PVsyst - Simulation report
Grid-Connected System

Project: TEST
Variant: New simulation variant
No 3D scene defined, no shadings
System power: 96.0 kWp

PVsyst TRIALVũng Tàu - Vietnam

PVsyst TRIAL

PVsyst TRIAL
Author

PVsyst TRIAL
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

Project summary
Geographical Site Situation Project settings
Vũng Tàu Latitude 10.35 °N Albedo 0.20
Vietnam Longitude 107.08 °E
Altitude 10 m
Time zone UTC+7

Weather data
Vũng Tàu
Meteonorm 8.2 (1991-2009), Sat=100% - Synthetic

System summary

PVsyst TRIAL
Grid-Connected System No 3D scene defined, no shadings

Orientation #1 Near Shadings User's needs


Fixed plane no Shadings Unlimited load (grid)
Tilt/Azimuth 10.3 / 0 °

System information
PV Array Inverters
Nb. of modules 160 units Nb. of units 0.8 unit
Pnom total 96.0 kWp Pnom total 80.0 kWac
Pnom ratio 1.200

Results summary
Produced Energy 156107 kWh/year Specific production 1626 kWh/kWp/year Perf. Ratio PR 86.06 %

PVsyst TRIAL
Project and results summary

Main results
Loss diagram
Predef. graphs
Table of contents

General parameters, PV Array Characteristics, System losses


2
3
4
5
6
CO₂ Emission Balance 7

PVsyst TRIAL

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 2/7
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

General parameters
Grid-Connected System No 3D scene defined, no shadings

Orientation #1 Models used


Fixed plane Sheds configuration Transposition Perez
Tilt/Azimuth 10.3 / 0 ° No 3D scene defined Diffuse Perez, Meteonorm
Circumsolar separate

Horizon Near Shadings User's needs


Free Horizon no Shadings Unlimited load (grid)

PV Array Characteristics

PVsyst TRIAL
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model JKM-600N-66HL4M-BDV Model SOFAR 110KTLX-G4
(Original PVsyst database) (Original PVsyst database)
Unit Nom. Power 600 Wp Unit Nom. Power 100 kWac
Number of PV modules 160 units Number of inverters 8 * MPPT 10% 0.8 unit
Nominal (STC) 96.0 kWp Total power 80.0 kWac
Modules 8 string x 20 In series Operating voltage 200-850 V
At operating cond. (50°C) Pnom ratio (DC:AC) 1.20
Pmpp 89.0 kWp No power sharing between MPPTs
U mpp 748 V
I mpp 119 A

Total PV power Total inverter power


Nominal (STC) 96 kWp Total power 80 kWac

PVsyst TRIAL
Total
Module area
Cell area

Thermal Loss factor


160
432
404
modules

Array losses
DC wiring losses
Nb. of inverters

Pnom ratio

Serie Diode Loss


1 unit
0.2 unused
1.20

Module temperature according to irradiance Global array res. 35 mΩ Voltage drop 0.7 V
Uc (const) 20.0 W/m²K Loss Fraction 0.5 % at STC Loss Fraction 0.1 % at STC
Uv (wind) 0.0 W/m²K/m/s

Module Quality Loss Module mismatch losses


Loss Fraction -0.8 % Loss Fraction 2.0 % at MPP

IAM loss factor

PVsyst TRIAL
Incidence effect (IAM): Fresnel, AR coating, n(glass)=1.526, n(AR)=1.290

0° 30° 50° 60° 70° 75° 80° 85° 90°


1.000 0.999 0.987 0.963 0.892 0.814 0.679 0.438 0.000

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 3/7
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

Main results
System Production
Produced Energy 156107 kWh/year Specific production 1626 kWh/kWp/year
Perf. Ratio PR 86.06 %

Normalized productions (per installed kWp) Performance Ratio PR

PVsyst TRIAL
Balances and main results

GlobHor DiffHor T_Amb GlobInc GlobEff EArray E_Grid PR


kWh/m² kWh/m² °C kWh/m² kWh/m² kWh kWh ratio
January 148.5 61.26 26.19 161.5 158.2 13592 13375 0.863

PVsyst TRIAL
February 147.3 72.44 26.90 155.7 152.6 13090 12887 0.862
March 178.1 80.91 28.31 182.2 178.7 15226 14989 0.857
April 189.7 76.25 29.13 187.1 183.2 15549 15312 0.852
May 170.6 86.81 28.96 163.3 158.7 13638 13431 0.857
June 158.8 81.25 27.78 150.0 145.6 12584 12390 0.861
July 158.0 81.14 27.65 150.0 145.7 12609 12413 0.862
August 160.6 82.64 27.55 156.7 152.7 13149 12943 0.861
September 148.6 72.39 26.88 149.6 146.1 12549 12349 0.860
October 148.4 75.70 27.07 154.4 150.8 12963 12762 0.861
November 127.1 77.56 26.61 134.9 131.5 11435 11262 0.870
December 132.5 66.05 26.42 144.1 140.7 12183 11994 0.867
Year 1868.3 914.41 27.46 1889.4 1844.6 158568 156107 0.861

PVsyst TRIAL
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 4/7
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

Loss diagram
1868 kWh/m² Global horizontal irradiation
+1.1% Global incident in coll. plane

-2.37% IAM factor on global

1845 kWh/m² * 432 m² coll. Effective irradiation on collectors

efficiency at STC = 22.22% PV conversion

177123 kWh Array nominal energy (at STC effic.)

PVsyst TRIAL
-0.65% PV loss due to irradiance level

-8.22% PV loss due to temperature

+0.75% Module quality loss

-2.00% Module array mismatch loss


-0.45% Ohmic wiring loss
158730 kWh Array virtual energy at MPP
-1.55% Inverter Loss during operation (efficiency)
-0.10% Inverter Loss over nominal inv. power
0.00% Inverter Loss due to max. input current
0.00% Inverter Loss over nominal inv. voltage

PVsyst TRIAL
0.00% Inverter Loss due to power threshold
0.00% Inverter Loss due to voltage threshold
0.00% Night consumption
156107 kWh Available Energy at Inverter Output
156107 kWh Energy injected into grid

PVsyst TRIAL

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 5/7
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

Predef. graphs
Daily Input/Output diagram

PVsyst TRIAL

PVsyst TRIAL System Output Power Distribution

PVsyst TRIAL

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 6/7
Project: TEST
Variant: New simulation variant

PVsyst V8.0.0
VC0, Simulation date:
03/12/24 15:41

PVsyst TRIAL
with V8.0.0

CO₂ Emission Balance


Total: 1647.3 tCO₂
Generated emissions Saved CO₂ Emission vs. Time
Total: 6.51 tCO₂
Source: Detailed calculation from table below
Replaced Emissions
Total: 1906.1 tCO₂
System production: 156.11 MWh/yr
Grid Lifecycle Emissions: 407 gCO₂/kWh
Source: IEA List
Country: Vietnam
Lifetime: 30 years

PVsyst TRIAL
Annual degradation: 1.0 %

System Lifecycle Emissions Details

Item LCE Quantity Subtotal


[kgCO₂]
Modules 1256 kgCO2/kWp 4.80 kWp 6029
Supports 2.71 kgCO2/kg 80.0 kg 217

PVsyst TRIAL
Inverters 269 kgCO2/ 1.00 269

PVsyst TRIAL

PVsyst TRIAL
03/12/24 PVsyst Evaluation mode Page 7/7