flow control
flow control
Problem description
Determine a suitable working point of the flow control system for the coming
commissioning.
Procedure
1. Which measured value lies exactly in the center of the working
range? Set the pump voltage for this
working point. Measure the sensor signal or the output signal of the measuring transducer.
2. Fill the mixing tank VE4 with ~7l
water each.
3. Open hand valve VW10 and VV12. Close allother
hand valves.
4. Start FluidLab®.PA closed-loop - select the "Measure and
control" menu.
5 Select "low rate", "A_OUTO Pump", and "OUT" as display values.
6. Switch on binary output bito (MA1).
7. Select "A_OUTO Pump" as the manipulated variable and specify a pump
voltage.
8. Start the execution andswitch the "manipulated variable" ON.
9. Change the pump voltage. What is the pump voitage for the constant flow rate at the working point?
Enter the values for the working point (center of the working range) into the worksheet.
Procedure
Question
Howcan the system behavior of the flow system be influenced?
Adiferent filling of tank VE1 or in the tanks VE1-VE3 changes the inlet pressure of the pump PL1. A
malfunction due to ball valve VW12 or air in the piping also influences the flow system. With a time
Variant measurement, the flow rate decreases proportionally to the current level.
Preparation
1. Fill the mixing tank VE4 with ~7l water each.
2. Open hand valve VW10 and VW12. Close all other hand valves.
3. Start Fluidlab®-PA closed-loop - select the Measure and control" menu.
4. Select "Flow rate", "A_OUTO pump", and "0UT" as measured variables.
5. Select A_OUT0 pump" as the manipulated variable.
6. Switch on binary output bito (MA1).
7. Set the pump voltage at the working point.
8. Start the execution.
9. Switch the "Manually controlled ON" switch ON.
10. Determine the parameters of the controlled system: system gain Ke, system time constant TP, and dead
time T using the following diag1ams and formulas.
Ayj
Ax
Ks = Ay
Dimensionless value
Parameter Value <
Ks
O Festo
M7-18
Didactic 8131020
2 Closed-loop control technology
Module 7-Analysis, ciosed-ioop control, and control technology with the Mixing Station
Ax
63%
2 4
Calculations
t2-t1 = 0.3 s
System time constant Ts =
3.9/min / 5.7V= 0.68 1/min / V
System gain Ks = Ax /Ay =
0.39/ 0.57 = 0.68
Ks dimensionless =
very short dead time
The deceleration during
start-up of the pump results in a
= 0.3 s
Dead time Tt = t1-t0
M7-19
the Mixing Station
controltechnology/with
control, and
2 Closed-loop control technology Module 7-Analysis, closed-loop
the
Information continuous signal for
controllers generate a
As opposed totwo-step controllers, continuous-action control deviation.
manipulated variable, the magnitude of which depends upon
point
parameters.
with different controllers and control
Check the behavior of the controlled system
Malfunction
Close hand valve VV12 further.
Problem
Aflow system should be operated with a PID controller with specified control parameters.
Procedure
1. Fillthe mixing tank VE4 with ~7 lwater each.
2. Open hand valve VV10 and VW12. Close allother hand valves.
3. Start FluidLab-PA closed-loop - select the"Continuous control" menu.
4. Select "Flow" as the
controlled system.
5. Switch on binary output bito
(MA1).
6. Select A_OUTO pump" as the manipulated variable.
7. Select the Plcontroller and set the reference variable of the controller.
8. Set the determined offset of the manipulated value (exercise 1.9).
9. Seta parameter pair for the PID controller and start the execution.
Parameter Value
Kp 1
T 2
T 0.5
Question
How does the system respond ifthe reference variable is changed in small steps aroundthe working
point or the manual valve VV12 is slightly closed?
if there is a malfunction, the Dcomponent of the closed-loop controller reacts the fastest and
increases the manipulated variable.