Tra Ning
Tra Ning
FORMAT
Version 1 - Before the commencement of the training (For those who attend the
training):
Soft copies of the approved training manuals must be submitted for each system/discipline at
least 1 Week prior to the commencement of training programme. Training will not be started
without submitting the same.
Upon the completion of the training programme, one soft copy of the training manuals shall be
submitted to Hilton. This must include, in addition to the above submittal (Version 1):
ii. Video record for both class room and on-the job training
iii. Any other hand outs, data sheets and related references distributed during the
training.
Hilton will review some selected Training manuals out of the submitted ones. Both Hilton
and consultants shall comment on the training manual submittals. The comments must be
incorporated by the contractors in the training manuals. After the incorporation of comments,
these manuals will be accepted by Hilton as a minimum standard format and must be used
as a template, adhered by all the packages, trades and discipline in the Project.
- The Consultant needs to make sure that all other submitted training manuals meet
the “minimum Hilton acceptable standard”
- All Training Manuals must be submitted for Consultant’s review and acceptance.
Each manual shall be reviewed and approved by the consultant with the approval
cover sheet included.
- All comments made on any section of the training Manual, shall be addressed
properly and accurately prior to the submission.
Page 1 of 42
The documents submitted by Vendors shall contain sufficient detailed information to provide
the Operator with a complete understanding of the installed equipment / system training. The
following are the minimum general requirements for the training manual which needs to be
followed:
Project name
Subject of training
- Training Aids: the training aids required to deliver the training program such as
(whiteboard and markers, laptop/PC and Multimedia Projector, Paper and pens
for trainees, flipchart, etc.)
Page 2 of 42
Interactive Question & Answer secessions.
The attendance sheet must contain the logos of the subcontractor, main contractor,
consultant, project management, and the client.
A complete & signed attendance sheet must be included in the training manual
(Version 2) upon satisfactory completion of each and every training conducted
Soft copy of the individual presentation provided by the subcontractors and will be
presented during the training course must be included in the training manual
submission (Version 1)
Once the training was conducted satisfactorily the training video will be provided at
the end of the training day and/or upon completion of training or as agreed by all
parties involved.
The training video must be Windows format and Windows compatible using VLC
software.
System Description
Schedule of Equipment
Operation details (This section should contain the Introduction, General
Operating Mode, Control Data, Start –Up & Shutdown Procedures, Standby
Operation and Hazards & Precautions).
Maintenance Details (This section should contain the Introduction,
Preventive Maintenance Activities, Corrective Maintenance Activities, Routine
Maintenance which includes periodic inspection, Cleaning Process,
Page 3 of 42
Recommended Maintenance Schedules and Fault Finding Table).
Interface details with other systems
Manufacturers Literature
Schematic Drawings/Single Line Diagrams
Page 4 of 42
HILTON GARDEN INN & EMBASSY SUITES
TRAINING MANUAL
FIRE PUMP
Page 5 of 42
Contents
1. SYSTEM DESCRIPTION..................................................................................................7
2. EQUIPMENT SCHEDULE................................................................................................7
3. OPERATION DETAILS....................................................................................................9
4. MAINTENANCE DETAILS & TROUBLESHOOTING....................................................18
5. INTERFACE DETAILS WITH OTHER SYSTEMS:........................................................30
6. MANUFACTURE /SUPPLIER DETAILS........................................................................32
7. SCHEMATIC DRAWINGS/SINGLE LINE DIAGRAMS.................................................33
8. TRAINING AGENDA......................................................................................................39
9. TRAINING AIDS.............................................................................................................39
10. TRAINING RECORDS................................................................................................40
Page 6 of 42
1. SYSTEM DESCRIPTION
The Fire Protection System is designed to safeguard the property from the hazard of fires in any
event. The supplied fire pumps are suitable for supplying the fire protection system with water at
various pressures in the event of a pressure drop in the line. The arrangement of the fire pump
configuration is such that the main pump has an electric motor, and the stand-by pump is a diesel
pump which receives is coupled to a diesel engine. At the initial stages, if there is any leakage in the
piping network of the system, the jockey pump or the pressure maintenance pump will start at its cut
in set pressure to make up for the loss in pressure and will run until the system pressure has been
restored. If the pressure has gone below the cut in pressure of the jockey, the pressure transducer
senses the pressure drop and signals the main pump to start and again if the pressure drops below
the cut in pressure of the main pump, the stand-by pump starts. The stand-by pump starts in the event
of a power failure too.
Aurora Fire Pump System(s) complete with pump, driver, controller, and accessories. The pumping
unit shall be listed by Underwriters' Laboratories, Inc. and/or shall be fully approved by the Associated
Factory Mutual Fire Insurance Companies, where applicable. The pumping unit shall meet all
requirements of UAE Fire and Life Code of Practice 2018 Ed. and the National Fire Protection
Association Pamphlet No.20 which is,
1. The Fire Pump shall deliver the rated capacity when operating at the rated head.
2. The pump shall also deliver not less than 150% of rated capacity at a pressure not less than
65% of rated pressure.
3. The shut off pressure shall not exceed 140% of rated pressure.
2. EQUIPMENT SCHEDULE
The supplied fire pump capacities for this project for the respective floors is as per the table given
below,
Basement Pump
Page 7 of 42
FIRE PUMP SET (1000GPM@16 BAR)
Page 8 of 42
3. OPERATION DETAILS
START –UP & SHUTDOWN PROCEDURES
1- START UP PROCEDURE
ELECTRIC DRIVEN
2- AUTOMATIC OPERATION
Open system butterfly valve and turn all the isolating valves to the fully open position.
Turn main disconnect switch into "ON" position.
Page 9 of 42
Switch fire pump circuit breaker to "ON" position.
Switch Jockey pump to "AUTO".
If the operating differential of pressure switches do not permit the following settings, the setting should
be close as the equipment will permit. The setting should be established by the pressures observed in
the test gauges. All devices are preset at the factory and normally do not require any adjustments. A
final adjustment may be made on any control to match the exact system requirements.
REMINDERS
After the start -up, make sure to open the system butterfly valve,
Make sure to bring minimum run timer back to 30 minutes.
The valve on the pump suction must be fully open as the throttle on the suction side is harmful to
the pump.
Make sure that the pump will not run dry. Centrifugal pump has close clearances and cannot run
dry without serious damages.
This document covers the philosophy of operation of the Fire Pump System. The system uses
centrifugal pumps to supply water to the Fire Water system, and is designed for unattended operation
SYSTEM DESCRIPTION
In case of any miner water leakage in the system, the pressure in the system will be released and it
will start decreasing. Jockey pump will start automatically at 15 Bar and try to maintain this small
pressure loss and it will stop automatically once reaches to the system pressure (16 Bar).
In case of more demand due to the opening of a fire hydrant, Landing valve, actuation of sprinkler
head etc. and the pressure drops to 14 Bar, then the main electric pump will start automatically and it
will stop automatically once the system pressure reaches 16 Bar + 10 Minutes. (Once started and
after reaching to the system pressure, the timer starts with the countdown for 10 minutes then the
main electric pump will stop automatically).
If main electric pump stops due to interruption in the power supply and the pressure drops to 13 Bar,
then the Diesel pump (Standby pump) will start automatically to provide the required flow and
pressure and it will run until stopped manually or it will stop automatically once the system pressure
Page 10 of 42
reaches 16 Bar + 30 Minutes depending on the entered settings (Both of two options acceptable for
NFPA so the setting of the diesel pump based on the concerned person requirement).
In case of any miner water leakage in the system, the pressure in the system will be released and it
will start decreasing. Jockey pump will start automatically at 13 Bar and try to maintain this small
pressure loss and it will stop automatically once reaches to the system pressure (14 Bar).
In case of more demand due to the opening of a fire hydrant, Landing valve, actuation of sprinkler
head etc. and the pressure drops to 12 Bar, then the main electric pump will start automatically and it
will stop automatically once the system pressure reaches 14 Bar + 10 Minutes. (Once started and
after reaching to the system pressure, the timer starts with the countdown for 10 minutes then the
main electric pump will stop automatically).
If main electric pump stops due to interruption in the power supply and the pressure drops to 11 Bar,
then the Diesel pump (Standby pump) will start automatically to provide the required flow and
pressure and it will run until stopped manually or it will stop automatically once the system pressure
reaches 14 Bar + 30 Minutes depending on the entered settings (Both of two options acceptable for
NFPA so the setting of the diesel pump based on the concerned person requirement).
Page 11 of 42
Controls and Displays Standard Features
Model GPD Diesel Engine Fire Pump Controllers
1. Alarm bell
2. Externally mounted pressure transducer
and run test solenoid valve with
protective cover
3. Key lock
4. ViZiTouch V2 operator interface
5. Exterior USB Port (Interior USB port
also supplied)
6. HAND OFF-AUTO selector switch
7. Remote alarm contacts with removable
terminals
8. Gland Plate
9. Automotive type engine connections
10. Battery chargers
Page 12 of 42
Model GPx Series - Electric Fire Pump Controllers
Page 13 of 42
• Gland plate • Audible alarm • Alarm contacts for remote indication • Available with full
voltage and reduced voltage starting
1. Alarm bell
2. Externally mounted pressure transducer and
run test solenoid valve with protective cover
3. Lifting Lugs
4. ViZiTouch V2 operator interface
5. Exterior USB Port (Interior USB port also
supplied)
6. Custom designed Isolation switch / Circuit
breaker operator handle
7. Key lock
8. Remote alarm contacts with removable
terminals
9. Surge arrestor
10. Custom designed emergency start
mechanism with integrated limit switch
11. Gland plate
12. Automatic power transfer switch
Page 14 of 42
OPERATING MODES
METHODS OF STARTING / STOPING for the Diesel engine driven pump controller
The controllers are available as combination automatic / non-automatic with provision for
manual or automatic shutdown (an automatic shutdown is only possible after an automatic
start).
METHODS OF STARTING
Page 15 of 42
• AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor
when the pressure drops below the cut-in threshold.
• MANUAL START
The engine can be started by pressing the CRANK 1 or and/or CRANK 2 push button,
regardless of the system pressure, when the Main Selector switch is in the HAND position.
The Fuel Solenoid Valve will open as soon as a CRANK button is pressed and will remain
in this state.
• REMOTE MANUAL START
The engine can be started from a remote location by momentarily closing a contact of a
manual push button.
• REMOTE AUTOMATIC START, DELUGE VALVE START
The engine can be started from a remote location by momentarily opening a contact
connected to an automatic device. The controller must be in automatic mode.
• SEQUENTIAL START
In case of a multiple pump application, it may be necessary to delay the starting of each
motor when there is a water pressure drop to prevent simultaneous starting of all motors.
• FLOW START, HIGH ZONE START
The pump can be started by opening/closing a contact on the FLOW/ZONE START/STOP
input.
• WEEKLY START
The engine can be started (and stopped) automatically at the preprogrammed time.
• TEST START
The motor can be started manually by pressing the run test button.
METHODS OF STOPPING
• MANUAL STOP
Manual stop is done by pressing the STOP push button. Note that pressing the stop push
button will stop the engine only if all starting causes have disappeared.
• AUTOMATIC STOP
The automatic stop is possible only after an automatic start and this function has been
activated. When this function is Enabled, the motor is automatically stopped 30 minutes
(adjustable) after the restoration of the pressure (above the cut-out threshold) given that no
other run cause is present.
• FLOW STOP, HIGH ZONE STOP
If the controller has been started by the FLOW/ZONE START/STOP input and the signal
has returned to normal, the motor will be stopped given that no other run cause is present.
• EMERGENCY STOP
The emergency stop is always possible in any running condition and is done by positioning
the main selector switch to the OFF position.
METHODS OF STARTING / STOPING for the electrical motor driven pump controller
The controllers are available as combination automatic / non-automatic with provision for
manual or automatic shutdown (an automatic shutdown is only possible after an automatic
start).
Page 16 of 42
METHODS OF STARTING
• AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor when
the pressure drops below the cut-in threshold.
• MANUAL START
The motor can be started by pressing the START push button, regardless of the system
pressure.
• REMOTE MANUAL START
The motor can be started from a remote location by momentarily closing a contact of a
manual push button.
• REMOTE AUTOMATIC START, DELUGE VALVE START
The motor can be started from a remote location by momentarily opening a contact connected
to an automatic device.
• EMERGENCY START
The motor can be started manually by using the emergency handle. This handle can be
maintained in a closed position.Important: to avoid damaging the contactor, it is
recommended to start the motor in this manner:1) Shutdown the main power by using the
main disconnect means,2) Pull the emergency handle and lock it in closed position,3) Turn
the power back on by using the main disconnect means.
• SEQUENTIAL START
In case of a multiple pump application, it may be necessary to delay the automatic (pressure
drop) starting of each motor to prevent simultaneous starting of all motors.
• FLOW START, HIGH ZONE START
The pump can be started by opening/closing a contact on the FLOW/ZONE START/STOP
input.
• WEEKLY START
The engine can be started (and stopped) automatically at the preprogrammed time.
• TEST START
The motor can be started manually by pressing the run test button.
METHODS OF STOPPING
• MANUAL STOP
Manual stop is done by pressing the priority STOP push button. Note that pressing the stop
push button will prevent the motor from restarting as long as the button is pressed, plus a two
second delay.
• AUTOMATIC STOP
Automatic stop is possible only after an automatic start and this function has been activated.
When this function is enabled, the motor is automatically stopped 10 minutes after the
restoration of the pressure (above the cut-out threshold) given that no other run cause is
present.
• FLOW STOP, HIGH ZONE STOP
If the controller has been started by the FLOW/ZONE START/STOP input and the signal has
returned to normal, the motor will be stopped given that no other run cause is present.
• EMERGENCY STOP
The emergency stop is always possible in any starting condition and is done by using the
main
disconnecting means located on the door.
Page 17 of 42
METHODS OF STARTING / STOPING for the Jockey pump controller
METHODS OF STARTING
• AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure
sensor when pressure drops below the cut-in threshold.
• MANUAL START
The motor can be started by pressing the START push button, regardless of the
system pressure.
METHODS OF STOPPING
• MANUAL STOP
Manual stop is done by pressing the priority STOP push button. Note that pressing
the stop push button will prevent the motor from restarting as long as the button is
pressed, plus a two seconds delay.
• AUTOMATIC STOP
The motor is automatically stopped after the restoration of the pressure (above the
cut-out threshold), after a programmable run period timer.
• EMERGENCY STOP
The emergency stop is always possible in any starting conditions and is done by
using the disconnect switch located on the door.
Page 18 of 42
4.1. PREVENTIVE MAINTENANCE ACTIVITIES, CORRECTIVE MAINTENANCE
ACTIVITIES, ROUTINE & MAINTENANCE WHICH INCLUDES PERIODIC
INSPECTION, CLEANING PROCESS.
This chapter shall provide the minimum requirements for the routine inspection, testing, and
maintenance of fire pump assemblies.
Table 4.1 shall be used to determine the minimum required frequencies for inspection,
testing, and maintenance.
Alternative Inspection, Testing, and Maintenance Procedures. In the absence of
manufacturer’s recommendations for preventive maintenance, Table 4.2 shall be used for
alternative requirements.
Auxiliary Equipment.
The pump assembly auxiliary equipment shall include the following:
1. Pump accessories as follows:
A. Pump shaft coupling
B. Automatic air release valve
C. Pressure gauges
D. Circulation relief valve (not used in conjunction with diesel engine drive with heat
exchanger)
2. Pump test device(s)
3. Pump relief valve and piping (where maximum pump discharge pressure exceeds the
rating of the
system components or the driver is of variable speed)
4. Alarm sensors and indicators
5. Right-angle gear sets (for engine-driven vertical shaft turbine pumps)
6. Pressure maintenance (jockey) pump and accessories
Page 19 of 42
Table 4.1 Alternative Fire Pump Inspection, Testing, and Maintenance
Procedures
Page 20 of 42
Page 21 of 42
Page 22 of 42
Table 4.2 Summary of Fire Pump Inspection, Testing, and Maintenance
Page 23 of 42
Table 4.3 Summary of Component Replacement Testing Requirements
Page 24 of 42
4.2. RECOMMENDED MAINTENANCE SCHEDULES AND FAULT FINDING
TABLE. & TROUBLESHOOTING
This chapter contains a partial guide for locating pump troubles and their possible causes The causes
listed here are in addition to possible mechanical breakage that would be obvious on visual
inspection. In case of trouble, it is suggested that those troubles that can be inspected easily should
be corrected first or eliminated as possibilities.
Page 25 of 42
Adjust impellers according to manufacturer’s instructions.
Page 27 of 42
Possible Causes of Fire Pump Troubles.
Page 28 of 42
Maintenance of Fire Pump Controllers After Fault Condition.
• Introduction.
In a fire pump motor circuit that has been properly installed, coordinated, and in service prior
to the fault, tripping of the circuit breaker or the isolating switch indicates a fault condition in
excess of operating overload. It is recommended that the following general procedures be
observed by qualified personnel in the inspection and repair of the controller involved in the
fault. These procedures are not intended to cover other elements of the circuit, such as
wiring and motor, which can also require attention.
• Caution.
All inspections and tests are to be made on controllers that are de-energized at the line
terminal, disconnected, locked out, and tagged so that accidental contact cannot be made
with live parts and so that all plant safety procedures will be observed.
• Enclosure.
Where substantial damage to the enclosure, such as deformation, displacement of parts, or
burning has occurred, replace the entire controller.
• Circuit Breaker and Isolating Switch.
Examine the enclosure interior, circuit breaker, and isolating switch for evidence of possible
damage. If evidence of damage is not apparent, the circuit breaker and isolating switch can
continue to be used after the door is closed. If there is any indication that the circuit breaker
has opened several short-circuit faults, or if signs of possible deterioration appear within
either the enclosure, circuit breaker, or isolating switch (e.g., deposits on surface, surface
discoloration, insulation cracking, or unusual toggle operation), replace the components.
Verify that the external operating handle is capable of opening and closing the circuit breaker
and isolating switch. If the handle fails to operate the device, this would also indicate the
need for adjustment or replacement.
• Terminals and Internal Conductors.
Where there are indications of arcing damage, overheating, or both, such as discoloration
and melting of insulation, replace the damaged parts.
• Contactor.
Replace contacts showing heat damage, displacement of metal, or loss of adequate wear
allowance of the contacts. Replace the contact springs where applicable. If deterioration
extends beyond the contacts, such as binding in the guides or evidence of insulation
damage, replace the damaged parts or the entire contactor.
• Return to Service.
Before returning the controller to service, inspect for the tightness of electrical connections
and for the absence of short circuits, ground faults, and leakage current. Close and secure
the enclosure before the controller circuit breaker and isolating switch are energized. Follow
operating procedures on the controller to bring it into standby condition.
Page 29 of 42
5. INTERFACE DETAILS WITH OTHER SYSTEMS:
Terminal Strip Descriptions for Diesel controller
Page 30 of 42
Terminal Strip Descriptions for Electrical controller
Page 31 of 42
6. MANUFACTURE /SUPPLIER DETAILS
Page 32 of 42
7. SCHEMATIC DRAWINGS/SINGLE LINE DIAGRAMS
Page 33 of 42
Page 34 of 42
Page 35 of 42
Page 36 of 42
Page 37 of 42
Page 38 of 42
Page 39 of 42
8. TRAINING AGENDA
The instruction program consists of two sessions, class room and field sessions. During the class
room session all the trainees will get the information regarding the type of Fire Pumps installed, how it
operates, how it is to be maintained. In the field session, the trainees will familiarize with the location
of the fire pump Upon completion of both class room and field sessions all the trainees will have
thorough information regarding the operation and maintenance of the system.
MAX NO OF TRAINEES
TRAINING SUBJECT DURATION
PER SESSION
Introduction 1 Hour 10 People
System Description & Equipment
Schedule
Operation with Schematic 1 Hour
Questions
Site Presentation operations and 1 Hour
maintenance)
Questions
9. TRAINING AIDS
Page 40 of 42
10. TRAINING RECORDS
ATTENDANCE SHEET
Page 41 of 42