is shown
System in vendor p&id

3 Steam V1916-P-48- Existing PRV will be


P&ID Regas used for 60/10k
Steam System service
4 Sewage System V1916-P- Line size proposed
54_P&ID as per site run is
Sewage 50ND
System

Level transmitter
L / LL signal

Level transmitter
HH signal ==
sewage
evaporation pump
off
5 N2 System V1916-P- Existing PRV will be
46_P&ID N2 utilised for 10 bar
System to 5 bar reduction
N2 Buffer tank
vendor is providing
Pressure gauge

6 Condensate V1916-P- Condensate Pump


52_R2_P&ID auto change over
Regas Steam of stand-by pump
Condensate based on pressure
System

Oil monitor
proposed by owner
for GW detection
Query
Whether Valve V-PB023 and solenoid valve to be
shown

Whether local control panel will be installed (See


vendor drawing)

Whether solenoid valve is required to shut off the PRV


in case of temperature above set point

not required

Owner will procure I/P converter ?


yes
Clarify client statement regarding no feedback
whether it means No feedback is required from Valve
positioner to IAS

yes right

Confirm representation in &ID, solenoid needed for


auto shut?

Solenoid not required

Sewage shore pump capacity is 50 m3/h


For 50ND pipe, velocity will be too high (6.4 m/s) in
suction

Synergy proposed 125ND pipe from APT to Pump


suction manifold

Low signal should trigger suppy to Sewage


evaporator, whether anything to be shown in P&ID
and IO List

Whether anything to be added in IO list/ (other


document) for this logic
Please share valve details - tag, drawing, size

Whether , upstream & downstream isolation valves


will be new or existing

Clarify whether N2 Vent as per site route meets class


requirement
whether additional pressure transmitter is required?

Comment not clear on N2 Bufffer tank drain

Whether Auto change over of Condensate pump will


be through IAS and any change in representation
required in p&ID

No feedback/confirmation from OCM Vendor for same


Sunbo relief line -5 deg C
sewage evaporation pump
N2 generator class comments
GW leakage detection
GW flow meter by pass required ?
Workshop : heat dissipation : AC/Fan?
Image ref
it will be IAS from existing buffer tank pressure

stock valve
additional keep PI, add new PT

ignore

2.5 bar
no action required
keep as exisitng
not required
no action required