PulsaFeeder MicroTrac Tech Sheet
PulsaFeeder MicroTrac Tech Sheet
inhibitor in cooling
tower systems. Featuring innovative toroidal sensor technology, the MicroTrac provides an economical control platform that is not susceptible to
sensor fouling and never requires calibration! The MicroTrac toroidal conductivity sensor is factory calibrated for the life of the probe eliminating
routine calibrations saves you valuable service time and money. By design, the MicroTrac toroidal conductivity sensor has no exposed electrodes,
which means that there is nothing to wear out or foul. When installed according to the manufacturer’s instructions, the need for routine sensor removal
and cleaning is virtually eliminated.
The MicroTrac measures the conductivity of the cooling tower recirculating water via a toroidal conductivity sensor. The controller activates two
independent relay outputs based on bleed and a selectable feed mode of operation. The MicroTrac conductivity controller has a 0 - 9,999 μS/cm
range, making it ideal for other applications as well, such as rinse, industrial process, wastewater, etc.
CONTROLS
Timers
• Water meter pulse timer
• Percent timer
• % post bleed timer
• Limit timer
• Alarm output
ENGINEERING DATA
Controller Specifications Sensor Specifications
Enclosure IP65 / NEMA 4X Maximum Temperature 1220F / 500C
Temperature Range 1220F / 500C Flow Switch Activate Flow Rate Approx. 1 GPM / 3.78 LPM
Power Supply 90 VAC – 240 VAC / 50/60Hz / 5A Conductivity Temp. Compensation Range 320F - 1220F / 00C - 500C
Line Voltage @ 240VA per Relay (2 Amps @ Maximum Pressure 125 PSI (8.6 BAR)
Control Output
120VAC)) Flow Switch Materials of Construction PVC and Glass Filled Polypropylene
Display LCD Sensor Type Toroidal Conductivity
Set Point Range 0 - 9,999 μS/cm Cable Length, Standard 15’ / 4.5m
Set Point Differential (Hystersis) Fixed 5% below the set point Cable Length, Maximum 100’ / 30.5m
0.5” Standard Thread-Excludes Tee and
Thread Size
Reducer
Maximum Outside Diameter 1.5” / 38mm-Excludes Tee and Reducer
Materials of Construction Virgin Polypropylene
DIMENSIONS