Large Earthing System - Earth Express
Large Earthing System - Earth Express
The correct earth resistance value is usually obtained from the flat part
of curve. See the below figure.
To obtain an ideal earth resistance curve at least 10 readings should
be taken at equally spaced intervals.
True resistance will be obtained where the curve flattens out
(typically around the 62% of distance D).
This method gives a correct value of earth resistance if the earth
resistivity and the soil conditions at the flat point do not vary at other
points (assuming there are no other measuring errors).
Localized reading deviations can be caused by buried metallic objects
such as pipes or inhomogeneous soil around construction sites.
If the curve obtained does not show a flat point, the measurements
should be retaken placing the auxiliary earth electrode C at a further
distance.
If the expected earth resistance value is very low, say, lower than 1 or
2 ohms, it is recommended to use earth testers with higher test
current since the higher test current creates a greater voltage drop
that is more measurable.
The earthing system under test has to be temporarily disconnected
from the main installation. To avoid possible risk of electric shock
while disconnecting the MEC (Main Earth Conductor), switch off the
power supply prior to implementing the temporary measures. The
power supply should only be restored after the temporary measures
have been removed.