i0000810
i0000810
(121.55 mm)
controllers in commercial heating and cooling
4.79"
building management systems. It is available
with multiple thermistor or RTD options.
2.25"
For optimal temperature readings, follow these (57.15 mm)
tips:
• Duct probe should be placed (3) to (4) duct segments
GALVANIZED ENCLOSURE (-GD)
3.88"
down from any bend or obstructions and away from (98.60 mm)
2.41" 1.78"
90° bends. (61.21 mm) (45.18 mm)
moisture.
4.20"
MOUNTING INSTRUCTIONS
(119.83 mm)
Drill a 3/8” hole in the duct and insert the probe through
4.72"
the hole until the foam pad is tight to the duct. Drill pilot
holes for the (2) mounting screws. Use the enclosure
flange as a guide, or use the dimensions listed below to
measure out.
NEMA -4X (-4X)
3.88" 2.19"
(98.60 mm) (55.69 mm)
0.61"
3.88" (15.49 mm)
3.70"
(98.60 mm)
0.98"
(24.89 mm)
2.55"
(64.77 mm)
Page 1
1.54"
(39.12 mm)
3.08"
(78.23 mm)
1.54" 1.59"
(40.39 mm) 1.54"
1.51" (39.12 mm) (39.12 mm)
(38.25 mm)
3.01" 3.08" 3.18" 3.08"
(76.51 mm) (78.23 mm) (80.77 mm) (78.23 mm)
WIRING INSTRUCTIONS
Open the cover of the enclosure. Note: GD enclosures will have the cover shipped loose.
ACI recommends 16 to 26 AWG twisted pair wires or shielded cable for all sensors. Signal wiring must be run
separate from low and high voltage wires (24/120/230VAC). All ACI thermistors and RTD temperature sensors
are both non-polarity and non-position sensitive. All thermistor type units are supplied with (2) flying lead
wires, and all RTD’s are supplied with (2) or (3) flying lead wires – see FIGURE 4 (below). The number of wires
needed depends on the application.
WIRE NUT
Page 2
Note: When using a shielded cable, be sure to connect only (1) end of the shield to ground at the
controller. Connecting both ends of the shield to ground may cause a ground loop. When
removing the shield from the sensor end, make sure to properly trim the shield to prevent any
chance of shorting.
Note: If the controller requires a (2) wire input for a RTD, connect the (2) common wires (same
color) together. If the controller requires (3) wires, use (3) individual wires.
TROUBLESHOOTING
PROBLEM SOLUTION(S)
Sensor reading is incorrect • Verify sensor wiring to controller is not damaged and has continuity.
• Verify sensor or wires are not shorted together.
• Verify controller is setup for correct sensor curve.
• Disconnect wires from sensor terminal block, tighten terminal block
screws down, and take a resistance (ohm) reading with a multimeter.
• Compare the resistance reading to the Temperature Vs Resistance
Curves online: http://www.workaci.com/content/thermistor-curves-0
• Verify proper mounting location to confirm no external factors are
affecting reading.
Sensor reads infinity/very high resistance • Sensor or wires are open.
Sensor reads low resistance • Sensor or wires are shorted together.
Erratic readings • Condensation on PCB board
• Bad wire connections.
WARRANTY
The ACI Duct Series temperature sensors are covered by ACI’s Five (5) Year Limited Warranty, which is located in
the front of ACI’S SENSORS & TRANSMITTERS CATALOG or can be found on ACI’s website: www.workaci.com.
W.E.E.E. DIRECTIVE
At the end of their useful life the packaging and product should be disposed of via a suitable recycling
centre. Do not dispose of with household waste. Do not burn.