CABLE SCHEDULE

FOR RESTAURANTS/SHOPS& CINEMA


PANEL NAME METER
LENGTH IN NO OF CABLE
SL NO VOLTAGE HZ PF SIZE IN QTY TYPE ECC QTY TYPE REMARKS
MTR CORES SIZE
AMPS
FROM TO
1 SCECO METER RESTAURANT-1 150 400 60 0.8 150 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
2 SCECO METER RESTAURANT-2 125 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
3 SCECO METER RESTAURANT-3 124 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
4 SCECO METER RESTAURANT-4 55 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
5 SCECO METER RESTAURANT-5 55 400 60 0.8 200 4 150 1 XLPE/PVC/SWA 70 1 PVC Y/G
6 SCECO METER RESTAURANT-6 45 400 60 0.8 150 4 185 1 XLPE/PVC/SWA 95 1 PVC Y/G
7 SCECO METER RESTAURANT-7 55 400 60 0.8 150 4 150 1 XLPE/PVC/SWA 70 1 PVC Y/G
8 SCECO METER RESTAURANT-8 150 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
9 SCECO METER RESTAURANT-9 140 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
10 SCECO METER RESTAURANT-10 140 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
11 SCECO METER RESTAURANT-11 120 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
12 SCECO METER RESTAURANT-12 118 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
13 SCECO METER RESTAURANT-13 116 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
14 SCECO METER RESTAURANT-14 100 400 60 0.8 200 4 120 1 XLPE/PVC/SWA 70 1 PVC Y/G
15 SCECO METER RESTAURANT-15 95 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
16 SCECO METER RESTAURANT-16 85 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
17 SCECO METER RESTAURANT-17 75 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
18 SCECO METER RESTAURANT-18 73 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
19 SCECO METER RESTAURANT-19 73 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
20 SCECO METER RESTAURANT-20 75 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
21 SCECO METER RESTAURANT-21 85 400 60 0.8 200 4 95 1 XLPE/PVC/SWA 50 1 PVC Y/G
22 SCECO METER KIOSK-1 120 400 60 0.8 50 4 25 1 XLPE/PVC/SWA 16 1 PVC Y/G
23 SCECO METER KIOSK-2 130 400 60 0.8 50 4 25 1 XLPE/PVC/SWA 16 1 PVC Y/G
24 SCECO METER CINEMA-LGT&POWER 120 400 60 0.8 1000 4 240 3 XLPE/PVC/SWA 120 3 PVC Y/G
25 SCECO METER CINEMA-A/C 120 400 60 0.8 1000 4 240 3 XLPE/PVC/SWA 120 3 PVC Y/G
26 SCECO METER ENTERTAINMENT AREA 60 400 60 0.8 1000 4 300 2 XLPE/PVC/SWA 150 2 PVC Y/G
CABLE SCHEDULE-MDB SERVICE

SHORT
PANEL NAME DEMAND DEMAND ACCUMU
LENGTH IN CONNECTED CONNECTED DEMAND DEMAND DEMAND BREAKER BREAKER NO OF CABLE CIRCUIT
SL NO VOLTAGE HZ PF LOAD IN LOAD IN QTY TYPE ECC QTY TYPE VD % LATED REMARKS
MTR LOAD IN VA LOAD IN KW FACTOR LOAD IN VA CURRENT SIZE-AT SIZE-AF CORES SIZE CURREN
KVA KW VD %
T
FROM TO
1 METER UNIT MDB SERVICE-1 20 400 60 0.8 133484.00 106.79 0.90 120135.60 120.14 96.11 173.41 250 250 4 95 1 XLPE/PVC 50 1 PVC Y/G 0.38 0.38 21.80
2 MDB SERVICE-1 LPPG-PR-1 30 400 60 0.8 830.00 0.66 0.90 747.00 0.75 0.60 1.08 40 63 4 10 1 XLPE/PVC/SWA 10 1 PVC Y/G 0.03 0.41 2.88
3 MDB SERVICE-1 MCC MECH-1 32 400 60 0.8 48330.00 38.66 0.70 33831.00 33.83 27.06 48.83 100 100 4 25 1 XLPE/PVC/SWA 16 1 PVC Y/G 0.54 0.93 5.74
4 MDB SERVICE-1 LP EXT 85 400 60 0.8 36012.00 28.81 1.00 36012.00 36.01 28.81 51.98 100 100 4 25 1 XLPE/PVC/SWA 16 1 PVC Y/G 1.54 1.92 2.58
5 MDB SERVICE-1 CP-FIRE PUMP 42 400 60 0.8 46812.00 37.45 1.00 46812.00 46.81 37.45 67.57 125 250 4 50 1 XLPE/PVC/SWA 25 1 PVC Y/G 0.56 0.94 7.30
6 MDB SERVICE-1 LPPG-EL-1 15 400 60 0.8 1500.00 1.20 1.00 1500.00 1.50 1.20 2.17 40 63 4 6 1 XLPE/PVC 6 1 PVC Y/G 0.05 0.43 3.34
7 METER UNIT MDB SERVICE-2 20 400 60 0.8 132954.00 106.36 0.90 119658.60 119.66 95.73 172.72 250 250 4 95 1 XLPE/PVC 50 1 PVC Y/G 0.38 0.38 21.80
8 MDB-SERVICE-2 LPPG-1 45 400 60 0.8 3490.00 2.79 0.90 3141.00 3.14 2.51 4.53 40 63 4 10 1 XLPE/PVC/SWA 10 1 PVC Y/G 0.17 0.55 2.00
9 MDB-SERVICE-2 LPPG-2 85 400 60 0.8 19208.00 15.37 0.90 17287.20 17.29 13.83 24.95 40 63 4 10 1 XLPE/PVC/SWA 10 1 PVC Y/G 1.77 2.15 1.11
10 MDB-SERVICE-2 LPPG-PR-2 70 400 60 0.8 780.00 0.62 0.90 702.00 0.70 0.56 1.01 40 63 4 10 1 XLPE/PVC/SWA 10 1 PVC Y/G 0.06 0.44 1.33
11 MDB-SERVICE-2 MCC MECH-2 70 400 60 0.8 21165.00 16.93 0.70 14815.50 14.82 11.85 21.38 60 63 4 16 1 XLPE/PVC/SWA 10 1 PVC Y/G 0.81 1.19 2.02
12 MDB-SERVICE-2 MCC MECH-R 60 400 60 0.8 30000.00 24.00 1.00 30000.00 30.00 24.00 43.30 100 63 4 25 1 XLPE/PVC/SWA 16 1 PVC Y/G 0.90 1.29 3.48
13 MDB-SERVICE-2 ELEVATOR 88 400 60 0.8 9999.00 8.00 1.00 9999.00 10.00 8.00 14.43 30 63 4 6 1 XLPE/PVC/SWA 6 1 PVC Y/G 1.77 2.15 0.65
14 MDB-SERVICE-2 CP-FIRE PUMP 67 400 60 0.8 46812.00 37.45 1.00 46812.00 46.81 37.45 67.57 125 250 4 50 1 XLPE/PVC/SWA 25 1 PVC Y/G 0.89 1.27 5.22
15 MDB-SERVICE-2 LPPG-EL-2 15 400 60 0.8 1500.00 1.20 1.00 1500.00 1.50 1.20 2.17 40 100 4 6 1 XLPE/PVC 6 1 0.05 0.43 3.34
CP WATER BOOSTER
16 MCC MECH-1 15 400 60 0.8 19665.00 15.73 0.70 13765.50 13.77 11.01 19.87 60 100 4 16 1 XLPE/PVC 10 1 PVC Y/G 0.16 1.09 3.70
PUMP
CP IRRI BOOSTER
17 MCC MECH-1 15 400 60 0.8 8433.00 6.75 0.70 5903.10 5.90 4.72 8.52 30 63 4 6 1 XLPE/PVC 6 1 PVC Y/G 0.18 1.10 2.33
PUMP
CP WATER FEATURE
18 MCC MECH-1 120 400 60 0.8 9366.00 7.49 0.70 6556.20 6.56 5.24 9.46 30 63 4 6 1 XLPE/PVC/SWA 6 1 PVC Y/G 1.58 2.51 0.45
PUMP-1
CP WATER FEATURE
19 MCC MECH-1 90 400 60 0.8 9366.00 7.49 0.70 6556.20 6.56 5.24 9.46 30 63 4 6 1 XLPE/PVC/SWA 6 1 PVC Y/G 1.19 2.11 0.59
PUMP-2
20 MCC MECH-1 CP SUMP PUMP 15 230 60 0.8 1500.00 1.20 0.50 750.00 0.75 0.60 1.08 20 60 3 4 1 XLPE/PVC
CP WATER BOOSTER
21 MCC MECH-2 15 400 60 0.8 19665.00 15.73 0.70 13765.50 13.77 11.01 19.87 60 100 4 16 1 XLPE/PVC 10 1 PVC Y/G 0.16 1.09 3.70
PUMP
22 MCC MECH-2 CP SUMP PUMP 15 230 60 0.8 1500.00 1.20 0.50 750.00 0.75 0.60 1.08 20 60 3 4 1 XLPE/PVC
23 MCC MECH-R PACKAGE UNIT-1 50 400 60 0.8 15000.00 12.00 1.00 15000.00 15.00 12.00 21.65 40 63 4 10 1 XLPE/PVC 10 1 PVC Y/G 0.91 2.19 1.26
24 MCC MECH-R PACKAGE UNIT-2 20 400 60 0.8 15000.00 12.00 1.00 15000.00 15.00 12.00 21.65 40 63 4 10 1 XLPE/PVC 10 1 PVC Y/G 0.91 2.19 1.26
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

Upstream Switchboard METER UNIT Load MDB SERVICE-1

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 96 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing TOUCHING No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 20
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 0.95
Overall derating factor 0.91
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 173 Amp Required current carrying capacity 191 Amp

For C.B.selection( I ) times 1.25 Rated operating current 217 Amp


C.B size (AT) 250 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 95 mm2 Catalogue Ampacity 305 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 278 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.248000 Ω X (ohm/Km/cable) 0.093000 Ω
Z (ohm/Km/cable) 0.254200 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 1.527 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.38 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 1.527 + 0.000 = 1.527 Volts

% Accumulated Voltage Drop 0.38 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

0.004960 0.001860

MDB SERVICE-1 0.004960 0.001860


Total 0.009920 0.003720
Impedence, Z (Ω/Km) = 0.010595 // Z =√ (R² + X²)
Calculated Short Circuit = 21.80 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB
Upstream Switchboard Load LPPG-PR-1
SERVICE-1

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) 45 Depth of laying (cm) 100

No.of cables/
Power (KW) 1 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 30
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.96
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 1 Amp Required current carrying capacity 1 Amp

For C.B.selection( I ) times 1.25 Rated operating current 1 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 87 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 83 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.108 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.03 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.108 + 1.527 = 1.635 Volts

% Accumulated Voltage Drop 0.41 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB SERVICE-1 0.0099200 0.0037200

LPPG-PR-1 0.069990 0.003270


Total 0.079910 0.006990
Impedence, Z (Ω/Km) = 0.080215 // Z =√ (R² + X²)
Calculated Short Circuit = 2.88 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB
Upstream Switchboard Load MCC MECH-1
SERVICE-1

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 27 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 32
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 49 Amp Required current carrying capacity 50 Amp

For C.B.selection( I ) times 1.25 Rated operating current 61 Amp


C.B size (AT) 100 Amp C.B size (AF) 100 Amp
Selected cable/conductor size 25 mm2 Catalogue Ampacity 145 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 143 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.927000 Ω X (ohm/Km/cable) 0.103000 Ω
Z (ohm/Km/cable) 0.803400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 2.174 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.54 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 2.174 + 1.527 = 3.701 Volts

% Accumulated Voltage Drop 0.93 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB SERVICE-1 0.0099200 0.0037200

MCC MECH-1 0.029664 0.003296


Total 0.039584 0.007016
Impedence, Z (Ω/Km) = 0.040201 // Z =√ (R² + X²)
Calculated Short Circuit = 5.74 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB
Upstream Switchboard Load LP EXT
SERVICE-1

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 29 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 85
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 52 Amp Required current carrying capacity 53 Amp

For C.B.selection( I ) times 1.25 Rated operating current 65 Amp


C.B size (AT) 100 Amp C.B size (AF) 100 Amp
Selected cable/conductor size 25 mm2 Catalogue Ampacity 145 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 143 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.927000 Ω X (ohm/Km/cable) 0.103000 Ω
Z (ohm/Km/cable) 0.803400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 6.148 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.54 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 6.148 + 1.527 = 7.675 Volts

% Accumulated Voltage Drop 1.92 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB SERVICE-1 0.0099200 0.0037200

LP EXT 0.078795 0.008755


Total 0.088715 0.012475
Impedence, Z (Ω/Km) = 0.089588 // Z =√ (R² + X²)
Calculated Short Circuit = 2.58 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB
Upstream Switchboard Load CP-FIRE PUMP
SERVICE-1

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 37 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 42
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 68 Amp Required current carrying capacity 69 Amp

For C.B.selection( I ) times 1.25 Rated operating current 84 Amp


C.B size (AT) 125 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 50 mm2 Catalogue Ampacity 207 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 204 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.494000 Ω X (ohm/Km/cable) 0.098000 Ω
Z (ohm/Km/cable) 0.454000 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 2.232 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.56 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 2.232 + 1.527 = 3.758 Volts

% Accumulated Voltage Drop 0.94 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB SERVICE-1 0.0099200 0.0037200

CP-FIRE PUMP 0.020748 0.004116


Total 0.030668 0.007836
Impedence, Z (Ω/Km) = 0.031653 // Z =√ (R² + X²)
Calculated Short Circuit = 7.30 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB
Upstream Switchboard Load LPPG-EL-1
SERVICE-1

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 1 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 15
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 2 Amp Required current carrying capacity 2 Amp

For C.B.selection( I ) times 1.25 Rated operating current 3 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 53 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 50 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.181 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.05 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.181 + 1.527 = 1.708 Volts

% Accumulated Voltage Drop 0.43 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB SERVICE-1 0.0099200 0.0037200

LPPG-EL-1 0.058950 0.001815


Total 0.068870 0.005535
Impedence, Z (Ω/Km) = 0.069092 // Z =√ (R² + X²)
Calculated Short Circuit = 3.34 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

Upstream Switchboard METER UNIT Load MDB SERVICE-2

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 96 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing TOUCHING No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 20
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 0.95
Overall derating factor 0.91
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 173 Amp Required current carrying capacity 190 Amp

For C.B.selection( I ) times 1.25 Rated operating current 216 Amp


C.B size (AT) 250 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 95 mm2 Catalogue Ampacity 305 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 278 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.248000 Ω X (ohm/Km/cable) 0.093000 Ω
Z (ohm/Km/cable) 0.254200 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 1.521 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.38 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 1.521 + 0.000 = 1.521 Volts

% Accumulated Voltage Drop 0.38 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

0.004960 0.001860

MDB SERVICE-2 0.004960 0.001860


Total 0.009920 0.003720
Impedence, Z (Ω/Km) = 0.010595 // Z =√ (R² + X²)
Calculated Short Circuit = 21.80 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load LPPG-1
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 3 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 45
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 5 Amp Required current carrying capacity 5 Amp

For C.B.selection( I ) times 1.25 Rated operating current 6 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 87 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 86 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.683 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.17 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.683 + 1.521 = 2.203 Volts

% Accumulated Voltage Drop 0.55 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

LPPG-1 0.104985 0.004905


Total 0.114905 0.008625
Impedence, Z (Ω/Km) = 0.115228 // Z =√ (R² + X²)
Calculated Short Circuit = 2.00 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load LPPG-2
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 14 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 85
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 25 Amp Required current carrying capacity 25 Amp

For C.B.selection( I ) times 1.25 Rated operating current 31 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 87 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 86 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 7.097 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.77 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 7.097 + 1.521 = 8.617 Volts

% Accumulated Voltage Drop 2.15 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

LPPG-2 0.198305 0.009265


Total 0.208225 0.012985
Impedence, Z (Ω/Km) = 0.208629 // Z =√ (R² + X²)
Calculated Short Circuit = 1.11 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load LPPG-PR-2
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) 45 Depth of laying (cm) 100

No.of cables/
Power (KW) 1 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 70
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.96
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 1 Amp Required current carrying capacity 1 Amp

For C.B.selection( I ) times 1.25 Rated operating current 1 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 87 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 83 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.237 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.06 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.237 + 1.521 = 1.758 Volts

% Accumulated Voltage Drop 0.44 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

LPPG-PR-2 0.163310 0.007630


Total 0.173230 0.011350
Impedence, Z (Ω/Km) = 0.173601 // Z =√ (R² + X²)
Calculated Short Circuit = 1.33 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load MCC MECH-2
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 12 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 70
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 21 Amp Required current carrying capacity 22 Amp

For C.B.selection( I ) times 1.25 Rated operating current 27 Amp


C.B size (AT) 60 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 16 mm2 Catalogue Ampacity 112 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 110 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 1.486000 Ω X (ohm/Km/cable) 0.106000 Ω
Z (ohm/Km/cable) 1.252400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 3.247 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.81 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 3.247 + 1.527 = 4.774 Volts

% Accumulated Voltage Drop 1.19 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

MCC MECH-2 0.104020 0.007420


Total 0.113940 0.011140
Impedence, Z (Ω/Km) = 0.114483 // Z =√ (R² + X²)
Calculated Short Circuit = 2.02 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load MCC MECH-R
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 24 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 60
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 43 Amp Required current carrying capacity 44 Amp

For C.B.selection( I ) times 1.25 Rated operating current 54 Amp


C.B size (AT) 100 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 25 mm2 Catalogue Ampacity 145 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 143 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.927000 Ω X (ohm/Km/cable) 0.103000 Ω
Z (ohm/Km/cable) 0.803400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 3.615 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.90 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 3.615 + 1.527 = 5.142 Volts

% Accumulated Voltage Drop 1.29 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

MCC MECH-R 0.055620 0.006180


Total 0.065540 0.009900
Impedence, Z (Ω/Km) = 0.066283 // Z =√ (R² + X²)
Calculated Short Circuit = 3.48 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load ELEVATOR
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 8 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 88
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 14 Amp Required current carrying capacity 15 Amp

For C.B.selection( I ) times 1.25 Rated operating current 18 Amp


C.B size (AT) 30 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 66 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 65 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 7.076 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.77 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 7.076 + 1.527 = 8.603 Volts

% Accumulated Voltage Drop 2.15 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

ELEVATOR 0.345840 0.010648


Total 0.355760 0.014368
Impedence, Z (Ω/Km) = 0.356050 // Z =√ (R² + X²)
Calculated Short Circuit = 0.65 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load CP-FIRE PUMP
SERVICE-2

ARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor G.DIRECT
Thermal resistivity of soil 1 90 Installation Method
temperature (°C) LAID

Ground Temperature (°C) 40 Air temp.(°C) ----- Depth of laying (cm) 100

No.of cables/
Power (KW) 37 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 67
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth 0.95

Derating factor for variation in thermal resistivity 1.00


Derating factor for variation in air temp. N/A
Derating factor for grouping 1.00
Overall derating factor 0.98
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 68 Amp Required current carrying capacity 69 Amp

For C.B.selection( I ) times 1.25 Rated operating current 84 Amp


C.B size (AT) 125 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 50 mm2 Catalogue Ampacity 207 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 204 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.494000 Ω X (ohm/Km/cable) 0.098000 Ω
Z (ohm/Km/cable) 0.454000 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 3.560 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.89 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 3.560 + 1.527 = 5.087 Volts

% Accumulated Voltage Drop 1.27 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

CP-FIRE PUMP 0.033098 0.006566


Total 0.043018 0.010286
Impedence, Z (Ω/Km) = 0.044231 // Z =√ (R² + X²)
Calculated Short Circuit = 5.22 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MDB-
Upstream Switchboard Load LPPG-EL-2
SERVICE-2

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 1 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 15
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 2 Amp Required current carrying capacity 2 Amp

For C.B.selection( I ) times 1.25 Rated operating current 3 Amp


C.B size (AT) 40 Amp C.B size (AF) 100 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 53 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 50 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.181 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.05 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.181 + 1.521 = 1.702 Volts

% Accumulated Voltage Drop 0.43 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MDB-SERVICE-2 0.0099200 0.0037200

LPPG-EL-2 0.058950 0.001815


Total 0.068870 0.005535
Impedence, Z (Ω/Km) = 0.069092 // Z =√ (R² + X²)
Calculated Short Circuit = 3.34 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

CP WATER BOOSTER
Upstream Switchboard MCC MECH-1 Load
PUMP

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 11 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 15
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 20 Amp Required current carrying capacity 21 Amp

For C.B.selection( I ) times 1.25 Rated operating current 25 Amp


C.B size (AT) 60 Amp C.B size (AF) 100 Amp
Selected cable/conductor size 16 mm2 Catalogue Ampacity 96 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 90 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 1.486000 Ω X (ohm/Km/cable) 0.106000 Ω
Z (ohm/Km/cable) 1.252400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.646 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.16 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.646 + 3.701 = 4.348 Volts

% Accumulated Voltage Drop 1.09 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-1 0.0395840 0.0070160

CP WATER BOOSTER PUMP 0.022290 0.001590


Total 0.061874 0.008606
Impedence, Z (Ω/Km) = 0.062470 // Z =√ (R² + X²)
Calculated Short Circuit = 3.70 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

CP IRRI BOOSTER
Upstream Switchboard MCC MECH-1 Load
PUMP

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 5 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 15
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 9 Amp Required current carrying capacity 9 Amp

For C.B.selection( I ) times 1.25 Rated operating current 11 Amp


C.B size (AT) 30 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 53 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 50 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 0.712 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.18 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 0.712 + 3.701 = 4.413 Volts

% Accumulated Voltage Drop 1.10 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-1 0.0395840 0.0070160

CP IRRI BOOSTER PUMP 0.058950 0.001815


Total 0.098534 0.008831
Impedence, Z (Ω/Km) = 0.098929 // Z =√ (R² + X²)
Calculated Short Circuit = 2.33 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

CP WATER FEATURE
Upstream Switchboard MCC MECH-1 Load
PUMP-1

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 5 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 120
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 9 Amp Required current carrying capacity 10 Amp

For C.B.selection( I ) times 1.25 Rated operating current 12 Amp


C.B size (AT) 30 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 53 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 50 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 6.327 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.58 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 6.327 + 3.701 = 10.028 Volts

% Accumulated Voltage Drop 2.51 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-1 0.0395840 0.0070160

CP WATER FEATURE PUMP-1 0.471600 0.014520


Total 0.511184 0.021536
Impedence, Z (Ω/Km) = 0.511637 // Z =√ (R² + X²)
Calculated Short Circuit = 0.45 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

CP WATER FEATURE
Upstream Switchboard MCC MECH-1 Load
PUMP-2

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 5 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 90
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 9 Amp Required current carrying capacity 10 Amp

For C.B.selection( I ) times 1.25 Rated operating current 12 Amp


C.B size (AT) 30 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 6 mm2 Catalogue Ampacity 53 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 50 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 3.930000 Ω X (ohm/Km/cable) 0.121000 Ω
Z (ohm/Km/cable) 3.216600 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 4.745 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.19 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 4.745 + 3.701 = 8.446 Volts

% Accumulated Voltage Drop 2.11 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-1 0.0395840 0.0070160

CP WATER FEATURE PUMP-2 0.353700 0.010890


Total 0.393284 0.017906
Impedence, Z (Ω/Km) = 0.393691 // Z =√ (R² + X²)
Calculated Short Circuit = 0.59 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MCC MECH-
Upstream Switchboard Load PACKAGE UNIT-1
R

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 12 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 50
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 22 Amp Required current carrying capacity 23 Amp

For C.B.selection( I ) times 1.25 Rated operating current 27 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 73 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 68 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 3.622 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.91 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 3.622 + 5.142 = 8.764 Volts

% Accumulated Voltage Drop 2.19 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-R 0.0655400 0.0099000

PACKAGE UNIT-1 0.116650 0.005450


Total 0.182190 0.015350
Impedence, Z (Ω/Km) = 0.182835 // Z =√ (R² + X²)
Calculated Short Circuit = 1.26 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : KHAMIS MUSHIT Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

MCC MECH-
Upstream Switchboard Load PACKAGE UNIT-1
R

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 12 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 50
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 22 Amp Required current carrying capacity 23 Amp

For C.B.selection( I ) times 1.25 Rated operating current 27 Amp


C.B size (AT) 40 Amp C.B size (AF) 63 Amp
Selected cable/conductor size 10 mm2 Catalogue Ampacity 73 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 68 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 2.333000 Ω X (ohm/Km/cable) 0.109000 Ω
Z (ohm/Km/cable) 1.931800 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 3.622 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 0.91 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 3.622 + 5.142 = 8.764 Volts

% Accumulated Voltage Drop 2.19 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

MCC MECH-R 0.0655400 0.0099000

PACKAGE UNIT-1 0.116650 0.005450


Total 0.182190 0.015350
Impedence, Z (Ω/Km) = 0.182835 // Z =√ (R² + X²)
Calculated Short Circuit = 1.26 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : DOHAIYYAN SULYMAN Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

SCECO
Upstream Switchboard Load Rest-1
METER

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 65 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 150
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 117 Amp Required current carrying capacity 125 Amp

For C.B.selection( I ) times 1.25 Rated operating current 147 Amp


C.B size (AT) 160 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 95 mm2 Catalogue Ampacity 305 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 285 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.248000 Ω X (ohm/Km/cable) 0.093000 Ω
Z (ohm/Km/cable) 0.254200 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 7.745 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.94 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 7.745 + 0.000 = 7.745 Volts

% Accumulated Voltage Drop 1.94 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

SCECO METER 0.0430180 0.0102860

Rest-1 0.037200 0.013950


Total 0.080218 0.024236
Impedence, Z (Ω/Km) = 0.083799 // Z =√ (R² + X²)
Calculated Short Circuit = 2.76 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : DOHAIYYAN SULYMAN Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

Upstream Switchboard Err:509 Load Err:509

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 90 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 95
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 162 Amp Required current carrying capacity 174 Amp

For C.B.selection( I ) times 1.25 Rated operating current 203 Amp


C.B size (AT) 200 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 95 mm2 Catalogue Ampacity 305 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 285 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.248000 Ω X (ohm/Km/cable) 0.093000 Ω
Z (ohm/Km/cable) 0.254200 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 6.792 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.70 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 6.792 + 0.000 = 6.792 Volts

% Accumulated Voltage Drop 1.70 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

Err:509 0.0430180 0.0102860

Err:509 0.023560 0.008835


Total 0.066578 0.019121
Impedence, Z (Ω/Km) = 0.069269 // Z =√ (R² + X²)
Calculated Short Circuit = 3.33 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : DOHAIYYAN SULYMAN Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

SCECO
Upstream Switchboard Load REST-10
METER

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 21 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 130
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 1.00
Overall derating factor 0.94
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 38 Amp Required current carrying capacity 41 Amp

For C.B.selection( I ) times 1.25 Rated operating current 47 Amp


C.B size (AT) 50 Amp C.B size (AF) 250 Amp
Selected cable/conductor size 25 mm2 Catalogue Ampacity 130 Amp
No. of cables/(conductor/ph) 1 Actual Ampacity 122 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.927000 Ω X (ohm/Km/cable) 0.103000 Ω
Z (ohm/Km/cable) 0.803400 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 6.854 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.71 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 6.854 + 0.000 = 6.854 Volts

% Accumulated Voltage Drop 1.71 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

SCECO METER 0.0430180 0.0102860

REST-10 0.120510 0.013390


Total 0.163528 0.023676
Impedence, Z (Ω/Km) = 0.165233 // Z =√ (R² + X²)
Calculated Short Circuit = 1.40 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)
CALCULATION SHEET

Project Name : DOHAIYYAN SULYMAN Date : 12/2/2024


Project No. : Computed By : ENG. ROY RAPHAEL
Building Name : Checked By : ENG. ROY RAPHAEL
Subject : VOLTAGE DROP AND SHORT CIRCUIT CALCULATIONS

SCECO
Upstream Switchboard Load OFFICE 22
METER

UNARM. CU
Selected Cable Type No. of cores 4 Insulation XLPE
CABLE
Conductor LAID IN FREE
Thermal resistivity of soil ----- 90 Installation Method
temperature (°C) AIR

Ground Temperature (°C) ----- Air temp.(°C) 45 Depth of laying (cm) -----

No.of cables/
Power (KW) 440 1 Voltage (V) 400
circuits in group
Power factor (Ø) 0.8 Spacing d No.of phases 3
Load factor for the cable 0.70 No of Tray layers 1 Length (m) 60
Frequency (Hz) 60 Standard selection NEC
DERATING FACTORS
Derating factor for variation in ground temp. N/A

Derating factor for variation in burial depth N/A

Derating factor for variation in thermal resistivity N/A


Derating factor for variation in air temp. 0.87
Derating factor for grouping 0.98
Overall derating factor 0.93
CABLE AND CIRCUIT BREAKER SELECTION
Rated operating current ( I ) 794 Amp Required current carrying capacity 858 Amp

For C.B.selection( I ) times 1.25 Rated operating current 992 Amp


C.B size (AT) 1000 Amp C.B size (AF) 400 Amp
Selected cable/conductor size 240 mm2 Catalogue Ampacity 1102 Amp
No. of cables/(conductor/ph) 2 Actual Ampacity 1019 Amp
VOLTAGE DROP CALCULATION
R (ohm/Km/cable) 0.099300 Ω X (ohm/Km/cable) 0.090000 Ω
Z (ohm/Km/cable) 0.133440 Ω // Z= ( RCOS(ø)+XSIN(ø))

Volts // for 3-ph: VD= √3*I*L*Z/(1000*no.of // cables)


Voltage drop on feeder 5.504 // for 1-ph: VD=2*I*L*Z/(1000*no.of // cables)
% Voltage drop 1.38 % // %VD = volt.drop*100/ voltage
Accumulated Voltage drop 5.504 + 0.000 = 5.504 Volts

% Accumulated Voltage Drop 1.38 %

SHORT CIRCUIT CALCULATION


Resistance (R) Ω Reactance (X) Ω

SCECO METER 0.0430180 0.0102860

OFFICE 22 0.002979 0.002700


Total 0.045997 0.012986
Impedence, Z (Ω/Km) = 0.047795 // Z =√ (R² + X²)
Calculated Short Circuit = 4.83 KA // S.C= VL-N / Z
Input Data (Variable)
Note: The above calculations are based upon the values taken from "Riyadh Cable" Catalogue
Output Data (Fixed)