User Manual: HGM9520 Genset Parallel (With Mains) Unit
User Manual: HGM9520 Genset Parallel (With Mains) Unit
USER MANUAL
Smartgen Technology
CONTENTS
1 OVERVIEW ........................................................................................................ 5
2 MODULES COMPARISON ................................................................................... 6
3 PERFORMANCE AND CHARACTERISTICS .......................................................... 7
4 SPECIFICATION ................................................................................................. 9
5 OPERATION .................................................................................................... 10
5.1 INDICATOR LIGHT .............................................................................................................................. 10
5.2 PUSHBUTTONS .................................................................................................................................. 11
5.3 LCD DISPLAY ...................................................................................................................................... 12
5.3.1 MAIN DISPLAY ................................................................................................................................ 12
5.3.2 USER MENU AND PARAMETERS SETTING MENU ..................................................................... 14
5.4 AUTO START/STOP OPERATION ...................................................................................................... 17
5.5 MANUAL START/STOP OPERATION ................................................................................................. 18
5.6 SWITCH CONTROL PROCEDURES................................................................................................... 19
5.6.1 MANUAL TRANSFER PROCEDURES ........................................................................................... 19
5.6.2 AUTOMATIC CONTROL PROCEDURE ......................................................................................... 19
6 PROTECTIONS.................................................................................................................. 20
6.1 WARNING ALARMS............................................................................................................................. 20
6.2 SHUTDOWN ALARMS ......................................................................................................................... 22
6.3 TRIP AND STOP ALARMS ................................................................................................................... 24
6.4 TRIP ALARM ........................................................................................................................................ 25
7 WIRING CONNECTION ..................................................................................................... 26
8 SCOPES AND DEFINITIONS OF PROGRAMMABLE PARAMETERS ........................... 29
8.1 CONTENTS AND SCOPES OF PARAMETERS .................................................................................. 29
8.2 PROGRAMMABLE OUTPUT PORTS .................................................................................................. 39
8.2.1 DEFINED PERIOD OUTPUT ........................................................................................................... 43
8.2.2 DEFINED COMBINATION OUTPUT ............................................................................................... 43
8.3 PROGRAMMABLE INPUT PORTS (ALL ACTIVE WHEN CONNECT TO GRAND (B-)) ..................... 45
8.4 SELECTION OF SENSORS ................................................................................................................. 47
8.5 CONDITIONS OF CRANK DINSCONNECT SELECTION ................................................................... 48
9 PARAMETERS SETTING .................................................................................................. 49
10 SENSORS SETTING ......................................................................................................... 50
11 COMMISSIONING.............................................................................................................. 51
11.1 STEP 1. GENSET DEBUGGING .......................................................................................................... 51
11.2 STEP 2: MANUAL PARALLEL OPERATION OFF-LOAD .................................................................... 51
11.3 STEP 3: MANUAL PARALLEL OPERATION ON-LOAD ...................................................................... 51
12 MAINS PARALLEL ............................................................................................................ 52
12.1 GENSET CONTROL MODE ................................................................................................................. 52
12.2 MAINS CONTROL MODE .................................................................................................................... 53
12.3 LOAD TAKEOVER MODE .................................................................................................................... 54
12.4 AMF MODE .......................................................................................................................................... 55
12.5 ISLAND MODE ..................................................................................................................................... 56
13 TYPICAL APPLICATION ................................................................................................... 57
14 INSTALLATION ................................................................................................................. 58
15 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE............................................. 60
15.1 CUMMINS ISB/ISBE............................................................................................................................. 60
15.2 CUMMINS QSL9 .................................................................................................................................. 60
15.3 CUMMINS QSM11 (IMPORT) .............................................................................................................. 61
15.4 CUMMINS QSX15-CM570 ................................................................................................................... 61
15.5 CUMMINS GCS-MODBUS ................................................................................................................... 62
15.6 CUMMINS QSM11 ............................................................................................................................... 62
15.7 CUMMINS QSZ13 ................................................................................................................................ 63
15.8 DETROIT DIESEL DDEC III / IV ........................................................................................................... 63
15.9 DEUTZ EMR2 ....................................................................................................................................... 64
15.10 JOHN DEERE....................................................................................................................................... 64
15.11 MTU MDEC .......................................................................................................................................... 64
15.12 MTU ADEC(SMART MODULE) ............................................................................................................ 65
15.13 MTU ADEC(SAM MODULE) ................................................................................................................ 65
15.14 PERKINS .............................................................................................................................................. 66
15.15 SCANIA ................................................................................................................................................ 66
15.16 VOLVO EDC3 ....................................................................................................................................... 66
15.17 VOLVO EDC4 ....................................................................................................................................... 67
15.18 VOLVO-EMS2 ...................................................................................................................................... 67
15.19 YUCHAI ................................................................................................................................................ 68
15.20 WEICHAI .............................................................................................................................................. 68
16 USB .................................................................................................................................... 69
17 FAULT FINDING ................................................................................................................ 70
1 OVERVIEW
HGM9520 controller is designed for manual/auto parallel systems generators. The controller
allows automatic start/stop, data measurement, alarm protection as well as remote control,
remote measurement and remote communication. It has LCD display, selectable Chinese,
English and other languages interface, and it is reliable and easy to use.
HGM9520 controller integrates GOV (Engine Speed Governor) and AVR (Automatic Voltage
Regulator) control functions. Multiple working modes can be selected, such as genset fixed
active power, reactive power/power factor output, mains peak lopping and uninterruptedly
restore to mains supply.
HGM9520 controller can accurately monitor multiple running states of the gen-set. When
gen-set abnormal condition occurs, it splits bus and shuts down the gen-set; simultaneously
the fault condition appears on LCD. HGM9520 controller has SAE J1939 interface that can
communicate with a number of ECU (ENGINE CONTROL UNIT) which equip with J1939.
HGM9520 controller adopt 32 bits micro-processor technology with precision parameters
measuring, fixed value adjustment, time setting and set value adjusting and etc..Majority
parameters can be configured from front panel, and all parameters can be configured by USB
interface (or RS485) to adjust via PC. It can be widely used in all types of automatic gen-set
control system with compact structure, advanced circuits, simple connections and high
reliability.
2 MODULES COMPARISON
HGM HGM HGM HGM HGM HGM HGM HGM HGM HGM
9210 9220 9310 9320 9410 9420 9610 9620 9510 9520
Dimension 3.7‖ 4.3‖
LCD
pixel 132 x 64 480 x 272
AMF ● ● ● ● ●
BUS Monitoring ●
Parallel
● ●
connection
Expansion
● ●
module
Input Ports 7 7 7 7 7 7 8 8 7 7
Output Ports 8 8 8 8 8 8 8 8 8 8
Sensor Number 5 5 5 5 5 5 5 5 5 5
Neutral (Earth)
● ●
current
Scheduled
● ● ● ● ● ● ● ● ● ●
function
ETHERNET ● ●
RS485 ● ● ● ● ● ● ● ●
GSM ● ● ● ● ● ●
J1939 ● ● ● ● ● ●
USB ● ● ● ● ● ● ● ● ● ●
LINK ● ●
Real-time clock ● ● ● ● ● ● ● ● ● ●
Event log ● ● ● ● ● ● ● ● ● ●
Micro SD card ● ●
NOTE:
(1) Two of the outputs are fixed: start output and fuel output.
(2)HGM9510’s analog sensors are composed by 3 fixed sensors (temperature, pressure, level)
and 2 configurable sensors.
NOTE:
The controller features of HGM9210/HGM9220/HGM9310/HGM9320/HGM9410/
HGM9420/HGM9510/ HGM9610/HGM9620 mentioned in this document may change, please
check the corresponding user manual for accurate information.
3 PERFORMANCE AND CHARACTERISTICS
With ARM-based 32-bit SCM, high integration of hardware and more reliable;
480x272 LCD with backlight, multilingual interface (including English, Chinese or other
languages) which can be chosen at the site, making commissioning convenient for factory
personnel;
Improved LCD wear-resistance and scratch resistance due to hard screen acrylic;
Silicon rubber panel and pushbuttons for better operation in high/low temperature
environment;
RS485 communication port enables remote control, remote measuring, remote
communication via ModBus protocol.
Equipped with CANBUS port and can communicate with J1939 genset. Not only can you
monitoring frequently-used data (such as water temperature, oil pressure, speed, fuel
consumption and so on) of ECU machine, but also control start, stop , raising speed and
speed droop via CANBUS port.
Suitable for 3-phase 4-wire, 3-phase 3-wire, single phase 2-wire, and 2-phase 3-wire
systems with voltage 120/240V and frequency 50/60Hz;
Collects and shows 3-phase voltage, current, power parameter and frequency of
mains/generator.
Mains Generator
Line voltage (Uab, Ubc, and Uca) Line voltage (Uab, Ubc, and Uca)
Phase voltage (Ua, Ub, and Uc) Phase voltage (Ua, Ub, and Uc)
Phase sequence Phase sequence
Frequency (Hz) Frequency (Hz)
4 SPECIFICATION
Parameter Details
Working Voltage DC8. 0V to 35. 0V, uninterruptible power supply
Overall Consumption <4W (Standby mode: ≤2W)
AC Input:
3 Phase 4 Wire AC 15V - 360V (ph-N)
3 Phase 3 Wire AC 30V - 620V (ph-ph)
Single Phase 2 Wire AC 15V - 360V (ph-N)
2 Phase 3 Wire AC 15V - 360V (ph-N)
Alternator Frequency 50Hz/60Hz
Speed Sensor Voltage 1. 0 V to 24 V (RMS)
Speed Sensor Frequency Maximum 10,000 Hz
Start Relay Output 16 Amp DC28V power supply output
Fuel Relay Output 16 Amp DC28V power supply output
Configurable Relay Output 1 7 Amp DC28V power supply output
Configurable Relay Output 2 7 Amp DC28V power supply output
Configurable Relay Output 3 7 Amp DC28V power supply output
Configurable Relay Output 4 7 Amp AC250V passive output
Configurable Relay Output 5 7 Amp AC250V passive output
Configurable Relay Output 6 7 Amp AC250V passive output
Case Dimensions 266mm x 182mm x 45mm
Panel Cutout 214mm x 160mm
CT Secondary Current Rated 5A
Temperature: (-25~+70)°C
Working Conditions
Humidity: (20~93)%RH
Storage Conditions Temperature:(-30~+80)°C
IP55: when waterproof rubber gasket installed between the
controller and panel fascia.
Protection Level
IP42: when waterproof rubber gasket is NOT installed
between the controller and panel fascia.
Object: input/output/power supply
Insulation Intensity Quote standard: IEC688-1992
Test method: AC1.5kV/1min Leakage current: 3mA
Weight 0.95kg
5 OPERATION
Running indicator: illuminated from crank disconnect to ETS while off during other periods.
Gen normal indicator:It is illuminated when generator is normal; flashing when generator state
is abnormal; off when there is no generator power.
Mains normal indicator: It is illuminated when mains is normal; flashing when mains state is
abnormal; off when there is no mains power.
5.2 PUSHBUTTONS
Manual Mode Press this key and controller enters in Manual mode.
Auto Mode Press this key and controller enters in Auto mode.
Mains
Can control mains to switch on or off in Manual mode.
Close/Open
1) Screen scroll;
Up/Increase
2) Up cursor and increase value in setting menu.
1) Screen scroll;
Down/Decrease
2) Down cursor and decrease value in setting menu.
WARNING: Default password is 00318, user can change it in case of others change the
advanced parameters setting. Please clearly remember the password after changing. If you
forget it, please contact Smartgen services and send all information in the controller page of
―ABOUT‖ to us.
5.3 LCD DISPLAY
Main screen is divided into left and right separate viewing areas, use to select a viewing
area; the selected area is marked with in its upper left corner. Both viewing areas show
pages; use to scroll the pages and to scroll the screen.
★Status, including as below,
Status of genset, ATS and mains
★Engine, including as below,
Speed, engine temperature, engine oil pressure, fuel level, configure sensor 1, configure
sensor 2, battery voltage, charger voltage, accumulated run time, accumulated start times.
NOTE: If read parameters via CANBUS port using J1939, this page also includes: coolant
pressure, coolant level, fuel temperature, fuel pressure, inlet temperature, exhaust
temperature, turbo pressure, fuel consumption, total fuel consumption and so on. (Different
engine with different parameters)
★Generator, including as below,
Phase voltage, Line voltage, frequency, phase sequence
★Mains, including as below
Phase voltage, Line voltage, frequency, phase sequence, mains current, active power,
reactive power, apparent power, power factor, rate of change of frequency (ROCOF), vector
shift (VS)
★Load, including as below,
Current, each phase and total active power (positive and negative), each phase and total
reactive power (positive and negative), each phase and total apparent power, each phase and
average power factor (positive and negative), accumulated energy (kWh, kVarh, kVAh), earth
current, negative sequence current
NOTE: Power factor shows as following,
Remark:
P stands for active power
Q stands for reactive power
Power Active Reactive
Conditions Remark
factor power power
COS>0L P>0,Q>0 Input Input Load is inductive resistance.
COS>0C P>0,Q<0 Input Output Load is capacitance resistance.
Load equal to one under excitation
COS<0L P<0,Q>0 Output Input
generator.
COS<0C P<0,Q<0 Output Output Load equal to one over excitation generator.
Note:
1. Input active power, genset or mains supply electricity to load.
2. Output active power, load supply electricity to genset or mains.
3. Input reactive power, genset or mains send reactive power to load.
4. Output reactive power, load send reactive power to genset or mains.
★SNYC, including as below,
voltage difference, frequency difference, angle difference, active power percentage, target
active power percentage, reactive power percentage, target reactive power percentage, GOV
output percentage and AVR output percentage
★Alarm:
NOTE: For ECU alarms and shutdown alarms, if the alarm information is displayed, check
engine according to it, otherwise, please check the manual of generator according to SPN
alarm code.
★Event log
Make records about all start/stop events (shutdown alarm, trip and stop alarm, manual /auto
start or stop) and the real time when alarm occurs.
★Others, including,
time and date, count down time for maintenance, input/output ports status.
★About, including,
Issue time of software and hardware version, product PD number
Example:
Status Engine
Generator Status Engine Speed
Manual Mode 1500r/min
Normal Running Engine Temperature
Mains Status 85℃ 185℉
Mains Abnormal Engine Oil Pressure
Mains Overvolts 465kPa 67.4psi 4.65Bar
Switch Status Fuel Level
Gen Closed 100%
1500r/min 27.6V Normal Running
Engine Gen
Engine Speed Voltage(L-N)
1500r/min 220V 220V 220V
Engine Temperature Voltage(L-L)
85℃ 380V 380V 380V
185℉ Frequency 50.00Hz
Engine Oil Pressure
465kPa Phase
67.4psi L1 – L2 – L3
1500r/min 27.6V Emergency Stop
NOTE: Long time pressing can exit setting directly during setting.
5.4 AUTO START/STOP OPERATION
Note: When started via ―Remote Start (off Load)‖ input, same procedures as above but
generator close relay deactivated, moreover, genset off load.
Stopping Sequence:
1) As soon as ―Remote Start‖ deactivates and moreover, mains is normal, then ―Stop Delay‖
begins.
2) When ―Stop delay‖ is over, the controller will gradually transfer load to other generators,
open breaker, and ―Cooling Time‖ will begin. During cooling delay, if ―Remote Start‖ signal
recover active again, the controller will be parallel state again. When ―Cooling Delay‖ is
over, ―Stop Idle Delay‖ starts;
3) Enter ―Stop Idle Delay‖ (if it is configured), idle relay is energized.
4) ―ETS delay‖ begins, ETS relay is energized while fuel relay is de-energized, and in addition,
complete stop is detected automatically.
5) "Fail to Stop" delay begins and complete stop is detected automatically.
6) Enter ―after stop‖ delay as soon as generator stops. Otherwise, controller will enter into
―Failed to stop‖ delay and corresponding warning will be sent. (If gen-set stopped
successfully after warning of ―Failed to Stop‖, it will enter ―after stop delay‖ and remove
alarm)
7) Enter ―generator standby‖ as soon as ―after stop time‖ is over.
a) MANUAL START: Press , controller enters into Manual mode and its indicator lights.
Press to start generator, can automatically detect crank disconnect, and generator
accelerates to high-speed running automatically. With high temperature, low oil pressure,
over speed and abnormal voltage during generator running, controller can protect genset
to stop quickly (please refer to No.4~9 of Starting Sequence for detail procedures).
b) MANUAL STOP: Press can stop the running generators. (Please refer to No.2~7
of Stopping Sequence for detail procedures).
NOTE: In ―manual mode‖, the procedures of ATS please refer to Switch Control
Procedure of generator in this manual.
5.6 SWITCH CONTROL PROCEDURES
When the controller detects trip and stop signal, it immediately disconnects generator breaker,
which leads to unloading and then generator is cooling down and stopped.
No. Type
When controller detects the generator current is higher than
1 Over Current the set value and the action select ―trip and stop‖, it will send a
―trip and stop‖ signal.
When count down time is 0 and the action select ―trip and
2 Maintenance Due
stop‖, it will send a ―trip and stop‖ signal.
When controller detects the generator reverse power value
3 Reverse Power (power is negative) is lower than the set value and the action
select ―trip and stop‖, it will send a ―trip and stop‖ signal.
When controller detects the power value (power is positive) is
4 Over Power higher than the set value and the action select ―trip and stop‖,
it will send a ―trip and stop‖ signal.
When digital input port is set as ―User Defined‖ and the action
5 Digital Input Ports select ―trip and stop‖, controller sends corresponding ―trip and
stop‖ signal when the alarm is active.
When controller detects earth current is greater than the set
6 Earth Fault value, and the action select ―trip and stop‖, it will send a ―trip
and stop‖ alarm signal.
When the controller detects that negative phase current has
Negative
7 exceeded the set value and the action select ―trip and stop‖, it
Sequence Current
will send ―trip and stop‖ signal.
When controller detects negative reactive power is greater
8 Loss of Excitation than the set value and the action select ―trip and stop‖, it will
send a ―trip and stop‖ signal.
When controller detects the mains frequency is higher than
9 Mains Over Freq
the set value, it will send a ―trip and stop‖ signal.
When controller detects the mains frequency is lower than the
10 Mains Under Freq
set value, it will send a ―trip and stop‖ signal.
Mains Over When controller detects the mains voltage is higher than the
11
Voltage set value, it will send a ―trip and stop‖ signal.
Mains Under When controller detects the mains voltage is lower than the
12
Voltage set value, it will send a ―trip and stop‖ signal.
When controller detects the ROCOF (rate of change of
13 Mains ROCOF frequency) is higher than the set value, it will send a ―trip and
stop‖ signal.
When controller detects the vector shift value is higher than
14 Mains Vector Shift
the set value, it will send a ―trip and stop‖ signal.
6.4 TRIP ALARM
When controller detects trip alarm, it will open breaker immediately, but genset not stop.
Trip alarm as following,
No. Type Description
When controller detects the current is higher than the set
1 Over Current
value and the action select ―trip‖, it will send a ―trip‖ signal.
When controller detects the reverse power value (power is
2 Reverse Power negative) is lower than the set value and the action select
―trip‖, it will send a ―trip‖ signal.
When controller detects the power value (power is positive) is
3 Over Power higher than the set value and the action select ―trip‖, it will
send a ―trip‖ signal.
When digital input port is set as ―User Defined‖ and the action
4 Digital Input Port select ―trip‖, controller sends corresponding ―trip‖ signal when
the alarm is active.
When controller detects earth current is greater than the set
5 Earth Fault value and the action select ―trip‖, it will send a ―trip‖ alarm
signal.
When the controller detects that negative phase current has
Negative
6 exceeded the set value and the action select ―trip‖, it will send
Sequence Current
a ―trip‖ alarm signal.
When controller detects negative reactive power is greater
7 Loss of Excitation than the set value and the action select ―trip‖, it will send a
―trip‖ signal.
7 WIRING CONNECTION
Form 1
No. Items Parameters Defaults Description
Mains Setting
Mains Setting-Basic
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Standard for checking mains over/under
voltage. (It is primary voltage when
using voltage transformer; it is line
2 Rated Voltage (30~30000)V 230
voltage when AC system is 3P3W while
it is phase voltage when using other AC
system).
Rated Standard for checking mains over/under
3 (10.0~75.0)Hz 50.0
Frequency frequency.
The delay from mains abnormal to
4 Normal Time (0~3600)s 10
normal.
Abnormal The delay from mains normal to
5 (0~3600)s 5
Time abnormal.
Volt.
6 (0~1) 0 0: Disable ; 1: Enable
Trans.(PT)
Setting value is mains rated voltage’s
percentage, and return value (default:
7 Over Voltage (0~200)% 120%
116%) and delay value (default: 5s) can
be set.
Setting value is mains rated voltage’s
percentage, and return value (default:
8 Under Voltage (0~200)% 80%
84%) and delay value (default: 5s) can
be set.
Setting value is mains rated frequency’s
Over percentage, return value (default:
9 (0~200)% 114%
Frequency 110%) and delay value (default: 5s) can
be set.
Setting value is mains rated frequency’s
Under
10 (0~200)% 90% percentage, return value (default: 94%)
Frequency
and delay value (default: 5s) can be set.
11 Current Trans. (5-6000)/5 500 The ratio of external CT
Full Load Mains’ active power, standard of load
12 (1-60000)kW 345
Active Power distribute.
Full Load
Mains’ reactive power, standard of load
13 Reactive (1-60000)kVar 258
distribute.
Power
Alarm action can be set (default:
Output Power
14 (0-60000)kW 0 warning); Alarm when output power
Limit Alarm
greater than the set value.
No. Items Parameters Defaults Description
Mains Setting-Sync
1 Alarm Action (0-1) 0 0:Trip and Stop;1:Auxiliary mains fail
2 Over Voltage (0-200)% 105% Setting value is mains rated voltage’s
percentage, action (default: trip and
3 Under Voltage (0-200)% 95% stop) and delay value (default: 0.1s) can
be set.
Over Setting value is mains rated frequency’s
4 (0-200)% 105%
Frequency percentage, action (default: trip and
Under stop) and delay value (default: 0.1s) can
5 (0-200)% 95%
Frequency be set.
Setting value is rate of change of
frequency (ROCOF), action (default: trip
6 ROCOF (0-1.00)Hz/s 0.20
and stop) and delay value (default:
0.1s) can be set.
Setting value is the change value of
VECTOR voltage waveform, action (default: trip
7 (0-20.0)° 6.0
SHIFT and stop) and delay value (default:
0.1s) can be set.
Timer Setting
Time from mains abnormal or remote
1 Start Delay (0~3600)s 5
start signal is active to start genset.
Time from mains normal or remote start
2 Stop Delay (0~3600)s 30
signal is deactivated to genset stop.
Time of pre-powering heat plug before
3 Preheat Delay (0~3600)s 0
starter is powered up.
4 Cranking Time (3~60)s 8 Time of starter power up
Crank Rest The waiting time before second power
5 (3~60)s 10
Time up when engine start fail.
Alarms for low oil pressure, high
Safety On temperature, under speed, under
6 (0~3600)s 10
Delay frequency/voltage, charge alt fail are
inactive.
Idle running time of genset when
7 Start Idle Time (0~3600)s 10
starting.
Warming Up Warming time between genset high
8 (0~3600)s 30
Time speed running and switch on.
Radiating time before genset stop, after
9 Cooling Time (0~3600)s 60
it unloads.
10 Stop Idle Time (0~3600)s 10 Idle running time when genset stop.
ETS Solenoid Stop electromagnet’s power on time
11 (0~3600)s 20
Hold when genset is stopping.
Time between end of genset idle delay
and stopped when ―ETS Solenoid Hold‖
Fail to Stop is set as 0;
12 (0~3600)s 0
Delay Time between end of ETS hold delay
and stopped when ―ETS Solenoid Hold‖
is not 0.
13 After Stop (0~3600)s 0 Time between genset stopped and
No. Items Parameters Defaults Description
Time standby
Engine Setting
Default: Conventional genset (not
J1939)
1 Engine Type (0~39) 0
When connected to J1939 engine,
choose the corresponding type.
Tooth number of the engine, for judging
Flywheel of starter disconnect conditions and
2 (10~300) 118
Teeth inspecting of engine speed. See
following section entitled Installation.
Offer standard to judge
3 Rated Speed (0~6000)r/min 1500
over/under/loading speed.
Setting value is percentage of rated
speed. Controller detects when it is
Speed on
4 (0~100)% 90% ready to load. It won’t enter into normal
Load
running when speed is under loading
speed.
Loss of Speed Time from detecting speed is 0 to
5 (0~3600)s 5
Signal confirm the action.
Loss of Speed
6 (0~1) 0 0:Warn; 1:Shutdown
Action
Setting value is percentage of rated
Over Speed
7 (0~200)% 114% speed and delay value (default: 2s) also
Shutdown
can be set.
Setting value is percentage of rated
Under Speed
8 (0~200)% 80% speed and delay value (default: 3s) also
Shutdown
can be set.
Setting value is percentage of rated
Over Speed speed and delay value (default: 5s) and
9 (0~200)% 110%
Warn return value (default: 108%) also can be
set.
Setting value is percentage of rated
Under Speed speed and delay value (default: 5s) and
10 (0~200)% 86%
Warn return value (default: 90%) also can be
set.
Battery Rated Standard for detecting over/under
11 (0~60.0)V 24.0
Voltage voltage of battery.
Setting value is percentage of rated
Battery Over voltage of battery. Delay value (default:
12 (0~200)% 120%
Volts 60s) & return value (default: 115%) also
can be set.
Setting value is percentage of rated
Battery Under voltage of battery. Delay value (default:
13 (0~200)% 85%
Volts 60s) & return value (default: 90%) also
can be set.
In normal running, when charger
D+(WL) voltage under this value,
14 Charge Alt Fail (0~60.0)V 8.0
charge failure alarms. Delay value
(default: 10s) & return value (default:
No. Items Parameters Defaults Description
10.0V) also can be set.
Maximum crank times of crank
15 Start Attempts (1~10)times 3 attempts. When reach this number,
controller will send start failure signal.
See form 5
There are 3 conditions of disconnecting
Crank starter with engine. Each condition can
16 (0~6) 2
Disconnect be used alone and simultaneously to
separating the start motor and genset
as soon as possible.
Setting value is percentage of generator
Disconnect
rated frequency. When generator
17 Generator (0~200)% 30%
frequency higher than the set value,
Freq
starter will be disconnected.
Setting value is percentage of rated
Disconnect speed. When generator speed higher
18 (0~200)% 30%
Engine Speed than the set value, starter will be
disconnected.
When generator oil pressure higher
Disconnect Oil
19 (0~1000)kPa 200 than the set value, starter will be
Pressure
disconnected.
Generator Setting
0: 3P4W; 1: 3P3W;
1 AC System (0~3) 0
2: 2P3W; 3: 1P2W.
Number of generator poles, used for
2 Poles (2~32) 4 calculating starter rotate speed when
without speed sensor.
To offer standards for detecting of
generator’ over/under voltage and
loading voltage. (It is primary voltage
3 Rated Voltage (30~30000)V 230 when using voltage transformer; it is
line voltage when AC system is 3P3W
while it is phase voltage when using
other AC system).
Setting value is percentage of generator
rated voltage. Detect when controller
Loading
4 (0~200)% 90% prepare loading. When generator
Voltage
voltage under load voltage, won’t enter
into normally running.
Rated To offer standards for detecting of
5 (10.0~75.0) Hz 50.0
Frequency over/under/load frequency.
Setting value is percentage of generator
rated frequency. Detect when controller
Loading
6 (0~200)% 90% prepare loading. When generator
Frequency
frequency under load frequency, it won’t
enter into normal running.
Volt.
7 (0~1) 0 0: Disable; 1:Enable
Trans.(PT)
8 Over Volt. (0~200)% 120% Setting value is percentage of generator
No. Items Parameters Defaults Description
Shutdown rated voltage. Delay value (default: 3s)
Under Volt. also can be set.
9 (0~200)% 80%
Shutdown
Setting value is percentage of generator
Over Freq.
10 (0~200)% 114% rated frequency. Delay value (default:
Shutdown
2s) also can be set.
Setting value is percentage of generator
Under Freq.
11 (0~200)% 80% rated frequency. Delay value (default:
Shutdown
3s) also can be set.
Setting value is percentage of generator
Over Volt. rated voltage. Delay value (default: 5s)
12 (0~200)% 110%
Warn and return value (default: 108%) also
can be set.
Setting value is percentage of generator
Under Volt. rated voltage. Delay value (default: 5s)
13 (0~200)% 84%
Warn and return value (default: 86%) also can
be set.
Setting value is percentage of generator
Over Freq. rated frequency. Delay value (default:
14 (0~200)% 110%
Warn 5s) and return value (default: 108%)
also can be set.
Setting value is percentage of generator
Under Freq. rated frequency. Delay value (default:
15 (0~200)% 84%
Warn 5s) and return value (default: 86%) also
can be set.
16 Loss of Phase (0~1) 1
Phase
0: Disable 1: Enable
17 Sequence (0~1) 1
Wrong
Load Setting
1 Current Trans. (5~6000)/5 500 The ratio of external CT
Full Current Generator’s rated current, standard for
2 (5~6000)A 500
Rating load current.
Generator’s full load active power,
3 Full kW rating (1~20000)kW 276
standard for load power.
Generator’s full load reactive power,
4 Full kVar rating (1~20000)kVar 210
standard for load power.
Setting value is percentage of generator
rated full load current. Delay value can
be set as Definite Time or Inverse
5 Over Current (0~200)% 120%
Definite Minimum Time (IDMT) and full
setting details are given in the section
follow form 1.
Setting value is percentage of generator
rated full load active power. Delay value
6 Over Power (0-200)% 110%
(default: 30s) and action (default: trip
and stop) also can be set.
7 Reverse (0-200)% 10% Setting value is percentage of generator
No. Items Parameters Defaults Description
Power rated full load active power. Delay value
(default: 10s) and action (default: trip
and stop) also can be set.
8 Earth Fault (0~1) 0 0: Disable 1: Enable
Negative
9 Sequence (0~1) 0 0: Disable 1: Enable
Current
Setting value is percentage of generator
Loss of rated full load reactive power. Delay
10 (0-200)% 20%
Excitation value (default: 5s) and action (default:
trip) also can be set.
Switch Setting
Pulse width of switch on. When it is 0,
1 Close Time (0~20.0)s 5.0
means output constantly.
2 Open Time (0~20.0)s 3.0 Pulse width of switch off.
Module Setting
Power on 0: Stop mode 1: Manual mode
1 (0~2) 0
Mode 2: Auto mode
Module Controller’s address during remote
2 (1~254) 1
Address sensing.
3 Stop Bits (0~1) 0 0: 2 stop bits; 1: 1 stop bit
0: Simplified Chinese 1: English
4 Language (0~2) 0
2: Others
For entering advanced parameters
5 Password (0~65535) 00318
setting.
Scheduling And Maintenance Setting
Scheduled
1 (0~1) 0 0: Disable; 1: Enable
Run
Scheduled Not
2 (0~1) 0 0: Disable; 1: Enable
Run
3 Maintenance (0~1) 0 0: Disable; 1: Enable
Analog Sensors Setting
Temperature Sensor
1 Curve Type (0~15) 7 SGX See form 4.
Open Circuit
2 (0~2) 0 0: Warn; 1: Shutdown; 2: No action
Action
Shutdown when sensor temperature
High Temp. higher than this value. Detect only when
3 (0~300)ºC 98
Shutdown safety delay is over. The delay value
(default: 3s) also can be set.
Warn when sensor temperature higher
than this value. Detect only when
High Temp.
4 (0~300) ºC 95 safety delay is over. The delay value
Warn
(default: 5s) and return value (default:
93) also can be set.
Low Temp.
5 (0~1) 0 0: Disable; 1: Enable
Warn
Oil Pressure Sensor
No. Items Parameters Defaults Description
1 Curve Type (0~15) 7 SGX See form 4.
Open Circuit
2 (0~2) 0 0: Warn 1: Shutdown 2: No action
Action
Shutdown when oil pressure higher
Low OP than this value. Detect only when safety
3 (0~1000)kPa 103
Shutdown delay is over. The delay value (default:
3s) also can be set.
Warn when oil pressure higher than this
value. Detect only when safety delay is
4 Low OP Warn (0~1000)kPa 124 over. The delay value (default: 5s) and
return value (default: 138) also can be
set.
Liquid Level Sensor
1 Curve Type (0~15) 4 SGH See form 4
Open Circuit
2 (0~2) 0 0:Warn; 1:Shutdown; 2:No action
Action
Warn when level lower than this value.
Low Level It is detecting all the time. The delay
3 (0~300)% 10
Warn value (default: 5s) and return value
(default: 15%) also can be set.
Flexible Sensor 1
Flexible 0: Disable 1: Enable; (can be set as
1 Sensor 1 (0~1) 0 temperature/pressure/liquid lever
Setting sensor).
Flexible Sensor 2
Flexible 0: Disable; 1: Enable; (can be set as
1 Sensor 2 (0~1) 0 temperature/pressure/liquid lever
Setting sensor).
Flexible Input Ports
Flexible Input Port 1
Contents Remote Start On Load Demand. See
1 (0~50) 31
Setting form 3
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Input Port 2
Contents Low oil pressure shutdown
1 (0~50) 27
Setting See form 3
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Input Port 3
Contents High temperature shutdown
1 (0~50) 26
Setting See form 3
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Input Port 4
Contents Generator Closed Auxiliary.
1 (0~50) 13
Setting See form 3
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Input Port 5
Contents
1 (0~50) 0 User defined. See form 3
Setting
No. Items Parameters Defaults Description
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 3
2: Always 3:Never
0: Warn; 1: Shutdown; 2:Trip and stop
4 Active Actions (0~4) 4
3:Trip 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Flexible Input Port 6
Contents
1 (0~50) 44 Reserved. See form 3
Setting
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Input Port 7
Contents
1 (0~50) 0 User defined. See form 3
Setting
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
0: From safety on 1: From starting
3 Arming (0~3) 3
2: Always 3:Never
0: Warn; 1: Shutdown; 2:Trip and stop
4 Active Actions (0~4) 4
3:Trip 4: Indication
5 Active Delay (0~20.0)s 2.0 Time from detecting active to confirm
LCD display detailed contents when the
6 Description
input is active.
Flexible Input Port 8
Contents
1 (0~50) 15 Mains Closed Auxiliary. See form 3
Setting
2 Active Type (0~1) 0 0: Closed to active 1: Open to active
Flexible Output Ports
Flexible Output Port 1
Contents
1 (0~239) 44 Generator OK. See Form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 2
Contents
1 (0~239) 48 Common Alarm. See Form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 3
Contents
1 (0~239) 38 Energize to Stop. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 4
Contents
1 (0~239) 35 Idle Control. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Flexible Output Port 5
Contents
1 (0~239) 30 Open Gen Output. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
No. Items Parameters Defaults Description
Flexible Output Port 6
Contents
1 (0~239) 29 Close Gen Output. See form 2
Setting
2 Active Type (0~1) 0 0:Normally open; 1:Normally close
Sync Setting -Basic
Voltage difference between generator
and mains. It is considered voltage
Voltage synchronization when the voltage
1 (0-30)V 3
Difference difference between generator and
mains is lower than voltage difference
value.
Positive Freq Frequency difference between
2 (0-2.0)Hz 0.2
Difference generator and mains. It is considered
frequency synchronization when the
Negative Freq frequency difference between generator
3 (0-2.0)Hz 0.1
Difference and mains is less than Check Up Freq
but more than Check Low Freq.
Initial phase difference between
generator and mains. It is considered
Phase Angle
4 (0-20)° 10 Check Phase Angle when the initial
Difference
phase difference is lower than phase
angle difference value.
Adjust generator frequency and enable
5 Slip Frequency (0-1.00)Hz 0.10
it greater than slip frequency of mains.
Load Ramp
6 (0-100.0)% 3.0 Speed rate of genset upload/unload
Rate
Fail to Sync When the controller detects no Sync
7 (5.0-300.0)s 60.0
Delay signal during the preset delay, it will
send corresponding alarm signal
Fail to Sync
8 (0-1) 0 according to the action type.
Action
Action Type: 0:Warn;1:Shutdown.
9 Load Mode (0-2) 0 0:Generator;1:Mains;2:Takeover.
Output Active
10 (0-100.0)% 30.0 Used for load control.
Power
Reactive
11 (0-1) 0 0:kVAr control;1:PF control
Power Control
Reactive
12 (0-100.0)% 8.0 Used for load control.
Power range
Sync Setting - GOV
1 Output Type (0-1) 1 0:Internal Relays;1:Internal Analogue
Output
2 (0-1) 0 0:Disable;1:Enable.
Reverse
0:None;1:Adjust to Rated Frequency;
3 Action (0-2) 1
2:Adjust to Center Point
Center Voltage
4 (0-10.0) 0 Default central voltage: 0V.
SW1
Voltage
5 (0-10.0) 2.0 Default volt. range: (-2.5~+2.5)V
Range SW2
No. Items Parameters Defaults Description
6 Sync Gain (0-500) 20 Adjust and control before paralleling.
7 Sync Stability (0-2000) 20 Adjust and control before paralleling.
8 Load Gain (0-500) 20 Adjust and control after paralleling.
9 Load Stability (0-2000) 20 Adjust and control after paralleling.
Sync Setting - AVR
0: None 1:Internal Relays;
1 Output Type (0-2) 2
2:Internal Analogue
Output
2 (0-1) 0 0:Disable;1:Enable.
Reverse
0:None;1:Adjust to Rated Frequency;
3 Action (0-2) 1
2:Adjust to Center Point
Center Voltage
4 (0-10.0) 0 Default central voltage: 0V.
SW1
Voltage
5 (0-10.0) 2.0 Default volt. range: (-2.5~+2.5)V
Range SW2
6 Sync Gain (0-500) 20 Adjust and control before paralleling.
7 Sync Stability (0-2000) 20 Adjust and control before paralleling.
8 Load Gain (0-500) 20 Adjust and control after paralleling.
9 Load Stability (0-2000) 20 Adjust and control after paralleling.
Note:overcurrent setting details about definite time delay and inverse definite minimum
time are as following.
Definite Time :overcurrent delay is definite time delay. Different overcurrent value has
corresponding delay.
Inverse Definite Minimum Time(IDMT):overcurrent delay decrease with the increase of
overcurrent. Different overcurrent value has corresponding delay.
IDMT formula:
T = t / ((IA/IT)-1)2
T:Overcurrent delay (second)
t:Timing multiplier ratio
IA:Present maximum load current(L1/L2/L3)
IT:Overcurrent setting value
Example:
t = 36
IA = 550A
IT =500A
Conclusion: T = 3600s (1hour)
8.2 PROGRAMMABLE OUTPUT PORTS
Form 2
No. Type Description
0 Not Used
1 Custom Period 1
2 Custom Period 2
3 Custom Period 3
4 Custom Period 4
5 Custom Period 5
6 Custom Period 6 Details of function description please see the
7 Custom Combined 1 following.
8 Custom Combined 2
9 Custom Combined 3
10 Custom Combined 4
11 Custom Combined 5
12 Custom Combined 6
13 Reserved
14 Reserved
15 Reserved
16 Reserved
Action when over speed shutdown and
17 Air Flap Control emergence stop. It also can close the air inflow to
stop the engine as soon as possible.
Action when warning, shutdown, trips. Can be
connected annunciator externally. When ―alarm
18 Audible Alarm
mute‖ configurable input port is active, it can
remove the alarm.
Action when genset start and disconnect when
19 Louver Control
genset stopped completely.
GRAND (B-))
Form 3
No. Type Description
Including following functions,
Indication: indicate only, not warning or shutdown.
Warning: warn only, not shutdown.
Shutdown: alarm and shutdown immediately
Trip and stop: alarm, generator unloads and shutdown
0 Users Configured after hi-speed cooling
Trip: alarm, generator unloads but not shutdown.
Never: input inactive.
Always: input is active all the time.
From crank: detecting from generator start.
From safety on: detecting after safety on delay.
1 Reserved
2 Alarm Mute Can prohibit ―Audible Alarm‖ output when input is active.
Can reset shutdown alarm and trip alarm when input is
3 Reset Alarm
active.
4 60Hz Active Use for CANBUS engine and it is 60Hz when input is active.
5 Lamp Test All LED indicators are illuminating when input is active.
Form4
No. Description Remark
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO
4 CURTIS
Defined resistance’s
Temperature 5 VOLVO-EC
1 range is 0~6KΩ, default
Sensor 6 DATCON
is SGX sensor.
7 SGX
8 SGD
9 SGH
10 PT100
11~15 Reserved
0 Not used
1 Custom Res Curve
2 Custom 4-20mA curve
3 VDO 10Bar
4 CURTIS Defined resistance’s
2 Pressure Sensor 5 VOLVO-EC range is 0~6KΩ, default
6 DATCON 10Bar is SGX sensor.
7 SGX
8 SGD
9 SGH
10~15 Reserved
0 Not used
1 Custom Res Curve
Defined resistance’s
2 Custom 4-20mA curve
3 Fuel Level Sensor range is 0~6KΩ, default
3 SGD
is SGH sensor.
4 SGH
5~15 Reserved
NOTE: User should make special declare when order controller if your genset equip with
4~20mA sensor.
8.5 CONDITIONS OF CRANK DINSCONNECT SELECTION
No. Setting description
0 Generator Frequency
1 Engine Speed
2 Engine Speed + Generator Frequency
3 Oil pressure
4 Oil pressure + Generator Frequency
5 Oil pressure + Engine Speed
6 Oil pressure + Engine Speed + Generator Frequency
NOTE:
a. There are 3 conditions to make starter disconnected with engine, that is, engine speed,
generator frequency and oil pressure. They all can be used separately. We recommend
that oil pressure should be using with speed sensor and generator frequency together, in
order to make the starter separate with engine as soon as possible and can check start
exactly.
b. Speed sensor is the magnetic equipment which be installed in starter for detecting flywheel
teeth.
c. When set as engine speed, must ensure that the number of flywheel teeth is as same as
setting, otherwise, ―over speed stop‖ or ―under speed stop‖ may be caused.
d. If genset without speed sensor, please don’t select corresponding items which include
engine speed, otherwise, ―start fail‖ or ―loss of speed signal‖ maybe caused.
e. If genset without oil pressure sensor, please don’t select corresponding items which
include oil pressure.
f. If not select generator frequency in crank disconnect setting, controller will not collect and
display the relative power quantity (can be used in water pump set); if not select engine
speed in crank disconnect setting, the rotating speed displayed on LCD is calculated by
generator frequency and number of poles.
9 PARAMETERS SETTING
1) When reselect sensors, the sensor curve will be transferred into the standard value. For
example, if default temperature sensor is SGX (120°C resistor type), its sensor curve is SGX
(120°C resistor type); if select the SGD (120°C resistor type), the temperature sensor curve is
SGD curve.
2) When there is difference between standard sensor curves and using one, user can adjust it
in ―curve type‖.
3) When input the sensor curve, X value (resistor) must be input from small to large, otherwise,
mistake occurs.
4) If select sensor type as ―None‖, sensor curve is not working.
5) If corresponding sensor has alarm switch only, user must set this sensor as ―None‖,
otherwise, shutdown or warning alarm occurs.
6) The headmost or backmost values in the vertical coordinates can be set as the same one,
as shown below,
1) Set the controller as generator control mode, active power as 0% and reactive power as
0%;
2) During parallel operation off load, check if the active and reactive power is equal to zero;
1) Set the controller as generator control mode, active power as 50% and reactive power as
20%;
2) After manual parallel operation off load, check if the genset output active power is 50%
and reactive power is 20%.
12 MAINS PARALLEL
Set the mains on load power value. Once over the set value, genset will share the spare power.
Make sure that controller soundly connect to mains CT.
12.3 LOAD TAKEOVER MODE
Note: Fuse F1:min. 2A; max. 20A. Fuse F2:max. 32A. Users should select suitable
fuse depend on practical application.
3 Phase 3 Wire
2 Phase 3 Wire
Controller is panel built-in design; it is fixed by clips when installed. The controller’s overall
dimensions and cutout dimensions for panel, please refers to as following,
4) AC Input
Current transformer must be connected externally and the current transformer’s secondary
side current must be 5A. At the same time, the phases of current transformer and input voltage
must correct. Otherwise, the collected current and active power maybe not correct.
NOTE: ICOM port must be connected to negative pole of battery.
WARNING! When there is load current, transformer’s secondary side prohibit open
circuit.
5) Withstand Voltage Test
CAUTION! When controller had been installed in control panel, if need the high voltage test,
please disconnect controller’s all terminal connections, in order to prevent high voltage into
controller and damage it.
15 CONNECTIONS OF CONTROLLER WITH J1939 ENGINE
It is suitable for CM570 engine control module. Engine type is QSM11 G1, QSM11 G2.
Terminals of controller C1 connector Remark
Outside expand relay; When fuel
Fuel relay output 5&8 output, making port 5 and port 8 of C1
be connected.
Start relay output - Connect to starter coil directly
It is suitable for GCS engine control module. Use RS485-MODBUS to read engine information.
Engine types are QSX15, QST30, QSK23/45/60/78 and so on.
Terminals of controller D-SUB connector 06 Remark
Outside expand relay; When fuel
Fuel relay output 5&8 output, making port 05 and 08 of the
connector 06 be connected.
Start relay output - Connect to starter coil directly
It is suitable for MTU engine with ADEC (ECU8) and SMART module.
Terminals of controller ADEC (X1port) Remark
Fuel relay output X1 10 X1 Terminal 9 Connected to
negative of battery
Start relay output X1 34 X1 Terminal 33 Connected to
negative of battery
It is suitable for MTU engine with ADEC (ECU7) and SAM module.
Terminals of controller ADEC (X1port) Remark
Fuel relay output X1 43 X1 Terminal 28 Connected to
negative of battery
Start relay output X1 37 X1 Terminal 22 Connected to
negative of battery
15.15 SCANIA
It is suitable for S6 engine control module. Engine type is DC9, DC12, and DC16.
Terminals of controller B1 connector Remark
Fuel relay output 3
Start relay output - Connect to starter coil directly
CAN communication shielding
CAN GND - line(connect with controller at
controller’s side only)
Impedance 120Ω connecting line is
CAN(H) 9
recommended.
Impedance 120Ω connecting line is
CAN(L) 10
recommended.
Engine type: Scania
15.18 VOLVO-EMS2
Volvo Engine types are TAD734, TAD940, TAD941, TAD1640, TAD1641, and TAD1642.
Terminals of controller Engine’s CAN port Remark
ECU stop
Configurable output 1 6 Set configurable output 1 as ―ECU
stop‖
ECU power
Configurable output 2 5 Set configurable output 1 as ―ECU
power‖
3 Negative power
4 Positive power
CAN communication shielding
CAN GND - line(connect with controller at
controller’s side only)
Impedance 120Ω connecting line is
CAN(H) 1(Hi)
recommended.
Impedance 120Ω connecting line is
CAN(L) 2(Lo)
recommended.
Engine type: Volvo-EMS2
NOTE: When this engine type is selected, preheating time should be set more than 3
seconds.
15.19 YUCHAI
It is suitable for BOSCH common rail pump engine.
Terminals of controller Engine 42 pins port Remark
Fuel relay output 1.40 Connect to engine ignition lock
Start relay output - Connect to starter coil directly
CAN communication shielding
CAN GND - line(connect with controller at
controller’s side only)
Impedance 120Ω connecting line is
CAN(H) 1.35
recommended.
Impedance 120Ω connecting line is
CAN(L) 1.34
recommended.
15.20 WEICHAI
It is suitable for Weichai BOSCH common rail pump engine.
Terminals of controller Engine port Remark
Fuel relay output 1.40 Connect to engine ignition lock
Start relay output 1.61
CAN communication shielding
CAN GND - line(connect with controller at
controller’s side only)
CAN(H) 1.35 Impedance 120Ω connecting line is
recommended.
CAN(L) 1.34 Impedance 120Ω connecting line is
recommended.
Engine type: GTSC1
NOTE: If there is any question about communication between controller and ECU, please
feel free to contact Smartgen’s service.
16 USB
Users can set the controller’s parameters and monitor the controller’s status via the test
software which provided by Smartgen company. The connection way between PC and
controller as following:
17 FAULT FINDING