Space Input Data

CONE - CAMPOS 04/15/2024


Ambient Air 10:45

ADMINISTRAÇÃO

1. General Details:
Floor Area 159,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 1,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 800,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 108,0 61 0 0
SE 75,0 0 0 0

3.1. Construction Types for Exposure S


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure SE


Wall Type parede externa .47

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 159,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 340,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 1 of 46 1


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 00

1. General Details:
Floor Area 118,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 28 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 118,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 2 of 46 2


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 01

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 3 of 46 3


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 02

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 4 of 46 4


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 03

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 5 of 46 5


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 04

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 6 of 46 6


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 05

1. General Details:
Floor Area 149,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 105,0 20 0 0
SSW 33,0 0 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure SSW


Wall Type parede externa .47

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 149,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 384,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 7 of 46 7


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 06

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 8 of 46 8


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 07

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 9 of 46 9


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 08

1. General Details:
Floor Area 110,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 99,0 20 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 110,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 10 of 46 10


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 09

1. General Details:
Floor Area 110,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 114,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 11 of 46 11


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 10

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 75,0 20 0 0

3.1. Construction Types for Exposure SW


Wall Type parede externa .26
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 12 of 46 12


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 11

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 13 of 46 13


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 12

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 14 of 46 14


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 13

1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 15 of 46 15


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 14

1. General Details:
Floor Area 147,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 107,0 20 0 0
NW 33,0 20 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 147,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 376,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 16 of 46 16


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 15

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 17 of 46 17


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 16

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .26
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 18 of 46 18


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 17

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 19 of 46 19


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

GABINETE 18

1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 200,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 20 of 46 20


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

HALL

1. General Details:
Floor Area 227,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Seated at Rest
Ballast Multiplier 1,00 Sensible 230,0
Schedule 8h as 23h BTU/hr/person
Latent 120,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 166,0 20 0 0
S 166,0 0 0 0

3.1. Construction Types for Exposure W


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure S


Wall Type parede externa .47

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 227,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 271,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 21 of 46 21


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 01

1. General Details:
Floor Area 311,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 166,0 41 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 311,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 497,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 22 of 46 22


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 02

1. General Details:
Floor Area 311,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 600,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 28 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 23 of 46 23


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 03

1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 600,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 36 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 24 of 46 24


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 04

1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 600,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 36 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 25 of 46 25


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 05

1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 101,0 28 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 26 of 46 26


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 06

1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 101,0 28 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 27 of 46 27


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 07

1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 105,0 28 0 0

3.1. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 437,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 28 of 46 28


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 08

1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 542,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 29 of 46 29


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 09

1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 105,0 28 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 437,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 30 of 46 30


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 10

1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 250,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 542,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 31 of 46 31


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 11

1. General Details:
Floor Area 407,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 800,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 150,0 58 0 0

3.1. Construction Types for Exposure SW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 407,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 617,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 32 of 46 32


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 12

1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 96,0 28 0 0

3.1. Construction Types for Exposure SW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 181,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 428,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 33 of 46 33


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 13

1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 96,0 28 0 0

3.1. Construction Types for Exposure NE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 181,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 428,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 34 of 46 34


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 14

1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 400,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 178,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 527,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 35 of 46 35


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 15

1. General Details:
Floor Area 159,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 600,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 159,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 512,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 36 of 46 36


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 16

1. General Details:
Floor Area 393,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 800,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 211,0 57 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 393,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 527,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 37 of 46 37


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 17

1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 135,0 36 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 38 of 46 38


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 18

1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 135,0 36 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 39 of 46 39


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 19

1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 101,0 28 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 40 of 46 40


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

ORGÃO 20

1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 500,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 101,0 28 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 41 of 46 41


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

RECEPÇÃO

1. General Details:
Floor Area 1487,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 89,0 People
Wattage 0,86 W/ft² Activity Level Seated at Rest
Ballast Multiplier 1,00 Sensible 230,0
Schedule 8h as 23h BTU/hr/person
Latent 120,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 256,0 192 0 0
SE 256,0 192 0 0

3.1. Construction Types for Exposure SW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure SE


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 1487,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 1250,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 42 of 46 42


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

SALA CONCILIAÇÃO

1. General Details:
Floor Area 139,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 139,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 43 of 46 43


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

SALA DESCOMPRESSÃO

1. General Details:
Floor Area 173,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 90,0 16 0 0
SW 150,0 39 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

3.2. Construction Types for Exposure SW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 173,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 316,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 44 of 46 44


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

SALA TREINAMENTO

1. General Details:
Floor Area 965,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 25,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:


(No Wall, Window, Door data).

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 965,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 1175,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 45 of 46 45


Space Input Data
CONE - CAMPOS 04/15/2024
Ambient Air 10:45

SERVIDOR

1. General Details:
Floor Area 142,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0,00 W/ft² Sensible 0 BTU/hr
Schedule None Schedule None
Latent 0 BTU/hr
Schedule None
2.3. Electrical Equipment:
Wattage 0,0 Watts
Schedule 8h as 23h

3. Walls, Windows, Doors:

Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 90,0 23 0 0

3.1. Construction Types for Exposure NW


Wall Type parede externa .47
1st Window Type vidro cinza espelhado s/ cort

4. Roofs, Skylights:

Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 142,0 0 0

4.1. Construction Types for Exposure H


Roof Type laje+forro(.19)

5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.

6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).

7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 396,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F

Hourly Analysis Program v4.90 Page 46 of 46 46