3.2.1. - AGC-200 - Operators - Manual - 4189340607C
3.2.1. - AGC-200 - Operators - Manual - 4189340607C
DEIF A/S · Frisenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com
isenborgvej 33 · DK-7800 Skive · Tel.: +45 9614 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com Document no.: 4189340607C
14 9614 · Fax: +45 9614 9615 · [email protected] · www.deif.com SW version: 4.21.x or later
AGC 200 Operators manual 4189340607
UK
1. General information
1.1. Warnings, legal information and safety..................................................................................................3
1.1.1. Warnings and notes ......................................................................................................................3
1.1.2. Legal information and disclaimer ..................................................................................................3
1.1.3. Safety issues ................................................................................................................................3
1.1.4. Electrostatic discharge awareness ...............................................................................................3
1.1.5. Factory settings ............................................................................................................................3
1.2. About the operator's manual..................................................................................................................4
1.2.1. General purpose ...........................................................................................................................4
1.2.2. Intended users ..............................................................................................................................4
1.2.3. Contents and overall structure ......................................................................................................4
1. General information
1.1 Warnings, legal information and safety
1.1.1 Warnings and notes
Throughout this document, a number of warnings and notes with helpful user information will be presented.
To ensure that these are noticed, they will be highlighted as follows in order to separate them from the gener-
al text.
Warnings
Warnings indicate a potentially dangerous situation, which could result in death, personal in-
jury or damaged equipment, if certain guidelines are not followed.
Notes
Notes provide general information, which will be helpful for the reader to bear in mind.
The Multi-line 2 unit is not to be opened by unauthorised personnel. If opened anyway, the war-
ranty will be lost.
Disclaimer
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
Be aware of the hazardous live currents and voltages. Do not touch any AC measurement in-
puts as this could lead to injury or death.
The general purpose of this document is to give the operator important information to be used in the daily
operation of the unit.
Please make sure to read this document before starting to work with the Multi-line 2 unit and
the generator set to be controlled. Failure to do this could result in human injury or damage to
the equipment.
1 2 3
11
10
9 8 7 6 5 4
1. Shifts the first line displaying in the setup menus. Push two seconds to switch to master display in case
more than one display is connected.
2. Moves the cursor left for manoeuvring in the menus.
3. Increases the value of the selected setpoint (in the setup menu). In the daily use display, this button func-
tion is used for scrolling the second line displaying of generator values.
4. Selects the underscored entry in the fourth line of the display.
5. Moves the cursor right for manoeuvring in the menus.
6. Decreases the value of the selected setpoint (in the setup menu). In the daily use display, this button
function is used for scrolling the second line displaying of generator values.
7. Changes the menu line (line 4) in the display to mode selection.
8. Jumps one step backwards in the menu (to previous display or to the entry window).
9. Shifts the display three lower lines to show the event and alarm list. The list holds 150 events. These
events are deleted when the AGC is switched off.
10. Manual activation of close breaker and open breaker sequence if "SEMI-AUTO" is selected.
11. Manual activation of close breaker and open breaker sequence if "SEMI-AUTO" is selected.
12. Stop of the genset if "SEMI-AUTO" or "MANUAL" is selected.
13. Start of the genset if "SEMI-AUTO" or "MANUAL" is selected.
14. Enters a specific menu number selection. All settings have a specific number attached to them. The
JUMP button enables the user to select and display any setting without having to navigate through the
menus (see later).
15. Shifts the display three lower lines to show the alarm list.
1 2 3
9 8 7 6 5 4
10. LED flashing indicates that unacknowledged alarms are present. LED fixed light indicates that ALL alarms
are acknowledged, but some are still present.
Basically, all measured and calculated values can be read in the display. These may be selected via the PC
utility software (USW).
The event and alarm list will appear at power up if an alarm is present.
MAINS FAILURE
U-supply 24.1 V
G 0.001 PF 0 kW
G 0 kVA 0 kVAr
Energy Total 0 kWh
Run Absolute 0 hrs
1 MAINS FAILURE
U-supply 24.1 V
2 G 0.001 PF 0 kW
G 0 kVA 0 kVAr
Energy Total 0 kWh
3
Run Absolute 0 hrs
4 1/20
For detailed information about configuration, please see the Designer’s Reference Handbook.
The views contain up to 20 different windows which can be selected using the and push-buttons
located on the right hand side of the display.
G BB
50.00 Hz 50.19 Hz
400 V 400 V
G BB
50.00 Hz 50.19 Hz
400 V 400 V
Press
The scrollbar
indicates that more
readings are MAINS FAILURE
available below 1010 G -P> 1
Setpoint : -9.0 %
Timer : 10.2 s
Output A : Not used
Output B : Not used
Using the and push-buttons moves the cursor, and the appropriate mode can be selected by pressing
the SEL button:
Mode Description
SEMI - The display push-buttons (START, STOP, GB ON, GB OFF) are active and can be used by
the operator.
- The regulators are also active, i.e. the speed control will bring the generator to nominal speed
upon start.
- When pushing a breaker button for closing, the AGC 200 will synchronise (if allowed) the
breaker. When the breaker closes, the controls stop.
TEST - The unit will start the generator, carry out the test sequence (predefined time period) and
stop the generator again. Subsequently, the generator will return to AUTO or SEMI-AUTO
mode. The mains breaker will remain closed, and the generator breaker will remain open.
NOTE: The test running can be: Simple test: Starting the genset without closing the GB; Load
test: Parallel to the mains and take load to a predefined value; Full test: Transfer the load to
the genset and open the MB.
AUTO - The unit will automatically carry out the control type selected (AMF, fixed power, etc.).
- The display control push-buttons (START, STOP, GB ON, GB OFF) are disabled.
- If the selected running mode is fixed power, mains power export, load takeover or island, tim-
er start/stop (week watch) or binary input, then start/stop can be used.
MAN - The display push-buttons (START, STOP) are active and can be used by the operator.
- The regulators are not active, i.e. speed (and voltage) control has to take place using exter-
nal controls for generator speed and possibly generator voltage control.
- The breakers will be able to open or close at any time. A synchronisation check will always
be performed to ensure safe closing of the breakers.
BLOCK - The unit will not be able to start. BLOCK mode can be selected during standstill and the
password is needed to exit BLOCK mode. If the BLOCK mode is selected while the genset is
running, the mode will have no effect until the genset is stopped. To select another mode af-
ter the BLOCK mode, the password must be entered.
To return to the other display functions from MODE selection, press the BACK push-button.
display of the alarm. If setting 6900 is OFF, you have to press to enter the alarm list.
If reading of the alarms is not desired, use the ESC push-button to exit the alarm list.
If you decide to enter the alarm list later, use the push-button to jump directly to the alarm list reading.
The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active (i.e.
the alarm condition is still present). Once an alarm is acknowledged and the condition has disappeared, the
alarm will no longer be displayed in the alarm list.
This means that if there are no alarms, the alarm list will read "No alarms".
MAINS FAILURE
Alarm list:
Ch 1300 UNACK
BB U< 1
10-01-06 15:20:21:0
This display example indicates an unacknowledged alarm. The display can show only one alarm at a time.
Therefore, all other alarms are hidden.
To see the other alarms, use the and push-buttons to scroll in the display.
To acknowledge an alarm, place the cursor (grey area) over the channel number and then press .
An event is e.g. closing of breaker and starting of engine. An alarm is e.g. overcurrent or high cooling water
temperature. A battery test is e.g. test OK or test failed.
1. Press .
2. Select the needed list by using the and push-buttons (move the highlight of the list) and press
the push-button.