SASO-2012 - Emergency Lighting
SASO-2012 - Emergency Lighting
ICS:
CONTENTS
Page
Section 1: Emergency Lighting
Introduction 3
...............................…...............................................................
1.1 Scope ...............................…........................................................... 4
1.2 Definitions ...........................…....................................................... 4
1.3 Emergency escape lighting 5
.....…....................................................
1.3.1 General .....................................….................................................. 5
1.3.2 Escape route lighting .................…................................................ 6
1.3.3 Open area (anti-panic) lighting ....….............................................. 8
1.3.4 High risk task area lighting .............…........................................... 8
1.3.5 Stand-by lighting .................................…....................................... 9
1.4 Safety signs .......................................…......................................... 9
Annex A
Luminance and illuminance measurements 10
……………………………........
Annex A 20
Emergency lighting design guide
....................................................................
Annex B 22
Emergency lighting application classes
1
SAUDI ARABIAN STANDARD SASO 2012/2002
...........................................................
2
SAUDI ARABIAN STANDARD SASO 2012/2002
Page
Section 3: Automatic Test Systems for Battery Powered
Emergency Escape Lighting
3.1 Scope ..................................…........................................................ 25
3.2 Definitions ..............................….................................................... 25
3.3 Requirements .............................…................................................ 25
3.4 Test duration and frequency ........…............................................... 27
3.5 Marking .........................................…............................................. 27
3.6 Protection of a building during recharge of batteries 27
.....................
3.7 Indication of results of test ...............….......................................... 28
3
SAUDI ARABIAN STANDARD SASO 2012/2002
1.0 Introduction
Emergency lighting is provided for use when the supply to the normal lighting
fails and has therefore to be powered from a source independent of that
supplying the normal lighting.
Emergency lighting
Escape route lighting Open area lighting High risk task area
lighting
The requirements given in this standard are a minimum for design purposes
and are calculated for the full rated duration period and end of design life of
the equipment; the contribution to illumination by reflected light is ignored.
The overall objective of emergency escape lighting is to enable safe exit from a
location in the event of failure of the normal supply.
The objective of escape route lighting is to enable the safe exit from a location
for occupants by providing appropriate visual conditions and direction finding
on escape routes and in special locations, and to ensure that fire fighting and
safety equipment can be readily located and used.
4
SAUDI ARABIAN STANDARD SASO 2012/2002
5
SAUDI ARABIAN STANDARD SASO 2012/2002
1.2.5 open area lighting (in some countries known as anti-panic lighting):
That part of emergency escape lighting provided to avoid panic and provide
illumination allowing people to reach a place where an escape route can be
identified.
1.2.6 high risk task area lighting:
That part of emergency escape lighting that provides illumination for the safety
of people involved in a potentially dangerous process or situation and to enable
proper shut down procedures for the safety of the operator and other occupants
of the premises.
1.2.7 stand-by lighting:
That part of emergency lighting provided to enable normal activities to
continue substantially unchanged.
1.2.8 emergency exit:
A way out that is intended to be used during an emergency.
1.2.9 safety sign:
A sign which gives a general safety message, obtained by a combination of
colour and geometric shape and which, by the addition of a graphic symbol of
text, gives a particular safety message.
1.2.10 externally illuminated safety sign:
A sign that is illuminated when it is required, by an external source.
1.2.11 internally illuminated safety sign:
A sign that is illuminated when it is required, by an internal source.
1.3 Emergency escape lighting
1.3.1 General
To satisfy the visibility for evacuation purposes lighting is required in the
volume of the space. In this standard the recommendation is fulfilled by the
mounting of luminaires at least 2 m above the floor. Signs which are provided
at all exits intended to be used in an emergency and along escape routes shall
be illuminated to indicate unambiguously the route of escape to a point of
safety..
Where direct sight of an emergency exit is not possible, an illuminated
directional signs (or series of signs) shall be provided to assist progression
towards the emergency exit.
An escape lighting shall be sited to provide appropriate illuminance near each
exit door and at positions where it is necessary to emphasize potential danger
or safety equipment. The position to be emphasized shall include the
following:
6
SAUDI ARABIAN STANDARD SASO 2012/2002
Figure 1.2
7
SAUDI ARABIAN STANDARD SASO 2012/2002
Figure 1.3
NOTE - High contrast between a luminaire and its background may produce glare. In escape
route lighting the main problem will be disability glare, in which the brightness of the
luminaires may dazzle and prevent obstructions or signs being seen.
Table 1: Disability glare limits
Mounting height above Escape route and open High risk task area lighting
floor level h area (anti-panic) lighting maximum luminous
maximum luminous intensity lmax
intensity lmax
m cd cd
h < 2.5 500 1000
2.5 ≤ h < 3.0 900 1800
3.0 ≤ h < 3.5 1600 3200
3.5 ≤ h < 4.0 2500 5000
4.0 ≤ h < 4.5 3500 7000
h ≥ 4.5 5000 10000
1.3.2.4 In order to identify safety colours the minimum value for the colour rendering
index Ra from a lamp shall be 40. The luminaire shall not substantially
subtract from this.
1.3.2.5 The minimum duration of the illumination of the emergency escape lighting
allowed for escape purposes shall be 1 h.
1.3.2.6 The emergency escape route lighting shall reach 50% of the required
illuminance level within 5 s and full required illuminance within 60 s.
8
SAUDI ARABIAN STANDARD SASO 2012/2002
9
SAUDI ARABIAN STANDARD SASO 2012/2002
10
SAUDI ARABIAN STANDARD SASO 2012/2002
Annex A
(normative)
11
SAUDI ARABIAN STANDARD SASO 2012/2002
2.1 Scope
This section specifies the indication and illumination requirements of escape
routes in the event of failure of the normal supply, and specifies the minimum
provision of such emergency lighting based on the size, type and usage of the
premises.
This section relates to the provision of electric emergency escape lighting in all
work places and premises open to the public.
This section does not cover private domestic premises but its provisions may
be applicable to common access routes within multistorey dwellings.
This section is also applicable to standby lighting used as emergency escape
lighting.
2.2 Definitions
For the purposes of this section the following definitions apply.
2.2.1 Combined emergency luminaire:
An emergency lighting luminaire containing at least two lamps, at least one of
which is energized from the emergency lighting supply and the other from
normal lighting supply. A combined emergency luminaire is either maintained
or non-maintained.
2.2.2 Duration:
The period of time that the luminaire can continuously provide the minimum
illuminance required in the emergency condition.
NOTE: The time is specified in hours.
2.2.3 Externally illuminated safety signs:
A sign which is illuminated, when it is required, by an external source.
2.2.4 Internally illuminated signs:
A sign which is illuminated, when it is required, by an internal source.
2.2.5 Emergency escape route lighting:
That part of Emergency Escape Lighting which is provided to ensure that the
means of escape can be effectively identified and safely used at all times when
normal or emergency lighting is required.
12
SAUDI ARABIAN STANDARD SASO 2012/2002
13
SAUDI ARABIAN STANDARD SASO 2012/2002
14
SAUDI ARABIAN STANDARD SASO 2012/2002
15
SAUDI ARABIAN STANDARD SASO 2012/2002
16
SAUDI ARABIAN STANDARD SASO 2012/2002
17
SAUDI ARABIAN STANDARD SASO 2012/2002
In this case, operation of the emergency lighting shall be protected from the
effect of a short circuit, a contact to earth or an interruption of the wiring
between the control switch and the central system or self contained luminaires.
Any fault in the wiring to the control switch shall not prevent operation of the
emergency escape lighting.
NOTE: The control switch shall be either mechanically or electrically interlocked with an
essential service to ensure that the emergency lighting is not isolated when the premises are
occupied.
2.5 Choice of Appropriate Emergency Lighting System
The mode of operation and duration will need to meet National Legislation and
the following specific conditions. See Annex B.
2.5.1 Areas in which the normal lighting is reduced or dimmed during occupation
These areas shall have maintained or combined emergency luminaires.
2.5.2 Building higher than 10 storeys or areas that are underground
These locations which have restricted access for emergency services shall have
extended emergency durations.
2.5.3 Multiple use of a premises
Requires that the whole premise is provided with the longest emergency
lighting duration period requirement of any one part of it.
2.6 Emergency escape lighting system records and log book
On completion of the work, drawings of emergency lighting installation shall
be provided and retained on the premises. Such drawings should be regularly
updated with any subsequent changes to the system.
In addition, a log book conforming to 2.6.2 shall be provided for the recording
of routine examinations, tests, defects and alterations.
These shall be available as either a manual record or as a hard copy of an
automatic testing device.
2.6.1 System record:
On completion of a yearly inspection and test schedule as required in periodic
inspection and test certificate should be supplied to the person responsible for
the premises.
2.6.2 Log book:
A log book shall be kept on the premises in the care of a responsible person
appointed by the occupier/owner and shall be readily available for examination
by any duly authorized person.
The log book shall be used to record at least the following information:
18
SAUDI ARABIAN STANDARD SASO 2012/2002
19
SAUDI ARABIAN STANDARD SASO 2012/2002
The following minimum inspections and tests shall be carried out at the
intervals recommended in 2.7.3.2 to 2.7.3.4. Specific tests may be required by
the regulating authority.
2.7.3.2 Daily
Central power supply indicators shall be inspected for healthy operation.
2.7.3.3 Monthly
Tests shall be carried out as follows:
(a) Illuminate each luminaire and internally illuminated exit sign from its
battery simulation of a failure of the supply to the normal lighting for a
period sufficient to ensure that each lamp is illuminated.
NOTE: The period of simulated failure should not exceed one-quarter of the rated
duration of the luminaire or sign.
During this period, all luminaires and signs shall be checked to ensure
that they are present, clean and functioning correctly.
At the end of this test period the supply to the normal lighting should be
restored and any indicator lamp or device checked to ensure that it is
showing that the normal supply has been restored.
(b) In addition to (a), for central battery systems, the correct operation of
system monitors shall be checked.
NOTE: In general a 1 h duration is required.
(c) Automatic testing devices. Detection of failure during testing by, or of
an automatic testing system shall be indicated.
2.7.3.4 Annually
The monthly inspection shall be carried out and the following additional tests
made:
a) Each luminaire and internally illuminated sign shall be tested as 2.7.4.3
but for its full rated duration.
b) The supply of the normal lighting shall be restored and any indicator
lamp or device checked to ensure that it is showing that normal supply
has been restored. The charging arrangements should be checked for
proper functioning.
c) The date of the test and its results shall be recorded in the system log
book.
2.7.4 Automatic test devices
The functional operation of automatic test devices is under consideration.
20
SAUDI ARABIAN STANDARD SASO 2012/2002
Annex A (informative)
2.A.1 General
Before any detailed design work commences it is essential that consultation is
carried out in accordance with clause 2.4.1. The design procedure should
proceed as set out in the following sub-clauses of this annex.
2.A.2 Factors to be considered
In determining requirements the following points should be considered:
a) Verify escape routes;
b) Establish fire alarm call point position;
c) Establish position of fire fighting equipment;
d) Establish position of fire and safety signs;
e) Investigate potential hazards on escape routes;
f) Establish high risk areas;
g) Establish open areas;
h) Establish requirements for external escape lighting;
i) Locate lifts;
j) Locate moving stairways and walkways;
k) Locate toilet accommodation over 8m2 gross area;
l) Locate motor generator control and plant rooms;
m) Locate covered car parks;
n) Investigate need for standby lighting;
o) Establish areas of low fire risk for location of central power systems.
2.A.3 Design of illuminance
Having determined the positions and areas which need to be illuminated from
the emergency lighting system, the detailed design to minimum illuminances
can commence, as set out below:
a) Position emergency luminaires on plan to cover points of emphasis;
b) Verify mounting height of luminaires;
c) Investigate possible deterioration of luminaire light output due to dirt and
dust;
d) Check voltage and possible volt drop;
21
SAUDI ARABIAN STANDARD SASO 2012/2002
22
SAUDI ARABIAN STANDARD SASO 2012/2002
Annex B (informative)
2.B.1 General
The types of premises to which this code applies may be divided into the
following broad classes of application of B2 to B11. Examples of premises
falling within each of these classes are given but these are not necessarily
comprehensive. In case of doubt, the appropriate product class should be
agreed with the enforcing authority.
2.B.2 Premises used as sleeping accommodation
This class includes such premises as hospitals, nursing homes, hotels, guest
houses, clubs, colleges and schools.
Occupants of hospitals and nursing homes are likely to be infirm and difficult
to evacuate so extended durations are recommended.
Other sleeping risk areas are unlikely to be evacuated in the event of a normal
supply failure so an extended duration or rest mode system should be provided.
2.B.3 Common access routes within multi-storey dwellings
The majority of persons using access routes within multi-storey dwellings will
be familiar with them and the identification of such routes by signs may not,
therefore always be necessary. However the escape routes should be provided
with an emergency lighting system for evacuation duration unless it is higher
than 10 stories when extended duration is required.
2.B.4 Non-residential premises used for treatment or care
This class includes such premises as special schools, clinics and similar
premises. Reaction time to an emergency in premises of this type may be
expected to be shorter than when emergencies arise during the night but
possible difficulties of evacuation require the use of extended duration or rest
mode units.
2.B.5 Non-residential premises used for recreation
This included such premises as theatres, concert halls, exhibition halls, sports
halls, sports stadia, public houses and restaurants. Many of these premises will
not be evacuated in a mains failure so extended durations or rest mode should
be provided.
The people using such premises may be expected to be unfamiliar with their
layout so exit signs should be maintained. In parts of premises where the
normal lighting may be dimmed, a maintained emergency lighting system
should be installed.
23
SAUDI ARABIAN STANDARD SASO 2012/2002
24
SAUDI ARABIAN STANDARD SASO 2012/2002
25
SAUDI ARABIAN STANDARD SASO 2012/2002
3.1 Scope
This section specifies performance and safety requirements for automatic
testing systems for use with electrical light sources on supply voltages not
exceeding 1000v. It covers testing systems which can be built into and operate
with a single luminaire and systems which control and test a system
comprising.
Manual test facilities which rely on manual initiation and/or visual inspection
of the lamp condition are outside the scope of this standard..
3.2. Definitions
3.2.1 self-contained luminaires with built in automatic facilities
self-contained emergency luminaires with independent built in facilities to
initiate and indicate the results of tests.
3.2.2 self-contained luminaires with remote automatic facilities
multiple emergency luminaires working in conjunction with a remote panel.
This system initiates tests and indicates their results.
3.2.3 centrally powered system with automatic facilities
system in which the luminaires are initiated and tested for operation which is
then indicated.
NOTE - Compatibility between the central power supply and luminaires is outside the scope of
this standard.
3.3 Requirements
3.3.1 Safety, design and construction
All components shall conform to their relevant appropriate safety and
constructional requirements.
The design and construction of the system shall be such as to ensure that test
duration and frequency periods can only be changed by authorized personnel.
NOTE - Test circuit components may be installed within or adjacent to either self contained or
centrally powered slave luminaires. Additional components may be located in a remote panel.
26
SAUDI ARABIAN STANDARD SASO 2012/2002
3.3.2 Self-monitoring
The system shall monitor its own conformity to the test duration and frequency
requirements of clause 3.4. Any failure within the system that compromises
conformity to clause 3.4 shall be indicated as a malfunction.
Compliance is checked by simulating a fault in the circuit which interrupts the
progress of the test sequence.
3.3.3 Functional requirements
3.3.3.1 The test system shall automatically check emergency lighting luminaires and
power supplies, at frequencies and for durations specified in clause 3.4 to
identify faults that would impair their operational duty.
3.3.3.2 The test system shall check that the emergency supply is healthy and available.
Compliance is checked by disconnecting the battery during the test sequence -
a fault must then be indicated.
3.3.3.3 The test system shall check that any changeover device fitted has operated,
powering the lamp from the emergency battery supply.
Compliance is tested by checking that, during test conditions, the lamp power
must be obtained either solely from the battery or the discharge test must be
compensated for the effect of the battery charger.
3.3.3.4 The test system shall check that, in permanently maintained systems which do
not have a changeover device, the lamp operates correctly in both the mains
supply healthy and failed conditions.
NOTE - Maintained luminaires with a changeover device should be tested according to clause
3.3.3.3.
Compliance is checked by inspection and test.
3.3.4 Any failure of intercommunication between system components shall not
inhibit the emergency operation of a luminaire nor initiate an unwanted test.
During a functional test any failure of communication or operation shall be
indicated as a fault, either on the luminaire or remote panel.
Compliance is checked by inspection and test.
3.3.5 The test system shall check that lamp(s) are correctly energized for the
duration of the test.
Compliance is checked by:
a) removal of the emergency lamps; and
b) for fluorescent lamps, substitution by a failed lamp.
A fault indication shall be given in both cases.
27
SAUDI ARABIAN STANDARD SASO 2012/2002
28
SAUDI ARABIAN STANDARD SASO 2012/2002
29
SAUDI ARABIAN STANDARD SASO 2012/2002
4.1 Scope
This section specifies the general requirements for central power supply
systems for an independent energy supply to essential safety equipment. In
particular it covers systems permanently connected to a.c. supply voltages not
exceeding 1000 V and that use batteries as the alternative power source.
The central power supplies are intended to energize essential safety equipment
in the case of failure of the normal supply, for example:.
- emergency escape lighting
- electrical circuits of automatic fire extinguishing installations
- paging systems and signalling safety installations
- smoke extraction equipment
- carbon monoxide warning systems
- specific safety installations related to specific buildings e.g. high risk
areas.
A schematic representation of a typical central power supply equipment is
depicted in Clause 4.3. The scope of this section specifically excludes power
supplies for UPS systems.
4.2 Definitions
For the purposes of this standard, the following definitions apply.
4.2.1 automatic transfer switching device (ATSD):
A device arranged to connect the emergency supply automatically to the
essential safety equipment circuit(s) on failure of the normal supply or to
transfer the load from the normal supply to the battery.
4.2.2 battery charger:
That part of the equipment which provides the charge to the battery from the
normal supply.
4.2.3 inverter:
A device for the conversion of direct current (d.c.) to alternating current (a.c.).
30
SAUDI ARABIAN STANDARD SASO 2012/2002
31
SAUDI ARABIAN STANDARD SASO 2012/2002
32
SAUDI ARABIAN STANDARD SASO 2012/2002
The stored energy time in the case of a power failure is determined by the load,
the level of discharge and the capacity of the battery. Where the load requires
an a.c. supply, an inverter is included in the circuit, where a d.c. supply is
required, a converter circuit is included.
Figure 1
Figure 2
4.3.3 Changeover mode with additional control switching device for central
switching of the load:
In addition to the devices detailed in 4.3.1, the equipment includes a control
switch device(s) (C.S.D.) which is manually or automatically activated and is
dependent upon the mains supply being available and to ensure the emergency
power supply is not isolated at any material time (see figure 3).
33
SAUDI ARABIAN STANDARD SASO 2012/2002
NOTE: A number of control switch devices may be used to switch sections of the load.
Figure 3
4.3.4 Changeover mode with additional control switching device for partial
switching of the load:
In addition to the devices detailed in 4.3.1, the equipment includes a control
switching device for switching of the load activated by the existing power
supply voltage (see 4.3.3).
In variation to the concept defined in 4.3.3 part of the load, however, is
continuously supplied (see figure 4).
Figure 4
34
SAUDI ARABIAN STANDARD SASO 2012/2002
Figure 5
35
SAUDI ARABIAN STANDARD SASO 2012/2002
4.5 Construction
The equipment shall comply with the following requirements.
4.5.1 Structure of enclosure
4.5.1.1 Enclosures shall have adequate mechanical strength.
Compliance shall be checked by inspection and the following tests.
A straight and unjointed test finger is used with the same dimensions as the
standard test finger. The finger is pressed against the surface with a force of 30
N. During the test metal parts shall not touch live parts. After the test covers
shall not be excessively deformed.
4.5.1.2 Enclosures of the system shall have a degree of protection of at least IP 20.
4.5.1.3 Enclosures shall be resistant to heat and fire.
Compliance shall be checked by subjecting a sample of the material to the
850oC glow wire test. Fire Hazard Testing, Part 2: Test methods, glow wire
Test and Guidance.
NOTE: Metal enclosures are deemed to comply with this requirement.
4.5.1.4 All switching and testing devices intended to be actuated as well as the
indicating monitors and signalling devices shall be arranged so as to be visible
when in normal use.
4.5.1.5 Doors and removable panels shall be so fastened that access to dangerous live
parts is not possible without the use of a tool or key.
4.5.1.6 Devices within the enclosure shall be arranged to facilitate maintenance and
functional tests.
4.5.1.7 The arrangement of interconnections between components and equipments
shall be adequately and permanently identified.
4.5.1.8 Wireways shall be smooth and free from sharp edges, burrs, flashes etc, which
might cause damage to the insulation of the wiring parts. Metal screws shall
not protrude into wireways.
4.5.1.9 Battery chargers and rectifiers
Battery chargers and rectifiers shall comply with the following requirements:
4.5.2 Battery chargers shall be designed with full regard to the battery
manufacturer’s data and recommendations so as to optimize the battery service
life.
4.5.2.1 Battery chargers shall be of a controlled type and shall be capable of
automatically charging their batteries that have been discharged so that they
can perform at least 80% of their specified duration within 12 h on charge.
36
SAUDI ARABIAN STANDARD SASO 2012/2002
In the case of parallel standby mode where the load is supplied from the
charger, the nominal output current of the charger shall be equivalent to at least
110% of the sum of the specified load and battery recharge current.
Compliance shall be checked by carrying out the test given in 4.5.2.4.
4.5.2.2 Where maintained loads are permanently connected in the parallel standby
mode, the design of the battery charger and its associated system shall be such
that the voltage appearing at the output terminal shall not exceed the maximum
rated voltage of the loads.
4.5.2.3 Battery chargers shall incorporate smoothing circuits. The RMS ripple current
at the battery terminals which is superimposed by the float charge current and
may be fed back from the load (ie inverters) shall not exceed in sum 5 A per
100 Ah battery capacity. During temporary boost charge a higher RMS ripple
current is permitted.
4.5.2.4 Battery chargers shall provide their rated performance over their designed
ambient temperature range when operating on mains supply voltage.
Automatic compensation of battery charge voltage dependent on temperature
variations shall be provided if required by the battery manufacturer.
Compliance shall be checked by inspection and the following test.
The battery shall be charged for 36 h by application of the minimum rated
input voltage to the battery charger at nominal conditions. Immediately
following the charge, the battery shall be discharged using the designed load or
resistive equivalent to provide rated current at the nominal battery voltage.
The discharge shall be continued for the specified duration of the equipment
ensuring at the end of discharge that the battery voltage provided is not less
than the specified minimum voltage.
The battery shall be recharged at the minimum rated input voltage for 12 h at a
room ambient temperature of (20 ± 5)oC. Immediately following the recharge,
the battery shall be discharged at rated current to 80% of rated duration period
of the system at which time the battery voltage shall not be less than that
specified.
Equipment that does not pass this test shall be retested. Equipment that does
not pass the repeat test shall be deemed not to comply.
4.5.2.5 The battery charger shall be so designed that a short circuit on it’s output will
not cause damage.
Compliance shall be checked by disconnecting the battery and applying a short
circuit to the battery charger output. No damage other than operation of
protective devices shall occur.
4.5.3 Switching devices
4.5.3.1 Automatic transfer switches and electronic devices shall be of the appropriate
category for the load; they shall operate within the response time required.
Both poles of the safety equipment circuit shall be switched by the device.
37
SAUDI ARABIAN STANDARD SASO 2012/2002
38
SAUDI ARABIAN STANDARD SASO 2012/2002
39
SAUDI ARABIAN STANDARD SASO 2012/2002
NOTE: The removal of a fuse is not an acceptable means to isolate the a.c. supply.
c) indication of the actual power supply source (normal supply or battery).
d) indication of the following faults:
- float charge voltage (trickle charge current for Nickel/cadmium
battery) out of the permissible range.
- interruption of the battery charging circuit.
- failure in charge equipment; no charge current, although normal
supply is available.
- supply from the battery, although normal supply is available.
- deep discharge protection initiated.
When fitted, the following devices shall also provide indication of their
operation:
- Operation of the insulation monitoring device (earth leakage
indication).
- Failure of a powered ventilation system for battery cabinet or battery
room.
e) Facilities for a remote display of the following indicators via a potential-
free contact shall be provided for:
- systems in operation.
- supply from the battery.
- system disturbance combined fault indication as specified in item d).
NOTE: An audible alarm may also be provided.
4.5.6.3 Failure of the alarm indicator facility shall not prejudice the operation of the
power supply.
Compliance with the requirements of 4.5.6.1 to 4.5.6.3 is checked by
inspection and measurement by disconnecting the battery charger from the
battery.
4.5.7 Fuses, circuit protective devices
Semi-conductor protection fuses shall be of the special purpose high-speed
type.
Double pole protective devices and protective devices used in d.c. circuits shall
be d.c. rated for the required duty.
Alternatively digital meters may be used provided they are of equivalent
accuracy to the analogue meters.
Compliance shall be checked by inspection.
40
SAUDI ARABIAN STANDARD SASO 2012/2002
41
SAUDI ARABIAN STANDARD SASO 2012/2002
4.5.11 Batteries
4.5.11.1 Batteries shall comply with the appropriate one of the following applications:
1- Applies to lead-acid cells and batteries which are designed for service in
a fixed location (i.e. not habitually to be moved from place to place) and
which are permanently connected to the load and to the d.c. power
supply.
2- Applies to valve regulated stationary lead-acid cells and batteries for
service in a fixed location (i.e. not habitually to be moved from place to
place) and permanently connected to a load and to a d.c. power supply.
3. Specifies tests and requirements for sealed nickel-cadmium cylindrical
rechargeable single cells, suitable for use in any orientation. Specific
tests and requirements for cells intended for use in permanent charge at
elevated temperatures are also included.
4.5.11.2 Batteries for central power systems (CPS) shall be of a type having a declared
life expectancy of at least 10 years at 20oC ambient temperature.
Batteries for low power systems (LPS) shall be of a type having a declared life
expectancy of at least 5 years at 20oC ambient temperature.
NOTE: To achieve full performance at the end of life the battery capacity should be sized in
accordance with the battery manufacturers’ data.
4.5.11.3 Lead acid automotive batteries shall not be used.
4.5.11.4 The battery and system design shall be capable of meeting the declared
performance initially, during and at the end of the stated life.
NOTE 1: Usually batteries are rated to meet the specified performance and declared life
expectancy at 20oC.
Where a battery rated temperature different from 20oC is agreed between the
supplier and user, this shall be stated.
Where batteries are subjected to boost charge, the surface temperature of the
batteries within any cubicle shall not exceed 35oC when operated in an ambient
temperature of 25oC.
NOTE 2: When equipment is operated continuously in an ambient temperature outside the
range declared, the equipment manufacturer or supplier should be consulted.
4.5.11.5 At the end of the specified duration of the system, the output voltage shall be
not less than 90% of the nominal voltage at the nominal load.
Compliance is checked by inspection.
4.5.12 Battery installation and provision for maintenance
Batteries shall be installed and provision for maintenance made in accordance
with manufacturer’s recommendations.
42
SAUDI ARABIAN STANDARD SASO 2012/2002
43
SAUDI ARABIAN STANDARD SASO 2012/2002
- rated current;
- number of phases;
d) Output
- rated voltage (in r.m.s. volts);
- maximum load (in volt-amperes);
- minimum load (in volt-amperes);
- rated power (in watts) for duration (in hours);
- rated frequency (in hertz);
- power factor range;
- waveform description (non-sinusoidal shall be identified);
- harmonic distortion;
e) Maximum battery input ripple current (if applicable).
Compliance with clauses 4.5.13.2 to 4.5.13.5 shall be checked by inspection
and test.
4.5.14 Warning labels
4.5.14.1 A safety sign acceptable to National Requirements shall be fixed externally to
every panel or door giving access to live parts.
4.5.14.2 Where vented cells are used:
- a label indicating whether a battery of the alkaline of the acid type is
fitted and the treatment required after contact with the electrolyte shall be
fixed in a visible position within the battery enclosure;
- a label warning or explosion risks caused by naked flames shall be fixed
in a visible position on the exterior of the battery enclosure.
4.5.14.3 An external warning label shall state “Isolation of the normal supply to the
equipment may not make it safe for maintenance purposes”.
NOTE: Such warnings are necessary because, for example, non-illumination of an indicator
lamp does not always indicate that a circuit is dead, and a circuit still alive could present a
hazard to maintenance personnel.
Compliance is checked by inspection.
4.5.14.4 Equipment sited in a secure area
When equipment is sited in a secure area, a warning sign showing an electrical
equipment hazard shall be displayed as required by the local authority.
Compliance is checked by inspection.
4.6 Information for Installation and Operation of Central Power Supply
Systems
The system shall be provided with installation safety and operating
instructions.
44
SAUDI ARABIAN STANDARD SASO 2012/2002
The preliminary draft of this standard has been developed by the work team composed of:
Name Agency
1. Eng. M. J. Yousef Saudi Lighting Company
The draft standard was studied and the comments received thereon from concerned bodies
discussed. It has been adopted, in its present from, by the following members of Technical
Committee No. (4).
Name Agency
1. Dr. Mohamed Salah SMIAI King Abdul Aziz City for Sciences
and Technology (KACST)
2. Dr. Ibrahim O. Habiballah King Fahd University
Petroleum & Minerals - Dhahran
3. Dr. Abdul Rahman Ibrahim Alolah King Saud University - Riyadh
4. Eng. Abdul Rahman Saddiq Al-Fattani Saudi Arabia Airlines - Jeddah
5. Eng. Mohamed J. Yousef Saudi Lighting Co. - Riyadh
6. Eng. Ahmad H. Mohana EC
7. Eng. Ibraheem Al-Rathakany Ministry of Municipal & Rural Affairs
8. Mohamed El Sawy Farahat SASO
45