Chapter 5 Earthing
Chapter 5 Earthing
Types of earthing
Earthing is classified into two types:
A. System (Neutral ) earthing
B. Equipment earthing
System (Neutral) Earthing
• Intentional connection of neutral points of star connected 3 phase
windings of generators, transformers, motors to ground is called
system earthing.
• System earthing ensures the system security and protection.
The angle made by straight line joining overhead earth wire and
line conductor with vertical plane is known as Shielding Angle (or
angle of protection) and denoted by θ.
For proper protection of the line conductors from lightning
strokes, the shielding angle should be within 30°.
The ground wire shields the phase or line conductors by attracting
itself the lightning strokes creating these conductors within zone of
protection
2. Lightning Arrestors:
The most common device used for protection of the power
system against the high voltage surge is surge-diverter which
is connected between the line and earth, and diverts the
incoming high voltage wave to earth. Such a diverter is called
lightning arrestor.
As the overvoltage is incident by any means on the protective
device, a part of energy content in the overvoltage is charged
to the ground through protective device, when a high voltage
wave reaches the surge diverter, it sparks over and provides a
conducting path of relatively low impedance between the line
and earth, so that resulting current flows to the earth. These
prevent the flow of the normal power or signal currents to
ground, but provide a path over which high-voltage lightning
current flows, bypassing the connected equipment. Their
purpose is to limit the rise in voltage when a communications
or power line is struck by lightning or is near to a lightning
strike.
Classification of lightning arrestors
Lightning arrestors can be classified as:
1. Rod Gap Lightning Arrestor
2. Horn Gap Lightning Arrestor
3. Surge Absorber
1. Rod Gap Lightning Arrestor
A rod gap arrestor is very simple
type of diverter and consists of two
1.5 cm diameter rods, which bent
at right angles with the gap. One
rod is connected to line circuit and
other is connected to the ground.
The distance between gap and
insulator must not be less than l/3
of the rod gap length (l), in order to
protect the insulator from the arc.
• Under normal operating condition, the gap remains non
conducting. On the occurrence of high surge voltage on the
line, the gap sparks over the surge current conducted to
earth. The rod gap arrestor has the advantage of low cost and
easy adjustment on site.
However, it has limitations as listed below:
• The rods may melt or get damaged due to excessive heat
produced by arc,
• The climate condition like rain, humidity, temperature, etc
affects the performance.
The rod gap depends upon the operating voltage of the
system.
System Voltage (KV) Rod Gap in mm
33 225
66 350
132 650
275 1230
2. Horn Gap Lightning Arrester
It consists of two horn- shaped pieces of
metal separated by a small air gap and
connected in shunt between each conductor
and earth.
Applications:
This system is used on the networks where normal impedance is quite large.
Experience shows that combined impedance of the apparatus, circuit and
ground return path in systems operating at voltages below 3.3 kV and those
operating at voltages exceeding 33 kV is sufficiently large so as to limit the
value of fault current to a safe value.
Resistance Grounding
When the neutral point of a 3 phase system
(generator, transformer etc.) is connected to
earth through a resistor it is called resistance
grounding.
The value of resistance is so designed that, the ground fault current does not
exceed the 3-phase short circuit current. Grounding resistors are normally
designed to carry their rated current for short period, usually 30 seconds.
Applications:
This system is usually employed for the systems operating on
voltages exceeding 3.3 kV but not exceeding 33 kV.
Advantages:
1. It permits the use of discriminative protective gear.
2. It minimizes the hazards of arcing ground.
3. Fault current (If) is less than effective grounding and hence less
interference on neighboring communication circuits.
Disadvantages:
1. Voltage of healthy phases will become greater than 80% of line
voltage. Therefore, insulation increases, rating of arrestors
increases and ultimately cost increases.
2. It is costlier than solidly grounded system.
3. There is enormous energy loss in Resistor for dissipation of fault
energy.
Reactance grounding
Reactance grounding means
grounding through impedance
which is highly inductive. A
reactance is connected between
the earth and the neutral point.
Applications:
Reactance grounding may be used for grounding the neutral of
circuits where high charging currents are involved such as
transmission lines, underground cables etc. For networks where
capacitance is relatively low, resistance grounding is preferred.
Arc Suppression grounding or Peterson
coil grounding or Resonance grounding
Peterson coil is an iron core reactor connected between
transformer neutral and ground.
It is used for limiting the capacitance earth fault current which is
flowing when the line ground fault occurs in the line.
The coil is provided with the tapping so that it can be adjusted
with the capacitance of the system. The reactance is selected so
that the current through the reactor is equal to the small line
charging current which would flow into the line-to-ground fault.
vNB
Numerical Example
1. Determine the value of reactance to be connected in the
neutral connection to neutralize the capacitance current, of an
overhead line to ground capacitance of each line equal to 0.015
μF. Frequency = 50 HZ
Solution:
2. A 33 kV, 3 phase 50 HZ OH line 50 km long has a
capacitance to earth line equal to 0.01 μF per km. Determine
the inductance and kVA rating of the arc suppression coil.
Solution:
3. Calculate the reactance of a coil suitable for a 33 kV, 50 HZ, 3
phase transmission system of which the capacitance to earth of
each conductor is 4.5 μF.
Solution:
IOE Questions
Why the neutral in a power system is grounded? What are the
methods of grounding a neutral? Explain one of them in detail.
[2070 Bhadra, 2073 Magh]
Describe the protection of stations and sub-stations against direct
lighting strokes. [2078 Chaitra]
Explain the methods of overvoltage protection of electrical
equipment. [2077 Chaitra]
A 90 km long 66 KV, 50Hz, 3 phase overhead line has capacitance
to earth equal to 0.02 micro Farad per km. What should be the
inductance and KVA rating of the arc suppression coil. [2077
Chaitra]
What are the causes of over voltages on power system? List the
merits and demerits of solid grounding. [2076 Bhadra]
Calculate the inductance and KVA rating of the arc suppression coil
of a 50 Km long 33 KV, 50 Hz, 3 phase overhead transmission
system having line to earth capacitance of each phase equal to
0.0125 microfarad. [2076 Bhadra]
A 33 KV, 3 phase, 50 Hz, overhead line 60 Km long has a
capacitance to ground of each line equal to 0.015 microfarad per
km. Determine the inductance and KVA rating of the Peterson coil.
[2075 Bhadra, 2075 Baisakh, 2074 Bhadra, 2073 Magh]
What are the factors affecting soil resistivity? How can we reduce
earth resistance? [2075 Bhadra]
What is neutral Earthing? Briefly discuss different types of neutral
Earthing. [2074 Bhadra]
An alternator rated at 10 KV protected by the balanced circulating
current system has its neutral grounded through a resistance of 10
ohms. The protective relay is set to operate when there is out of
balance current of 1.8 A in the pilot wires, which are connected to
the secondary windings of 1000/5 ratio current transformers.
Determine: a. the percentage winding which remain unprotected
b. the minimum value of earthing resistance required to protect
80% of the winding.[2073 Bhadra]
A transmission line has a capacitance of 0.1 microfarad per phase.
Determine the inductance of Peterson coil to neutralize the effect
of capacitance of a. complete length b. 90 % length of the line
f=50Hz.
What is chemical earthing? Writhe the factors affecting the earth
resistance. [2072 Magh]
The neutral point of a three-phase 20 MVA, 11 KV alternator is
earthed through a resistance of 5 ohm, the relay is set to operate
when there is an out of balance current of 1.5 A. The CTs hence a
ratio 1000/5. What percentage of winding is protected against an
earth fault and what should be the minimum value of earthing
resistance to protect 90% of the winding. [2072 Ashwin]
A 13.8 KV, 125 MVA, star-connected alternator has a synchronous
has a synchronous reactance of 1.4 per unit per phase and
negligible resistance. It is protected by a Merz-Price balanced
current system which operated when out of balance current
exceeds 10% of the full load current. If the neutral point is earthed
though a resistance of 2 ohm, determine what proportion of
winding is protected against earth fault. [2071 Magh]
Define causes of overvoltage and explain methods of overvoltage
protection of electrical equipment. [2071 Bhadra]
A 5000 KVA, 6600 V, star- connected alternator has a synchronous
reactance of 2 ohm per phase and 0.5 ohm resistance. It is
protected by Merz price balanced current system which operates
when out of balance current exceeds 30% of load current.
Determine what proportion of a alternator winding is unprotected
if the star is earthed through a resistance of 6.5 ohm. [2070 Magh]