Operating Manua Scheider
Operating Manua Scheider
GMA
Gas-Insulated Switchgear up to 24 kV
Operating Instructions
www.schneider-electric.com
Manufacturer:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-0
7 +49 (0) 9 41 46 20-418
Service:
Schneider Electric Sachsenwerk GmbH
Rathenaustrasse 2
D-93055 Regensburg
Germany
( +49 (0) 9 41 46 20-0
7 +49 (0) 9 41 46 20-418
GMA Content
1 Safety provisions............................................................................... 6
2 Technical data..................................................................................... 7
2.1 Nameplate........................................................................................................ 7
2.3 Technical data for electrical control and operating devices . ........................... 8
2.4 Utilization in line with the intended purpose..................................................... 9
2.5 Applied standards.......................................................................................... 10
2.6 Environmental and operating conditions.........................................................11
2.7 Disposal after the end of the service life.........................................................11
3 Variants overview............................................................................. 12
6 Operation.......................................................................................... 19
6.2 Interlocks........................................................................................................ 21
6.2.1 Internal mechanical interlocks of the panel............................................... 21
6.2.2 Mechanical lock-out with cylinder lock (optional)....................................... 21
6.2.3 Mechanical interlock with padlocks (optional)........................................... 21
6.2.4 Electromagnetic interlocks......................................................................... 22
6.3 Operating specifications................................................................................. 23
6.4 Operation – Circuit-breaker............................................................................ 24
6.4.1 Charging the circuit-breaker’s energy storing device................................ 24
6.4.2 Switching operations on the circuit-breaker............................................... 25
6.5 Operation - Switch disconnector panel.......................................................... 28
6.7 Standard switching operations in circuit-breaker panels................................ 32
6.7.3 Connecting busbar sections with bus section coupler............................... 33
6.8 Earthing the busbar........................................................................................ 34
6.8.1 Earthing the busbar with earthing device on the cable connection
via the circuit-breaker of a feeder panel.................................................... 34
6.8.2 Earthing the busbar by means of the bus section coupler......................... 35
9 Maintenance..................................................................................... 43
9.1 Safety provisions............................................................................................ 43
9.2 Maintenance schedule................................................................................... 43
9.3 Cleaning......................................................................................................... 44
9.4 Corrosion protection....................................................................................... 44
9.5 Replacement of components and panels....................................................... 44
9.6 Lubrication instructions.................................................................................. 45
10 Annex................................................................................................ 47
10.1 Auxiliary products........................................................................................... 47
10.2 Operation accessories................................................................................... 47
This Technical Manual cannot describe every imaginable individual case or every
customer-specific version of the product. For information which is not included in this
manual, please contact the manufacturer.
As our products are subject to continuous further development, we reserve the right
to make changes regarding the standards, illustrations and technical data described
in this Technical Manual.
All dimensions specified in this manual are in millimeters.
Reference documents
The following additional documents must be complied with:
■■ purchase agreement with the stipulations regarding the switchgear-specific
equipment and the legal details
■■ the appropriate switchgear-specific circuit diagrams / documentation
■■ Assembly Instructions for GMA series (no. AGS 531 526-01)
■■ the Operating Manuals of the devices installed in the switchgear (e.g. IVIS,
devices in low-voltage compartment)
■■ the Switchgear Configuration “GMA”
■■ the Technical Manual for the use and handling of the insulating gas sulphur
hexafluoride SF6 (no. AGS 535 051-01)
■■ Selection lists for H.V.H.R.C. fuses of approved suppliers can be provided on
request.
"Danger!"
This danger symbol warns about dangerous electrical voltage.
Contact with voltage may result in fatal injury!
"Warning!"
This danger symbol warns about the risk of injury. Please comply
with all the provisions identified by this symbol in order to avoid
death or serious injury.
"Important:"
This instruction symbol is used for information which is important to
avoid material damage.
The work described in this manual may only be performed by specialist electricians
who have proved their experience with the GMA series (training certificate) and the
applicable safety provisions.
Applicable standards and ■■ Common regulations for high-voltage switchgear and control gear:
regulations: IEC 62271-1
■■ Use and handling of sulphur hexafluoride (SF6) in high-voltage switchgear: IEC
62271-303
■■ The locally applicable accident prevention, operating and work instructions
must be complied with.
■■ Installation: IEC 61936-1/HD 637 S11
■■ Operation of electrical equipment: EN 50110-11
1
The national standards applicable in the country where the equipment is to be
installed must be complied with.
Danger!
Before starting work on high-voltage components, de-energize
the system, verify it for zero voltage and earth the system in ac-
cordance with the applicable safety rules pursuant to EN 50110-1.
Warning!
After removal of covers, operator safety in accordance with IEC
62271-200 may be restricted if the appropriate part of the switch-
gear unit has not been isolated from the power supply.
Danger!
Before performing work in the drive area of the switchgear panels,
switch off the supply voltage and prevent it from being switched
ON again.
Warning!
There is a risk of injury when working on the drive mechanism.
Before commencing work, release the energy-storing device by
– the OFF-ON-OFF (Open/Close/Open) operating sequence on the
circuit-breaker
– closing via the make-proof earthing switch.
Behaviour in case of incidents or For the case of an internal fault, the GMA switchgear features pressure relief ports
accidents which prevent the panels and the switchgear unit from bursting.
In case of fire or of internal faults, toxic and caustic decomposition products may be
produced. Comply with the locally applicable accident and safety provisions.
In case of personal injury, take first-aid measures or cause them to be taken.
2.1 Nameplate
1 GMA 12 – 25 - 04
2 TD137501-01 2006 3
IEC 62271-200
12 1250 50
75 25 1
28
E1 M2
4
0.03 0.02 0.014
1.3
AFL 16kA 1s
110 V DC IR busbar 1250A
Operating and Installation Instructions: 531521, 531526
Fig. 1
Nameplate on the operating cover (front side) of the switchgear panel
1 Type designation
2 Serial number
3 Year of construction
4 Technical data
Blocking coil Blocking coils prevent the circuit breaker from being closed and opened via the
pushbuttons “ON“ or “OFF“, as well as actuation of the interrogating slides of the
disconnectors and earthing switches. In deenergized condition, blocking coils are
always in “blocked” condition.
Auxiliary switch Auxiliary switches are always actuated directly by the switch shaft via an intermedia-
te linkage. Their position always corresponds to that of the main contacts
The switching functions have been set in the factory according to the circuit diagram.
Power consumption
DC AC 50/60 Hz
approx. [W] approx. [VA]
Closing release 160 160
Opening release without auxiliary spring 160 160
energy store
Opening release with auxiliary spring 25 25
energy store
Undervoltage release 15 15
Secondary release - 12
Blocking coil 12 12
Motor 200 - 250 200 - 250
Please enquire at the manufacturer’s for details of the motor’s starting current. The
supply voltage data is required to this effect.
Disclaimer of liability The manufacturer shall not be held responsible for damage which occurs if
■■ instructions in this Technical Manual are not complied with,
■■ the switchgear is not operated according to its intended use (see above),
■■ the switchgear is assembled, connected or operated improperly,
■■ accessories or spare parts are used which have not been approved by the
manufacturer,
■■ the switchgear is converted without the manufacturer’s approval, or if inadmissi-
ble parts are attached.
No liability is accepted for parts provided by customers, e.g. current transformers.
Fig. 2
Circuit-breaker panel with current and voltage transformers, panel width 600 mm
1 Busbar connectors (in the coupling 7 Earthing link bar 14 Low-voltage compartment with
tank / end tank), shown: right-hand 8 Cable compartment cover control device
side; left-hand side analogous 9 Cable connection three-fold com- 15 Busbar
2 Circuit-breaker bination 16 Disconnector
3 Toroidal-core current transformer 10 Manual operator interface 17 Earthing switch
4 Disconnecting device for voltage 11 Instrument niche
transformer (optional) 12 Voltage detection systems
5 Voltage transformer (optional) 13 Pressure gauge (temperature-
6 Adjustable cable supports compensated)
Fig. 3 Fig. 4
Switchgear panel with circuit-breaker Switchgear panel with circuit-breaker, voltage transformer,
double cable connection
Fig. 5 Fig. 6
Switchgear panel with switch disconnector Switchgear panel with switch fuse combination
10 7 8 2
9
5
Fig. 7
3 single panels, showing all function and control elements regarding the gas com-
partment as an example These have been shown in graded grey shades to reflect
the various insulating gas compartments.
1 Switchgear panel
2 Busbar coupling tank
3 Gas connector socket
4 Check valve
5 Pressure gauge
6 Gas-proof electrical bushing
7 Vave open (code 2)
8 Vave closed (code 0)
9 Pressure relief port
10 Busbar end tank
Important:
The switchgear-specific gas compartment diagram must be complied
with.
3 2 1 4 1 3 2
4
Fig. 8 Fig. 9
Pressure gauge without remote signal- Pressure gauge with remote signalling
ling contacts contacts
1 Pointer 1 Pointer
2 Pointer in the green area (Ready 2 Pointer in the green area (Ready
for operation) for operation)
3 Pointer in the yellow area (Preal- 3 Pointer in the yellow area (Preal-
arm) arm)
4 Pointer in the red area (Main 4 Pointer in the red area (Main
alarm) alarm)
Important:
For a description of all functions and messages of the IVIS system,
please refer to the separate Operating Manual “IVIS”
(No. AGS 531 757-01).
Important:
Comply with the manufacturer’s Operating Manual of the voltage indi-
cators used.
All three phases L1, L2 and L3 must always be checked together.
Close non-used socket-contacts using a cap.
Fig. 12
Socket-contacts for HR system
Fig. 11
Voltage indicator unit (HR-ST)
Manufacturer: Horstmann GmbH
If IVIS is used, phase comparison can be performed by means of the phase compa-
rator MS 100 (Fig. 13, ref. no. AGS C26320-01).
Phase comparators are optionally available and not included in the scope of sup-
plies.
Fig. 13
Phase comparator MS 100
14
13
2
3 12
4
5 11
6
10
7
8 9
Fig. 14
Operator interface “Circuit-breaker”
1 Nameplate
2 Opening for operation of the disconnector
3 Position indicator of disconnector
4 Circuit-breaker position indicator DISCHARGED / CHARGED
5 Circuit-breaker switch position indicator
6 Circuit-breaker OFF pushbutton
7 Circuit-breaker ON pushbutton
8 Circuit-breaker operations counter
9 Insertion port for mechanical charging of the circuit-breaker’s energy storing device
10 Unlocking slide for cable compartment cover
11 Position indicator of earthing switch
12 Insertion port for operation of the earthing switch
13 Mechanical interrogation interlock of insertion ports (interrogation slide)
14 Mechanical lockout mechanism with lock (optional)
1
1 Nameplate
8 2 Position indicator of switch discon-
nector
3 Opening for operation of the
switch disconnector
2 7 4 Mechanical interrogation interlock
3 of insertion ports (interrogation
6
slide)
4
5 5 Unlocking slide for cable compart-
ment cover
6 Position indicator of earthing
switch
7 7Insertion port for operation of the
earthing switch
8 Mechanical lockout mechanism
with lock (optional)
Fig. 15
Operator interface “Switch disconnector”
1 Nameplate
1 2 Position indicator of disconnector
3 Opening for operation of the dis-
connector
9 4 Indication of fuse tripping
(H.V.H.R.C. fuses)
8 green: no fuse tripped
red H.V.H.R.C. fuse tripped
2 7 5 Unlocking slide for cable compart-
3 ment cover
6
6 Position indicator of earthing
4
5 switch
7 Insertion port for operation of the
earthing switch
8 Mechanical interrogation interlock
of insertion ports (interrogation
slide)
9 Mechanical lockout mechanism
with lock (optional)
Fig. 16
Operator interface “Switch disconnec¬tor with fuse”
6.2 Interlocks
Warning!
Complete switchgear interlocking can only be ensured with com-
plete locking devices.
Important:
Please note the purchase contract and the switchgear-specific circuit
diagram as regards the design of the interlocking systematics.
6.2.2 Mechanical lock-out with cylinder lock (optional, see also Fig.
16 to Fig. 18)
If the lever for actuation of the disconnector or earthing switch has not been remo-
ved, the key of the mechanical lock-out can neither be turned nor removed.
1 2
Fig. 17
1 Interlock flaps for ON/OFF pushbutton
2 Insertion port for earthing switch blocked (disconnector analogous)
Important:
–– If no blocking coils are being used for the locking devices, a me-
chanical lock-out with cylinder or U lock must be provided.
–– In case of failure of the supply voltage, all electrical interlocks are
in their “locked” position. Measure: Re-establish supply voltage.
ON
OFF
blocking coil
Fig. 18
Blocking coil interlocks in GMA switchgear with bus section coupler
1 2
Fig. 19
Blocking coils in a circuit-breaker panel
1 Blocking coil on ON pushbutton of circuit-breaker
2 Blocking coil on interrogation slide
Switchgear panel with switch disconnector, earthing switch and disconnector with fuse, earthing switch
Important:
These accessories are supplied together with the panel. The panel
may only be operated by means of these accessories (see page 47).
■■ After each switching operation for which you have used an actuating lever/a
crank, remove the actuating lever and store it in the tool board.
Warning!
The ON - OFF movements need to be fully completed (to their
stop).Never let off detachable lever before the switching operation
has been completed. Risk of injury as the lever might rebound if it
is not actuated to its mechanical stop.
Important:
■■ While the supply voltage is not available, an undervoltage release
(optional) has dropped out.
■■ Comply with interlocking conditions in Chapter 6.2
Charging by means of a motor The energy storing device is charged automatically, as soon as the supply voltage is
available.
The position indicator of the energy storing device indicates the “charged” condition.
charge
Fig. 20
Charge the circuit-breaker’s energy storing device (closing spring) manually
1 Energy storing device charged
Important:
The energy storing device can be charged again immediately (manu-
ally) after ON actuation. When the supply voltage is on, the energy
storing device is charged automatically via the motor.
OFF ON
Fig. 21
Circuit-breaker. Switching ON/OFF.
Pos. Position indicator Position indicator Circuit- Opening spring Possible operating
Energy-storing device breaker sequence
(closing spring)
released, is charged
2 charged OFF C–O
via C
3 released ON charged O
charged, is re-charged
4 charged ON O–C–O
via C
Important:
Motor drive on disconnector (optional): During actuation of the interro-
gation slide or while the actuating lever is inserted, the motor circuit is
interrupted. For emergency manual actuation moving the detachable
lever into ON position, first a short pressure must be exercised in OFF
position (to overcome the dead center in the drive linkage), and vice
versa.
Initial situation:
■■ Circuit-breaker OFF
■■ Disconnector OFF
■■ Earthing switch OFF
Switching ON manually: 1. Actuate interrogating lever to the right to release the appropriate insertion port.
2. Insert actuating lever and move it clockwise
3. Remove crank
Switching OFF manually: 1. Push interrogating lever to the right to release the appropriate insertion port
2. Insert actuating lever and move it counter-clockwise.
3. Remove crank.
ON OFF
Fig. 22
Disconnector. Switching ON/OFF.
Important:
Motor drive on earthing switch (optional): During actuation of the inter-
rogation slide or while the actuating lever is inserted, the motor circuit
is interrupted. For emergency manual actuation moving the detachable
lever into ON position, first a short pressure must be exercised in OFF
position (to overcome the dead center in the drive linkage), and vice
versa.
Initial situation:
■■ Circuit-breaker OFF
■■ Disconnector OFF
■■ Earthing switch OFF
Switching ON manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port.
2. Insert actuating lever and move it clockwise
3. Remove actuating lever
Switching OFF manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port
2. Insert actuating lever and move it counter-clockwise.
3. Remove actuating lever.
ON OFF
Fig. 23
Earthing switch. Switching ON/OFF.
Warning!
If the main alarm of the pressure gauge is issued, the switch dis-
connector must not be operated.
Important:
Motor drive on switch disconnector (optional): During actuation of
the interrogation slide or while the actuating lever is inserted, the
motor circuit is interrupted. For emergency manual actuation moving
the detachable lever into ON position, first a short pressure must be
exercised in OFF position (to overcome the dead center in the drive
linkage), and vice versa.
Switching ON manually: 1. Actuate interrogating lever to the right to release the appropriate insertion port.
2. Insert actuating lever and move it clockwise
3. Remove lever.
Switching OFF manually: 1. Push interrogating lever to the right to release the appropriate insertion port.
2. Insert actuating lever and move it counter-clockwise.
3. Remove lever.
ON OFF
Fig. 24
Switch disconnector. Switching ON/OFF.
Initial situation:
■■ Switch disconnector OFF
■■ Earthing switch OFF
Switching ON manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port.
2. Insert actuating lever and move it clockwise.
3. Remove actuating lever.
Switching OFF manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port.
2. Insert actuating lever and move it counter-clockwise.
3. Remove actuating lever.
ON OFF
Fig. 25
Earthing switch. Switching ON/OFF.
Warning!
If the main alarm of the pressure gauge is issued, the switch dis-
connector must not be operated.
Switching ON manually: 1. Actuate interrogating lever to the right to release the appropriate insertion port.
2. Actuate detachable lever speedily to the left until the breaker mechanism has
latched (approx. 95°) (thus, the opening spring is charged).
Subsequently, actuate detachable lever speedily to the right (approx. 115°) until
closing is complete (at the same time, the closing spring is charged and set
free).
3. Remove detachable lever immediately afterwards.
Switching OFF manually: 1. Push interrogating lever to the right to release the appropriate insertion port
2. Insert detachable lever.
3. Actuate detachable lever speedily to the left (approx. 20°) until opening is
complete.
OFF
ON
charge
Fig. 26
Switch disconnector. Switching ON/OFF and charging.
Initial situation:
■■ Switch disconnector OFF
■■ Earthing switch OFF
Switching ON manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port.
2. Insert actuating lever (red) and turn it clockwise (approx. 95°).
3. Remove actuating lever.
Switching OFF manually: 1. Actuate interrogating lever to the left to release the appropriate insertion port
2. Insert actuating lever and move it counter-clockwise.
3. Remove actuating lever.
ON OFF
Fig. 27
Earthing switch. Switching ON/OFF.
A A
B C
Initial situation Switch outgoing feeder cable ON Switch outgoing feeder cable
–– Circuit-breaker OFF 1. Switch disconnector OFF
–– Disconnector OFF ON (A). 1. Switch circuit-breaker
–– Earthing switch OFF 2. Switch circuit-breaker OFF (C).
ON (B). 2. Switch disconnector
OFF (A).
D D
L R Initial situation
■■ Circuit-breaker OFF
■■ Disconnector OFF
■■ Earthing switch OFF
Fig. 34
Initial situation
D C A B
Fig. 35
Connect/disconnect busbar sections
Disconnect busbar sections
1. Switch circuit-breaker (D) OFF.
2. Switch both disconnectors (A) and (B) OFF.
Important:
For all switching operations, comply with the interlocking conditions
(Chapter 6.2) and the operating specifications in Chapter 6.3.
Important:
Comply with the manufacturer’s information regarding the earthing
device and the earthing adapter.
B A
D C
De-earthing busbar
(See Fig. 39)
1. Switch circuit-breaker OFF (D).
2. Switch disconnector (B) OFF.
3. Switch earthing switch (A) ON.
4. Remove earthing device and earthing adapter.
5. Connect high-voltage cable to cable connection in surge-proof condition.
L R Initial situation:
Circuit-breaker OFF
Both disconnectors OFF
Both earthing switches OFF
A C
D B
Fig. 39
Earthing/de-earthing left-hand busbar section
E F
Fig. 40
Earthing/de-earthing right-hand busbar section
Ordering data The following data must be specified in the Purchase Order:
■■ Transformer rated power
■■ Transformer operating voltage
■■ Rated current of the selected H.V.H.R.C. fuse links.
Selection lists and applicable Selection lists of approved suppliers for H.V.H.R.C. fuses can be provided as requi-
standards red. These selection lists take the following standards and regulations into account:
■■ Protection of distribution transformers in accordance with IEC 60787, VDE
0670, part 402
■■ Fuse links in acc. with IEC 60282-1 or DIN 43625 (striker type “medium” with
mit max. initial tripping force of 80 N)
■■ Specifications of IEC 62271-105
■■ Max. ambient temperature for switchgear: 40 ºC according to
IEC 62271-1, identical with max. ambient temperature for the switchgear within
the housing of a packaged substation in accordance with IEC 62271-202.
■■ No transformer operation during an overload condition
■■ Temperature-rise limits within the switchgear enclosure
Series Supplier
H.V.H.R.C. fuse links with temperature limiter SIBA
H.V.H.R.C. backup fuses with overload protection (temperature EFEN
limiter)
H.V.H.R.C. fuse links, type IKUS, with thermo-striker JEAN MÜLLER
38max.
“D” or “e”
ø20max.
ø45±1
striker
ø88 max.
pin
ø88 max.
ø50 min.
33+2 33+2
dimensions in mm
Fig. 41
Dimensions of fuse links
Important:
As the earthing switches are arranged upstream and downstream of
the fuses, the fuses can be replaced without using insulating equip-
ment.
The fuse symbol on the operator interface indicates mechanically if one of the fuses
has melted (red marking, Fig. 46, item 1). The switch disconnector is switched OFF
automatically by the fuse tripping.
Transformer outgoing feeder If the transformer outgoing feeder is designed without an all-pole fuse tripping, this
without all-pole fuse tripping feature is indicated by an information sign. This sign is located near the fuse symbol
on the operator interface.
Important:
Melting of the fuse does not trip the switch disconnector.
In this case, the switch disconnector is equipped with a snap-action drive (SFU) and
must be switched OFF separately (manually or electrically, depending on design).
Replacement of short fuse GMA switchgear with a rated voltage of 24 kV may also be operated with an ope-
links in switchgear with a fuse rating voltage of 12 kV. An adapter is available to enable the use of an H.V.H.R.C.
dimension of e = 442 mm fuse link with the standard dimension for 12 kV, dimension “e”=292 mm for a fuse
dimension of “e”=442 mm.
The fuse links are not included in the scope of supply.
Replacement of fuse kits: 1. Clean contact surfaces (brand-new fuse link, adapter and grip end) using a
non-fibrous cloth, in case of severe soiling, use a cleaning product. Apply a thin
and uniform film of lubricant KL, clean and grease.
2. Introduce the brand-new fuse link with contact strip with striker into the grip end
contact by turning it slightly. Secure fuse link from being removed by tightening
clamping screw in the grip end.
Fasten the adapter on the opposite contact end of the fuse link without striker.
Fig. 42 Fig. 43
Attachment of fuse link grip end Lock “cam” on the grip end in the re-
cess of the insulating tube
Fig. 44
Assembly of short fuse links
Fig. 45
Assembly of short fuse links
Description of the steps for fuse 1. Switch the earthing switch ON.
replacement: 2. Unlock the fuse with cover and open compartment double-bit key.
3. Fold fuse compartment cover forward and down, and remove it.
4. Pull grip end with fuse link out without turning it.
5. Remove grip end with fuse link using both hands.
6. Release clamp screw in the grip end.
7. Pull fuse link out of the grip end by turning it slightly.
8. Prepare fuse link for insertion.
–– Clean contact surfaces on the grip end and on the brand-new fuse link
using a non-fibrous cloth, in case of severe soiling, use a cleaning product.
–– Apply a thin and uniform coat of lubricant KL
–– Introduce the contact end with striker of the brand-new fuse link into the
contact of the grip end by turning it slightly.
–– Secure fuse link from being removed by tightening clampscrew in the grip
end.
9. Push grip end with fuse link inwards without turning it.
10. The “cam” on the grip end must engage in the recess of the insulating tube (see
Fig. 43).
11. Reinsert fuse cover, close it using the double-bit key, and lock it. Press interlo-
cking slide (3) down.
5
4
Fig. 46 Fig. 47
Replacement of fuses Removing the fuse link
1 Fuse tripping indicator (red)
2 Earthing switch ON
3 Unlock fuse cover
4 Double-bit key for opening
5 Fold fuse shutter forward, and
remove it
Fig. 48
Checking the all-pole mechanical fuse
tripping
Fig. 50
Disconnecting device for voltage trans-
Fig. 49 former and insertion port.
Disconnecting device for voltage trans- 1 Lock pin
former 2 Detachable lever
Fig. 51
Removing the cover from the instrument recess.
1 1
2
2
3 3
Fig. 52 Fig. 53
Switching the voltage transformer OFF Switching the voltage transformer ON
1 Position indicator reads: 1 Position indicator reads:
Voltage transformer OFF (O) Voltage transformer ON (I)
2 Lock pin 2 Lock pin
3 Detachable lever 3 Detachable lever
Warning!
Refer to the safety provisions on page 6.
Important:
In case of humidity and condensation or air pollution (dust, smoke or
corrosive gases), the maintenance intervals must be adapted to the
actual conditions. In case of ambiguities or irregularities, please contact
the manufacturer’s Service Center immediately.
Insulating gas: GMA series panels have a hermetically sealed pressure system in accordance with
IEC 62271-200. It does not require servicing over its entire service life.
Switching devices: The components in the cladded high-voltage parts of the panel (vacuum circuit-brea-
ker, disconnector and earthing switch) do not require any maintenance either.
Gas tank: The pressure tanks are made of stainless, non-magnetic steel.
Warning!
Neither drill holes into nor open gas tanks. Risk of loss of insula-
ting gas.
Drive mechanisms / covers: Drive mechanisms and covers outside of the enclosure are corrosion-protected with
lasting effect. Damage to the paint, scratches and deterioration must be repaired
immediately to avoid corrosion.
9.3 Cleaning
When deposited dirt and humidity are detected, the panels must be cleaned in an
expert fashion.
When performing cleaning, make sure that the lubrication in the drive mechanisms
is not removed. If the drive mechanisms are no longer sufficiently lubricated, new
lubrication must be applied.
Warning!
Risk of injuries: The drives must not be disassembled for service
and maintenance work.
Slight contamination Clean using a dry, lint-free cloth. Depending on the degree of soiling, replace cloth
as often as necessary.
Severe soiling Use cleaning agent, 1 litre can (see page 47). The use of other cleaning agents is
not admissible.
■■ Wear protective gloves
■■ Use cleaning agents according to manufacturer‘s instructions
■■ Soak the cloth thoroughly and wipe the insulating components. Keep duration
of exposure as short as possible.
■■ Expose the cleaned surface to the air for at least two hours.
Warning!
Refer to the safety provisions on page 6.
Removing operating cover Once the operating cover has been removed, the drive is accessible from the switch-
gear front end. Refer also to the Assembly Instructions.
1. Remove the bolts (4 ea.) from the operating cover.
2. Remove the operating cover by lifting it forward.
Remount operating cover by reversing the above sequence once maintenance is
finished.
Points of lubrication: The drive is completely lubricated at the factory with lubricant KL.
All surfaces and joints in the circuit-breaker, disconnector and earthing switch drives
which are sliding on each other must be lubricated.
Important:
The following elements must not be lubricated:
■■ Motor
■■ Ball bearings
■■ Auxiliary releases
■■ Push switches
■■ Blocking coils
■■ Auxiliary switches
30 000
10 000
5000
GMA 12 – 25 - 04
Number of breaking operations n
Fig. 54
Circuit-breaker
Ir = Rated (normal) current [A]
Isc = Short-circuit breaking current [kA]
The diagram defines exclusively the maximum admissible numbers of breaking operations of the circuit-breaker as a function of
the rated normal current Ir and of the short-circuit breaking current Isc.
The data for the rated normal current Ir and the short-circuit breaking current Isc are indicated on the nameplate.
3 000 3 000
1 000 1 000
500 500
Number of breaking operations n
100 100
50 50
10 10
100
500
630
1000
10
50
100
200
500
1000
10
50
Fig. 55 Fig. 56
Switch disconnector without fuse. Transformer feeder with switch disconnector / fuse.
Rated normal current 630 A Rated normal current 200 A
Warning!
Risk of injury if the auxiliary products are handled improperly.
Comply with the safety data sheets of the auxiliary products.
Schneider Electric As our products are subject to continuous development, we reserve the
35, rue Joseph Monier right to make changes regarding the standards, illustrations and technical
CS 30323 data described in this Technical Manual. For any requests, please contact
92506 Rueil-Malmaison Cedex, France the address given below.