0% found this document useful (0 votes)
25 views

Pi 269P

Uploaded by

Mohamed Taha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views

Pi 269P

Uploaded by

Mohamed Taha
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

PI 269P POWERED BY

Industrial Generating Set

(1) (2)
MODEL rpm / Hz VOLTAGE PRIME STANDBY
PI 269P 1800 / 60 480 / 277 245 kVA / 196kWe 269 kVA / 215.2kWe

ENGINE SPECIFICATIONS FUEL SYSTEM


(1)
218 kW m Fuel Filter: Spin on primary,secondary and water filter
Rated Output (PRP) separator
(2)
Rated Output (ESP) 239 kW m Recommended Fuel Class A2 Diesel
Engine Make & Model Perkins 1506A-E88TAG1 Fuel Consumption Standby TBA

No. of Cylinders 6 Vertical In-line Fuel Consumption 100% PRP TBA

Cycle 4 Strokes Fuel Consumption 75% PRP TBA


Turbocharged
Aspiration Aftercooled Fuel Consumption 50% PRP TBA

Cooling Method Liquid EXHAUST SYSTEM


Governing Type Electronic Muffler Type Industrial Grade
Governing Class G2 - ISO 8528 Part 1 Max. Back Pressure 10 kPa
3
Compression Ratio 16.1:1 Exhaust Gas Flow (PRP/ESP) TBA m /min
3 Exhaust Gas
Displacement 8.8 L (537.in ) TBA
Temperature(PRP/ESP)
BorexStroke (mm/in) 112x149 / 4.5x 5.8 ALTERNATOR SPECIFICATIONS
(1)
Battery and Charger Alternator 24 VDC , 45 Amp Rated Output (Prime) 255 kVA
(2)
AIR SYSTEM Rated Output (Standby) 280 kVA

Air Filter Type Dry Element Alternator Make & Model Stamford UCI274H
3
Combustion Air Flow (PRP) TBA m /min Number of Poles 4
3
Combustion Air Flow (ESP) TBA m /min Number of Winding Leads 12
Radiator Air Flow 370 m³/min Type of Bearing Single
COOLING SYSTEM Insulation Class / Temp Rise H/H
Total Coolant Capacity (L) 29.6 L (7.8 US gal) Efficiency @ Rated Voltage 93.3%
Water Pump Type Centrifugal Eng-Driven Ingress Protection Rating IP 23
Radiator Fan Load 10 kW Excitation System Self Excited
Heat Radiation to Room (PRP) TBA kW AVR Model Stamford - SX460

Heat Radiation to Room (ESP) TBA kW ALTERNATOR OPERATING DATA


LUBRICATION SYSTEM Overspeed 2250 r.p.m
Oil Filter Type Spin on full flow filter Voltage Regulation ±1%
No load < 1.5%,
Total Oil Capacity 41 L (10.83 US gal) Waveform distortion
Linear load < 5%
Oil Pan 36 L (9.5 US gal) Radio Interface EN 61000-6-2 & EN 61000-6-4
Oil Type API CH4/CI4; SAE 15W-40 Cooling Air Flow 0.617 m³/sec

(1)
PRIME POWER RATING (PRP): PRP is defined as the maximum power which a Generating set is capable of delivering continuously whilst supplying a variable electrical load when
operated for an unlimited number of hours per year. The permissible average power output over 24 hours shall not exceed 70% of PRP unless otherwise agreed by RIC engine manufacturer.
An overload capability of 10% of 100% of the prime rated electrical power is permitted for emergency use for a period of 1 hour within 12 hours of operation

(2)
EMERGENCY STANDBY POWER RATING (ESP): ESP is defined as the maximum power available during a variable electrical power sequence, under the stated operation condition, for
which a generating set is capable of delivering power in the event of a utility power outage or under test condition for up to 200 Hours of operation per year. The permissible average output
over 24 hour of operation shall not exceed 70 % of the ESP power rating noting that no over load is permitted.

ALL RIGHTS RESERVED - 2018


PI 269P POWERED BY

Industrial Generating Set

CONTROLLER SPECIFICATIONS ENCLOSURE SPECIFICATIONS


Controller Make & Model DeepSea 6120 Enclosure Type Acoustic & Weather Proof
Operation Mode MRS / AMF (optional) Anticorrosive Protection
Display Graphic Back-lit LCD (128x64) pixles Polyester Powder Coated Galvanized Sheet
Ingress Protection Rating IP65 Ingress Protection Rating IP23
Binary Inputs/Outputs 6/4 Lifting ISO Standard Lifting
Analog Inputs 4 Emergency External Emergency Push Button

Measurement Vac, A, Hz, kVA, kW, Vdc Canopy RAL Color RAL 2000
Event Log Alarms log, Hrs log Baseframe RAL Color RAL 9011
Communication USB Noise Pressure level @ 7m 76 dB(A)

GENSET DIMENSIONS & WEIGHT

GENSET TYPE Length Width Height Fuel Tank


Dry Weight (kg) Wet Weight (kg)
(mm) (mm) (mm) Capacity (L)
OPEN 3030 915 1845 435 1560 1620
CLOSE 3764 1155 2195 435 2439 2500

STANDARD MECHANICAL FEATURES STANDARD ELECTRICAL FEATURES


Genset design provides a low noise level with an optimized An advance Control system is designed to provide a
performance of the ventilation and exhaust systems at 50 ºC comperhensive protection and to monitor the parameters of
ambient temperature. generating set.
Robust structure design of Enclosure and Baseframe. MCCB power circuit breaker.
Hevy duty lifting lugs. Battery with charging alternator, cables, and tray.
Multi doors for easy access & maintenance. Sealed harness & high resistant electrical connections.
Ingress Protection Rating according to BS EN 60529. Fast and accurate protection response.
Heavy Duty Baseframe with built-in tank & forklift pockets. Generating Set remote start function.
Industrial Grade Muffler with rain cap. Numeric display with LED. Various languages capable.

OPTIONAL FEATURES
Advanced Controllers are available on request.
4 poles manual / Motorized Circuit breaker
Jacket water pre-heater
Static Battery Charger
Residential / Critical grade muffler

Fuel Filter / Water seperator Fuel Filter

Remote Annunciator

Application
Infrastructure, Industrial , Residential , Telecom,
Defense , Mining , Aggriculture
Address: 24b St., Community 365 Al Quoz Ind. 2, Dubai, UAE I Tel: +971 4 338 4033 I Fax: +971 4 338 3997

ALL RIGHTS RESERVED - 2018 [email protected] www.pi-dubai.com


I

You might also like