CNP NM Fire Fighting System Co., Ltd.


www.nmfirepumps.com

SPLIT- CASE TYPE


CENTRIFUGAL FIRE PUMPS
(XXXXgpm@XXXpsi)
PRODUCT TYPES

Electric Motor Driven Pump Set


Diesel Engine Driven Pump Set
Containerized Pump Station
NFPA20 Package
Customer : Pump Performance Datasheet
Reference : Quotation System 24.1.1

Item number : 001 Size : SCF200-150-310@2980rpm


Service : Stages :1
Quantity :1 Based on curve number : SCF200-150-310@2980rpm Rev
Quote number : 2140094 S235013
Date last saved : 03 Aug 2024 9:51 AM

Operating Conditions Liquid


Flow, rated : 1,500.0 USgpm Liquid type : Clean Water
Differential head / pressure, rated (requested) : 110.0 m Additional liquid description :
Differential head / pressure, rated (actual) : 110.0 m Solids diameter, max : 0.00 mm
Suction pressure, rated / max : 0.00 / 0.00 bar.g Solids concentration, by volume : 0.00 %
NPSH available, rated : Ample Temperature, max : 20.00 deg C
Site Supply Frequency : 50 Hz Fluid density, rated / max : 1.000 / 1.000 kg/dm3
Performance Viscosity, rated : 1.00 cSt
Speed criteria : Synchronous Vapor pressure, rated : 0.00 bar.a
Speed, rated : 2980 rpm Material
Impeller diameter, rated : 284 mm
Material selected : Standard
Impeller diameter, maximum : 335 mm
Pressure Data
Impeller diameter, minimum : 240 mm
Maximum working pressure : 12.39 bar.g
Efficiency : 80.54 %
Maximum allowable working pressure : 25.51 bar.g
NPSH required / margin required : 4.04 / 0.00 m
Ns (imp. eye flow) / Nss (imp. eye flow) : 1,362 / 19,026 US Units Maximum allowable suction pressure : 5.17 bar.g
MCSF :- Hydrostatic test pressure : 38.27 bar.g
Head, maximum, rated diameter : 126.3 m Driver & Power Data (@Max density)
Head rise to shutoff : 14.79 % Driver sizing specification : Maximum power
Flow, best eff. point : 2,025.2 USgpm Margin over specification : 0.00 %
Flow ratio, rated / BEP : 74.07 % Service factor : 1.00 (used)
Diameter ratio (rated / max) : 84.90 % Power, hydraulic : 137 hp
Head ratio (rated dia / max dia) : 70.27 % Power, rated : 170 hp
Cq/Ch/Ce/Cn [ANSI/HI 9.6.7-2010] : 1.00 / 1.00 / 1.00 / 1.00 Power, maximum, rated diameter : 194 hp
Selection status : Acceptable Minimum recommended engine rating : 239 hp / 178 kW
200 100

180 335 mm 90

160 80

140 70
284 mm Efficiency

Efficiency - %
120 60
Head - m

100 50

80 40
240 mm
60 30

40 20

20 10

0 0
NPSHr - m

10
NPSHr
5

240

Power
Power - hp

180

120

60

0
0 500 1,000 1,500 2,000 2,500 3,000 3,500 4,000

Flow - USgpm
CNP NM FIRE FIGHTING SYSTEM CO.,LTD
Add:No.45 Xi Chong Road, Quan Tang Street, Changsha, Hunan, P.R.
China
Engine Data Sheet Zip Code:410100
Tel +86-731-84091707
Fax: +86-731-84091727

Engine Model NM6-110D Date 2020/11/19


Drawing No. NM6-110D-00 Document No. DS06110DF
239 HP @ 2900 RPM Performance Curve No. C06110DF
Rated Power
178 KW @ 2900 RPM Version A

GENERAL ENGINE DATA


Type 4 Cycle; In-line; water cooled; 6 Cylinder
Aspiration Turbocharged +Water Cooled
Bore and Stroke mm×mm 110x125
Cylinder Liner Type Wet Dry
Displacement L 7.127
Compression Ratio 16.8 :1
Firing Order 1-5-3-6-2-4
Combustion System Direct Injection
Rotation Viewed from flywheel Counter Clockwise
Valves Per Cylinder Intake :1 Exhuast :1
Intake mm 0.3
Valves lashes at cold
Exhaust mm 0.35
Charge Air Cooling Type Raw Water
Dry Weight Approx. kg 1070
Dimension Approx. (L*W*H) mm 1685*1080*1520
Flywheel/ Flywheel House Dimension 11.5"/ SAE 2
EXHAUST SYSTEM
Exhaust Gas Temp. ℃ 540 @ 2900rpm
Exhaust Gas Flow kg/h 1342 @ 2900rpm
Max. Allowable Back Pressure kpa 7.5
Minimum Exhaust Pipe Diameter DN 125
Minimum exhaust pipe diameter is based on 6 meter of pipe, one elbow, and a silencer. Pressure drop no greater than one half the
max. allowable back pressure

AIR INTAKE SYSTEM


Air Cleaner Type Dry Type
Air Flow kg/h 1290 @2900rpm
Max. Allowable Air Inlet Restriction kpa 5
LUBRICATION SYSTEM
Oil Capacity L 26
Engine Normal Operating Sump Oil Temp. ℃ 80-120
Normal Operating Oil Pressure Range bars 3.4~5.0
Oil Pressure at Idle bar >0.98
COOLING SYSTEM
Coolant Capacity - Engine + Heat Exchanger L 26
Start Open ℃ 76
Thermostat Range
Full Open ℃ 86
Coolant Pressure Cap bar 0.9
Raw Water Working Pressure Range at Heat Exchanger bar 5
Engine Normal Operating Coolant Temp. ℃ 76-95
Engine Coolant Flow at Full Load m3/h 14
CNP NM FIRE FIGHTING SYSTEM CO.,LTD
Add:No.45 Xi Chong Road, Quan Tang Street, Changsha, Hunan, P.R.
China
Engine Data Sheet Zip Code:410100
Tel +86-731-84091707
Fax: +86-731-84091727

Minimum Raw Water Flow @ Engine Speed (rpm) 2900


3
Raw Water Temperatures to 16 ℃ (m /h) 6
3
Raw Water Temperatures to 38 ℃ (m /h) 8
Raw Water Inlet G1"
Raw Water Pipe Size
Raw Water Outlet G1 1/4"
HEATER SYSTEM
Wattage W 3000
Voltage AC V 220
ELECTRICAL SYSTEM-DC
System Voltage(Nominal) V 24
Starter motor Kw 6
Recommended Battery Capacity AH 150
Cold Cranking Amperes @ -18℃ (0⁰F) CCA 900
Charging Alternator Output Amps 70
FUEL SYSTEM
Injection Pump
Injection Advance Angle ° 24
Minimum Supply line Size mm 10
Minimum Return line Size mm 10
Fuel Management Control Mechanical
Idle Speed rpm 750
Governed Speed Rate % <10
Engine Performance Data
All data is based on the engine operating with fuel system, lubricating oil pump, air cleaner, and alternator; not
included are compressor, fan, optional equipment, and driven components.;Data is based on operation at SAE
standard J1394 conditions of 300ft (91,4m) altitude, 29.61 in.(752mm) Hg dry barometer, and 77⁰F (25⁰C) intake air
temperature, using 0# diesel fuel follow the standard GB 252-2011.

Altitude above which output should be Limited m (ft.) 91 (300)


Correction Factor per 305m.(1,000ft.) above Altitude Limit 3%
Temperature above which output should be Limited ⁰C (⁰F) 25 (77)
Correction Factor per 5.6⁰C (10⁰F) above Temperature Limit 1%
Remark:
1.All daa certified within 5%;
2.TBD - To Be Determined;
3.N/A - Not Applicable;
CNP NM FIRE FIGHTING SYSTEM CO.,LTD
Add:No.45 Xi Chong Road, Quan Tang Street, Changsha, Hunan, P.R.

DIESEL ENGINE China


Zip Code:410100
Tel +86-731-84091707
Fax: +86-731-84091727

Engine Model NM6-110D Curve No. C06110DF Date 2020/11/19

Displacement 7.13 L Aspiration Turbocharged+Water cooled Power Standard UL/FM

Bore 110 mm Cylinder Qty. 6 178 KW @ 2900 r/min

Stroke 125 mm Fuel System In-Line; Mechanical 239 HP @ 2900 r/min

250

200

178

150
KW

100

50

0
1470 1760 2100 2350 2650 2900 RPM

Torque Output Power Fuel Consumption

Speed Torque Speed Output Power Speed Consumption


RPM N-m lb-ft. RPM KW HP RPM g/KW-HR lb/BHP-HR
1470 1470 1470
1760 1760 1760
2100 2100 2100
2350 2350 2350
2650 2650 2650
2900 587 433 2900 178 239 2900 235 0.386

REV: A

CNP NM FIRE FIGHTING SYSTEM CO., LTD


Add:No.45 Xi Chong Road, Quan Tang Street, Changsha, Hunan, P.R. China 410100
Tel: + 86-731-84091707 Fax.:+86-731-84091727
NOTE: Grooved end waste cone is available on request.
GVI Fire Pump Test Meters
The industry leader in flow meters

Global Vision Inc 8730 Jefferson Highway


Osseo, Minnesota 55369 USA tel: 763-391-0990 fax: 763-391-7668
Www.gviflow.com [email protected]
2
Production / Testing
GVI produces all venturis from domestic U.S. thick wall tube. This heavy duty steel ensures
our venturi will be around years longer than the thinner, lightweight alternatives, so much
longer, GVI has a 12 year warranty on this venturi.

With 2 tolerances After machining,


new CNC of .005 every venturi is
lathes at mean a inspected with
GVI, lead perfect ISO certified
times are venturi test equipment
in hours, every time
not weeks

NIST METER TESTING


Every GVI gauge undergoes advanced computerized testing before
leaving the factory. These tests include leakage, calibration, and
accuracy tests.

Upon successful testing the gauge is issued an NIST certificate tied


specifically to the serial number on the dial face.

The certification is stored in a plastic pouch connected to the


gauge. This pouch also illustrates the typical installation and the
operating instructions for the fire pump flow test.

Contact your GVI rep for duplicate sheets or updated certifications.

5
6
Standard Model List

7
Installation / Operation
1. Close the system valve
2. Open the by-pass valve and throttle valve
3. Purge air from meter as follows:

- Open Ball valve on red and green hoses


- Open the high side bleeder knob until a
steady stream of water is coming from the
Clear hose
- Close high pressure bleeder knob
- Repeat for low pressure side
- Ensure both bleeder knobs are closed

4. Start fire pump, read meter in gpm/lpm/m3h


5. Refer to pump requirements and adjust
throttle valve for this requirement
6. After test, open system valve and close the Typical flow loop configuration
by-pass and throttle valves
Can be installed vertically or horizontally

Typ. Install with 5/2 pipe diameters. If reducers are used, lengthen the min pipe dia.
Clear of obstructions, valves, or bends. To 10/4 to ensure accuracy is maintained.

9
Facebook GVIFLOW.COM

Global Vision Inc 8730 Jefferson Highway


Osseo, Minnesota 55369 USA
tel: 763-391-0990 fax: 763-391-7668
Www.gviflow.com [email protected]

12