Corrections To: IEEE Recommended Practice For Protection and Coordination of Industrial and Commercial Power Systems
Corrections To: IEEE Recommended Practice For Protection and Coordination of Industrial and Commercial Power Systems
(Revision of
IEEE Std 242-1986)
Corrections to:
IEEE Recommended Practice for Protection
and Coordination of Industrial and
Commercial Power Systems
Sponsor
Industrial and Commercial Power Systems Department
of the
IEEE Industry Applications Society
Correction Sheet
Issued 24 January 2003
Page 296: The titles of Table 9-3b and Table 9-3c should be exchanged. Also, 600 kV in both
titles should be corrected to 600 V. Following are the corrected tables.
Frame size
225–600 A 1600–4000 A
Instantaneous (cycles) 2–3 3
Short time (cycles) 10–30 10–30
Long time (s) over 100
Ground fault (cycles) 10–30 10–30
Frame size
100–1200 A
100 A 225–1200 A
(current limiting)
--``,,``,``,`,,,``,`,,,`,,,`-`-`,,`,,`,`,,`---