Resources Steam-Engineering-Tutorial
Resources Steam-Engineering-Tutorial
You are here: Home Resources Steam Engineering Tutorials Condensate Recovery Sizing Condensate Return Lines
Related Content
Electric Pumps Sizing Condensate Return Lines
Condensate recovery units are
A guide to sizing condensate lines to and from steam traps, including examples and calculations using the condensate pipe sizing chart.
designed to handle hot
condensate, which is commonly Use the quick links below to take you to the main sections of this tutorial:
returned for use as boiler
feedwater.
The four main types of condensate line, as mentioned in Tutorial 14.2, are shown in Table 14.3.1:
Pressure Powered Pumps
View the full range of pumps and Table 14.3.1 The four basic types of condensate line
pump-traps required for
condensate removal under stall
conditions.
8/5/2012
Page 2 of 25
Fig. 14.3.1 The drain line should not be sized on the plant connection
Feature
The Steam and Condensate Regarding the conditions inside the drain line, as there is no significant pressure drop between the plant and the trap, no flash steam is present in the pipe,
Loop Book and it can be sized to carry condensate only.
When sizing the drain line, the following will need consideration:
The condensing rate of the equipment being drained during full-load.
The condensing rate of the equipment at start-up.
At plant start-up, the condensing rate can be up to three times the running load - this is where the temperature difference between the steam and
colder product is at its maximum.
The drain line, trap, and discharge line also have to carry the air that is displaced by the incoming steam during this time.
The sizing routine for the steam trap will have to consider both of these variables, however, in general:
For steam mains drainage, the condensate load for each drain trap is typically 1% of the steam capacity of the main based on drain points at 50 m
intervals, and with good insulation.
A comprehensive best practice For most drain points, sizing the trap to pass twice the running load at the working pressure (minus any backpressure) will allow it to cope with the start
guide to saving energy and -up load.
optimising plant performance, On constant steam pressure processes such as presses, ironers, unit heaters, radiant panels and boiling pans, sizing the traps on approximately twice
this book covers all aspects of the running load at the working pressure (less any backpressure) will provide sufficient capacity to cope with the start-up load.
steam and condensate systems.
On temperature controlled applications, the steam pressure, the plant turndown, the set temperature and steam trap location need to be considered in
detail, and the trap needs to be sized to cater for both the full and minimum load conditions. If these conditions are not known it is recommended that
Order your copy today the steam trap be sized on 3 x the running load at the running differential pressure. This should satisfy the start-up condition and provide proper
drainage at minimum loads.
When the trap is sized in this way, it will also cater for the start-up load. Consequently, if the drain line to the trap is sized on the trap size, it will never
be undersized.
For practical purposes, where the drain line is less than 10 m, it can be the same pipe size as the steam trap selected for the application. Drain lines less than
10 m long can also be checked against Appendix 14.3.1 and a pipe size should be selected which results in a pressure loss at maximum flowrate of not more
than 200 Pa per metre length, and a velocity not greater than 1.5 m/s. Table 14.3.2 is an extract from Appendix 14.3.1.
On longer drain lines (over 10 m), the pressure loss at maximum flowrate should not be more than 100 Pa/m, and a velocity not greater than 1 m/s.
8/5/2012
Page 3 of 25
Example 14.3.1
An item of plant, using steam at constant pressure, condenses 470 kg of steam an hour at full-load. The pipework between the plant item and the steam trap
has an equivalent length of 2 m.
As the pipe length is less than 10 metres, the maximum allowable pressure drop is 200 Pa/m.
Using Table 14.3.1, by looking across from 200 Pa/m it can be seen that a 25 mm pipe has a capacity of 1 141 kg/h, and would therefore be suitable for the
expected starting load of 940 kg/h.
Checking further up the 25 mm column, it can be seen that a flowrate of 940 kg/h will incur an actual pressure drop of just less than 140 Pa/m flowing through
a 25 mm pipe.
Example 14.3.2
An item of plant uses steam at a constant 4 bar g pressure. A mechanical steam trap is fitted, and condensate at saturation temperature is discharged into a
condensate main working at 0.5 bar g.
Determine the proportions by mass, and by volume, of water and steam in the condensate main.
8/5/2012
Part 1 - Determine the proportions by mass
Page 4 of 25
From steam tables:
Equation 2.2.5
Where:
P1 = Initial pressure
P2 = Final pressure
hf = Specific liquid enthalpy (kJ/kg)
hfg = Specific enthalpy of evaporation (kJ/kg)
Clearly, if 7.9% is flashing to steam, the remaining 100 - 7.9 = 92.1% of the initial mass flow will remain as water.
Water:
The density of saturated water at 0.5 bar g is 950 kg/m,
Steam:
From steam tables, specific volume (vg) of steam at 0.5 bar g = 1.15 m/kg
The volume occupied by the steam is 0.079 kg x 1.15 m/kg = 0.091 m
The total volume occupied by the steam and condensate mixture is:
0.001 m (water) + 0.091 m (steam) = 0.092 m
By proportion (%):
From this, it follows that the two-phase fluid in the trap discharge line will have much more in common with steam than water, and it is sensible to size on
reasonable steam velocities rather than use the relatively small volume of condensate as the basis for calculation. If lines are undersized, the flash steam
8/5/2012
velocity and backpressure will increase, which can cause waterhammer, reduce the trap capacity, and flood the process.
Page 5 of 25
Steam lines are sized with attention to maximum velocities. Dry saturated steam should travel no faster than 40 m/s. Wet steam should travel somewhat
slower (15 to 20 m/s) as it carries moisture which can otherwise have an erosive and damaging effect on fittings and valves.
Trap discharge lines can be regarded as steam lines carrying very wet steam, and should be sized on similarly low velocities.
Condensate discharge lines from traps are notoriously more difficult to size than steam lines due to the two-phase flow characteristic. In practice, it is
impossible (and often unnecessary) to determine the exact condition of the fluid inside the pipe.
Although the amount of flash steam produced (see Figure 14.3.2) is related to the pressure difference across the trap, other factors will also have an effect.
Recommendations:
1. Correctly sized trap discharge lines which slope in the direction of flow and are open-ended or vented at a receiver, will be non-flooded and allow flash
steam to pass unhindered above the condensate (Figure 14.3.3). A minimum slope of 1 in 70 (150 mm drop every 10 m) is recommended. A simple
visual check will usually confirm if the line is sloping - if no slope is apparent it is not sloping enough!
8/5/2012
Page 7 of 25
Fig. 14.3.3 Discharge line sloping 1:70 in the direction of flow
2. If it is unavoidable, non-pumped rising lines (Figure 14.3.4) should be kept as short as possible and fitted with a non-return valve to stop condensate
falling back down to the trap. Risers should discharge into the top of overhead return lines. This stops condensate draining back into the riser from the
return main after the trap has discharged, to assist the easy passage of flash steam up the riser.
It is sensible to consider using a slightly larger riser, which will produce a lower flash steam velocity. This will reduce the risk of waterhammer and
noise caused by steam trying to force a path through the liquid condensate in the riser.
Important: A rising line should only be used where the process steam pressure is guaranteed to be higher than the condensate backpressure at the
trap outlet. If not, the process will waterlog unless a pumping trap or pump-trap combination is used to provide proper drainage against the
backpressure.
Fig. 14.3.4 Keep rising lines short and connect to the top of return lines
3. Common return lines should also slope down and be non-flooded (Figure 14.3.4). To avoid flash steam occurring in long return lines, hot condensate
from trap discharge lines should drain into vented receivers (or flash vessels where appropriate), from where it can be pumped on to its final
destination, via a flooded line at a lower temperature.
8/5/2012
Page 9 of 25
Note: The reasoning employed for the sizing of a steam trap is different to that used for a discharge line, and it is perfectly normal for a trap discharge line to
be sized different to the trap it is serving. However, when the trap is correctly sized, the usual ancillary equipment associated with a steam trap station, such as
isolation valves, strainer, trap testing chamber, and check valve, can be the same size as the trapping device selected, whatever the discharge line size.
A steam trap passing a full-load of 1000 kg/h at 6 bar g saturated steam pressure through a
falling discharge line down to a flash vessel at 1.7 bar g.
As the discharge line is non-flooded, the lower figure of 25 mm is selected from the chart
(Figure 14.3.5).
Fig. 14.3.6 A non-flooded pressurised trap discharge line (refer to Example 14.3.3)
A steam trap passing a full-load of 1000 kg/h at 18 bar g saturated steam pressure through a
discharge line rising 5 m up to a pressurised condensate return line at 3.5 bar g.
Add the 0.5 bar static pressure (5 m head) to the 3.5 bar condensate pressure to give 4 bar g
backpressure.
As the discharge line is rising and thus flooded, the upper figure of 32 mm is selected from the chart, (Figure 14.3.5).
8/5/2012
Page 11 of 25
A steam trap passing a full-load of 200 kg/h at 2 bar g saturated steam pressure through a
sloping discharge line falling down to a vented condensate receiver at atmospheric pressure (0
bar g).
As the line is non-flooded, the lower figure of 20 mm is selected from the chart, (Figure 14.3.5).
8/5/2012
Page 12 of 25
Fig. 14.3.8 A non-flooded vented trap discharge line (refer to Example 14.3.5)
A pump-trap passing a full-load of 200 kg/h at 4 bar g saturated steam space pressure through
a discharge line rising 5 m up to a non-flooded condensate return line at atmospheric pressure.
As the trap discharge line is rising, the upper figure of 25 mm is selected from the chart, (Figure 14.3.5).
8/5/2012
Page 13 of 25
In this case, the condensate line is based on the maximum capacity of the pump to achieve
the desired delivery head. Calculating pump capacities is covered in Tutorial 14.4 'Pumping
Condensate from Vented Receivers', but for this example, it is assumed that the maximum
condensate load will be 1200 kg/h.
Because the condensate will have lost its flash steam content to atmosphere via the receiver vent, the pump will only be pumping liquid condensate. In this
instance, it is only necessary to use the top part of the chart in Figure 14.3.5. As the line from the pump is rising, the upper figure of 25 mm is chosen.
Note: If the pumped line were longer than 100 m, the next larger size must be taken, which for this example would be 32 mm. A useful tip for lines of 100 m or
less is to choose a discharge pipe which is the same size as the pump. For further details refer to Tutorial 14.4 'Pumping condensate from vented receivers'.
8/5/2012
Page 14 of 25
Fig. 14.3.10 A discharge line from the condensate pump (refer to Example 14.3.7)
The common line slopes down to the flash vessel at 1.5 bar g, situated in the same plant room. Condensate in the flash vessel falls via a float trap down to a
vented receiver, from where it is pumped directly to the boiler house.
The trap discharge lines are sized on full-load with steam pressure at 3 bar g and condensate pressure of 1.5 bar g, and as each is not flooded, the lower line
sizes are picked from the graph.
Determine the condensate line sizes for the falling discharge lines and common lines.
8/5/2012
Page 15 of 25
Example 14.3.9
Figure 14.3.12 shows the same three heat exchangers as in Example 14.3.8.
8/5/2012
Page 16 of 25
However, in this instance, the common line rises 15 m and terminates in an overhead non-flooded condensate return main, giving the same backpressure of
1.5 bar as in Example 14.3.8. Each of the discharge lines is sized as a rising line.
Determine the condensate line sizes for the discharge lines and common lines.
Example 14.3.9
Figure 14.3.12 shows the same three heat exchangers as in Example 14.3.8.
However, in this instance, the common line rises 15 m and terminates in an overhead non-flooded condensate return main, giving the same backpressure of
1.5 bar as in Example 14.3.8. Each of the discharge lines is sized as a rising line.
Determine the condensate line sizes for the discharge lines and common lines.
Fig. 14.3.13
Note that the steam loads are the same as Example 14.3.10, but the discharge lines are one size larger due to the rising common line.
8/5/2012
Page 18 of 25
Fig. 14.3.14
The procedure shown in Examples 14.3.10 and 14.3.11 can be simplified by using Appendix 14.3.3.
For example, where pipes A and B (20 mm and 50 mm) join, the minimum required pipe diameter is shown as 54 mm. Clearly, the user would fit the next
largest size of commercial pipe available, unless the calculated bore is close to a nominal bore size pipe.
8/5/2012
Page 19 of 25
Appendix 14.3.1 Flow of water in heavy steel pipes
8/5/2012
Page 20 of 25
8/5/2012
Page 21 of 25
8/5/2012
Page 22 of 25
Appendix 14.3.2 Condensate pipe sizing chart
8/5/2012
Page 23 of 25
Appendix 14.3.3 Common pipe sizing table
D1 = Connecting branch size (N.B.)
D2 = Common pipe size
8/5/2012
Page 24 of 25
8/5/2012
Page 25 of 25
What do I do now?
The printable version of this page has now been replaced by The Steam and Condensate Loop Book
Try answering the Questions for this tutorial
View the complete collection of Steam Engineering Tutorials
Contact Us
8/5/2012