Network Installation Sheet Profibus Slave Interface

Product Overview Network Status LEDs


The Profibus Slave interface can be either top or bottom
mounted. Both options are illustrated below. LED State Indication
Acyclic Off No acyclic traffic
• Top Mounted Interface Green Processing acyclic request
Online Green On line
Profibus Off Not on line
Address (x10) Offline Red Off line
Address (x1) Off Not off line
Diagnostics Flashing red, 1Hz Configuration error
Flashing red, 2Hz User Parameter Data error
Flashing red, 4Hz Profibus ASIC error
Off No diagnostics present
Gateway Power1

• Front View Address Switches

Top mounted Slave interface Two switches provides an address range of 1 - 99.
Acyclic Example:
Online
In this example, the Profibus node
Offline
address will be 42 (4 x 10)+(2 x 1).
Diagnostics
x10 x1
Gateway Status1 Profibus Connector

Acyclic Pin Signal


Online 1, 2, 7, 9 (Not connected)
Offline 3 B-line 5 1
Diagnostics 4 RTS
5 GND Bus
Gateway Status1 6 +5V Bus Out 9 6

8 A-line
Housing Protective Earth

Bottom mounted Slave interface Accessories Checklist


The following items are required for installation:
• Bottom Mounted Interface
• Null modem cable (optional, not included)
• GSD-file, required for network configuration (Availa-
ble on the HMS website, ‘www.anybus.com’)
• Profibus cable (not included)
Gateway Config1
Installation and Startup Summary
1. Connect the gateway to the Profibus network. If the
Profibus node is the last device on a bus segment, use a Profibus
Address (x10) connector with built in terminating resistors.
Address (x1) 2. If required, connect a PC to the gateway via null mo-
dem cable
3. Power up and (if required) configure the gateway
4. Install the.GSD file in the Profibus configuration tool

Profibus Support
Technical questions regarding the Profibus fieldbus system
should be addressed to your local Profibus User Group.
Online: www.profibus.com
1. See Gateway Installation Sheet for further information

online: www.anybus.com Revision 1.03, Part. no. SP0741