Input Cone - Campos
Input Cone - Campos
ADMINISTRAÇÃO
1. General Details:
Floor Area 159,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 1,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
S 108,0 61 0 0
SE 75,0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 159,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 340,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 00
1. General Details:
Floor Area 118,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 118,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 01
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 02
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 03
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 04
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 410,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 05
1. General Details:
Floor Area 149,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 105,0 20 0 0
SSW 33,0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 149,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 384,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 06
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 07
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 08
1. General Details:
Floor Area 110,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 99,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 110,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 09
1. General Details:
Floor Area 110,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 114,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 10
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 75,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 11
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 84,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 12
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 13
1. General Details:
Floor Area 115,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 75,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 115,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 406,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 14
1. General Details:
Floor Area 147,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 107,0 20 0 0
NW 33,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 147,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 376,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 15
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 16
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 17
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
GABINETE 18
1. General Details:
Floor Area 122,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 3,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 78,0 20 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 122,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 358,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
HALL
1. General Details:
Floor Area 227,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Seated at Rest
Ballast Multiplier 1,00 Sensible 230,0
Schedule 8h as 23h BTU/hr/person
Latent 120,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 166,0 20 0 0
S 166,0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 227,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 271,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 01
1. General Details:
Floor Area 311,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 166,0 41 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 311,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 497,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 02
1. General Details:
Floor Area 311,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 03
1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 36 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 04
1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 9,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 135,0 36 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 05
1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 101,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 06
1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 101,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 07
1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SE 105,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 437,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 08
1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 542,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 09
1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 105,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 437,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 10
1. General Details:
Floor Area 187,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 187,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 542,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 11
1. General Details:
Floor Area 407,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 150,0 58 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 407,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 617,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 12
1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 96,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 181,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 428,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 13
1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NE 96,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 181,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 428,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 14
1. General Details:
Floor Area 181,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 6,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 178,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 527,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 15
1. General Details:
Floor Area 159,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 5,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 159,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 512,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 16
1. General Details:
Floor Area 393,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 12,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 211,0 57 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 393,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 527,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 17
1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 135,0 36 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 18
1. General Details:
Floor Area 244,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 135,0 36 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 244,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 467,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 19
1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 101,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
ORGÃO 20
1. General Details:
Floor Area 189,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 8,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 101,0 28 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 189,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 432,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
RECEPÇÃO
1. General Details:
Floor Area 1487,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 89,0 People
Wattage 0,86 W/ft² Activity Level Seated at Rest
Ballast Multiplier 1,00 Sensible 230,0
Schedule 8h as 23h BTU/hr/person
Latent 120,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
SW 256,0 192 0 0
SE 256,0 192 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 1487,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 1250,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
SALA CONCILIAÇÃO
1. General Details:
Floor Area 139,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 139,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 482,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
SALA DESCOMPRESSÃO
1. General Details:
Floor Area 173,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 4,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 90,0 16 0 0
SW 150,0 39 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 173,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 316,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
SALA TREINAMENTO
1. General Details:
Floor Area 965,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 25,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 965,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 1175,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F
SERVIDOR
1. General Details:
Floor Area 142,0 ft²
Avg. Ceiling Height 10,0 ft
Building Weight 101,0 lb/ft²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 10,0 CFM/person
OA Requirement 2 0,0 CFM
Space Usage Defaults ASHRAE Standard 62.1-2010
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 2,0 People
Wattage 0,86 W/ft² Activity Level Office Work
Ballast Multiplier 1,00 Sensible 245,0
Schedule 8h as 23h BTU/hr/person
Latent 205,0
BTU/hr/person
Schedule 8h as 23h
Exp. Wall Gross Area (ft²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
NW 90,0 23 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (ft²) Roof Slope (deg.) Skylight Qty.
H 142,0 0 0
5. Infiltration:
Design Cooling 0,00 CFM
Design Heating 0,00 CFM
Energy Analysis 0,00 CFM
Infiltration occurs only when the fan is off.
6. Floors:
Type Floor Above Conditioned Space
(No additional input required for this floor type).
7. Partitions:
7.1. 1st Partition Details: 7.2. 2nd Partition Details:
Partition Type Wall Partition (No partition data).
Area 396,0 ft²
U-Value 0,400 BTU/(hr-ft²-
°F)
Uncondit. Space Max Temp 95,0 °F
Ambient at Space Max Temp 77,0 °F
Uncondit. Space Min Temp 77,0 °F
Ambient at Space Min Temp 75,0 °F