Switching Overvoltage Measurements and Simulations Part I Filed Test Overvoltages Measurements BY J MARTINEZ
Switching Overvoltage Measurements and Simulations Part I Filed Test Overvoltages Measurements BY J MARTINEZ
6, DECEMBER 2014
Abstract—This paper presents the work carried out by the the transient is initiated and the trapped charge on the phases).
IEEE Working Grou[ on field-measured overvoltages and their Therefore, a number of simulations using the same system have
analysis for validating power system component models to be to be made with the time of energization modified in each sim-
used in switching transients studies. The work uses measurement
data obtained from field tests performed by Bonneville Power ulation either in a predictable manner (i.e., for determining the
Administration in June 1995 where switching overvoltages were peak overvoltage) or statistically (for obtaining an overvoltage
measured on one of its 230 kV lines. This paper includes a descrip- probability distribution) [1]–[6]. Thus, model validation must
tion of the switching tests and the main results derived from field be performed using specified parameters (e.g., point on wave in
measurements. Details of the switching procedures that were fol- which the transient is initiated, etc.).
lowed to calibrate component models used to match field-recorded
waveforms can be found in the Part II paper. Field measurements are the preferred method of validation
of models for switching transients. This is due to the range of
Index Terms—Power system switching transients, switching
frequencies associated with most switching transients and the
transients, transmission system.
fact that the initiation of the transient can be predefined; that is,
there is no randomness involved in the origin of the transient
I. INTRODUCTION events. However, field measurement data obtained with accu-
rate measuring equipment are relatively rare. Some field mea-
0885-8977 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
MARTINEZ et al.: SWITCHING OVERVOLTAGE MEASUREMENTS AND SIMULATIONS—PART I: FIELD TEST OVERVOLTAGE MEASUREMENTS 2503
Fig. 2. Single-phase switching test from Big Eddy with trapped charge (Test 1–04).
For each test, the circuit breaker initially energizing the line 341 kV (bus line) and the resulting overvoltage measured at
was opened for 500 ms (30 cycles) and then reclosed 3-phase. Chemawa was 500 kV. The traveling waves on B-ph, interacting
The opening was controlled to leave the same trapped charge between the line and the system at Big Eddy, took approximately
on the line for each test. During the field test, the average time two cycles to dampen out. The waveforms show the relatively
constant of trapped charge decay was measured and found to be complicated voltages induced on A and C phases compared to
approximately 1 min. The trapped charge voltage thus decreased the relatively simple waves on B phase.
about 1% during the 500 ms open time. This decay time constant Approximately 25 switching tests were performed from each
for trapped charge is consistent with other BPA field test mea- line end, involving a three-phase reclose into a trapped charge.
surements made on other lines with these voltage dividers. The Nearly all tests conducted from a particular end of the line had
3-phase reclosing test was repeated 20 times from each end, with the same trapped charge, within a few kilovolts. Table I pro-
the closing signal incremented by 18 electrical degrees for each vides a summary of the average trapped charge voltages and
test. Incrementing the electrical angle in this way provided a the highest overvoltages measured on each phase during the
uniform distribution across a 60 Hz cycle. About five additional three-phase switching tests. The trapped charges were approx-
tests were performed from each end with the breaker timing fo- imately 1.2 p.u. on the highest phase and 0.9 to 1.0 p.u. on the
cused around the closing times that generated the highest over- other two phases. The highest overvoltages ranged from 2.9 to
voltages. 3.3 p.u.
While switching from Big Eddy (a relatively strong source),
B. Trapped Charge and Overvoltages C-phase had the highest maximum and average overvoltages,
Fig. 2 shows a 40 ms window from a single-phase switching even though A-phase had the highest level of trapped charge
test with trapped charge. In this test, the Big Eddy breaker was (see Table I). While switching from Chemawa (a relatively
tripped and reclosed in about 500 ms. Phases A and C of the weak source), A-phase had the highest level of trapped charge
line disconnect had been blocked open so only B-ph of the line and the highest maximum and average overvoltages. Switching
was directly energized. The trapped charge voltage on B-ph of from either end produced overvoltages exceeding 3.0 p.u.,
176 kV is shown on the left side of the waveforms prior to with the highest at 3.30 p.u. The upper 25% of overvoltages
the breaker close. The A and C phase voltage waveforms show measured when switching from Big Eddy were higher than
a partial trapped charge (approximately 32 kV each) that had those when switching from Chemawa. This was expected
been induced from B-ph. The step voltage applied to B-ph was since a stronger source, with more connected lines (and lower
MARTINEZ et al.: SWITCHING OVERVOLTAGE MEASUREMENTS AND SIMULATIONS—PART I: FIELD TEST OVERVOLTAGE MEASUREMENTS 2505
C. Multiple Prestrikes
The measurements taken during the three-phase reclosing
tests revealed an unexpected phenomenon—that breaker
closing operations into trapped charge can result in multiple
prestrikes [6], [14], [15]. The majority of breaker closings
Fig. 3. Distribution of maximum overvoltages measured during the test for
both receiving and sending ends. resulted in only a single prestrike; however, in a few tests, up
to four prestrikes occurred on one phase during a single closing
operation. During breaker prestrike, a current wave (initiated
source surge impedance) will produce a larger voltage step by arcing across contacts) travels down the line to the receiving
onto a switched line. However, in the range of 15%–75% of (open) end where it is reflected. As the reflected wave travels
overvoltages, this did not hold true and the levels were larger back toward the sending end of the line, it reduces the current
when switching from the Chemawa end, indicating additional to near zero along the line. When the reflected current wave
variables at work. reaches the sending end, it creates a current zero and allows
Along with the receiving-end overvoltages, the sending end the prestrike arc between the breaker contacts to extinguish,
of the line also experienced overvoltages which were higher isolating the line voltage from the bus voltage. The line voltage
than expected. These occurred because of induced voltages from may then increase due to travelling waves that continue to be
transients on other phases and because of the breakers having reflected from the receiving end and induced voltages. The
multiple prestrikes, which are discussed later. Fig. 3 provides voltage across the breaker then builds up until another prestrike
2506 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 29, NO. 6, DECEMBER 2014
Fig. 4. Three-phase high-speed reclose test while switching from the Chemawa end of the line (Test 5–71).
Fig. 6. Identification of prestrikes on the Chemawa breaker during a three-phase reclosing operation.
TABLE II the number of prestrikes for this test is different for each phase
BREAKER DIELECTRIC SLOPES DURING CLOSING OPERATIONS and results in up to three on A phase [13].
TABLE III
LINE ENTRANCE GAP SWITCHING IMPULSE TEST RESULTS VOLTAGES IN PU
WHERE 1 p.u. 197 kV PK [16]