0% found this document useful (0 votes)
129 views148 pages

Sunny Remote Control 30M 44M 60H 80H Operating Manual V32

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
129 views148 pages

Sunny Remote Control 30M 44M 60H 80H Operating Manual V32

Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 148

Operating Manual

SUNNY ISLAND 3.0M / 4.4M / 6.0H / 8.0H


SUNNY REMOTE CONTROL

SI30M-44M-60H-80H-BE-en-32 | Version 3.2 ENGLISH


Legal Provisions SMA Solar Technology AG

Legal Provisions
The information contained in this document is the property of SMA Solar Technology AG. Publishing its content, either
partially or in full, requires the written permission of SMA Solar Technology AG. Any internal company copying of the
document for the purposes of evaluating the product or its correct implementation is allowed and does not require
permission.

SMA Warranty
You can download the current warranty conditions from the Internet at www.SMA-Solar.com.

Trademarks
All trademarks are recognized, even if not explicitly identified as such. A lack of identification does not mean that a
product or symbol is not trademarked.
The BLUETOOTH® word mark and logos are registered trademarks owned by Bluetooth SIG, Inc. and any use of these
marks by SMA Solar Technology AG is under license.
Modbus® is a registered trademark of Schneider Electric and is licensed by the Modbus Organization, Inc.
QR Code is a registered trademark of DENSO WAVE INCORPORATED.
Phillips® and Pozidriv® are registered trademarks of Phillips Screw Company.
Torx® is a registered trademark of Acument Global Technologies, Inc.

SMA Solar Technology AG


Sonnenallee 1
34266 Niestetal
Germany
Tel. +49 561 9522-0
Fax +49 561 9522-100
www.SMA.de
E-mail: [email protected]
© 2004 to 2015 SMA Solar Technology AG. All rights reserved.

2 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG Table of Contents

Table of Contents
1 Information on this Document. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.1 Validity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.2 Target Group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 Typographies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
1.5 Nomenclature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2 Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.1 Intended Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.2 Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.3 Information on Handling Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 Control Panel of the Sunny Island Inverter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Type Label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Sunny Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.5 Compatable Communication Product. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
4 Starting and Stopping the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.1 Switching on the Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.2 Starting the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
4.3 Stopping the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.4 Switching off the Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.5 Tripping the Emergency Disconnection of the System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.6 Setting Time-Controlled Inverter Operation in Off-Grid Systems. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
5 Operation of the Sunny Island Inverter with the Sunny Remote Control . . . . . . . . . . . . . . . . . 21
5.1 Display Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
5.2 Standard Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2.1 Display of Operating States . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22
5.2.2 Information Page in Systems for Increased Self-Consumption and Battery Backup Systems . . . . . . . . . . . . . . .22
5.2.3 Information Page in Off-Grid Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .24
5.3 User Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.1 Displaying Parameters and Operating and Setting the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
5.4 Installer Mode and Expert Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
5.4.1 Switching to Installer Mode or Expert Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
5.4.2 Exiting Installer Mode or Expert Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
5.4.3 Menus in Installer and Expert Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.4.4 Parameter Page in Installer and Expert Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.4.5 Selecting Menus and Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
5.4.6 Setting the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
5.4.7 Directly Accessing the Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .31
6 Operation of the Sunny Island Inverter With a Communication Product . . . . . . . . . . . . . . . . . 32
7 Data Storage and Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
7.1 Data Storage on the Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Operating Manual SI30M-44M-60H-80H-BE-en-32 3


Table of Contents SMA Solar Technology AG

7.2 Data Storage on SD Memory Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33


7.2.1 Inserting the SD Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
7.2.2 Saving and Loading Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .33
7.2.3 Saving the Event History and Error History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.2.4 Displaying the SD Memory Card Status Message . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.2.5 Removing the SD Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.2.6 Displaying the SD Memory Card Content. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34
7.3 Firmware Update . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
7.3.1 Display of the Firmware Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
7.3.2 Updating the Firmware Using an SD Memory Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36
7.3.3 Updating the Firmware Using Sunny Explorer. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
7.3.4 Performing a Remote Update Using the Sunny Home Manager. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
8 Manually Controlling the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
8.1 Starting the Generator with Sunny Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.2 Stopping the Generator with Sunny Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
8.3 Starting the Generator without Autostart Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
8.4 Stopping the Generator without Autostart Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
9 Disconnecting the Sunny Island from Voltage Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
10 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
10.1 Display of Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
10.1.1 Display of Errors on the Sunny Remote Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
10.1.2 Display of Errors on the Communication Product (example) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
10.2 Sunny Island Inverter Behavior Under Fault Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.3 Acknowledge Errors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
10.4 Logged Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
10.4.1 Sunny Island Category (1xx). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44
10.4.2 Battery Category (2xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
10.4.3 Generator Category (4xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
10.4.4 Utility Grid Category (5xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
10.4.5 Relay Category (6xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
10.4.6 System Category (7xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
10.4.7 External Device and Component Category (8xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
10.4.8 External Events. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47
10.5 Logged Warning Messages and Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
10.5.1 Sunny Island Category (1xx). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48
10.5.2 Battery Category (2xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
10.5.3 Generator or Utility Grid Category (3xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .54
10.5.4 Generator Category (4xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
10.5.5 Utility Grid Category (5xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .62
10.5.6 Relay Category (6xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
10.5.7 System Category (7xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63
10.5.8 External Device and Component Category (8xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
10.5.9 General Category (9xx) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
10.6 Frequently Asked Questions (FAQ) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
10.6.1 Questions Regarding the Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77

4 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG Table of Contents

10.6.2 Questions Regarding the Sunny Remote Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78


10.6.3 Questions Regarding the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .78
10.6.4 Questions Regarding the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .79
10.6.5 Questions Regarding Multicluster Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .80
10.7 Charging the Battery After Automatic Shutdown in Off-Grid Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
10.8 Changing Slave Addresses in a Cluster . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
11 Cleaning and Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.1 Cleaning and Checking the Sunny Island Inverter Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.2 Cleaning the Sunny Remote Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.3 Performing a Manual Equalization Charge in the Off-Grid System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.4 Checking the Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
11.5 Checking the Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.6 Checking and Maintaining the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
11.7 Cleaning the Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
11.8 Replacing the Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
12 Decommissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
12.1 Disassembling the Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
12.2 Packaging the Sunny Island . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
12.3 Disposing of the Sunny Island. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
13 Parameters in Sunny Remote Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
13.1 Directory of the Parameters in User Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
13.1.1 Inverter Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .92
13.1.2 Battery Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .93
13.1.3 Generator Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .94
13.1.4 Grid Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
13.1.5 SI Charger Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
13.1.6 Self Cnsmptn Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
13.1.7 Grid Cnsmptn Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
13.1.8 Grid Feed Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
13.1.9 Loads Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
13.1.10 PV System Category. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .96
13.1.11 System Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
13.1.12 Time Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
13.1.13 Identity Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
13.1.14 Password Category . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
13.2 Directory of the Parameters in Installer Mode and Expert Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
13.2.1 Display Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
13.2.1.1 Inverter (110#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
13.2.1.2 Battery (120#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
13.2.1.3 External (130#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
13.2.1.4 Charge Controller (140#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
13.2.1.5 Compact (150#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
13.2.1.6 SlfCsmp (160#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
13.2.1.7 Multicluster (170#). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
13.2.2 Adjustable Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
13.2.2.1 Inverter (210#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111

Operating Manual SI30M-44M-60H-80H-BE-en-32 5


Table of Contents SMA Solar Technology AG

13.2.2.2 Battery (220#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112


13.2.2.3 External/Backup (230#). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
13.2.2.4 Relay (240#). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
13.2.2.5 System (250#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131
13.2.2.6 SlfCsmpBackup (#260). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
13.2.2.7 Authent (270#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.2.3 Information (300#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .134
13.2.3.1 Inverter (310#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.2.3.2 Battery (320#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
13.2.3.3 External (330#). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
13.2.4 Report (400#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139
13.2.5 Operation (500#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .140
13.2.5.1 Inverter (510#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
13.2.5.2 Battery (520#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
13.2.5.3 Generator (540#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
13.2.5.4 MMC card (550#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
13.2.5.5 Grid (560#) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142

14 Parameters in the Communication Product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143


15 Sunny Remote Control Menu Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
15.1 User Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
15.2 Installer Mode and Expert Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145
16 Contact. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146

6 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 1 Information on this Document

1 Information on this Document


1.1 Validity
This document is valid for the following device types:
• SI3.0M-11 (Sunny Island 3.0M) with firmware version 3.2
• SI4.4M-11 (Sunny Island 4.4M) with firmware version 3.2
• SI6.0H-11 (Sunny Island 6.0H) with firmware version 3.1
• SI8.0H-11 (Sunny Island 8.0H) with firmware version 3.1
• SRC-20 (Sunny Remote Control)

1.2 Target Group


This document is intended for qualified persons and operators. Only qualified persons are allowed to perform the
activities marked in this document with a warning symbol and the caption "Qualified person". Activities that may also be
performed by operators are not marked and may be performed by operators.

Operators
Operators must be given training on the following subjects by qualified persons:
• Training on the dangers involved in handling electrical devices
• Training on operation of the Sunny Island
• Training on the safe handling of batteries
• Training on secure disconnection of the Sunny Island under fault conditions
• Training on how to secure a system against unintentional reactivation
• Training on the maintenance and cleaning of the Sunny Island inverter
• Knowledge of and compliance with this document and all safety information

Qualified Persons
Only qualified persons are allowed to perform the activities marked in this document with a warning symbol and the
caption "Qualified person". Qualified persons must have the following skills:
• Training in how to deal with the dangers and risks associated with installing and using electrical devices and batteries
• Training in the installation and commissioning of electrical devices
• Knowledge of and adherence to the local standards and directives
• Knowledge of and compliance with the documentation of the Sunny Island inverter with all safety information

1.3 Symbols
Symbol Explanation

'$1*(5 Indicates a hazardous situation that, if not avoided, will result in death or serious injury

:$51,1* Indicates a hazardous situation that, if not avoided, can result in death or serious injury

&$87,21 Indicates a hazardous situation that, if not avoided, can result in minor or moderate
injury

/05*$& Indicates a situation that, if not avoided, can result in property damage

Information advising that the following section contains activities that may be
performed only by qualified persons.

Operating Manual SI30M-44M-60H-80H-BE-en-32 7


1 Information on this Document SMA Solar Technology AG

Symbol Explanation
Content that is relevant for SMA Flexible Storage Systems.

Content that is relevant for off-grid systems.

Information that is important for a specific topic or goal, but is not safety-relevant

☐ Indicates a requirement for meeting a specific goal


☑ Desired result
✖ A problem that might occur

1.4 Typographies
Typography Usage Example
bold • Display messages • Connect PE to AC2Gen/Grid.
• Parameters • Select the parameter 235.01 GnAutoEna
• Terminals and set to Off.
• Slots
• Elements to be selected or
entered
> • Connects several elements to be • Select 600# Direct Access > Select
selected Number.

1.5 Nomenclature
Complete designation Designation in this document
Off-grid system, battery backup system, system for increased self-consumption System
Sunny Boy, Sunny Mini Central, Sunny Tripower PV inverters
Sunny Home Manager, Sunny Portal, Sunny Explorer Communication product
Grid failure or deviation from the country-specific thresholds for voltage and Grid failure
frequency
Automatic transfer switch with battery-backup function Automatic transfer switch
Gird-forming generators such as electric generators or utility grids External energy sources
Sunny Explorer, Sunny Portal, Sunny Home Manager Communication product

Menus on the Sunny Remote Control are presented as follows: menu number, hash, and menu name (e.g., 150#
Compact Meters).
Parameters are presented as follows: menu number, period, parameter number, and parameter name (e.g., 150.01
GdRmgTm). The term "parameter" includes parameters with configurable values as well as parameters for displaying
values.

8 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 2 Security

2 Security
2.1 Intended Use
Sunny Island
The Sunny Island is a battery inverter that controls the electrical energy balance in an off-grid system, in a battery backup
system, or in a system for increased self-consumption. In a battery backup system, you can also use the Sunny Island for
increased self-consumption.
The Sunny Island must be used only as stationary equipment.
The Sunny Island is not suitable for supplying life-sustaining medical devices. A power outage must not lead to personal
injury.
The Sunny Island uses batteries for the storage of energy. The battery room must be ventilated in accordance with the
requirements of the battery manufacturer and with the locally applicable standards and directives (see documentation of
the battery manufacturer).
Use this product only in accordance with the information provided in the enclosed documentation and with the locally
applicable standards and directives. Any other application may cause personal injury or property damage.
Alterations to the product, e.g. modifications or conversions, are permitted only with the express written permission of
SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and usually void the
operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such alterations.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future
reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.

Sunny Remote Control


You can configure and control the system from a central location using the Sunny Remote Control display.
Use the product only in accordance with the information provided in the enclosed documentation. Alterations to the
product, e.g. modifications or conversions, are permitted only with the express written permission of
SMA Solar Technology AG. Unauthorized alterations will void guarantee and warranty claims and usually void the
operating license. SMA Solar Technology AG shall not be held liable for any damage caused by such alterations.
Any use of the product other than that described in the Intended Use section does not qualify as appropriate.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future
reference and observe all instructions contained therein.
The type label must remain permanently attached to the product.

2.2 Safety Information


This section contains safety information that must be observed at all times during work on or with the product.
To prevent personal injury and property damage and to ensure long-term operation of the product, read this section
carefully and observe all safety information at all times.

Operating Manual SI30M-44M-60H-80H-BE-en-32 9


2 Security SMA Solar Technology AG

:$51,1*
Danger to life from electric shocks due to live voltage and risk of injury from short-circuit currents
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be touched,
which can result in death or serious injury due to electric shock. Short-circuit currents in the battery can cause heat
build-up and electric arcs. Burns or eye injuries due to flashes may result.
• When carrying out any work on the electrical installation, wear suitable personal protective equipment.
• Switch off or disconnect the following components in the following order:
– Sunny Island
– The control and measurement voltages in the distribution board of the Sunny Island circuit breakers
– Load-break switch of the battery
• Ensure that the system cannot be reconnected.
• Open the enclosure lid of the Sunny Island and ensure that no voltage is present.
• Ground and short-circuit the AC conductors outside the Sunny Island inverter.
• Cover or isolate any adjacent live components.
Danger to life from electric shock due to damaged Sunny Island
Operating a damaged Sunny Island can lead to hazardous situations that can result in death or serious injuries due to
electric shock.
• Operate the Sunny Island only when it is technically faultless and in an operationally safe state.
• Regularly check the Sunny Island for visible damage.
• Make sure that all external safety equipment is freely accessible at all times.
• Make sure that all safety equipment is in good working order.
Risk of crushing injuries due to movable generator parts
Moving parts in the generator can crush or sever body parts. A generator can be started automatically by the
Sunny Island.
• Operate the generator only with the safety equipment.
• Install, maintain, and operate the generator according to the manufacturer's specifications.

&$87,21
Risk of burns due to short-circuit currents on the disconnected Sunny Island
The capacitors at the DC connection input area store energy. After the battery is isolated from the Sunny Island, battery
voltage is still temporarily present at the DC terminal. A short circuit on the DC connection can lead to burns and may
damage the Sunny Island.
• Wait 15 minutes before performing any work at the DC connection or on the DC cables. This allows the capacitors
to discharge.
Risk of burns due to hot components
Some components of the Sunny Island can get very hot during operation. Touching these components can cause burns.
Heat build-up can cause burns.
• During operation, do not touch any parts other than the enclosure lid of the Sunny Island.
• When the Sunny Island is open, do not touch any hot surfaces.

10 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 2 Security

/05*$&
Destruction of the Sunny Island inverter due to electrostatic discharge (ESD)
By touching electronic components within the Sunny Island, you can damage or destroy the Sunny Island.
• Do not touch any electronic assemblies.
• Ground yourself before touching any connections.

2.3 Information on Handling Batteries


:$51,1*
Danger to life due to explosive gases
Explosive gases may escape from the battery and cause an explosion. This can result in death or serious injury.
• Protect the battery environment from open flames, embers, or sparks.
• Install, operate, and maintain the battery in accordance with the manufacturer's specifications.
• Do not heat the battery above the temperature permitted or burn the battery.
• Ensure that the battery room is sufficiently ventilated.
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.

&$87,21
Risk of burns due to hot battery components
Improper battery connection may result in excessively high transition resistances. Excessive transition resistances give
rise to localized heat build-up.
• Ensure that all pole connectors are connected with the connecting torque specified by the battery manufacturer.
• Ensure that all DC cables are connected with the connecting torque specified by the battery manufacturer.

Operating Manual SI30M-44M-60H-80H-BE-en-32 11


2 Security SMA Solar Technology AG

/05*$&
Damage to the battery due to incorrect settings
The set battery parameters influence the charging behavior of the Sunny Island inverter. The battery can be damaged
by incorrect settings for the battery type, nominal voltage and capacity parameters.
• Ensure that the values recommended by the battery manufacturer are set (refer to the technical data for the battery
in the manufacturer documentation). Note that the battery charging behavior names used by
SMA Solar Technology AG and the battery manufacturer may, in some cases, differ in meaning (for the battery
charging behavior of the Sunny Island inverter, see "Battery Management" technical information).
• Set the battery capacity for a ten-hour electric discharge (C10). The battery manufacturer specifies the battery
capacity in relation to discharge time.
Permanent damage to the battery due to improper handling
Improper set-up and maintenance of the battery can cause it to become permanently damaged. Logs can help to
determine the cause.
• Comply with all requirements of the battery manufacturer with regard to mounting location.
• Check and log the status of the battery before performing maintenance work:
• Check the battery for visible damage and log.
• Measure and log the fill level and acid density of FLA batteries.
• In the case of lead-acid batteries, measure and log the voltages of the individual cells.
• Perform and log the test routines required by the battery manufacturer.
Tip: Many battery manufacturers provide suitable logs.

Prior damage to batteries


Batteries may have suffered prior damage due to production defects. Logs can help to determine the cause.
• Check and log the status of the battery before performing maintenance work.
Performance impairment of batteries
Transition resistances can impair the performance of the batteries.
• Ensure that the torques at the battery connections are correct each time that maintenance is performed.

12 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 3 Product Description

3 Product Description
3.1 Sunny Island
The Sunny Island is a battery inverter and controls the electrical energy balance in off-grid systems, in battery backup
systems, or in systems for increased self-consumption. In a battery backup system, you can also use the Sunny Island for
increased self-consumption.

Figure 1: Design of the Sunny Island inverter

Position Designation
A Ventilation grid
B Type label
C Control panel
D Enclosure lid

The Sunny Island supplies AC loads in the system from a battery or charges the battery with the energy provided by AC
sources (e.g., PV inverter). AC sources supply loads and are used by the Sunny Island to recharge the battery.

3.2 Control Panel of the Sunny Island Inverter

Figure 2: Layout of the control panel

Position Symbol Designation Status Explanation


A Start-stop button ‒ By pressing the start-stop button, you can start or stop
TSS the system. In display messages on the
Sunny Remote Control, the start-stop button is
referred to as TSS.

Operating Manual SI30M-44M-60H-80H-BE-en-32 13


3 Product Description SMA Solar Technology AG

Position Symbol Designation Status Explanation


B "On" button ‒ Pressing the "On" button will switch the Sunny Island
on. The Sunny Island is in standby mode after being
switched on.
C "Off" button ‒ Pressing the "Off" button will switch the Sunny Island
off.

D Inverter LED not glowing The Sunny Island is switched off.


glowing green The Sunny Island is in operation.
glowing orange The Sunny Island is in standby mode.
glowing red The Sunny Island switched off due to an error.
flashing quickly* The Sunny Island is not configured.
flashing The Sunny Island is in overnight shutdown.
slowly**
E Grid LED not glowing There is no voltage present from the generator or the
utility grid.
glowing green Generator or utility grid is connected.
glowing orange The Sunny Island is synchronizing the stand-alone
grid with the generator or the utility grid.
glowing red Error at the connection of the generator or the utility
grid.
F Battery LED glowing green The battery state of charge is greater than 50%.
glowing orange The battery state of charge is between 50% and
20%.
glowing red The battery state of charge is less than 20%.
G Standby ‒ Position of the buttons for switching on and off
H AC operation ‒ Position of the button for starting and stopping
operation
* Flashing at intervals of 0.5 s to 1 s
** Flashing at intervals of 1.5 s to 2 s

3.3 Type Label


The type label clearly identifies the product. The type label is located on the right-hand side of the enclosure. You will find
the following information on the type label:
• Address of SMA Solar Technology AG
• Device type (Model)
• Serial number (Serial No.)
• Device-specific characteristics
You will require the information on the type label to use the product safely and when seeking customer support from the
SMA Service Line.

14 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 3 Product Description

Symbols on the Type Label


Symbol Explanation
Danger to life due to high voltages
The product operates at high voltages. All work on the product must be carried out by qualified
persons only.
Risk of burns due to hot surfaces
The product can get hot during operation. Avoid contact during operation. Allow the product to cool
down sufficiently before carrying out any work. Wear personal protective equipment such as safety
gloves.
Observe the documentation
Observe all documentation supplied with the product.

AC
Alternating current
DC
Direct current
Transformer
The product has a transformer.
WEEE designation
Do not dispose of the product together with the household waste but in accordance with the locally
applicable disposal regulations for electronic waste.
CE marking
The product complies with the requirements of the applicable EU directives.
Protection class I
All electrical equipment is connected to the grounding conductor system of the product.
Degree of protection
The product is protected against interior dust deposits and splashing water from all angles.

DVE Certified safety


The product is VDE-tested and complies with the requirements of the German Equipment and Product
Safety Act.
RCM tick
The product complies with the requirements of the applicable Australian EMC standards.

Operating Manual SI30M-44M-60H-80H-BE-en-32 15


3 Product Description SMA Solar Technology AG

3.4 Sunny Remote Control


You can configure and control the system from a central location using the Sunny Remote Control display.

Figure 3: Layout of the Sunny Remote Control

Position Designation Explanation


A Display Four-line display shows operating data (e.g., operating state, display values) and
events, warnings, or errors on the Sunny Island inverter.
The display backlight is automatically deactivated after a short period of inactivity.
B Switch Pressing the button will turn on the backlight, confirm parameters, or switch the level
within a menu. The return symbol " " in the display indicates when you can perform
an action by pressing the button.
Turning the button will switch on the backlight, change parameters, or navigate within a
menu level.
C SD memory card ‒
slot

Service interface, SD memory card


The Sunny Remote Control has a slot for SD memory cards. The SD memory card stores data for system control and
facilitates service work. The SD memory card also allows you to update the firmware on the Sunny Island inverter. The
following data is stored on the SD memory card:
• Parameter settings
• Every minute, measurement data from the areas:
– Battery
– Sunny Island
– Generator
– Utility grid
– Stand-alone grid
• Events and errors
• Statistical values of the battery
The SD memory card must be formatted as FAT-16 or FAT-32.

16 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 3 Product Description

3.5 Compatable Communication Product


Sunny Home Manager and Sunny Portal
The Sunny Home Manager is a device for PV system monitoring and for controlling loads in households with PV systems.
The Sunny Home Manager and the Sunny Island inverter communicate via Speedwire and are a substantial part of the
SMA Flexible Storage System (see Quick Reference Guide of the Sunny Island inverter).
Sunny Portal is an Internet portal for visualization of the data of the PV system, of SMA radio-controlled sockets and of
other components of the SMA Flexible Storage System. In addition, Sunny Portal serves as a user interface for configuring
the Sunny Home Manager and SMA radio-controlled sockets (see User Manual of the SUNNY HOME MANAGER in
SUNNY PORTAL).

Sunny Explorer
With the Sunny Explorer software, you can visualize and manage the data of your Sunny Island system. You can also
use it to configure single devices or entire device classes in your system.
To enable this, the Sunny Explorer software must be installed on a computer that is connected to the Sunny Island via
Speedwire (see User Manual of Sunny Explorer).

Operating Manual SI30M-44M-60H-80H-BE-en-32 17


4 Starting and Stopping the System SMA Solar Technology AG

4 Starting and Stopping the System


4.1 Switching on the Sunny Island
Requirements:
☐ The load-break switch in the DC cable must be closed.
☐ The Sunny Island must not have switched itself off (see Section 10.7 "Charging the Battery After Automatic Shutdown
in Off-Grid Systems", page 81).
Procedure:
• For systems with one Sunny Island, press the "On" button on the
Sunny Island.
• For systems with up to three Sunny Island inverters, press and hold
the "On" button on the master until an acoustic signal sounds.
• For multicluster systems, press and hold the "On" button on each
master until an acoustic signal sounds.

☑ The inverter LED on each Sunny Island inverter is glowing orange and the Sunny Island inverters are in standby
mode.

4.2 Starting the System


Requirement:
☐ All Sunny Island inverters must be switched on.
Procedure:
• Press the start-stop button on the Sunny Island and hold it until an
acoustic signal sounds.

or

Press and hold the button on the Sunny Remote Control until an acoustic signal sounds.
☑ The inverter LED on each Sunny Island is glowing green.

18 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 4 Starting and Stopping the System

4.3 Stopping the System


If you stop the system, the Sunny Island switches from operation into standby mode. In standby mode, the Sunny Island
discharges the battery due to its standby consumption. Tip: For longer shut-down periods, switch off the Sunny Island
(see Section 4.4, page 19).
Procedure:
• Press and hold the start-stop button on the Sunny Island until the
inverter LED is glowing orange.

or

Press and hold the button on the Sunny Remote Control until the progress bar has run down.
☑ The inverter LED on each Sunny Island is glowing orange. The Sunny Island inverters are in standby mode.

4.4 Switching off the Sunny Island


Requirement:
☐ The system is stopped.
Procedure:
• Press and hold the "Off" button on the Sunny Island until an
acoustic signal sounds.

☑ The inverter LED is off on all Sunny Island inverters.

4.5 Tripping the Emergency Disconnection of the System


Effects of an emergency disconnection
Emergency disconnection triggers the uncontrolled shutdown of the system and unsaved data is lost.
• Use emergency disconnection only to avoid danger or consequential damage.

Operating Manual SI30M-44M-60H-80H-BE-en-32 19


4 Starting and Stopping the System SMA Solar Technology AG

Procedure:
• Press and hold the "Off" button on the Sunny Island until an
acoustic signal sounds.

☑ The inverter LED is off on all Sunny Island inverters.

4.6 Setting Time-Controlled Inverter Operation in Off-Grid Systems


Example: Parameter settings for time-controlled inverter operation
You want to operate the Sunny Island in inverter operation every Sunday from 10:00 a.m. to 6:00 p.m., starting on
Sunday, January 8, 2012. To do this, set the Sunny Island as follows:
• Str.Date: 08.01.2012
• Start Time: 10:00:00
• Run Time: 08:00:00
• Repetition: Weekly

Procedure:
1. Log in to the communication product as User (see User Manual of the Communication Product) or switch to user
mode on the Sunny Remote Control (see Section 5.3, page 26).
2. To set the time-controlled inverter operation on the Sunny Remote Control, select
the Inverter display page on the Sunny Remote Control and press the button.

☑ The Sunny Remote Control switches to the Inverter setting page.

3. Set the time-controlled inverter operation:


• Select the Start date for time-controlled inverter operation / Str.Date parameter and set it to the desired
start date.
• Select the Start date for time-controlled inverter operation / Str.Date parameter and set it to the desired
start time.
• Select the Start date for time-controlled inverter operation / Str.Date parameter and set it to the desired
running time.
• Select the Repetition cycle for time-controlled inverter operation / Repetition parameter and set it to the
desired repetition cycle.
4. To activate time-controlled inverter operation, select the Time controlled inverter operation / Timed Start
parameter and set it to Enable.
☑ Time-controlled inverter operation is activated. If the Sunny Island has started automatically under time-control and
you stop the Sunny Island, time-controlled inverter operation is deactivated automatically.

20 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

5 Operation of the Sunny Island Inverter with the Sunny Remote Control
5.1 Display Modes
The Sunny Remote Control uses four display modes for the display. The Sunny Remote Control will switch to standard
mode if the button has not been used for over five minutes.
Mode Page contents
Standard mode • Message regarding operating states
<home> • Display of energy flows
• Display of key parameters
In display messages on the Sunny Remote Control, <home> refers to the standard mode.
User mode • Display of and access to key operating parameters
User In display messages on the Sunny Remote Control, User refers to the user mode.
Installer mode • Display of and access to configuration and operation parameters
Installer The installer mode is protected with an installer password. In display messages on the
Sunny Remote Control, Installer refers to the installer mode.
Expert mode • Display of and access to all parameters for the system configuration set in QCG
Expert The expert mode can be accessed only via installer mode (see Section 5.4.1, page 29). In display
messages on the Sunny Remote Control, Expert refers to the expert mode.

The parameters for devices that are not configured are hidden, e.g., the generator parameters are hidden for systems
without a generator. The parameters for multicluster systems are available only in expert mode.

Operating Manual SI30M-44M-60H-80H-BE-en-32 21


5 Operation of the Sunny Island Inverter with the Sunny Remote Control SMA Solar Technology AG

5.2 Standard Mode


5.2.1 Display of Operating States
The Sunny Remote Control displays the following operating states until the Sunny Island is started.

Figure 4: Display of operating states (example: Standby)

Position Designation Explanation


A Boot The Sunny Island is initializing.
Error The Sunny Island is in error status.
LBM 1 The Sunny Island is in battery preservation mode level 1.
LBM 2 The Sunny Island is in battery preservation mode level 2.
LBM 3 The Sunny Island is in battery preservation mode level 3.
Restart The Sunny Island is performing a restart.
Shutdown The Sunny Island is stopped.
Silent The Sunny Island is in energy-saving mode.
Standby The Sunny Island is in standby mode or in time-controlled inverter operation.
Startup The Sunny Island is starting up.

5.2.2 Information Page in Systems for Increased Self-Consumption and Battery


Backup Systems
When the Sunny Island is started, the Sunny Remote Control provides information on the status of the system for increased
self-consumption.

Figure 5: Energy flows and status messages of the Sunny Island

Position Symbol Designation Explanation


A Warning symbol Symbol for warnings and errors that do not affect the Sunny Island
operation.(see Section 10.1 "Display of Errors", page 42)
B Device assignment The Sunny Island connected to the Sunny Remote Control is the
master.
The Sunny Island connected to the Sunny Remote Control is slave 1.

The Sunny Island connected to the Sunny Remote Control is slave 2.

22 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

Position Symbol Designation Explanation


C SD memory card SD memory card is inserted.
Symbol The Sunny Island is accessing the SD memory card.
flashing
No SD memory card not inserted.
symbol
D Multifunction relay 1 Multifunction relay 1 is deactivated.

Multifunction relay 1 is activated.

E Multifunction relay 2 Multifunction relay 2 is deactivated.

Multifunction relay 2 is activated.

F Battery power and The battery is being charged.


battery state of
charge The battery is being discharged.

Battery power in kW, battery state of charge (SOC) as %


G hh:mm:ss Time System time
H Power and status of Power in kW
the utility grid
The utility grid voltage and frequency are within the configured limits.

The maximum reverse power in the utility grid has been exceeded.

Operating Manual SI30M-44M-60H-80H-BE-en-32 23


5 Operation of the Sunny Island Inverter with the Sunny Remote Control SMA Solar Technology AG

5.2.3 Information Page in Off-Grid Systems

Figure 6: Energy flows and status of the Sunny Island inverter (example)

Position Designation
A Graphical representation of the energy flows
B Symbol for loads in the stand-alone grid and output power of the Sunny Island inverter in kW
C Status of the Sunny Island inverter
D Battery state of charge
E Status of the generator

Graphical representation of the energy flows

Figure 7: Energy flow diagram in standard mode (example)

Position Symbol Designation Explanation


A Battery Battery symbol
B Direction of energy flow The battery is supplying the loads.
The battery is being charged.
C Generator Generator symbol
D Internal transfer relay The generator is disconnected from the stand-alone grid.

The stand-alone grid is synchronized with the generator. The


generator is supplying the loads and charging the battery.
E Direction of energy flow Loads are being supplied.

AC sources in the stand-alone grid are supplying more energy than


is being consumed by the stand-alone grid.
F Loads in the stand-alone Symbol for loads in the stand-alone grid
grid

24 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

Status of the Sunny Island inverter

Figure 8: Status of the Sunny Island inverter (example)

Position Symbol Designation Explanation


A Warning symbol Symbol for warnings and errors that do not affect the Sunny Island
operation.
If this symbol is flashing, acknowledge the error or warning (see
Section 10.3, page 43).
B Device assignment The Sunny Island connected to the Sunny Remote Control is the
master.
The Sunny Island connected to the Sunny Remote Control is
slave 1.
The Sunny Island connected to the Sunny Remote Control is
slave 2.
C SD memory card SD memory card is inserted.
Symbol The Sunny Island is accessing the SD memory card.
flashing
No SD memory card not inserted.
symbol
D Multifunction relay 1 Multifunction relay 1 is deactivated.

Multifunction relay 1 is activated.

E Multifunction relay 2 Multifunction relay 2 is deactivated.

Multifunction relay 2 is activated.

F hh:mm:ss Time Off-grid system time

Battery state of charge

Figure 9: Battery state of charge in standard mode (Example)

Position Explanation
A Battery symbol
B Battery state of charge as %.

Operating Manual SI30M-44M-60H-80H-BE-en-32 25


5 Operation of the Sunny Island Inverter with the Sunny Remote Control SMA Solar Technology AG

Status of the external energy source

Figure 10: Status of the external energy source in standard mode (example)

Position Symbol Designation Explanation


A Status of the generator Voltage and frequency of the generator are within the thresholds
set.
The maximum reverse power in the generator has been exceeded.

Battery
Electricity generator was requested due to state of charge.
Cycle
Generator was requested via time control.
External
Generator was requested by an extension cluster.
Load
Electricity generator was requested due to load.
Start
You have manually started the generator via
Sunny Remote Control or a generator was requested via the DigIn
input.
Time
You have started the generator for one hour via
Sunny Remote Control.
B ‒ Power of the generator or Power in kW
the utility grid
C Generator Generator symbol
D Internal transfer relay The generator is disconnected from the stand-alone grid.
The stand-alone grid is synchronized with the generator. The
generator is supplying the loads and charging the battery.

5.3 User Mode


5.3.1 Displaying Parameters and Operating and Setting the System
User mode displays all important information for the system sorted by category. User mode enables manual control of
the Sunny Island inverter or system devices, e.g., generator start.
User mode distinguishes between display pages and setting pages. Display pages show the parameters of a category.
Setting pages enable the operation and setting of the system.

26 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

Figure 11: Layout of a page in user mode (example)

Position Designation Symbol or Explanation


message
A Page type Information
This symbol indicates display pages.
Set
This symbol indicates setting pages.
B Category − Category name (see Section 13.1 "Directory of the Parameters in
User Mode", page 92)
C Page and number ‒ Page and number of pages of the selected category
of pages
D Return symbol On display pages, this symbol means that setting pages are
available for this category.
On setting pages, this symbol points to the selected parameter.
No symbol No setting pages are available for this category.
E Parameters ‒ Parameters with the current values

Procedure:
1. Press the button to activate the display illumination of the Sunny Remote Control.
2. Turn the button to the right.
☑ The Sunny Remote Control switches from standard mode to
user mode.

3. To scroll through the display pages, continue to turn the button to the right.
4. To go back to a previous page, turn the button to the left.
5. To select a setting page, scroll to the display page for the category of the desired setting (see Section 13.1 "Directory
of the Parameters in User Mode", page 92).
Example: Selecting the display page.
You want to restart the Sunny Island. This setting is in the Inverter category.
• Select display page Inverter (1/1).

6. Press the button. The Sunny Remote Control displays the setting pages belonging to the display page.

Operating Manual SI30M-44M-60H-80H-BE-en-32 27


5 Operation of the Sunny Island Inverter with the Sunny Remote Control SMA Solar Technology AG

Example: Selecting the setting page


You have selected the display page Inverter (1/1).
• Press the button.

☑ The setting page Inverter (1/2) appears.

7. To select the desired parameter, turn the button to the right until the return symbol appears to the right of the desired
parameter.
☑ You have selected the parameter.
8. To set the parameter, press the button and then turn it to the left or right.
9. Once you have set the required parameter, press the button. This saves the setting.
Example: The Sunny Island is to start in time-controlled inverter operation weekly.
For this, the repetition type (Repetition) must be set to "Weekly".
• Access the setting page Inverter (1/2).
☑ The setting page Inverter (1/2) appears.

• Turn the button until the return symbol appears next to the parameter Repetition.
The Sunny Remote Control switches from setting page Inverter (1/2) to setting page Inverter (2/2).
• Press the button.
• Turn the button to the right until Weekly appears.
• Press the button. This saves the parameter.
☑ You have set the repetition type to Weekly in
time-controlled inverter operation.

10. To exit the setting page, switch to the display page or the standard mode:
• Turn the button to the left until the return symbol appears in the first line.
• To return to the display page, turn the button to the left until <back> appears.
• To switch to standard mode, turn the button to the left until <home> appears.
• Press the button.
Tip: <back> and <home> also appear at the end of the list if the button is turned to the right.

28 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

5.4 Installer Mode and Expert Mode


5.4.1 Switching to Installer Mode or Expert Mode
The installer mode is protected with an installer password. The installer password changes constantly and must be
recalculated every time. Expert mode can be accessed only via installer mode.

/05*$&
System failures due to entry of incorrect parameter values
The system can become unstable and fail due to entry of incorrect parameter values. All parameters that could affect
the operational safety of the system are protected by the installer password.
• Only a qualified person is permitted to set and adjust system parameters.
• Give the installer password only to qualified persons and operators.

Procedure:
1. On the Sunny Remote Control, select the setting page Password (1/1) in user mode.
2. Calculate the checksum of the operating hours Runtime. This determines the installer password.
Example: Calculating the checksum
The operating hours Runtime are 1234 h. The checksum is the sum of all digits:
1 + 2 + 3 + 4 = 10
The checksum is 10.

3. Select the parameter Set and set the installer password calculated.
☑ The Sunny Remote Control is in installer mode.

4. To switch to expert mode, select the parameter 700.01 ActLev and set to Expert (see Section 5.4.6 "Setting the
Parameters", page 31).

5.4.2 Exiting Installer Mode or Expert Mode


If you do not press or turn the button on the Sunny Remote Control for five minutes, the Sunny Remote Control will switch
from installer or expert mode to standard mode automatically.
• Select the parameter 700.01 ActLev on the Sunny Remote Control and set to User (see Section 5.4.6 "Setting the
Parameters", page 31).

Operating Manual SI30M-44M-60H-80H-BE-en-32 29


5 Operation of the Sunny Island Inverter with the Sunny Remote Control SMA Solar Technology AG

5.4.3 Menus in Installer and Expert Mode

Figure 12: Layout of the menu page in installer mode (example)

Position Designation Explanation


A Menu path The two previously selected menu levels
If you are in the top menu level, the display will show Installer in installer mode
and Expert in expert mode.
B Return symbol Return symbol for selecting a menu
C Menu ‒

5.4.4 Parameter Page in Installer and Expert Mode

Figure 13: Layout of the parameter page in installer mode (example)

Position Designation Explanation


A Menu number and parameter number ‒
B Menu path The two previously selected menu levels
C Return symbol Return symbol for setting the parameter
If no return symbol is displayed, the parameter cannot be set.
D Name of the parameter ‒
E Value and unit of the parameter ‒

5.4.5 Selecting Menus and Parameters


1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Turn the button to the right until the return symbol appears to the right of the desired menu. The Sunny Remote Control
scrolls through the menu items on the display line by line.
3. Press the button. This accesses the sub-menu level.
☑ The Sunny Remote Control displays the sub-menu level. The selected menu level is shown in the first line.
4. Repeat steps 2 and 3 until the Sunny Remote Control displays the first parameter page.
5. Turn the button to the right until the Sunny Remote Control displays the desired parameter.
6. Set the parameter (see Section 5.4.6, page 31).
7. To exit the parameter page, switch to the higher level or switch to standard mode:
• Turn the button to the left until the return symbol appears in the first line.
• To switch to a higher menu level, turn the button to the left until <back> appears.
• To switch to standard mode, turn the button to the left until <home> appears.
• Press the button.
Tip: <back> and <home> also appear at the end of the list if the button is turned to the right.

30 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 5 Operation of the Sunny Island Inverter with the Sunny Remote Control

5.4.6 Setting the Parameters


1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the desired parameter. You can set only the parameters for
which < Set > is shown in the second line in the display.
3. Press the button.
☑ The return symbol is flashing next to the value.
✖ Stop device to change the value? appears in the display.
The parameter can be changed only in standby mode.
• Stop the system (see Section 4.3, page 19).
✖ No permission to change the value appears in the display.
You are not allowed to change the parameter in installer mode.
• If you want to change the parameters for the battery, select the menu New Battery in the QCG
(see Section 11.8 "Replacing the Battery", page 87).
• For all other settings, select the menu New System in the QCG (see the Sunny Island inverter installation
manual).
4. To set the parameter, turn the button to the left or right.
5. Press the button.
☑ The Sunny Remote Control requests confirmation of the set
parameter.

6. To confirm the value, turn the button to the right until Y is flashing and then press the button.
7. To discard the value, turn the button to the right until N is flashing and then press the button.

5.4.7 Directly Accessing the Parameters


Any parameter can be accessed directly by entering a five-digit number. The five-digit number is composed as follows:
• The first three digits are the menu number.
• The last two digits are the parameter number.
Example: Five-digit number for direct parameter access.
The parameter 111.01 TotInvPwrAt allows you to display the complete active power of the Sunny Island inverters in
a cluster. The five-digit number for direct access is 11101.

Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the parameter 600.02 Select Number and set the five-digit number.
☑ The parameter is displayed.
✖ The display shows Item not Found?
You cannot access the parameter in installer mode.
• Press the button and switch to expert mode (see Section 5.4.1, page 29).
The number set is incorrect.
• Press the button and enter the number again.

Operating Manual SI30M-44M-60H-80H-BE-en-32 31


6 Operation of the Sunny Island Inverter With a Communication Product SMA Solar Technology AG

6 Operation of the Sunny Island Inverter With a Communication Product


When operating a Sunny Island inverter with a communication product, observe the following differences compared with
operation via Sunny Remote Control:
• When the parameters and messages of the Sunny Island inverter are accessed via the communication product, the
defined access rights of the communication product apply (see user manual of the communication product).
• The inverter messages are displayed on the screen of the communication product as clear-text names (see technical
information "SUNNY ISLAND – Message of the same event for Speedwire (e. g. Sunny Explorer) and RS485 /
Sunny Remote Control").
Example:
The Sunny Remote Control displays the following message when the Sunny Island inverter is warning of high
operating temperatures: W212 BatTmpHiWarn.
The same warning message appears as clear text on the screen of the communication product:
Overtemperature fault in battery.

• The inverter parameters are displayed on the screen of the communication product as clear-text names (see technical
information "SUNNY ISLAND – Comparison of the same parameters for Speedwire (e. g. Sunny Explorer) and
RS485 / Sunny Remote Control").
Example:
The information regarding the reason for the generator request sent by the Sunny Island is displayed on the screen
of the Sunny Remote Control as parameter number and parameter name: 133.01 GnDmdSrc.
The same information appears as clear text on the screen of the communication product: Reason for requesting
generator.

• A three-phase cluster is shown as a three-phase inverter on the screen of the communication product.
Function of the Sunny Island inverter in a Display on the communication product (example)
three-phase cluster
Master Phase 1
Slave 1 Phase 2
Slave 2 Phase 3

• The parameters at the Sunny Remote Control can be adjusted only one at a time. The communication product allows
associated parameters to be grouped. To edit the parameters, this group must be selected on the communication
product.
Example:
The battery states of charge for the battery protection mode are set via three parameters on the
Sunny Remote Control:
• 223.05 BatPro1Soc: State of charge for battery-preservation mode, level 1
• 223.05 BatPro1Soc: State of charge for battery-preservation mode, level 2
• 223.05 BatPro1Soc: State of charge for battery-preservation mode, level 3
On the communication product, all three battery states of charge can be set via the parameter Battery state of
charge for preservation mode.

32 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 7 Data Storage and Firmware Update

7 Data Storage and Firmware Update


7.1 Data Storage on the Computer
With Sunny Explorer, you can save system yields and events as CSV files on your computer (see user manual of
Sunny Explorer). The CSV files can be opened in Microsoft Excel and the data can be used e.g. to create diagrams.

7.2 Data Storage on SD Memory Card


7.2.1 Inserting the SD Memory Card
Requirements:
☐ The SD memory card must be formatted as FAT-16 or FAT-32.
☐ The SD memory card must be used exclusively as a data medium for the system.
Procedure:
• Insert the SD memory card, with the slanted corner facing
upwards, into the SD memory card slot in the
Sunny Remote Control.

7.2.2 Saving and Loading Parameters


You can load and save the current parameter settings in two different parameter sets on the SD memory card. The Sunny
Remote Control calls the two parameter sets Set1 and Set2. Each parameter set saves all settings. This makes it possible
to test the settings of a new parameter set without having to delete the old parameter set. Tip: As soon as you have
adjusted the system to your requirements, save the parameter settings to the SD memory card. After saving, you can make
further adjustments to the system. If the adjustment does not lead to the desired results, reload the saved parameter set.
Requirement:
☐ The SD memory card must be inserted.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. To save a parameter set, select the parameter 550.01 ParaSto and set the parameter:
Value Explanation
Set1 Save the settings in the first parameter set.
Set2 Save the settings in the second parameter set.

3. Proceed as follows to load a parameter set:


• Switch to expert mode on the Sunny Remote Control (see Section 5.4.1, page 29).
• Select the parameter 550.02 ParaLod and set the parameter:
Value Explanation
Set1 Loads the settings from the first parameter set.
Set2 Loads the settings from the second parameter set.
Factory Starts the quick configuration guide.

Operating Manual SI30M-44M-60H-80H-BE-en-32 33


7 Data Storage and Firmware Update SMA Solar Technology AG

7.2.3 Saving the Event History and Error History


Requirement:
☐ The SD memory card must be inserted.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. To save the event history, select the parameter 550.03 CardFunc and set to StoEvtHis.
3. To save the error history, select the parameter 550.03 CardFunc and set to StoFailHis.
4. To save the error history and the event history, select the parameter 550.03 CardFunc and set to StoHis.

7.2.4 Displaying the SD Memory Card Status Message


The Sunny Remote Control determines the SD memory card status (see Section 13.2.3.1 "Inverter (310#)", page 134).
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the parameter 312.11 CardStt and read off the value.

7.2.5 Removing the SD Memory Card


If the SD memory card is removed without preparation, the removal will cause data loss. Data loss affects the log data
of the last 15 minutes at most.
Procedure:
1. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
2. Select the parameter 550.03 CardFunc and set to ForcedWrite. Unsaved data will now be saved to the SD
memory card.
3. Remove the SD memory card.

7.2.6 Displaying the SD Memory Card Content

Figure 14: Content of an SD memory card (example)


The files saved to the SD memory card depend on the configuration and on the system.
Explanation of the folders:
Folder name Explanation
BATSTAT Folder containing battery statistics for each month
The files are stored by year and month in sub-folders.
HISTORY Folder containing event and error histories
LOGGING Folder containing the data logging, event and error histories for each day
The files are stored by year and month in sub-folders.
SIPAR Folder containing the parameter lists

34 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 7 Data Storage and Firmware Update

Explanation of the files within the folders:


File name Explanation
evthis.log Event history
errhis.log Error history
si010112.evt Event and error histories for one day
The date (ddmmyy) is part of the file name.
si010112.log Data logging for the day
The date (ddmmyy) is part of the file name.
sipar.lst Current parameter set
sipar1.lst Parameter set 1
sipar2.lst Parameter set 2
update.bin Sunny Island inverter firmware
batstat.txt Statistical values of the battery
These values are saved every night at 10:00 p.m.
batstat.sma Statistical values of the battery for evaluation by SMA Solar Technology AG
sim.ccf System information of the Sunny Island inverter
bootex.log File generated by the operating system of the computer
This file is not generated by every operating system.

Structure of the files:


The files are CSV files, which means that the data is saved as ASCII text. The files are structured as follows:
• The first lines in the file are used for information. Information lines start and end with the character #.
• The data in the following lines is separated by semicolons.
• Decimal places are separated by periods.
• The date format is dd.mm.yyyy.
• The time format is hh:mm:ss.
• Some of the parameter values are saved with plain text numbers (see Section 13.2 "Directory of the Parameters in
Installer Mode and Expert Mode", page 98).
Requirements:
☐ A computer with spreadsheet software installed must be available.
☐ The spreadsheet software must be able to read CSV files.
Procedure:
1. Insert the SD memory card into the card reader and display the content.
2. Start the spreadsheet software and import the required file. When importing, set the import filter in accordance with
the file structure (see spreadsheet software manual).

Operating Manual SI30M-44M-60H-80H-BE-en-32 35


7 Data Storage and Firmware Update SMA Solar Technology AG

7.3 Firmware Update


7.3.1 Display of the Firmware Version
The current firmware version of the Sunny Island and the SMA Speedwire data module Sunny Island can be
downloaded as a software package at www.SMA-Solar.com. The software package contains the following components
that are displayed differently on the screen of the Sunny Remote Control and communication product.
Hardware component Display of the firmware Display of the firmware
components on the components on the communication
Sunny Remote Control product (e.g. Sunny Explorer)
Sunny Island Master (Operation Control Unit) Main processor
Digital signal processor Logic component
SMA Speedwire data module – Protocol converter
Sunny Island

The version number of the software package is based on the first two digits of the version number of the operation control
unit.
Example
The version number of the operation control unit is, for example, 3.113. The first two digits are therefore 3 and 1.
The version number of the software package is as follows: 03.01.00.R

7.3.2 Updating the Firmware Using an SD Memory Card


Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
Requirements:
☐ The SD memory card must be formatted as FAT-16 or FAT-32.
☐ SD memory card with the current firmware in the main directory must be available.
☐ The SD memory card must be used exclusively as a data medium for the system.
☐ A computer must be able to read from and write to the SD memory card.
☐ The Sunny Remote Control must be connected to the master.
Procedure:
1. Insert the SD memory card into the SD memory card slot (see Section 7.2.1, page 33).
2. Wait until the message UPDATE AVAILABLE appears. This can take up to two minutes.
3. Confirm the question UPDATE AVAILABLE Start update now ? with YES.
☑ The Sunny Island switches to standby and updates the firmware.

36 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 7 Data Storage and Firmware Update

7.3.3 Updating the Firmware Using Sunny Explorer


-
Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
Using Sunny Explorer, transfer the firmware update to the SMA Speedwire data module Sunny Island. Then,
the SMA Speedwire data module Sunny Island automatically transfers the firmware update to the SD memory card in
the Sunny Remote Control. This transfer takes some time. With this transfer, you ensure that the same firmware version is
installed for both the Sunny Island and Speedwire data module Sunny Island. This is essential for successful
communication via Speedwire.
Requirements:
☐ The SMA Speedwire data module Sunny Island of the type SWDMSI-NR10 with firmware version 1.01.06.R or
higher must be installed in the system.
☐ A computer with Sunny Explorer and the current firmware must be available.
☐ The Sunny Remote Control must be connected to the master.
Procedure:
1. Ensure that a writable SD memory card is inserted in the Sunny Remote Control and remains inserted throughout the
entire update.
2. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
3. Ensure that the parameter 250.32 UpdMode is set to Auto.
4. Set the parameter 250.33 UpdAutoTime to the desired firmware update time.
5. Transfer the firmware update from the computer to the Sunny Island using Sunny Explorer (see the Sunny Explorer
user manual).
6. Once the transfer is complete, close Sunny Explorer.
☑ Once the transfer to the SD memory card is complete, the Sunny Island updates automatically at the specified time.
The Sunny Island switches to standby mode and updates the firmware.

7.3.4 Performing a Remote Update Using the Sunny Home Manager


Automatic Sunny Island inverter start
If the Sunny Island was in operation before the firmware update, the Sunny Island restarts automatically upon
completion of the firmware update.
The Sunny Home Manager can automatically make the current firmware available via Sunny Portal. For this,
the Sunny Home Manager first transfers the firmware update to the SMA Speedwire data module Sunny Island.
Then, the SMA Speedwire data module Sunny Island automatically transfers the firmware update to the SD memory card
in the Sunny Remote Control. This transfer takes some time. With this transfer, you ensure that the same firmware version
is installed for both the Sunny Island and Speedwire data module Sunny Island. This is essential for successful
communication via Speedwire.
Requirements:
☐ The Sunny Island must be registered in Sunny Portal.
☐ The SMA Speedwire data module Sunny Island of the type SWDMSI-NR10 must be installed in the system.
☐ The Sunny Home Manager must be integrated in the system.
☐ The Sunny Remote Control must be connected to the master.

Operating Manual SI30M-44M-60H-80H-BE-en-32 37


7 Data Storage and Firmware Update SMA Solar Technology AG

Procedure:
1. Ensure that a writable SD memory card is inserted in the Sunny Remote Control and remains inserted.
2. Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
3. Ensure that the parameter 250.32 UpdMode is set to Auto.
4. Set the parameter 250.33 UpdAutoTime to the desired firmware update time.
5. Activate the automatic software update in the Sunny Home Manager (see user manual of the
Sunny Home Manager).
☑ Once the transfer to the SD memory card is complete, the Sunny Island updates automatically at the specified time.
The Sunny Island switches to standby mode and updates the firmware.

38 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 8 Manually Controlling the Generator

8 Manually Controlling the Generator


8.1 Starting the Generator with Sunny Remote Control
Requirements:
☐ The Sunny Island must be able to control the generator via a control cable.
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure:
1. Select the Generator display page on the Sunny Remote Control and press the button (see Section 5.3.1
"Displaying Parameters and Operating and Setting the System", page 26).
2. To start the generator and run it permanently, select the parameter Mode and set to Start.
☑ The electricity generator starts and runs until you stop it again.
3. To start the generator and run it for one hour, select the parameter Mode and set to Run1h.
☑ The generator starts. If there is no generator request after one hour, the Sunny Island stops the generator.

8.2 Stopping the Generator with Sunny Remote Control


:$51,1*
Risk of crushing injuries due to movable generator parts
Moving parts in the generator can crush or sever body parts. A generator can be started automatically by the
Sunny Island.
• Before performing work on the generator, permanently stop the generator and secure it against inadvertent
restarting.
• Carry out work on the generator in accordance with the manufacturer's specifications.

Requirements:
☐ The Sunny Island must be able to control the generator via a control cable.
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure:
1. Select the Generator display page on the Sunny Remote Control and press the button (see Section 5.3.1
"Displaying Parameters and Operating and Setting the System", page 26).
2. Select the parameter Mode and set to Stop.
☑ The generator is stopped temporarily. The generator restarts when a generator request is issued in automatic
generator mode and the minimum stop time has elapsed.
3. To stop the generator permanently, deactivate the automatic generator mode:
• Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
• Select the parameter 235.01 GnAutoEna and set to Disable.
☑ The generator is permanently stopped.

Operating Manual SI30M-44M-60H-80H-BE-en-32 39


8 Manually Controlling the Generator SMA Solar Technology AG

8.3 Starting the Generator without Autostart Function


1. Start the generator (see manufacturer's manual).
2. Close the load-break switch between the generator and Sunny Island.
☑ After the warm-up period, the Sunny Island connects the stand-alone grid to the generator.

8.4 Stopping the Generator without Autostart Function


1. Stop the generator on the Sunny Remote Control (see Section 8.2, page 39). When you do this, the Sunny Island
disconnects the stand-alone grid from the generator.
2. Open the load-break switch between the generator and the Sunny Island.
3. Stop the generator (see manufacturer's manual).
☑ The generator is stopped. After the power-down time and the minimum stop time, you can use the generator again.

40 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 9 Disconnecting the Sunny Island from Voltage Sources

9 Disconnecting the Sunny Island from Voltage Sources

1. Switch the system off (see Section 4.4, page 19).


2. Disconnect the circuit breakers and the load-break switches in the sub-distributions and secure against reconnection.
3. Open the load-break switch in the DC cable and secure against reconnection.
4. /05*$&
Destruction of the Sunny Island inverter due to electrostatic discharge (ESD)
By touching electronic components within the Sunny Island, you can damage or destroy the Sunny Island.
• Do not touch any electronic assemblies.
• Ground yourself before touching any connections.
5. Loosen all screws of the enclosure lid and remove the enclosure lid.
6. Ensure that the DC connection is disconnected from voltage sources.
7. Ensure that the connections AC1 Loads/SunnyBoys, AC2
Gen/Grid, and ExtVtg (position A) are disconnected from
voltage sources.

8. Ensure that the connections Relay1 and Relay2 (position A) are


disconnected from voltage sources.

9. Ground and short-circuit the AC power cables outside the Sunny Island.
10. Cover or isolate any adjacent live components.

Operating Manual SI30M-44M-60H-80H-BE-en-32 41


10 Troubleshooting SMA Solar Technology AG

10 Troubleshooting
10.1 Display of Errors
10.1.1 Display of Errors on the Sunny Remote Control
Display of errors, warnings, and events
Pending warnings and errors are shown automatically on the display of the Sunny Remote Control until the cause of the
warning or error is no longer logged by the Sunny Island or has been acknowledged. Events are logged by the
Sunny Island. The following menus log warnings, errors and events:
• 410# Error active - display of currently pending warnings and errors
• 420# Error history - warning and error history
• 430# Event history - events history
• In systems for increased self-consumption and battery backup systems: 440# Error Grid - history of the last five utility
grid errors

Structure of Display Numbers


Each error and each event has a unique three-digit display number that is determined based on the parameter or
measurement value assignment. Events and errors use the same number range:
• 1xx - Sunny Island
• 2xx - Battery
• 3xx - Generator or utility grid
• 4xx - Generator
• 5xx - Utility grid
• 6xx - Relay
• 7xx - System
• 8xx - External devices and components
• 9xx - General

Meaning of abbreviations
F indicates an error, W a warning, and E an event.
In the event of an error, the display shows whether the error has come or gone using ! for "Set" and C for "Clear".

10.1.2 Display of Errors on the Communication Product (example)


Most warnings, errors and events of the Sunny Island inverter can be called up on the communication product
(e.g. Sunny Explorer or Sunny Portal). Links to additional information can be found at www.SMA-Solar.com:
Document title Document type
SUNNY EXPLORER User manual
SUNNY HOME MANAGER in SUNNY PORTAL User manual
SUNNY ISLAND – Message of the same event for Speedwire (e.g. Sunny Explorer) Technical information
and RS485 (e.g. Sunny Remote Control)

42 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.2 Sunny Island Inverter Behavior Under Fault Conditions


Error Levels
The Sunny Island distinguishes between five different levels of errors, each requiring different user interaction.
Level Designation Display on the Explanation
Sunny Remote
Control
1 Warning Warning Warning; the Sunny Island continues to run. Information in standard
mode indicating that a warning has been generated.
2 Malfunction 1 Malfunction Malfunction that is detectable only during operation. The Sunny Island
shuts down. Restart can be initiated immediately (e.g. via autostart).
3 Malfunction 2 Malfunction Malfunction that is also detectable in standby mode. The Sunny Island
shuts down. Restart is blocked until the malfunction is no longer detected
by the Sunny Island.
4 Failure Failure Device failure; the Sunny Island switches off. Troubleshooting,
acknowledgment of the error and manual restart necessary.
5 Device defect Defect The Sunny Island is defective and switches itself off. The Sunny Island
must be replaced.

Handling of pending errors upon activation


During the activation procedure, all pending errors are acknowledged without the error being logged in the list 420#
Error history. Errors that are still pending are entered again after activation. Errors that were detected by the
Sunny Island before activation and are no longer detected after activation are shown in the list 420# Error history.

Autostart
The autostart function allows automatic restarts in the event of malfunctions. If the autostart function fails in the event of a
malfunction, the Sunny Island attempts to carry out the next autostart immediately. The number of autostarts is restricted.
If the Sunny Island is in operation without malfunctions for ten minutes, it resets the autostart counter.
When the maximum number of autostarts has been reached, the Sunny Island reacts as follows:
• The Sunny Island waits ten minutes.
• The autostart counter is reset.
• The Sunny Island attempts to perform an autostart.
• When the maximum number of autostarts has been reached, the Sunny Island waits again for ten minutes.

10.3 Acknowledge Errors


If a malfunction or failure occurs, the Sunny Island switches to standby mode. Once you have eliminated the cause of the
error, you can enable a restart of the Sunny Island inverter by acknowledging the error.
Procedure:
1. Eliminate the cause.
2. Press the button on the Sunny Remote Control. This acknowledges the error.
3. Start the system (see Section 4.2, page 18).

Operating Manual SI30M-44M-60H-80H-BE-en-32 43


10 Troubleshooting SMA Solar Technology AG

10.4 Logged Events


10.4.1 Sunny Island Category (1xx)
No. Name Description
E101 Standby Waiting mode
E102 Startup Startup process
E103 Run Operation
E104 RunExtGn Operation with a generator
E105 RunExtGd Operation with the utility grid
E106 RunGdFeed Feed-in grid operation
E108 Silent Energy-saving mode
E110 ErrShutdown Shutdown due to error
E115 EmgCharge Emergency charging
E118 AutoStart Automatic start
E119 ManStart Manual start
E120 ManStop Manual stop
E121 PwrSaveStart Start of energy-saving mode
E122 PwrSaveStop End of energy-saving mode
E129 Ext.Start External start
E130 Ext.Stop External stop
E131 AfraStart Automatic frequency synchronization control is activated
E132 AfraStop Automatic frequency synchronization control is not activated
E133 SlfCsmpStart Start of increased self-consumption
E134 SlfCsmpStop Stop of increased self-consumption
E135 SlfCsmpChrgOnly Battery is charged only when increased self-consumption is active
E136 SLfCsmpBatMnt Full charge or equalization charge when increased self-consumption active
E137 SlfCsmpNormal Switch back to increased self-consumption after completion of full or equalization charge
E138 InvShutdown The Sunny Island shuts down
E140 FedInOn Setpoint activated
E141 FedInOff Setpoint deactivated

44 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.4.2 Battery Category (2xx)


No. Name Description
E202 BmsNewBat (Partial) reset of battery management due to new battery
E203 BmsFloat Status change to float charge of the battery
E204 BmsBoost Status change to boost charge of the battery
E205 BmsFull Status change to full charge of the battery
E206 BmsSilent Switches to energy-saving mode
E207 BmsEqual Status change to equalization charge of the battery
E224 BMS20PReCal 20% recalibration being performed.

10.4.3 Generator Category (4xx)


No. Name Description
E401 GnAutoStart Automatic generator start (e.g., via state-of-charge-dependent generator request)
E402 GnAutoStop Automatic generator stop
E403 GnManStart Manual generator start
E404 GnManStop Manual generator stop
E405 GnManAck Manual error acknowledgment of generator error
E406 GnDmdSrc Generator request
E407 GnCurCtlStr Current-controlled generator operation started
E408 GnCurCtlStp Current-controlled generator operation stopped

10.4.4 Utility Grid Category (5xx)


No. Name Description
E501 GdSocOn Grid request due to low battery state of charge
E502 GdSocOff Grid release due to adequate battery SOC
E503 GdPwrOn Grid request due to power limit being exceeded
E504 GdPwrOff Grid approval due to falling below the power limit
E505 GdManOn Manual grid request
E506 GdManOff Manual grid release

10.4.5 Relay Category (6xx)


No. Name Description
E601 Rly1Off Multifunction relay 1 is deactivated.
E602 Rly1On Multifunction relay 1 is activated.
E603 Rly1Slv1Off Multifunction relay 1 of slave 1 is deactivated.
E604 Rly1Slv1On Multifunction relay 1 of slave 1 is activated.
E605 Rly1Slv2Off Multifunction relay 1 of slave 2 is deactivated.

Operating Manual SI30M-44M-60H-80H-BE-en-32 45


10 Troubleshooting SMA Solar Technology AG

No. Name Description


E606 Rly1Slv2On Multifunction relay 1 of slave 2 is activated.
E609 TransferOff Internal transfer relay is open.
E610 TransferOn Internal transfer relay is closed.
E611 TransferSlv1Off Internal transfer relay of slave 1 is open.
E612 TransferSlv1On Internal transfer relay of slave 1 is closed.
E613 TransferSlv2Off Internal transfer relay of slave 2 is open.
E614 TransferSlv2On Internal transfer relay of slave 2 is closed.
E617 Rly2Off Multifunction relay 2 is deactivated.
E618 Rly2On Multifunction relay 2 is activated.
E619 Rly2Slv1Off Multifunction relay 2 of slave 1 is deactivated.
E620 Rly2Slv1On Multifunction relay 2 of slave 1 is activated.
E621 Rly2Slv2Off Multifunction relay 2 of slave 2 is deactivated.
E622 Rly2Slv2On Multifunction relay 2 of slave 2 is activated.
E625 DigInOff No voltage at input DigIn (Low).
E626 DigInOn Voltage at input DigIn (High).

10.4.6 System Category (7xx)


No. Name Description
E705 PwrOn Device start
E706 DateSet Date or time has been changed.
E707 NewSys New system configured in the QCG.
E708 Fw1Update Part 1 of the firmware updated.
E709 Fw2Update Part 2 of the firmware updated.
E710 ClstUpdate Cluster firmware updated.
E711 CardInsert SD memory card is inserted.
E712 ParaUpdate Parameter set has been loaded from SD memory card.
E715 SRCOn Sunny Remote Control is activated.
E716 PvDiscon Disconnection of inverters whose power is not controllable depending on the frequency
E718 NoComMod1 Communication interface 1 is incorrectly plugged or missing.
E719 NoComMod2 Communication interface 2 is incorrectly plugged or missing.

46 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.4.7 External Device and Component Category (8xx)


No. Name Description
E824 UpdFileComplete File for firmware update transferred.
E825 UpdFileCrcOK File for firmware update is OK.
E827 UpdFileCrcNOK File for firmware update is damaged.
E851 Sic1Detect Sunny Island Charger 1 has been detected.
E852 Sic2Detect Sunny Island Charger 2 has been detected.
E853 Sic3Detect Sunny Island Charger 3 has been detected.
E854 Sic4Detect Sunny Island Charger 4 has been detected.

10.4.8 External Events


XE06XE06
No. Name Description
E901 BMSStrSOCRecal SOC recalibration started
E902 BMSStpSOCRecal SOC recalibration stopped
E903 BMSStrPwrLim Active power limitation started (derating)
E904 BMSStpPwrLim Active power limitation stopped (derating)
E905 BMSPrevShutdown Preventive battery shutdown
E906 XE06 Message of the external battery management (see battery manufacturer's
documentation
E907 XE07 Message of the external battery management (see battery manufacturer's
documentation
E908 XE08 Message of the external battery management (see battery manufacturer's
documentation

Operating Manual SI30M-44M-60H-80H-BE-en-32 47


10 Troubleshooting SMA Solar Technology AG

10.5 Logged Warning Messages and Error Messages


10.5.1 Sunny Island Category (1xx)
No. Name Level Cause Corrective measures
F 109 InvTmpHi 3 Overtemperature in the • Ensure that the Sunny Island is
transformer of the device at L1: functional. For this, wait until the
Temperature of the transformer in Sunny Island has cooled down
the master is too high due to and then restart it.
overload or ambient temperature. • Clean the fans (see Section 11.7
W 110 InvTmpHiSlv1 1 Overtemperature in the "Cleaning the Fans", page 86).
transformer of the device at L2: • Reduce the total power of the
Temperature of the transformer in loads, e.g. by staggering their use
the Slave 1 is too high due to over time.
overload or ambient temperature.
W 111 InvTmpHiSlv2 1 Overtemperature in the
transformer of the device at L3:
Temperature of the transformer in
Slave 1 is too high due to overload
or ambient temperature.
F 113 InvTmpHi 3 Overtemperature in the • Ensure that the Sunny Island is
transformer of the device at L1: functional. For this, wait until the
Temperature of the heat sink in the Sunny Island has cooled down
master is too high due to overload and then restart it.
or ambient temperature. • Reduce the total power of the
loads, e.g. by staggering their use
over time.
W 114 InvTmpHiSlv1 1 Overtemperature in the • Ensure that the Sunny Island is
transformer of the device at L2: functional. For this, wait until the
Temperature of the heat sink in Sunny Island has cooled down
Slave 1 is too high due to overload and then restart it.
or ambient temperature. • Reduce the total power of the
W 115 InvTmpHiSlv2 1 Overtemperature in the loads, e.g. by staggering their use
transformer of the device at L3: over time.
Temperature of the heat sink in
Slave 2 is too high due to overload
or ambient temperature.

48 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 117 AcCurLim 2 AC current limitation Line • Ensure that the Sunny Island is
conductor L1: The power of the functional. For this, clean the fans
loads is too high for the master. and restart the Sunny Island (see
Section 11.7 "Cleaning the Fans",
W 118 AcCurLimSlv1 1 AC current limitation Line
page 86).
conductor L2: The power of the
loads is too high for Slave 1. •
W 119 AcCurLimSlv2 1 AC current limitation Line Ensure that there are no short
conductor L3: The power of the circuits in the system and that the
loads is too high for Slave 2. power of the loads is not greater
than the power of the
Sunny Island inverter.

Use a star delta electronic circuit
to start three-phase loads with a
high start-up electricity demand
(e.g., engines).

Connect the loads with very high
power directly to the generator
whenever possible. Ensure that the
generator is not overloaded.
F 121 InvVtgHi 3 Inverter overvoltage Line •
conductor L1: An overvoltage Ensure that the Sunny Island is
has occurred at connection AC1 of functional. For this, disconnect all
the master. AC sources and loads from the
W 122 InvVtgHiSlv1 1 Inverter overvoltage Line Sunny Island and restart the
conductor L1: An overvoltage Sunny Island.
has occurred at connection AC1 of •
Slave 1.
Find the cause of the overvoltage
W 123 InvVtgHiSlv2 1 Inverter overvoltage Line through measurement and
conductor L1: An overvoltage step-by-step connection of the AC
has occurred at connection AC1 of sources and loads.
Slave 2.
F 129 InvFrqHi 3 Inverter overfrequency Line •
conductor L1: An overfrequency Ensure that the Sunny Island is
has occurred at connection AC1 of functional. For this, disconnect all
the master. AC sources and loads from the
W 130 InvFrqHiSlv1 1 Inverter overfrequency Line Sunny Island and restart the
conductor L1: An overfrequency Sunny Island.
has occurred at connection AC1 of •
Slave 1.
Find the cause of the
W 131 InvFrqHiSlv2 1 Inverter overfrequency Line overfrequency through
conductor L3: An overfrequency measurement and step-by-step
has occurred at connection AC1 of connection of the AC sources and
Slave 2. loads.

Operating Manual SI30M-44M-60H-80H-BE-en-32 49


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 133 InvFrqLo 3 Inverter underfrequency Line •
conductor L1: An Ensure that the Sunny Island is
underfrequency has occurred at functional. For this, disconnect all
connection AC1 of the master. AC sources and loads from the
W 134 InvFrqLoSlv1 1 Inverter underfrequency Line Sunny Island and restart the
conductor L2: An Sunny Island.
underfrequency has occurred at •
connection AC1 of Slave 1.
Find the cause of the
W 135 InvFrqLoSlv2 1 Inverter underfrequency Line underfrequency through
conductor L3: An measurement and step-by-step
underfrequency has occurred at connection of the AC sources and
connection AC1 of Slave 2. loads.
W 137 Derate 1 Derating due to • Clean the fans (see Section 11.7
temperature L1: The master has "Cleaning the Fans", page 86).
reduced the battery charging • Reduce the total power of the
current due to overtemperature in loads, e.g. by staggering their use
the Sunny Island. over time.
W 138 DerateSlv1 1 Derating due to •
temperature L2: Slave 1 has
If the Sunny Island frequently
reduced the battery charging
reduces its power, increase power
current due to overtemperature in
by replacing the Sunny Island
the Sunny Island.
with a higher-powered version or
W 139 DerateSlv2 1 Derating due to by installing additional
temperature L3: Slave 2 has Sunny Island inverters.
reduced the battery charging
current due to overtemperature in
the Sunny Island.
F 141 InvVtgLo 2 Inverter undervoltage Line •
conductor L1: The voltage at Ensure that the Sunny Island is
connection AC1 of the master is functional. For this, disconnect all
too low due to AC sources in the AC sources and loads from the
system. Sunny Island and restart the
W 142 InvVtgLoSlv1 1 Inverter undervoltage Line Sunny Island.
conductor L2: The voltage at •
connection AC1 of Slave 1 is too
Find the cause of the undervoltage
low due to AC sources in the
through measurement and
system.
step-by-step connection of the AC
W 143 InvVtgLoSlv2 1 Inverter undervoltage Line sources and loads.
conductor L3: The voltage at
connection AC1 of Slave 2 is too
low due to AC sources in the
system.

50 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 158 VtgOnAC1Det 2 Voltage at AC connection Line A bypass switch may have bridged the
conductor L1: The master has internal transfer relay.
measured an undesired voltage at • Ensure that the bypass switch is in
connection AC1. the position for operation with the
W 159 VtgOnAC1DetSlv1 1 Voltage at AC connection Line Sunny Island.
conductor L2: Slave 1 has •
measured an undesired voltage at
Ensure that the Sunny Island is
connection AC1.
functional. For this, disconnect all
W 160 VtgOnAC1DetSlv2 1 Voltage at AC connection Line AC sources and loads from the
conductor L3: Slave 2 has Sunny Island and restart the
measured an undesired voltage at Sunny Island.
connection AC1. An external energy source
(e.g., generator) may have been
connected to the connection AC1.

Disconnect external energy
source from connection AC1 and
connect to connection AC2
(see the Sunny Island inverter
installation manual).
F 162 OvrCurDet 2 Too much current is flowing • Reduce the power of the loads.
through the DC connection of the
master.
W 163 OvrCurDetSlv1 1 Too much current is flowing
through the DC connection of
slave 1.
W 164 OvrCurDetSlv2 1 Too much current is flowing
through the DC connection of
slave 2.
F 166 Overload5min 3 The device at L1 (Master) has
been loaded over its five-minute
rated capacity.
W 167 Overload5minSlv1 1 The device at L2 (Slave 1) has
been loaded over its five-minute
rated capacity.
W 168 Overload5minSlv2 1 The device at L3 (Slave 2) has
been loaded over its five-minute
rated capacity.

Operating Manual SI30M-44M-60H-80H-BE-en-32 51


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 169 Overload30min 3 The device at L1 (Master) has • Reduce the power of the loads.
been loaded over its 30-minute
rated capacity.
W 170 Overload30minSlv1 1 The device at L2 (Slave 1) has
been loaded over its 30-minute
rated capacity.
W 171 Overload30minSlv2 1 The device at L3 (Slave 2) has
been loaded over its 30-minute
rated capacity.
F 172 Overload 3 The device at L1 (Master) has
been loaded over its rated
short-term capacity.
W 173 OverloadSlv1 1 The device at L2 (Slave 1) has
been loaded over its rated
short-term capacity.
W 174 OverloadSlv2 1 The device at L3 (Slave 2) has
been loaded over its rated
short-term capacity.
F 175 StopSlvError 2 Slave is in Fault mode. The cluster • Contact the SMA Service Line.
is stopped.
F 176 CurTrfSns 4 The current sensor is not
connected, not available or
defective.

10.5.2 Battery Category (2xx)


No. Name Level Cause Corrective measures
F 201 VBATMAX 2 Measuring range of battery • Check whether the value of the
voltage exceeded in device parameter 120.02 BatVtg is above
at L1: Battery voltage at the 65.0 V. If the value is above 65.0 V,
master is above the permissible check the settings of the DC sources and
measurement range. ensure that the battery capacity is
sufficient. When doing so, bear in mind
W 202 VBATMAXSL1 1 Measuring range of battery
the technical data for the battery at the
voltage exceeded in device
DC connection (see the Sunny Island
at L2: Battery voltage at
inverter installation manual).
Slave 1 is above the
permissible measurement •
range. Ensure that the DC sources are correctly
W 203 VBATMAXSL2 1 Measuring range of battery connected and configured.
voltage exceeded in device
at L3: Battery voltage at
Slave 2 is above the
permissible measurement
range.

52 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 206 BatTmpHi 3 Overtemperature fault in • Wait for the battery to cool down.
battery: The battery Tip: Protect the battery against
temperature is too high. temperatures above 25°C. This helps
prevent premature aging of the battery.

Check whether the electrical resistance of
the battery temperature sensor is approx.
2,000 Ω at 20°C to 25°C. If the
resistance deviates strongly from this
value, replace the sensor.
F 208 BatVtgHi 3 Measuring range of battery •
voltage exceeded in device Ensure that all DC sources are correctly
at L2: Battery voltage is higher configured.
than the target charge voltage.

Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 209 BatVtgWrnHi 1 The battery voltage is too high •
and has not been generated by Ensure that all DC sources are correctly
the device. configured.

Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 210 BatVtgHiWarn 1 Battery overvoltage: Battery •
voltage is temporarily too high. Ensure that all DC sources are correctly
configured.

Ensure that all SMA inverters are
configured to the country data set for
stand-alone grid operation.
W 211 BatTmpLoWarn 1 Undertemperature fault in • Ensure that the battery room is sufficiently
battery: The battery warm.
temperature is too low.
W 212 BatTmpHiWarn 1 Overtemperature fault in • Wait for the battery to cool down.
battery: The battery Tip: Protect the battery against
temperature is too high. temperatures above 25°C. This helps
prevent premature aging of the battery.

Operating Manual SI30M-44M-60H-80H-BE-en-32 53


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 213 BatVtgLow 3 Battery undervoltage: •
Battery voltage is too low. Charge the battery in emergency charge
operation or using an external battery
charger (see Section 10.7 "Charging the
Battery After Automatic Shutdown in
Off-Grid Systems", page 81).

Ensure that DC loads are shed via a
load-shedding contactor when the
battery state of charge is low.
W 220 BatSOH70Warn 1 Current battery capacity •
(SOH) is below 70%. Verify the plausibility of the error message
and replace the battery if necessary.
F 221 InvalidBatType 4 External battery management •
detected but not configured. Start QCG and configure a new system
with external energy management
(e.g., system with lithium-ion battery).
W 222 CheckBat 1 A 20% recalibration of the • Check the battery.
battery state of charge has
been performed with a jump of
more than 10%.

10.5.3 Generator or Utility Grid Category (3xx)


No. Name Level Cause Corrective measures
W 309 RlyProtect 1 Excessive current has • Reduce the total power of the loads, e.g.
been applied to the by staggering their use over time.
transfer relay of the •
device at L1: Excessive
current has been applied to Connect the loads with very high power
the internal transfer relay of directly to the generator whenever
the master. possible or connect the utility grid. Ensure
that the generator is not overloaded.
W 310 RlyProtectSlv1 1 Excessive current has

been applied to the
transfer relay of the In off-grid systems, ensure that the country
device at L2: Excessive data sets of the SMA inverters are set to
current has been applied to stand-alone grid operation
the internal transfer relay of (see the installation manuals of the SMA
Slave 1. inverters).

W 311 RlyProtectSlv2 1 Excessive current has


been applied to the
transfer relay of the
device at L3: Excessive
current has been applied to
the internal transfer relay of
Slave 2.

54 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 314 ExtVtgLoss 2 External voltage failure: Corrective measures for a generator:
The voltage and/or •
frequency of the generator
Adjust the thresholds for generator
or the utility grid are outside frequency and/or voltage on the
of the configured range. Sunny Island (see the Sunny Island
inverter installation manual). Observe
and analyze the measured values
134.02 ExtVtg and 134.04 ExtFrq
during operation.

Adjust the generator voltage and/or
generator frequency.
Corrective measures in battery backup
systems:
• Contact the SMA Service Line, if required.
W 315 ExtVtgLo 1 Disconnection from the Corrective measures for a generator:
external grid due to •
undervoltage at line
conductor L1: The voltage Adjust the thresholds for generator
of the generator or the utility voltage on the Sunny Island (see the
grid at the master is too low. Sunny Island inverter installation
manual). Observe and analyze the
W 316 ExtVtgLoSlv1 1 Disconnection from the
external grid due to measured values 134.02 ExtVtg during
undervoltage at line operation.
conductor L2: The voltage •
of the generator or the utility
If possible, adjust the generator voltage.
grid at Slave 1 is too low.
Corrective measures in battery backup
W 317 ExtVtgLoSlv2 1 Disconnection from the
systems:
external grid due to
undervoltage at line • Contact the SMA Service Line, if required.
conductor L3: The voltage
of the generator or the utility
grid at Slave 2 is too low.
W 319 ExtVtgHi 1 Disconnection from the
external grid due to
overvoltage at line
conductor L1: The voltage
of the generator or the utility
grid at the master is too high.
W 320 ExtVtgHiSlv1 1 Disconnection from the
external grid due to
overvoltage at line
conductor L2: The voltage
of the generator or the utility
grid at Slave 1 is too high.
W 321 ExtVtgHiSlv2 1 Disconnection from the
external grid due to
overvoltage at line
conductor L3: The voltage
of the generator or the utility
grid at Slave 2 is too high.

Operating Manual SI30M-44M-60H-80H-BE-en-32 55


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 323 ExtFrqLo 1 Disconnection from the Corrective measures for a generator:
external grid due to too • The generator may be overloaded.
low frequency at line Reduce the total power of the loads by
conductor L1: The staggering their use over time.
frequency of the generator
or the utility grid at the •
master is too low. Adjust the thresholds for generator
frequency on the Sunny Island (see the
W 324 ExtFrqLoSlv1 1 Disconnection from the
Sunny Island inverter installation
external grid due to too
manual). Observe and analyze the
low frequency at line
measured values 134.04 ExtFrq during
conductor L2: The
operation.
frequency of the generator
or the utility grid at Slave 1 is •
too low. Adjust the frequency of the external
W 325 ExtFrqLoSlv2 1 Disconnection from the energy source.
external grid due to too Corrective measures for a utility grid:
low frequency at line
• Contact the SMA Service Line, if required.
conductor L3: The
frequency of the generator
or the utility grid at Slave 2 is
too low.
W 327 ExtFrqHi 1 Disconnection from the
external grid due to too
high frequency at line
conductor L1: The
frequency of the generator
or the utility grid at the
master is too high.
W 328 ExtFrqHiSlv1 1 Disconnection from the
external grid due to too
high frequency at line
conductor L2: The
frequency of the generator
or the utility grid at Slave 1 is
too high.
W 329 ExtFrqHiSlv2 1 Disconnection from the
external grid due to too
high frequency at line
conductor L3: The
frequency of the generator
or the utility grid at Slave 2 is
too high.

56 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 331 AntiIsl 1 Disconnection from the •
external grid due to Ensure that the insulated wires at
undesired stand-alone connection AC2 are securely connected
grid at line conductor L1: and that the conductors in the terminals
Undesired stand-alone grid are free of insulation.
is present at connection AC2
of the master. Corrective measures for a generator:
W 332 AntiIslSlv1 1 Disconnection from the This may be caused by a contactor between
external grid due to the generator and the Sunny Island.
undesired stand-alone •
grid at line conductor L2: Control of the contactor via a
Undesired stand-alone grid Sunny Island inverter multifunction relay.
is present at connection AC2 Set the parameter of the multifunction
of Slave 1. relay, e.g., 241.01 Rly1Op, to AutoGn.
W 333 AntiIslSlv2 1 Disconnection from the •
external grid due to
Set the parameter 234.20 GdAiSns to a
undesired stand-alone
lower sensitivity.
grid at line conductor L3:
Undesired stand-alone grid Corrective measures for a utility grid:
is present at connection AC2
• Contact the SMA Service Line.
of Slave 2.
W 335 ExtVtgRdtErr 1 Disconnection from Corrective measures for a generator:
external source due to •
exceeding the configured
thresholds in the device Adjust the thresholds for generator
at L1: The voltage of the voltage on the Sunny Island (see the
generator or the utility grid at Sunny Island inverter installation
the master is outside the manual). Observe and analyze the
configured thresholds measured values 134.02 ExtVtg during
(redundant measurement). operation.

W 336 ExtVtgRdtErrSlv1 1 Disconnection from
external source due to If possible, adjust the generator voltage.
exceeding the configured Corrective measures for a utility grid:
thresholds in the device
at L2: The voltage of the • Contact the SMA Service Line, if required.
generator or the utility grid at
Slave 1 is outside the
configured thresholds
(redundant measurement).
W 337 ExtVtgRdtErrSlv2 1 Disconnection from
external source due to
exceeding the configured
thresholds in the device
at L3: The voltage of the
generator or the utility grid at
Slave 2 is outside the
configured thresholds
(redundant measurement).

Operating Manual SI30M-44M-60H-80H-BE-en-32 57


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 339 ExtVtgIncPro 1 Voltage increase protection •
Line conductor L1 Ensure that the conductor cross-section of
W 340 ExtVtgIncProSlv1 1 Voltage increase protection the AC cables is correctly sized.
Line conductor L2
W 341 ExtVtgIncProSlv2 1 Voltage increase protection
Line conductor L3
W 343 AcVtglim 1 Disconnection from the • Contact the SMA Service Line if required.
external grid due to
insufficient battery
voltage or overvoltage at
line conductor L1: The
master disconnects from the
external energy source
because the voltage at
connection AC2 is too high
or the battery voltage too
low.
W 344 AcVtglimSlv1 1 Disconnection from the
external grid due to
insufficient battery
voltage or overvoltage at
line conductor L2: Slave 1
disconnects from the external
energy source because the
voltage at connection AC2 is
too high or the battery
voltage too low.
W 345 AcVtglimSlv2 1 Disconnection from the
external grid due to
insufficient battery
voltage or overvoltage at
line conductor L3: Slave 2
disconnects from the external
energy source because the
voltage at connection AC2 is
too high or the battery
voltage too low.
W 347 ExtOverload 1 Disconnection from the • Reduce the total power of the loads, e.g.
external grid due to line by staggering their use over time.
conductor failure or •
overload at line
conductor 1: The master Ensure that there is not a short circuit
disconnects from the utility present at connection AC2.
grid due to line conductor
failure/overload at
connection AC2.

58 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 348 ExtOverloadSlv1 1 Disconnection from the • Reduce the total power of the loads, e.g.
external grid due to line by staggering their use over time.
conductor failure or •
overload at line
conductor 2: Slave 1 Ensure that there is not a short circuit
disconnects from the utility present at connection AC2.
grid due to line conductor
failure/overload at
connection AC2.
W 349 ExtOverloadSlv2 1 Disconnection from the
external grid due to line
conductor failure or
overload at line
conductor 3: Slave 2
disconnects from the utility
grid due to line conductor
failure/overload at
connection AC2.
W 351 ExtScirDet 1 Disconnection from the •
external grid due to Eliminate the short circuit.
external short circuit at
line conductor L1: Short
circuit is present at
connection AC2 of the
master.
W 352 ExtScirDetSlv1 1 Disconnection from the
external grid due to
external short circuit at
line conductor L2: Short
circuit is present at
connection AC2 of Slave 1.
W 353 ExtScirDetSlv2 1 Disconnection from the
external grid due to
external short circuit at
line conductor L3: Short
circuit is present at
connection AC2 of Slave 2.
W 355 PhsAngErr 1 External grid does not •
have a correct rotating Ensure that the master is connected to L1,
field: Assignment of the line slave 1 to L2, and slave 2 to L3.
conductors of the external
energy source to the AC2
connections of the
Sunny Island does not result
in a right-rotating magnetic
field.

Operating Manual SI30M-44M-60H-80H-BE-en-32 59


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 365 VAcExtPhsFail 3 Phase position of the
measured AC voltage at • Ensure that the neutral conductor and line
VExt and AC2 does not conductor are correctly connected to
match at line conductor L1 connection ExtVtg.
(Master).
• Ensure that the neutral conductor and line
conductor are correctly connected to
connection AC2.
• Ensure that connections ExtVtg and AC2
are connected to the same line
conductor.
F 366 HotAcBus 3 When the tie switch is open,
AC voltage is present at line • Ensure that the triggering of the tie switch
conductor L1 (Master). is correct.
• Ensure that the tie switch is correctly
wired.
F 367 ExtCtcNotOpen 3 Tie switch does not open.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the feedback contact is
correctly connected.
F 368 NRelNotOpen 3 Neutral conductor relay • Contact the SMA Service Line.
does not open at L1
(Master).
W 369 NRelNotOpenSlv1 1 Neutral conductor relay
does not open at L2
(Slave 1).
W 370 NRelNotOpenSlv2 1 Neutral conductor relay
does not open at L3
(Slave 2).
W 372 VtgFrqRatio 1 Disconnection from the • Contact the SMA Service Line if required.
external grid or generator
due to non-compliance with
the voltage-frequency ratio
at line conductor L1 (Master)
W 373 VtgFrqRatioSlv1 1 Disconnection from the
external grid due to
non-compliance with the
voltage-frequency ratio at
line conductor L2 (Slave 1)
W 374 VtgFrqRatioSlv2 1 Disconnection from the utility
grid due to non-compliance
with the voltage-frequency
ratio at line conductor L3
(Slave 2)

60 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 376 ExtCtcNotClose 3 Tie switch does not close.
• Ensure that the triggering of the tie switch
is correct.
• Ensure that the tie switch is correctly
wired.
• Ensure that the feedback contact is
correctly connected.
W 377 ExtCurExCeed 1 The external current
measured on L1 exceeds the • Reduce power consumption of all loads.
set parameter value
232.04 GdCurNom or • Reduce power output of the AC sources
234.03 GnCurNom (e.g. PV inverter).
by 2%.
W 378 ExCurExcSlv1 1 The external current
measured on L2 exceeds the
set parameter value
232.04 GdCurNom or
234.03 GnCurNom
by 2%.
W 379 ExCurExcSlv2 1 The external current
measured on L3 exceeds the
set parameter value
232.04 GdCurNom or
234.03 GnCurNom
by 2%.
W 380 VAcExtPhsFailS1 1 Phase position of the
measured AC voltage at • Ensure that the neutral conductor and line
VExt and AC2 does not conductor are correctly connected to
match at line conductor L2 connection ExtVtg.
(Slave 1).
• Ensure that the neutral conductor and line
W 381 VAcExtPhsFailS2 1 Phase position of the conductor are correctly connected to
measured AC voltage at connection AC2.
VExt and AC2 does not
• Ensure that connections ExtVtg and AC2
match at line conductor L3
are connected to the same line
(Slave 2).
conductor.
W 383 HotAcBusSlv1 1 When the tie switch is open,
AC voltage is present at line • Ensure that the triggering of the tie switch
conductor L2 (Slave 1). is correct.
W 384 HotAcBusSlv2 1 When the tie switch is open, • Ensure that the tie switch is correctly
AC voltage is present at line wired.
conductor L3 (Slave 2).

Operating Manual SI30M-44M-60H-80H-BE-en-32 61


10 Troubleshooting SMA Solar Technology AG

10.5.4 Generator Category (4xx)


No. Name Level Cause Corrective measures
W 401 GnRevPwrProt 1 Reverse power • Adjust the generator request to the properties of the
protection AC sources in the system and the loads, e.g., for PV
(Generator): AC inverters, preferably request the generator at night.
sources in the system •
are driving the
generator. The reverse If the generator can absorb reverse power, adjust
power in the generator the settings for reverse power (see the Sunny Island
has been exceeded for inverter installation manual).
too long.
W 402 GnFailLock 1 Blocking of generator
due to too many • Ensure that the generator triggering is functioning,
interrupted start-ups the generator starts, and there is constant and stable
generator voltage present at connection AC2.
• To re-enable connection of the generator,
acknowledge the generator error (see Section 10.3
"Acknowledge Errors", page 43).

A warm-up time 234.12 GnWarmTm that is too short


may have been configured and hence the generator is
unable to supply valid voltage.
• Ensure that the generator warm-up time is configured
appropriately (see the Sunny Island inverter
installation manual).

10.5.5 Utility Grid Category (5xx)


No. Name Level Cause Corrective measures
W 501 GdRevPwrProt 1 Non-permitted reverse feeding into the utility • Contact the SMA Service
grid at line conductor L1 (Master) Line, if required.
W 502 GdRevPwrProtSL1 1 Non-permitted reverse feeding into the utility
grid at line conductor L2 (Slave 1)
W 503 GdRevPwrProtSL2 1 Non-permitted reverse feeding into the utility
grid at line conductor L3 (Slave 2)
W 505 GdCurNomExceed 1 At line conductor L1 (Master), the feed-in
current is greater than the set maximum
value 232.04 GdCurNom.
W 506 GdCurNomExcSlv1 1 At line conductor L2 (Slave 1), the feed-in
current is greater than the set maximum
value 232.04 GdCurNom.
W 507 GdCurNomExcSlv2 1 At line conductor L3 (Slave 2), the feed-in
current is greater than the set maximum
value 232.04 GdCurNom.

62 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.5.6 Relay Category (6xx)


No. Name Level Cause Corrective measures
F 605 TransfNotOpn 4 Transfer relay does not open A bypass switch may have bridged the internal
at line conductor L1 (Master). transfer relay.
W 606 TransfNotOpnSL1 1 Transfer relay does not open • Ensure that the bypass switch is in the
at line conductor L2 (Slave 1). position for operation with the
Sunny Island.
W 607 TransfNotOpnSL2 1 Transfer relay does not open
at line conductor L3 (Slave 2). •
Ensure that the connections AC1 and
AC2 are not bridged.

10.5.7 System Category (7xx)


No. Name Level Cause Corrective measures
F 702 RsDsp 5 Reset of the signal processor in the • Contact the SMA Service Line.
device at L1 has been identified.
F 703 TimeOut 2 Internal timing fault: Time for
performing a particular task has been
exceeded.
F 704 Calib 4 Invalid Calibration in DSP: The
system has not calibrated.
W 705 TimeOut 1 Watchdog DSP: The watchdog of • Contact the SMA Service Line if
the signal processor of the master has required.
tripped.
F 706 TimeOut 4 Frequent watchdog fault: The • Contact the SMA Service Line.
watchdog of the signal processor of
the master has tripped several times.
W 707 TimeOutSlv1 1 Watchdog meter on slave 1 elapsed
(watchdog tripped several times in
succession).
W 708 TimeOutSlv2 1 Watchdog meter on Slave 2 elapsed
(watchdog tripped several times in
succession).
F 710 AutoStrCnt 4 Autostart meter elapsed in the device •
at L1 (several autostarts in Read off the pending and logged
succession). warnings and errors and eliminate
the causes.
• Ensure that the parameter 250.01
AutoStr is set to 3.
W 713 TimeOut 1 Watchdog OCU: The watchdog of • Contact the SMA Service Line if
the operation control unit has tripped. required.
W 715 MMCUpdFail 1 Impaired CAN communication • Copy the update file to an SD
with the device at L2: The update memory card with maximum 2 GB
cannot be carried out. The type or and with FAT-16 format.
format of the SD memory card is not
supported.

Operating Manual SI30M-44M-60H-80H-BE-en-32 63


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 716 VBATMIN 2 Measuring range of battery • Disconnect the DC loads and
voltage exceeded in device at L1: charge the battery.
Battery voltage at the master is below The usable battery capacity may be too
the permissible measurement range. small, e.g., due to aging. If a load with
W 717 VBATMINSL1 1 Measuring range of battery high power connects, the battery
voltage exceeded in device at L2: voltage collapses.
Battery voltage at Slave 1 is below •
the permissible measurement range.
If DC loads are installed in the
W 718 VBATMINSL2 1 Measuring range of battery system, install load shedding for
voltage exceeded in device at L3: DC loads.
Battery voltage at Slave 2 is below •
the permissible measurement range.
Ensure that all battery cells are
functional.
F 720 InvTmpSns 4 Short circuit or cable break on the • Contact the SMA Service Line.
temperature sensor of the transformer
L1 (Master).
F 721 InvTmpSns 4 Short circuit or cable break on the
temperature sensor of the inverter
bridge L1 (Master).
W 722 BatTmpSnsShort 1 Short circuit on battery temperature •
sensor Ensure that the battery temperature
W 723 BatTmpSnsOpn 1 Cable break on battery temperature sensor is correctly connected
sensor (see the Sunny Island inverter
installation manual).
• Contact the SMA Service Line.
W 724 AutoStrCntSlv1 1 Autostart meter elapsed in the •
device at L2: Maximum number of Read off the pending and logged
autostarts for slave 1 has been warnings and errors and eliminate
reached. the causes.
W 725 AutoStrCntSlv2 1 Autostart meter elapsed in the • Ensure that the parameter 250.01
device at L3: Maximum number of AutoStr is set to 3.
autostarts for slave 2 has been
reached.
F 731 ClstConfig 4 Error in the cluster configuration •
Change the addresses of the
slaves in the cluster
(see Section 10.8, page 83)
F 733 MstrLoss 4 No message from Master •
(only Slave): Communication with Ensure that undamaged CAT5e
the Master is interrupted. cables are used for communication
W 734 Slv1Loss 1 No message from Master and that the cables are plugged in
(only Slave): Communication from correctly.
the Master to Slave 1 is interrupted. •
W 735 Slv2Loss 1 No message from Master Ensure that the communication bus
(only Slave): Communication from is equipped with a terminator at
the Master to Slave 2 is interrupted. both ends.

64 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 737 BootUpdateFail 4 Updating of the boot loader failed. • Contact the SMA Service Line.
W 738 GnSynLoss 1 Synchronization with the generator • Ensure that the generator can be
not successful. started. The fuel level may be too
low.

Ensure that a constant and stable
voltage is present at connection
AC2.

Ensure that the thresholds for the
generator voltage are correctly
configured.
F 739 SPICom 3 No message from the device at L1: • Contact the SMA Service Line.
Internal device communication of the
master is disturbed.
W 740 SPIComSlv1 1 No message from the device at L2:
Internal device communication of
Slave 1 is disturbed.
W 741 SPIComSlv2 1 No message from the device at L3:
Internal device communication of
Slave 2 is disturbed.
F 743 CANCom 3 Internal CAN communication is •
missing in the device at L1 (Master). Ensure that the terminators in the
W 744 CANComSlv1 1 Internal CAN communication is communication bus are attached.
missing in the device at L2 (Slave 1). •
W 745 CANComSlv2 1 Internal CAN communication is Ensure that undamaged CAT5e
missing in the device at L3 (Slave 2). cables are used for communication
and that the cables are plugged in
correctly.
• Contact the SMA Service Line.
W 747 InvTmpSnsSlv1 1 Short circuit or cable break on the • Contact the SMA Service Line.
temperature sensor of the transformer
L2 (Slave 1).
W 748 InvTmpSnsSlv2 1 Short circuit or cable break on the
temperature sensor of the transformer
L3 (Slave 2).
W 750 InvTmpSnsSlv1 1 Short circuit or cable break on the
temperature sensor of the inverter
bridge L2 (Slave 1).
W 751 InvTmpSnsSlv2 1 Short circuit or cable break on the
temperature sensor of the inverter
bridge L3 (Slave 2).

Operating Manual SI30M-44M-60H-80H-BE-en-32 65


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 753 DateInvalid 1 Invalid date: System time is invalid. • Select the parameter 250.02 Dt
and set the date. Select the
parameter 250.03 Tm and set the
time.
F 754 BoxCom 2 Communication with MC BOX is •
interrupted: Communication with Ensure that undamaged CAT5e
Multicluster Box is interrupted. cables are used for communication
and that the cables are plugged in
correctly.

Ensure that the communication bus
is equipped with a terminator at
both ends.
W 755 LoBatMod1 1 Battery saver mode 1 is activated. • Disconnect the loads, start the
generator, start the Sunny Island
W 756 LoBatMod2 1 Battery saver mode 2 is activated.
and charge the battery.
W 757 LoBatMod3 1 Battery saver mode 3 is activated.
F 758 McNoVtg 2 Voltage of the main cluster cannot be • Ensure that all circuit breakers of
measured at L1 (Master). the Sunny Island inverters in the
Multicluster Box are closed.
W 759 McNoVtgSv1 1 Voltage of the main cluster cannot be
measured at L2 (Slave 1). •
W 760 McNoVtgSlv2 1 Voltage of the main cluster cannot be Ensure that the cabling at
measured at L3 (Slave 2). connection AC1 is correctly
installed.
W 778 DSPNoSlv1 1 CAN communication with slave 1 is •
faulty. Ensure that undamaged CAT5e
W 779 DSPNoSlv2 1 CAN communication with slave 2 is cables are used for communication
faulty. and that the cables are plugged in
correctly.

Ensure that the communication bus
is equipped with a terminator at
both ends.
F 781 SlvError 4 Error at a slave in the main cluster •
causing system shutdown. Read off the pending and logged
warnings and errors and eliminate
the causes.
F 782 AIVtgMonFail 4 Non-compliance of monitoring times • Contact the SMA Service Line.
(islanding detection) and external
grid voltage in the device at L1
(Master)

66 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


F 783 CANCom 2 Device-internal sync pulse in the •
device at L1 (Master) is missing. Ensure that undamaged CAT5e
W 784 CANComSlv1 1 Device-internal sync pulse in the cables are used for communication
device at L2 (Slave 1) is missing. and that the cables are plugged in
correctly.
W 785 CANComSlv2 1 Device-internal sync pulse in the
device at L3 (Slave 2) is missing. •
Ensure that the communication bus
is equipped with a terminator at
both ends.
F 787 VcoreFail 3 Processor voltage in the device at L1 • Contact the SMA Service Line.
(Master) is incorrect.
F 788 VcoreFailSlv1 3 Processor voltage in the device at L2
(Slave 1) is incorrect.
F 789 VcoreFailSlv2 3 Processor voltage in the device at L3
(Slave 2) is incorrect.
W 791 RsDspSlv1 1 Reset of the signal processor in the
device at L2 (Slave 1) has been
identified.
W 792 RsDspSlv2 1 Reset of the signal processor in the
device at L3 (Slave 2) has been
identified.
W 794 TimeOutDspSlv1 1 Timeout of the signal processor in the
device at L2 (Slave 1)
W 795 TimeOutDspSlv2 1 Timeout of the signal processor in the
device at L3 (Slave 2)
W 797 AiVtgMonFailSlv1 1 Non-compliance of monitoring times
(islanding detection) and external
grid voltage in the device at L2
(Slave 1)
W 798 AiVtgMonFailSlv2 1 Non-compliance of monitoring times
(islanding detection) and external
grid voltage in the device at L3
(Slave 2)

Operating Manual SI30M-44M-60H-80H-BE-en-32 67


10 Troubleshooting SMA Solar Technology AG

10.5.8 External Device and Component Category (8xx)


No. Name Level Cause Corrective measures
F 801 Box 4 Plausibility check on the • Contact the SMA Service Line.
contactors in the
Multicluster Box has failed.
W 805 BoxNoGn 1 Generator operation not •
possible Reset the off-grid system. For this,
disconnect all loads, AC sources,
generator and DC sources. Open the
load-break switch of the BatFuse. Wait ten
minutes and restart the off-grid system.
Wait until all AC sources are feeding into
the stand-alone grid and all loads are
connected before connecting the
generator.
• Contact the SMA Service Line.
F 806 BoxType 4 Box coding conflicts with •
software settings: Check whether the value of the parameter
Configuration of the 250.23 Box matches the
Sunny Island inverters does Multicluster Box. If the value does not
not match the Multicluster Box. match, restart the QCG (see the
Sunny Island inverter installation manual).
• Contact the SMA Service Line.
W 807 BoxGdVtg 1 Voltage of the external energy • Acknowledge the error
source is not within the valid (see Section 10.3, page 43).
thresholds for connection. • Contact the SMA Service Line.
F 809 BoxNoLod 4 Error Q10 contactor: • Reset the off-grid system. For this,
Load-shedding contactor Q10 disconnect the off-grid system and restart.
in the Multicluster Box is not The configuration may be incorrect.
functioning correctly.

Start the QCG and reconfigure
multicluster operation (see the
Sunny Island inverter installation manual).
• Contact the SMA Service Line.
F 810 Box15V 4 Error in the 15 V voltage • Contact the SMA Service Line.
supply of the MCBUBox:
15 V voltage supply in the
Multicluster Box is defective.
F 811 Box24V 4 Error in the 24 V voltage
supply of the MCBUBox:
24 V voltage supply in the
Multicluster Box is defective.

68 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 815 BoxQ5 1 Error Q5 contactor: • Reset the off-grid system. For this,
Contactor Q5 in the disconnect the off-grid system and restart.
Multicluster Box is not The configuration may be incorrect.
functioning correctly.

F 816 BoxQ7 2 Error Q7 contactor:
Start the QCG and reconfigure
Contactor Q7 in the
multicluster operation (see the
Multicluster Box is not
Sunny Island inverter installation manual).
functioning correctly.
• Contact the SMA Service Line.
F 817 BoxQ9 4 Error Q9 contactor:
Contactor Q9 in the
Multicluster Box is not
functioning correctly.
F 818 BoxPhsFail 4 Box phase missing: One line • Ensure that all circuit breakers of the
conductor of a Sunny Island Sunny Island inverters in the
inverter is missing. Multicluster Box are closed.
• Reset the off-grid system. For this,
disconnect the off-grid system and restart.

Search for the missing line conductor and
eliminate the error. For this, with loads
connected, measure the AC voltage
between each line conductor and
between the line conductors and the
neutral conductors. If an AC voltage
deviates from the nominal voltage by
±10%, the corresponding line conductor
is missing.
W 824 BoxQ4Overload 1 Multicluster Box signals an • Contact the SMA Service Line.
error at contactor Q4.
F 830 BoxQ2NotOpen 2 Error: Contactor Q2 does not
open
F 831 BoxQ2NotClose Error: Contactor Q2 does not
close
F 832 BoxQ9NotOpen Error: Contactor Q9 does not
open
F 833 BoxQ9NotClose Error: Contactor Q9 does not
close
W 840 eHZ1ComFail 1 Faulty communication with the • Ensure that the optical probe is correctly
PV production meter mounted.
W 841 eHZ2ComFail 1 Faulty communication with the • Ensure that the optical probe is correctly
feed-in meter and purchased connected.
electricity meter
W 842 ComBoxFail 1 Communication between •
device and SBUKomBox Ensure that the data cables are correctly
(Meter Box) is faulty installed.

Operating Manual SI30M-44M-60H-80H-BE-en-32 69


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 843 ComBoxWD 1 The SBUKomBox (Meter Box) • Contact the SMA Service Line.
watchdog has triggered.
W 844 eHZ1ProtFail 1 Unsupported protocol
detected on eHZ 1 (feed-in &
consumption meters)
W 845 eHZ2ProtFail 1 Unsupported protocol
detected on eHZ 2 (PV
production meter)
W 846 eHzInFail 1 Reading heads of the eHZ • Swap the optical probe connections.
interchanged in the input of the
SBUKomBox (Meter Box).
W 847 ComHMFaill 1 CAN communication with •
energy meter is faulty. Ensure that the data cables are correctly
installed.
• Ensure that the parameter
250.06 ComBaud is set to 115k Bd.
W 848 PhsMtrComFail 1 Faulty communication •
between the Sunny Island and Ensure that the data cables are correctly
the SMA Energy Meter: installed.
Electric power per line
conductor is not available. •
Ensure that the current firmware version of
the SMA Speedwire data module is
installed.
W 851 Sic1BatShort 1 Battery reversely •
connected or short circuit Ensure that the battery is correctly
on PV charge controller 1: connected to the DC connection of the
Connection of the battery to Sunny Island Charger charge controller.
the Sunny Island Charger 1 is
reverse-poled or there is a •
short circuit. Disconnect the PV array from the charge
controller and restart the system. This will
ensure that the PV array is not
short-circuited.
W 852 Sic1BatVtgHi 1 PV charge controller 1 •
battery overvoltage: Battery Ensure that the configuration of the
voltage at the Sunny Island Sunny Island Charger charge controller
Charger 1 is too high. with the DIP switches is correct.

Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 853 Sic1PvVtgHi 1 PV charge controller 1 PV • Contact the SMA Service Line if required.
generator overvoltage: PV
voltage at the Sunny Island
Charger 1 is too high.

70 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 854 Sic1PvVtgLo 1 No PV voltage or short • Contact the SMA Service Line if required.
circuit on PV charge
controller 1: No PV voltage
at the Sunny Island Charger 1
or there is a short circuit.
W 855 Sic1TmpLo 1 Sensor error (or •
undertemperature) for the Set the Sunny Island Charger charge
PV charge controller 1 controller to the operating mode "SMA
charger temperature: operation" (see the Sunny Island Charger
Sunny Island Charger 1 charge controller installation manual).
reports battery
undertemperature.
W 856 Sic1TmpHI 1 PV charge controller 1 •
device overtemperature: Set the Sunny Island Charger charge
Sunny Island Charger 1 controller to the operating mode "SMA
reports battery operation" (see the Sunny Island Charger
overtemperature. charge controller installation manual).
W 857 Sic1ComLoss 1 No communication with DC •
charger for more than 24 h Ensure that undamaged CAT5e cables
– PV charge controller 1: are used for communication and that the
Last communication with the cables are plugged in correctly.
Sunny Island Charger 1 was
more than 24 hours ago. •
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.

Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
W 861 Sic2BatShort 1 Battery reversely •
connected or short circuit Ensure that the battery is correctly
on PV charge controller 2: connected to the DC connection of the
Connection of the battery to Sunny Island Charger charge controller.
the Sunny Island Charger 2 is
reverse-poled or there is a •
short circuit. Disconnect the PV array from the charge
controller and restart the system. This will
ensure that the PV array is not
short-circuited.
W 862 Sic2BatVtgHi 1 PV charge controller 2 •
battery overvoltage: Battery Ensure that the configuration of the
voltage at the Sunny Island Sunny Island Charger charge controller
Charger 2 is too high. with the DIP switches is correct.

Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.

Operating Manual SI30M-44M-60H-80H-BE-en-32 71


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 863 Sic2PvVtgHi 1 PV charge controller 1 PV • Contact the SMA Service Line if required.
generator overvoltage: PV
voltage at the Sunny Island
Charger 2 is too high.
W 864 Sic2PvVtgLo 1 No PV voltage or short
circuit on PV charge
controller 2: No PV voltage
at the Sunny Island Charger 2
or there is a short circuit.
W 865 Sic2TmpLo 1 Sensor error (or •
undertemperature) for the Set the Sunny Island Charger charge
PV charge controller 2 controller to the operating mode "SMA
charger temperature: operation" (see the Sunny Island Charger
Sunny Island Charger 2 charge controller installation manual).
reports battery
undertemperature.
W 866 Sic2TmpHI 1 PV charge controller 2 •
device overtemperature: Set the Sunny Island Charger charge
Sunny Island Charger 2 controller to the operating mode "SMA
reports battery operation" (see the Sunny Island Charger
overtemperature. charge controller installation manual).
W 867 Sic2ComLoss 1 No communication with DC •
charger for more than 24 h Ensure that undamaged CAT5e cables
– PV charge controller 2: are used for communication and that the
Last communication with the cables are plugged in correctly.
Sunny Island Charger 2 was
more than 24 hours ago. •
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.

Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
W 871 Sic2BatShort 1 Battery reversely •
connected or short circuit Ensure that the battery is correctly
on PV charge controller 3: connected to the DC connection of the
Connection of the battery to Sunny Island Charger charge controller.
the Sunny Island Charger 2 is
reverse-poled or there is a •
short circuit. Disconnect the PV array from the charge
controller and restart the system. This will
ensure that the PV array is not
short-circuited.

72 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 872 Sic3BatVtgHi 1 PV charge controller 3 •
battery overvoltage: Battery Ensure that the configuration of the
voltage at the Sunny Island Sunny Island Charger charge controller
Charger 3 is too high. with the DIP switches is correct.

Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 873 Sic3PvVtgHi 1 PV charge controller 3 PV • Contact the SMA Service Line if required.
generator overvoltage: PV
voltage at the Sunny Island
Charger 3 is too high.
W 874 Sic3PvVtgLo 1 No PV voltage or short
circuit on PV charge
controller 3: No PV voltage
at the Sunny Island Charger 3
or there is a short circuit.
W 875 Sic3TmpLo 1 Sensor error (or •
undertemperature) for the Set the Sunny Island Charger charge
PV charge controller 3 controller to the operating mode "SMA
charger temperature: operation" (see the Sunny Island Charger
Sunny Island Charger 3 charge controller installation manual).
reports battery
undertemperature.
W 876 Sic3TmpHI 1 PV charge controller 3 •
device overtemperature: Set the Sunny Island Charger charge
Sunny Island Charger 3 controller to the operating mode "SMA
reports battery operation" (see the Sunny Island Charger
overtemperature. charge controller installation manual).
W 877 Sic3ComLoss 1 No communication with DC •
charger for more than 24 h Ensure that undamaged CAT5e cables
– PV charge controller 1: are used for communication and that the
Last communication with the cables are plugged in correctly.
charge controller 3 was more
than 24 hours ago. •
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.

Ensure that the communication interfaces
are correctly inserted in the Sunny Island.

Operating Manual SI30M-44M-60H-80H-BE-en-32 73


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


W 881 Sic4BatShort 1 Battery reversely •
connected or short circuit Ensure that the battery is correctly
on PV charge controller 4: connected to the DC connection of the
Connection of the battery to Sunny Island Charger charge controller.
the Sunny Island Charger 4 is
reverse-poled or there is a •
short circuit. Disconnect the PV array from the charge
controller and restart the system. This will
ensure that the PV array is not
short-circuited.
W 882 Sic4BatVtgHi 1 PV charge controller 4 •
battery overvoltage: Battery Ensure that the configuration of the
voltage at the Sunny Island Sunny Island Charger charge controller
Charger 4 is too high. with the DIP switches is correct.

Ensure that all DC sources and DC loads
are correctly configured and connected.
• Reset the system. For this, switch off the
system, wait ten minutes and restart.
W 883 Sic4PvVtgHi 1 PV charge controller 4 PV • Contact the SMA Service Line if required.
generator overvoltage: PV
voltage at the Sunny Island
Charger 4 is too high.
W 884 Sic4PvVtgLo 1 No PV voltage or short
circuit on PV charge
controller 4: No PV voltage
at the Sunny Island Charger 4
or there is a short circuit.
W 885 Sic4TmpLo 1 Sensor error (or •
undertemperature) for the Set the Sunny Island Charger charge
PV charge controller 4 controller to the operating mode "SMA
charger temperature: operation" (see the Sunny Island Charger
Sunny Island Charger 4 charge controller installation manual).
reports battery
undertemperature.
W 886 Sic4TmpHI 1 PV charge controller 4 •
device overtemperature: Set the Sunny Island Charger charge
Sunny Island Charger 4 controller to the operating mode "SMA
reports battery operation" (see the Sunny Island Charger
overtemperature. charge controller installation manual).

74 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 887 Sic4ComLoss 1 No communication with DC •
charger for more than 24 h Ensure that undamaged CAT5e cables
– PV charge controller 4: are used for communication and that the
Last communication with the cables are plugged in correctly.
Sunny Island Charger 4 was
more than 24 hours ago. •
Ensure that the configuration of the
Sunny Island Charger charge controller
with the DIP switches is correct.

Ensure that the communication interfaces
are correctly inserted in the Sunny Island.
W 890 BoxMeas 2 Voltage or current •
measurement interferences at Ensure that the control and measuring
external measurement point of cable between the Multicluster Box and
the AC sub-distribution the corresponding Sunny Island of the
(Multicluster Box) at line main cluster is correctly inserted. When
conductor L1 (Master) doing so, observe the correct sequence of
W 891 BoxMeasSlv1 2 Voltage or current the Multicluster Box connections to the
measurement interferences at Sunny Island inverters (see the
external measurement point of Sunny Island inverter installation manual
the AC sub-distribution and the Multicluster Box documentation).
(Multicluster Box) at line
conductor L2 (Slave 1)
W 892 BoxMeasSlv2 2 Voltage or current
measurement interferences at
external measurement point of
the AC sub-distribution
(Multicluster Box) at line
conductor L3 (Slave 2)

10.5.9 General Category (9xx)


No. Name Level Cause Corrective measures
F 905 CalFail 4 The calibration data cannot be read or • Contact the SMA Service Line
was not completely transferred from the (see Section 16, page 146).
device at L1 (Master).
F 906 CalFailSlv1 4 The calibration data cannot be read or
was not completely transferred from the
device at L2 (Slave 1).
F 907 CalFailSlv2 4 The calibration data cannot be read or
was not completely transferred from the
device at L3 (Slave 2).
W 915 Timeout 1 Watchdog OCU: An error has
occurred in the program run sequence.

Operating Manual SI30M-44M-60H-80H-BE-en-32 75


10 Troubleshooting SMA Solar Technology AG

No. Name Level Cause Corrective measures


F 920 XA01General 3 Error message via SiCom: General • Eliminating the error cause in
the external battery
F 921 XA02DcHiVolt 3 Error message via SiCom: Battery
management system (see
overvoltage
battery manufacturer's
F 922 XA03DcLoVolt 3 Error message via SiCom: Battery documentation).
undervoltage
F 923 XA04DcHiTmp 3 Error message via SiCom: Battery
overtemperature
F 924 XA05DcLoTmp 3 Error message via SiCom: Battery
undertemperature
F 925 XA06DcHiTmpC 3 Error message via SiCom: Battery
overtemperature in charge mode
F 926 XA07DcLoTmpC 3 Error message via SiCom: battery
undertemperature in charge mode
F 927 XA08DcHiCur 3 Error message via SiCom: battery
charging current too high
F 928 XA09DcHiChgCur 3 Error message via SiCom: Battery
charging current in charge mode too
high
F 929 XA10Contact 3 Error message via SiCom: Error in the
battery
F 930 XA11Short 3 Error message via SiCom: Short circuit
F 931 XA12Bms 3 Error message via SiCom: Internal error
in battery management
F 932 XA13CellBal 3 Error message via SiCom: Different
state of charge of the battery cells
F 935 XA16Generator 3 Error message via SiCom: Error in the
generator
W 936 XW01General 1 Warning via SiCom: General
W 937 XW02DcHiVolt 1 Warning via SiCom: Battery
overvoltage
W 938 XW03DcLoVolt 1 Warning via SiCom: Battery
undervoltage
W 939 XW04DcHiTmp 1 Warning via SiCom: Battery
overtemperature
W 940 XW05DcLoTmp 1 Warning via SiCom: Battery
undertemperature
W 941 XW06DcHiTmpC 1 Warning via SiCom: Battery
overtemperature in charge mode
W 942 XA07DcLoTmpC 1 Warning via SiCom: Battery
undertemperature in charge mode
W 943 XW08DcHiCur 1 Warning via SiCom: battery charging
current too high

76 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

No. Name Level Cause Corrective measures


W 944 XW09DcHiChgCur 1 Warning via SiCom: battery charging • Eliminating the error cause in
current in charge mode too high the external battery
management system (see
W 945 XW10Contact 1 Warning via SiCom: error in the battery
battery manufacturer's
W 946 XW11Short 1 Warning via SiCom: short circuit documentation).
W 947 XW12Bms 1 Warning via SiCom: internal error in
battery management
W 948 XW13CellBal 1 Warning via SiCom: different state of
charge of the battery cells
W 951 XW16Generator 1 Warning via SiCom: Error in the
generator
F 952 ExtBMSTimeout 3 The timeout monitoring system of the • Ensure that the data cable of
battery management has triggered the external lithium-ion battery
is connected correctly.
W 953 WrnExtBMSTmOut 1 The timeout monitoring system of the
battery management has triggered • Ensure that the terminators of
the CAN bus in the
communication bus are
attached.

10.6 Frequently Asked Questions (FAQ)


10.6.1 Questions Regarding the Sunny Island
Why is the Sunny Island not switching off even though I have opened the load-break switch of the
BatFuse?
The Sunny Island may still be supplied from the AC side.

Switch off all AC sources and disconnect them from the Sunny Island.

Why is the Sunny Island not switching to energy-saving mode?


Another function might have a higher priority than energy saving mode, e.g., equalization charge or full charge.

Why can the Sunny Island can no longer be started after automatic disconnection in battery
protection mode?

Charge the battery only when the Sunny Island cannot be switched on (see Section 10.7 "Charging the Battery
After Automatic Shutdown in Off-Grid Systems", page 81).
• Switch off all loads.
• If there is a generator in the system, start the generator manually. When doing so, observe the warm-up time of
the generator. Five minutes without charge current can result in disconnection of the Sunny Island inverter.
• If sufficient power is available from the generator or the AC sources in the stand-alone grid, e.g., sufficient solar
irradiation for PV inverters, switch the Sunny Island on. AC sources in the stand-alone grid can start feeding in
electric current only once the Sunny Island has been started and is in operation.

Operating Manual SI30M-44M-60H-80H-BE-en-32 77


10 Troubleshooting SMA Solar Technology AG

10.6.2 Questions Regarding the Sunny Remote Control


The display of the Sunny Remote Control is dark and nothing is displayed – why?
The Sunny Island might not be switched on.
• Switch the Sunny Island on (see Section 4.1, page 18).
✖ Why is the Sunny Island not switching on?
The fuse in the BatFuse may be defective.

Ensure that the fuse in the BatFuse is not defective.
The Sunny Remote Control might not be connected to the Sunny Island.

Ensure that the Sunny Remote Control is connected to the Sunny Island.
The RJ45 data cable may be damaged.

Replace the RJ45 data cable between the Sunny Remote Control and the Sunny Island.

Why can parameters not be changed?


It is possible that the parameter is displayed only in expert mode.
• Switch to expert mode on the Sunny Remote Control (see Section 5.4.1, page 29).
It might be possible to change the parameter only in standby mode or in the QCG.
• Observe the messages in the display (see Section 5.4.6 "Setting the Parameters", page 31).
The parameter may be hidden as it is not required in the configuration set for the system.
• Ensure that the configuration does not deactivate any functions which are required.

Why is "MMC/SD operation failed!" shown on the display?


An action with the SD memory card has failed.
• Use a computer to ensure that the SD memory card is free of errors.

Ensure that the data cable between the Sunny Remote Control and the Sunny Island is undamaged and that the
plugs are firmly inserted into the pin connectors.

Why is the display showing "WRONG FILE SYSTEM"?


The SD memory card is not formatted with the FAT-16 or FAT-32 file system.

10.6.3 Questions Regarding the Battery


What happens if a battery is defective?

Remove the defective battery cell from the battery system. This reduces the rated voltage of the battery by the
voltage of the battery cell.

In the QCG, set the current rated voltage of the battery under New Battery (see Section 11.8 "Replacing the
Battery", page 87).

78 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

Why is the battery state of charge not 100% after completion of full charge?
The power requirements of the loads might have been so high before completion of the full charge that the battery
could not be charged to 100 percent.
• If necessary, select the parameter 222.03 AptTmFul and set to a longer time period.

Why is the battery discharging even though the generator is running?


The Sunny Island may not have connected to the generator.
• Eliminate the cause (see Section 10.6.4 "Questions Regarding the Generator", page 79).
The power of the loads might exceed the power of the generator.

What do you need to do after replacing a battery current sensor?



Calibrate the battery current sensor (see the Commissioning section in the Sunny Island inverter installation
manual).

10.6.4 Questions Regarding the Generator


Why is the Sunny Island not connecting to the running generator?
A high output power of the Sunny Island inverter when the battery state of charge is low may lead to the
Sunny Island not being able to raise the AC voltage in the stand-alone grid to the AC voltage of the generator.
The Sunny Island cancels the synchronization.
• To charge the battery, reduce the power of the loads.
The generator voltage might not be within the thresholds for voltage and frequency.
• Check whether the symbol " " is displayed permanently in standard mode on the Sunny Remote Control.
If the " " symbol is not displayed, ensure that the fuse is not defective or the circuit breaker is activated.
If the " " symbol is not displayed permanently, the generator voltage is sporadically outside the thresholds.

Set the thresholds for voltage and frequency of the generator voltage (see the Sunny Island inverter
installation manual).
If the " " symbol is displayed permanently, the Sunny Island is in the warm-up period or is blocked for
connection. Tip: Check whether the Sunny Remote Control displays the " " warning symbol in standard mode.

Why does the Sunny Island connect to the generator for only a short time?
The generator may be overloaded.
• Select the parameter 234.03 GnCurNom and set it to 75% of the rated current of the generator.
• If possible, reduce the power of the loads.
The maximum permissible generator voltage may be set too low.

Select the parameter 234.02 GnVtgMax and set to the maximum generator voltage.
The minimum frequency for the generator voltage may be set too high.

Select the parameter 234.05 GnFrqMin and set to the minimum frequency of the generator voltage.
The permitted time 234.14 GnRvTm for reverse power might have been exceeded.
• Check whether warning W401 is registered in the menu 420# Error history. Tip: If a warning was registered,
the warning symbol " " is shown in the standard mode of the Sunny Remote Control.
• Select the 540.02 GnAck parameter and set to Ackn. This acknowledges the generator error.

Operating Manual SI30M-44M-60H-80H-BE-en-32 79


10 Troubleshooting SMA Solar Technology AG

The Sunny Island does not reconnect to the generator after disconnection from the generator due
to non-compliance with the thresholds for voltage and frequency – why?
The Sunny Island is switched with a hysteresis, i.e., the thresholds for connection do not correspond to the thresholds
for disconnection.
• To unload the generator, disconnect unnecessary loads.
• Wait until the voltage and frequency have reached the nominal values.

10.6.5 Questions Regarding Multicluster Systems


Why do extension clusters remain in standby mode even though the main cluster is in inverter
mode?
The data cable between the masters of the individual clusters might not be connected. The master of the main cluster
cannot forward the "Start" command to the masters of the extension clusters.

Why is the multicluster system not supplying full power?


An extension cluster or individual Sunny Island inverters of an extension cluster might have failed.

Why are high levels of energy being transferred between the clusters in the multicluster system?
The battery capacities might differ temporarily. The off-grid system equalizes different battery states of charge
automatically.
The nominal frequencies and nominal voltages may be defined differently.
• Set the frequencies and voltages in the 210# Inverter Settings menu to the same values for all masters.
The battery capacities might differ significantly.

Distribute the battery capacities to the clusters as evenly as possible.
Individual battery cells of a battery might have failed.

Disconnect defective battery cells and set the new rated voltage and capacity (see Section 11.8 "Replacing the
Battery", page 87).

80 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.7 Charging the Battery After Automatic Shutdown in Off-Grid Systems

When a battery undergoes deep discharge, the Sunny Island shuts down automatically and you cannot restart the
Sunny Island. In order to start the Sunny Island again after an automatic shutdown, you must charge the battery in
emergency charge mode.
In emergency charge mode, the Sunny Island does not form a separate stand-alone grid, and you can charge the battery
using a generator. Battery management is active in emergency charge mode and the Sunny Island charges the battery
in accordance with the parameter settings. In standby mode or in the QCG, you can adjust the parameters for the battery,
e.g., the battery nominal voltage, if a battery cell fails.

Restricted management functions in emergency charge mode


In emergency charge mode, the generator management is not active. The limits for voltage, current and frequency
are not monitored. Set the maximum current consumption of the Sunny Island inverter for charging the battery in
emergency charge mode. The Sunny Island does not record additional strain on the generator due to loads.
Requirement:
☐ The Sunny Remote Control must be connected to the master.
☐ The system must be an off-grid system.
☐ Lead-acid batteries must be connected.
Procedure:
• Connect the generator to connection AC1.
• Charge the battery.
• Disconnect the generator from connection AC1.
• Start the off-grid system.

Connecting the generator to connection AC1


1. :$51,1*
Danger to life from electric shock due to high voltages
High voltages are present on the AC power cables and on the control cables. Touching live parts can result in death
or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section 9, page 41).
2. If a generator is installed permanently in the off-grid system, bridge the connections AC1 and AC2.
3. If a mobile generator is used, connect the generator to connection AC1 (see the Sunny Island inverter installation
manual).
4. Close the Sunny Island (see Commissioning section in the Sunny Island inverter installation manual).

Charging the battery


1. Switch off all loads.
2. Connect or close all circuit breakers and fuse switch-disconnectors for energy sources.
3. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).
4. Start the generator.
5. Switch the Sunny Island on (see Section 4.1, page 18).

Operating Manual SI30M-44M-60H-80H-BE-en-32 81


10 Troubleshooting SMA Solar Technology AG

6. If the Sunny Remote Control displays <Init System> , press and hold the button.
☑ The Sunny Remote Control displays the QCG.

7. Select the menu Emerg Charge and press the button.

8. Confirm with Y.
☑ The Sunny Remote Control shows the ExtCurMax parameter.

9. Set the AC current of the connected generator and press the button.
10. Confirm the AC current with Y.
11. Turn the button to the right and confirm the message
Emerg.Confirm Charg Mode Start?.

Interrupting the emergency charge mode


You can interrupt the emergency charge mode, e.g., to add diesel to a generator.
• Press and hold the button.
☑ Emergency charge mode is stopped.
• Press and hold the button.
☑ Emergency charge mode is in operation.

Disconnecting the generator from connection AC1


1. Switch the Sunny Island off (see Section 4.4, page 19).
2. Ensure that the generator is stopped permanently.
3. :$51,1*
Danger to life from electric shock due to high voltages
High voltages are present on the AC power cables and on the control cables. Touching live parts can result in death
or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section 9, page 41).
4. If the connections AC1 and AC2 are bridged, remove the bridge.
5. If a mobile generator is used, disconnect the generator from connection AC1.
6. Close the Sunny Island (see Commissioning section in the Sunny Island inverter installation manual).

Starting the off-grid system


1. Connect or close all circuit breakers and fuse-switch-disconnectors.
2. Start the off-grid system (see Section 4.2, page 18).

82 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 10 Troubleshooting

10.8 Changing Slave Addresses in a Cluster

If you want to change slave addresses (e.g., after replacing a Sunny Island inverter), you can assign the slaves a new
address using the QCG. Only the address is changed; all other configurations remain as they were, e.g., assignment of
the clusters in a multicluster system. When replacing a master, you must reconfigure the cluster (see the quick reference
guide for the relevant system for configuring single-cluster operation or multicluster operation).
Requirements:
☐ All Sunny Island inverters must be switched off.
☐ A Sunny Remote Control is connected to the master only.
Procedure:
1. Switch the slave on.
2. Switch the master on.
3. When the Sunny Remote Control shows <Init System>, press and hold the button on the Sunny Remote Control.
☑ An acoustic signal sounds three times and the QCG starts.
4. Select the NewClstCfg menu on the Sunny Remote Control and confirm with Y.
5. Select number of line conductors in the system:
• For a single-phase system, set 1Phs and press the button.
• For a three-phase system, set 3Phs and press the button.
6. Confirm the question Setup new cluster ? with Y.
7. Wait until the inverter LED of slave 1 is flashing and the Sunny Remote Control shows the message To identify
Slave1 press Tss on the Slv.
8. Press the start-stop button on slave 1.
☑ The QCG configures slave 1.

9. To configure slave 2, wait until the inverter LED of slave 2 is flashing and the Sunny Remote Control shows the
message To identify Slave2 press Tss on the Slv.
10. Press the start-stop button on slave 2.
☑ An acoustic signal sounds and the QCG configures slave 2.
11. Press the button on the Sunny Remote Control. This closes the QCG.
☑ The Sunny Remote Control switches from display mode to standard mode.

Operating Manual SI30M-44M-60H-80H-BE-en-32 83


11 Cleaning and Maintenance SMA Solar Technology AG

11 Cleaning and Maintenance


11.1 Cleaning and Checking the Sunny Island Inverter Enclosure
• If the enclosure is heavily soiled, use a soft brush to remove the soiling.
• If the enclosure is dusty, remove the dust with a dry soft cloth. Do not use any solvents, abrasives or corrosive liquids.

11.2 Cleaning the Sunny Remote Control


• Clean the Sunny Remote Control with a dry soft cloth. Do not use any solvents, abrasives or corrosive liquids.

11.3 Performing a Manual Equalization Charge in the Off-Grid System


After extended periods without charging (e.g., systems operated seasonally), perform a manual equalization charge at
the end or start of the season.
Requirement:
☐ The Sunny Remote Control must be in standard mode or user mode.
Procedure:
1. Select the Battery display page on the Sunny Remote Control and press the button (see Section 5.3.1 "Displaying
Parameters and Operating and Setting the System", page 26).
2. Select the parameter Equalize and set to Start.

11.4 Checking the Function


• For the first six months after installation of new systems, check every week whether error messages have been
logged. This will reveal any hidden errors in the installation or configuration:
• Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
• Select the menu 420# Error history and check whether any error messages have been logged.
• If error messages have been logged, eliminate the cause (see Section 10 "Troubleshooting", page 42).
• Check every six months whether error messages have been logged:
• Switch to installer mode on the Sunny Remote Control (see Section 5.4.1, page 29).
• Select the menu 420# Error history and check whether any error messages have been logged.
• If error messages have been logged, eliminate the cause (see Section 10.5 "Logged Warning Messages and
Error Messages", page 48).

84 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 11 Cleaning and Maintenance

11.5 Checking the Connections

1. :$51,1*
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched, which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section 9, page 41).
2. Ensure that the cables on the DC+ and DC‒ connections are securely fastened (torque: 12 Nm).
3. Ensure that the connections are free of corrosion.
4. Ensure that the cables in the AC1 and AC2 connections are securely fastened.
5. Close the Sunny Island (see the Sunny Island inverter installation manual).
6. Switch on all load-break switches and circuit breakers.

11.6 Checking and Maintaining the Battery

:$51,1*
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Do not throw batteries into fire. Batteries may explode in fire.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.

:$51,1*
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.

Requirement:
☐ The Sunny Remote Control is in user mode.

Operating Manual SI30M-44M-60H-80H-BE-en-32 85


11 Cleaning and Maintenance SMA Solar Technology AG

Procedure:
1. Check whether the current state of the battery corresponds to the expected state:
• Select the Battery display page on the Sunny Remote Control.
• Select the parameter Cycle and compare the value with the expected nominal energy throughputs.
• Select the parameter Health (SOH) and compare with the expected usable battery capacity.
If the current state of the battery does not correspond to the expected state, carry out the following steps:
• Ensure that the requirements for the ambient temperature of the battery are met (see documentation of the battery
manufacturer).
• Check and optimize the battery management settings.
• If you cannot determine the cause for the deviation, contact the SMA Service Line.
2. Stop the system and switch off the Sunny Island (see Section 7, page 33).
3. Open the load-break switch of the BatFuse and secure against reconnection.
4. Check and maintain the battery (see documentation of the battery manufacturer).
5. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).
6. Start the system.

11.7 Cleaning the Fans

If the Sunny Remote Control shows the warning W137 Derate exceptionally often, one of the fans is probably defective
or blocked.
Procedure:
1. :$51,1*
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched, which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section 9, page 41).
2. Wait for the fans to stop rotating.
3. Check whether the fan guard is dusty or badly clogged.
If the fan guard is dusty, clean it with a vacuum cleaner or a soft brush.
If the fan guard is heavily soiled, remove it and clean it:
• Use a screwdriver to push the two locking tabs at the right-hand
edge of the fan guard to the right and remove them from the
retainer.

• Carefully remove the fan guard.


• Clean the fan guard with a soft brush, a paint brush, a cloth or compressed air.

86 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 11 Cleaning and Maintenance

4. Check whether the fan is soiled.


If the fan is soiled, remove the fan:
• If a fan guard is fitted, remove the fan guard (see step 3).
• Push the front locking tabs of the fan backwards and the rear
locking tabs of the fan forwards.

• Slowly remove the fan from the Sunny Island.


• Release and remove the fan plug.

5. /05*$&
Damage to the fan due to compressed air
• Clean the fan with a soft brush, a paint brush, or a damp cloth.
6. Insert the fan plug into the jack until it snaps into place.
7. Insert the fan into the Sunny Island until the fan audibly snaps into place.
8. Press the fan guard into the bracket until it audibly snaps into place.

11.8 Replacing the Battery

:$51,1*
Risk of injury due to short-circuit currents
Short-circuit currents in the battery can cause heat build-up and electric arcs. Burns or eye injuries due to flashes may
result.
• Remove watches, rings, and other metal objects.
• Use insulated tools.
• Do not place tools or metal parts on the battery.

Operating Manual SI30M-44M-60H-80H-BE-en-32 87


11 Cleaning and Maintenance SMA Solar Technology AG

:$51,1*
Danger to life due to incompatible lithium-ion battery
An incompatible lithium-ion battery can lead to a fire or an explosion. With incompatible lithium-ion batteries, it is not
ensured that battery management is intrinsically safe and will protect the battery.
• Verify that the battery complies with locally applicable standards and directives and is intrinsically safe.
• Ensure that the lithium-ion batteries are approved for use with the Sunny Island.
The list of lithium-ion batteries approved for the Sunny Island is updated regularly (see the Technical Information
"List of Approved Lithium-Ion Batteries" at www.SMA-Solar.com).
• If no lithium-ion batteries approved for the Sunny Island can be used, use lead-acid batteries.

:$51,1*
Chemical burns and poisoning due to battery electrolyte
If handled inappropriately, battery electrolyte can cause irritation to the eyes, respiratory system, and skin, and it can
be toxic. This may result in blindness and serious chemical burns.
• Protect the battery enclosure against destruction.
• Do not open or deform the battery.
• Do not throw batteries into fire. Batteries may explode in fire.
• Whenever working on the battery, wear suitable personal protective equipment such as rubber gloves, apron,
rubber boots, and goggles.
• Rinse acid splashes thoroughly with clear water and consult a doctor.
• Install, operate, maintain, and dispose of the battery according to the manufacturer's specifications.

/05*$&
Damage to the battery due to incorrect settings
The set battery parameters influence the charging behavior of the Sunny Island inverter. The battery can be damaged
by incorrect settings for the battery type, nominal voltage and capacity parameters.
• Ensure that the values recommended by the battery manufacturer are set (refer to the technical data for the battery
in the manufacturer documentation). Note that the battery charging behavior names used by
SMA Solar Technology AG and the battery manufacturer may, in some cases, differ in meaning (for the battery
charging behavior of the Sunny Island inverter, see technical information "Battery Management").
• Set the battery capacity for a ten-hour electric discharge (C10). The battery manufacturer specifies the battery
capacity in relation to discharge time.

Procedure:
1. Stop the system and switch off the Sunny Island (see Section 7, page 33).
2. Ensure that the battery is not grounded unintentionally.
If the battery is unintentionally grounded, identify the connection between the battery and ground potential and
remove the unintentional connection. This helps to prevent electric shock caused by malfunction of other system
devices.
3. Open the load-break switch of the BatFuse and secure against reconnection.
4. Remove the battery to be replaced (see battery manufacturer's instructions).
5. Mount and connect the new battery (see manuals of the battery manufacturer). The battery must comply with the
technical requirements of the Sunny Island inverter (refer to the Sunny Island inverter installation manual for technical
data of the DC connection).
6. Quickly connect the load-break switch of the BatFuse and close the BatFuse (see BatFuse installation manual).

88 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 11 Cleaning and Maintenance

7. Switch the Sunny Island on (see Section 4.1, page 18).


8. If the Sunny Remote Control displays <Init System> , press and hold the button until the Sunny Remote Control
displays the QCG.
9. Select the menu New Battery and press the button.
10. Confirm with Y.
11. Select the parameter BatTyp, set the battery type as follows and confirm with Y.
Value Explanation
VRLA Lead-acid battery with immobilized electrolyte in AGM (Absorbent Glass Mat Separator) or
gel
FLA Lead-acid battery with liquid electrolyte
LiIon_Ext-BMS Lithium-ion battery

12. Make the following settings for lead-acid batteries.


• Select the parameter BatVtgLst, set the battery voltage and confirm with Y.
• Select the parameter BatCpyNom, set the C10 capacity of the battery (see the Sunny Island inverter installation
manual for how to calculate the battery capacity) and confirm the battery capacity with Y.
13. Make the following settings for lithium-ion batteries.
• Select the parameter BatCpyNom, set the C10 capacity of the battery (see the Sunny Island inverter installation
manual for how to calculate the battery capacity) and confirm the battery capacity with Y.
14. Select the last page and confirm the question Setup New Battery with Y.

Operating Manual SI30M-44M-60H-80H-BE-en-32 89


12 Decommissioning SMA Solar Technology AG

12 Decommissioning
12.1 Disassembling the Sunny Island

1. :$51,1*
Danger to life from electric shock due to live voltage
High voltages are present inside the Sunny Island. When the enclosure lid is removed, live components can be
touched, which can result in death or serious injury due to electric shock.
• Disconnect the Sunny Island from voltage sources (see Section 9, page 41).
2. Remove all cables from the Sunny Island.
3. Close the Sunny Island.
4. Remove the ventilation grids laterally.

5. If the Sunny Island is protected against theft, loosen the security


screws.

6. Loosen the screws on both sides between the Sunny Island and the
wall mounting bracket using a hex key (AF 5).

90 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 12 Decommissioning

7. &$87,21
Risk of injury due to the heavy weight of the Sunny Island inverter
• Keep in mind the weight of the Sunny Island inverter.
• With the SI3.0M-11 and SI4.4M-11, remove the Sunny Island
vertically upwards from the wall mounting bracket. For this, use
the side recess grips. Keep the Sunny Island in a horizontal
position when moving it.

• With the SI6.0H-11 and SI8.0H-11, remove the Sunny Island


vertically upwards from the wall mounting bracket. For this,
use the side recess grips or a steel rod (diameter: maximum
30 mm). Keep the Sunny Island in a horizontal position when
moving it.

12.2 Packaging the Sunny Island


1. Remove the cable glands from the Sunny Island.
2. Pack the Sunny Island and the cable glands. For this, use the original packaging or packaging that is suitable for the
weight and dimensions of the Sunny Island inverter (for the technical data, see the Sunny Island installation manual).

12.3 Disposing of the Sunny Island


• Dispose of the Sunny Island in accordance with the locally applicable disposal regulations for electronic waste.

Operating Manual SI30M-44M-60H-80H-BE-en-32 91


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13 Parameters in Sunny Remote Control


13.1 Directory of the Parameters in User Mode
13.1.1 Inverter Category
Display page
Name Description Value Explanation
Tot.Power Total active power of the Sunny Island inverters ‒ ‒ ✓ ✓
in kW
This parameter is hidden in multicluster systems.
MC.Power Total active power of the multicluster system in kW ‒ ‒ ✖ ✓
This parameter is hidden in single systems and
single-cluster systems.
Timer mode Time-controlled inverter operation of the Sunny Island Enable Sunny Island is in ✖ ✓
in off-grid systems time-controlled inverter
operation.
Disable Time-controlled inverter
operation is disabled.

Setting pages
Name Description Value Explanation
Restart Initiate device restart Yes Initiate restart. ✖ ✓
No Do not initiate restart.
Str.Date Start date for time-controlled operation of the ‒ ‒ ✖ ✓
Sunny Island in dd.mm.yy
In time-controlled inverter operation, the Sunny Island
switches from standby mode to operation for the first
time on the start date.
Start time Start time for time-controlled inverter operation ‒ ‒ ✖ ✓
in hh:mm:ss
Run Time Run time for time-controlled inverter operation ‒ ‒ ✖ ✓
The Sunny Island switches to time-controlled inverter
operation from the start time for the configured run
time.
Repetition Repetition cycle for time-controlled operation Single Configures one-time ✖ ✓
operation on the start date.
Daily Configures daily operation
from the start date.
Weekly Configures weekly operation
from the start date.
The start date determines the
weekday.
Timed start Time-controlled operation Disable Disables time-controlled ✖ ✓
operation.
Enable Enables time-controlled
operation.

92 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

13.1.2 Battery Category


Display pages
Name Description Value Explanation
StateOfCharge Current battery state of charge in % ‒ ‒ ✓ ✓
Voltage Battery voltage in V ‒ ‒ ✓ ✓
PowerOut Current discharge power of the battery in kW ‒ If the value is positive, the ✓ ✓
battery is discharging. If the
value is negative, the battery
is charging.
Mode Active battery charging mode Boost Boost charge is enabled. ✓ ✓
Full Full charge is enabled.
Float Float charge is enabled.
Equalize Equalization charge is
enabled.
Silent The Sunny Island has
switched to energy-saving
mode.
Remain time Remaining absorption time of the current ‒ ‒ ✓ ✓
battery charge phase (hh:mm:ss)
Next equal Remaining time until next equalization charge ‒ ‒ ✓ ✓
in days
Health (SOH) Current battery capacity in relation to the ‒ ‒ ✓ ✓
rated capacity (SOH) as %
Cycle Number of nominal energy throughputs of the ‒ ‒ ✓ ✓
battery
A nominal energy throughput is the calculated
result of one full charge and discharge of the
battery.

Setting page
Name Description Value Explanation
Equalize Manual equalization charge Start Starts the equalization ✓ ✓
charge.
Stop Stops the equalization
charge.
Idle Remains idle until the
requirements for an
equalization charge are met.

Operating Manual SI30M-44M-60H-80H-BE-en-32 93


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.1.3 Generator Category


Display pages
The Sunny Remote Control displays these pages whenever a generator has been connected and configured.
Name Description Value Explanation
Power Active power of the generator in kW ‒ ‒ ✖ ✓
Voltage PV array voltage (external grid ‒ ‒ ✖ ✓
connection) in V
Frequency Frequency of the PV array voltage ‒ ‒ ✖ ✓
(external grid connection) in Hz
Request by Reason for requesting generator: None Generator has not been requested. ✖ ✓
Bat Electricity generator was requested
due to state of charge.
Lod Electricity generator was requested
due to load.
Tim Generator requested due to time.
Run1h Generator manually requested for
one hour.
Start Generator was started manually.
ExtSrcReq Generator was requested
externally.
Run Time Current run time of the generator ‒ ‒ ✖ ✓
in hh:mm:ss
Energy Energy supplied by the generator since ‒ ‒ ✖ ✓
the last start in kWh
No.OfStarts Number of generator starts ‒ ‒ ✖ ✓
Op.Hours Total operating hours of the generator ‒ ‒ ✖ ✓
Tot.Energy Released energy from generator in ‒ ‒ ✖ ✓
kWh

Setting page
The Sunny Remote Control displays these pages whenever a generator has been connected and configured.
Name Description Value Explanation
Mode Manual generator control Auto Enable automatic generator ✖ ✓
operation.
Stop Stops the generator.
Start Start the generator.
Run1h Starts the generator for one hour.
Error Error confirmation for generator error Ackn. Acknowledges the error. ✖ ✓

94 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

13.1.4 Grid Category


Display page
The Sunny Remote Control displays these pages in a battery backup system.
Name Description
Power Active power of utility grid in kW ✓ ✖
Voltage Voltage of utility grid (external grid connection) in V ✓ ✖
Frequency Frequency of utility grid (external grid connection) in Hz ✓ ✖

Setting page
The Sunny Remote Control displays these pages in a battery backup system.
Name Description Value Explanation
Mode Manual control of the Auto Enables automatic connection to the utility grid. ✓ ✖
utility grid
Stop Disconnects the Sunny Island from the utility grid.
Start Connects the Sunny Island to the utility grid.

13.1.5 SI Charger Category


Display page
The Sunny Remote Control shows this page only if at least one Sunny Island Charger charge controller is used in the
off-grid system.
Name Description
Tot.Power Total PV power of all Sunny Island Charger charge controllers in W ✖ ✓
Tot.Energy Energy of all Sunny Island Charger charge controllers in kWh ✖ ✓
Day Energy Total PV energy today ✖ ✓
This is the total energy of all Sunny Island Charger charge controllers in kWh

13.1.6 Self Cnsmptn Category


Display pages
The Sunny Remote Control displays these pages if the PV generation in a system for increased self-consumption is
transferred to the Sunny Island.
Name Description
IncPower Current increased self-consumption in kW ✓ ✖
IncToday Today's increased self-consumption in kWh ✓ ✖
IncEnergy Total increased self-consumption in kWh ✓ ✖
Energy Energy consumed internally in kWh ✓ ✖

Operating Manual SI30M-44M-60H-80H-BE-en-32 95


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.1.7 Grid Cnsmptn Category


Display page
The Sunny Remote Control displays these pages in a system for increased self-consumption.
Name Description
Power Power drawn from the utility grid in kW ✓ ✖
Energy Energy drawn from the utility grid in kWh ✓ ✖

13.1.8 Grid Feed Category


Display page
The Sunny Remote Control displays these pages in a system for increased self-consumption.
Name Description
Power Power fed into the utility grid in kW ✓ ✖
Energy Today's grid feed-in in kWh ✓ ✖

13.1.9 Loads Category


Display page
The Sunny Remote Control displays these pages if the PV generation in a system for increased self-consumption is
transferred to the Sunny Island.
Name Description
Power Current power of the loads in kW ✓ ✖
Energy Consumption meter reading in kWh ✓ ✖
ConState Reserved for future applications ✓ ✖

13.1.10 PV System Category


Display page
The Sunny Remote Control displays these pages if PV generation in a system for increased self-consumption is transferred
to the Sunny Island.
Name Description
Power Power PV generation in kW ✓ ✖
Energy PV production meter reading in kWh ✓ ✖
ConState Reserved for future applications ✓ ✖

96 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

13.1.11 System Category


Display page
Name Description Value Explanation
Type Configuration of the system 1Phase1 Single-phase system with one ✓ ✓
Sunny Island
1Phase2 Single-phase system with two
Sunny Island inverters
1Phase3 Single-phase system with three
Sunny Island inverters
3Phase Three-phase system
MC-Box Multicluster system
Box Type Type of connected Multicluster Box MC-Box-6 Multicluster Box 6 ✖ ✓
This parameter is shown only in multicluster MC-Box-12 Multicluster Box 12
systems.
MC-Box-36 Multicluster Box 36
Device Type of cluster MainClst Sunny Remote Control is ✖ ✓
This parameter is shown only in multicluster connected to the main cluster.
systems. ExtnClst The Sunny Remote Control is
connected to the extension cluster.

13.1.12 Time Category


Display page
Name Description
Date Date in dd.mm.yyyy ✓ ✓
Time Time in hh:mm:ss ✓ ✓

Setting page
Name Description Explanation
Date Date in dd.mm.yyyy Set the date. ✓ ✓
Time Time in hh:mm:ss Set the time. ✓ ✓

13.1.13 Identity Category


Display page
Name Description
Serial No. Serial number ✓ ✓
Firmware Firmware version ✓ ✓

Operating Manual SI30M-44M-60H-80H-BE-en-32 97


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.1.14 Password Category


Display page
Name Description Value Explanation
Level Current password level User Sunny Remote Control is in user mode. ✓ ✓

Setting page
Name Description
Set Enter the installer password. ✓ ✓
Runtime Displays the operating hours ✓ ✓

13.2 Directory of the Parameters in Installer Mode and Expert Mode


13.2.1 Display Values
13.2.1.1 Inverter (110#)

111# Total
No. Name Description
111.01 TotInvPwrAt Total active power of Sunny Island inverters in a cluster in kW. ✓ ✓
111.02 TotInvCur Total current of Sunny Island inverters in a cluster in A ✓ ✓
111.03 TotInvPwrRt Total reactive power of Sunny Island inverters in a cluster in kVAr (expert mode) ✓ ✓
111.05 TotLodPwr Total current active power of the loads in a cluster in kW ✓ ✓
111.06 TotMccLodPwr Total current active power of the loads in a multicluster system in kW ✓ ✓

112# Device
No. Name Description Value Explanation
(plain text no.)
112.01 InvOpStt Operating state of the Sunny Island Init (1) Initialization ✓ ✓
inverter Startup (2) Switch from standby
to operation
Standby (3) Standby
Run (4) Operation
I-Loop (5) Current-controlled
generator operation
Error (6) Error status
112.02 InvPwrAt Active power of the Sunny Island ‒ ‒ ✓ ✓
inverter at line conductor L1 in kW
112.03 InvVtg Grid voltage of the Sunny Island ‒ ‒ ✓ ✓
inverter at line conductor L1 in V
112.04 InvCur Line current of the Sunny Island inverter ‒ ‒ ✓ ✓
at line conductor L1 in A
112.05 InvFrq Grid frequency of the Sunny Island ‒ ‒ ✓ ✓
inverter in Hz
112.06 InvPwrRt Reactive power of the Sunny Island ‒ ‒ ✓ ✓
inverter at line conductor L1 in kVAr
(expert mode)

98 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation


(plain text no.)
112.07 Rly1Stt Multifunction relay status 1 Off Multifunction relay is ✓ ✓
deactivated.
On Multifunction relay is
activated.
112.08 Rly2Stt Multifunction relay status 2 Off Multifunction relay is ✓ ✓
deactivated.
On Multifunction relay is
activated.
112.12 TrfTmp Temperature of the transformer in °C ‒ ‒ ✓ ✓
(expert mode)
The temperature of the transformer is
displayed in the master of a cluster.
112.13 HsTmp Temperature of the heat sink in the ‒ ‒ ✓ ✓
Sunny Island in °C (expert mode)
The temperature of the heat sink is
displayed in the master of a cluster.

113# Slave1
No. Name Description Value Explanation
113.01 InvOpSttSlv1 Operating state of slave 1 Init (1) Initialization ✓ ✓
Startup (2) Switch from standby to
operation
Standby (3) Standby
Run (4) Operation
I-Loop (5) Current-controlled generator
operation
Error (6) Error status
113.02 InvPwrAtSlv1 Active power of slave 1 at line ‒ ‒ ✓ ✓
conductor L2 in kW
113.03 InvVtgSlv1 Line voltage of Slave 1 at line ‒ ‒ ✓ ✓
conductor L2 in V
113.04 InvCurSlv1 Line current of the Slave 1 at line ‒ ‒ ✓ ✓
conductor L2 in A
113.05 InvPwrRtSlv1 Reactive power of slave 1 at line ‒ ‒ ✓ ✓
conductor L2 in kVAr (expert
mode)
113.06 Rly1SttSlv1 Multifunction relay status 1 of Off Multifunction relay is ✓ ✓
Slave 1 deactivated.
On Multifunction relay is
activated.

Operating Manual SI30M-44M-60H-80H-BE-en-32 99


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation


113.07 Rly2SttSlv1 Multifunction relay status 2 of Off Multifunction relay is ✓ ✓
Slave 1 deactivated.
On Multifunction relay is
activated.
113.09 TrfTmpSlv1 Temperature of the transformer ‒ ‒ ✓ ✓
in slave 1 in °C (expert mode)
113.10 HsTmpSlv1 Temperature of the heat sink in ‒ ‒ ✓ ✓
slave 1 in °C (expert mode)

114# Slave2
No. Name Description Value Explanation
114.01 InvOpSttSlv2 Operating state of slave 2 Init (1) Initialization ✓ ✓
Startup (2) Switch from standby to
operation
Standby (3) Standby
Run (4) Operation
I-Loop (5) Current-controlled generator
operation
Error (6) Error status
114.02 InvPwrAtSlv2 Active power of slave 2 at line ‒ ‒ ✓ ✓
conductor L3 in kW
114.03 InvVtgSlv2 Line voltage of slave 2 at line ‒ ‒ ✓ ✓
conductor L3 in V
114.04 InvCurSlv2 Line current of slave 2 at line ‒ ‒ ✓ ✓
conductor L3 in A
114.05 InvPwrRtSlv2 Reactive power of slave 2 at line ‒ ‒ ✓ ✓
conductor L3 in kVAr (expert
mode)
114.06 Rly1SttSlv2 Multifunction relay status 1 of Off Multifunction relay is ✓ ✓
slave 2 deactivated.
On Multifunction relay is
activated.
114.07 Rly2SttSlv2 Multifunction relay status 2 of Off Multifunction relay is ✓ ✓
slave 2 deactivated.
On Multifunction relay is
activated.
114.09 TrfTmpSlv2 Temperature of the transformer ‒ ‒ ✓ ✓
in slave 2 in °C (expert mode)
114.10 HsTmpSlv2 Temperature of the heat sink in ‒ ‒ ✓ ✓
slave 2 in °C (expert mode)

100 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

13.2.1.2 Battery (120#)


No. Name Description Value (plain Explanation
text no.)
120.01 BatSoc Momentary battery state of charge 0% … 100% ‒ ✓ ✓
(SOC) in relation to nominal capacity
of the battery in %
120.02 BatVtg Battery voltage in V ‒ ‒ ✓ ✓
120.03 BatChrgVtg Current battery charging voltage ‒ ‒ ✓ ✓
setpoint in V
120.04 AptTmRmg Remaining absorption time for ‒ ‒ ✓ ✓
completion of the current battery
charge phase 120.05 BatChrgOp
in hh:mm:ss
120.05 BatChrgOp Active battery charging mode Boost (1) Boost charge ✓ ✓
Full (2) Full charge
Float (3;7) Float charge
Equalize (4;5) Equalization charge
Silent (6;8) Energy-saving mode
active
120.06 TotBatCur Total battery current of the cluster in A ‒ ‒ ✓ ✓
120.07 BatTmp Battery temperature in °C ‒ ‒ ✓ ✓
120.08 RmgTmFul Remaining time until next full charge in ‒ ‒ ✓ ✓
days
120.09 RmgTmEqu Remaining time until next equalization ‒ ‒ ✓ ✓
charge in days
120.10 AptPhs Status of the absorption phase Off (1) Absorption phase ✓ ✓
not active
On (2) Absorption phase is
active
120.11 BatSocErr Estimated error of the battery state of ‒ ‒ ✓ ✓
charge (SOC) in % (expert mode)
120.12 BatCpyThrpCnt Number of nominal energy throughputs ‒ ‒ ✓ ✓
of the battery
A nominal energy throughput is the
calculated result of one full charge and
discharge of the battery.

Operating Manual SI30M-44M-60H-80H-BE-en-32 101


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.1.3 External (130#)

131# Total
No. Name Description
131.01 TotExtPwrAt Total active power of the external grid connection in kW ✓ ✓
131.02 TotExtCur Total current of the external grid connection in A ✓ ✓
131.03 TotExtPwrRt Total reactive power of the external grid connection in kvar ✓ ✓

132# Grid State


No. Name Description Value Explanation
(plain text no.)
132.01 GdStt Utility grid status Off (1) Off; Grid operation is disabled. ✓ ✓
(expert mode)
Init (2) Initialization; Utility grid has been
detected.
Detect (3) Grid monitoring started.
Wait (4) Waiting until the stand-alone grid is
synchronized with the utility grid.
RunVExt (5) Grid operation without feed-back; The
stand-alone grid is synchronized with
and connected to the utility grid.
Feed (6) Grid operation with feed-back; Grid
feed-in into the utility grid is possible.
Silent (7) Energy-saving in the utility grid; the
Sunny Island is in energy-saving mode.
SiStr (8) The Sunny Island is switching to
energy-saving mode.
SiStp (9) The Sunny Island is leaving
energy-saving mode.
Error (10) An error occurred when connecting.
Reinit (11) Initialization; Utility grid has been
detected again.
132.02 GdRmgTm Standby time to feed-in ‒ ‒ ✓ ✓
in hh:mm:ss
This is the remaining time
of grid monitoring
in hh:mm:ss

102 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

133# Gen State


No. Name Description Value (plain Explanation
text no.)
133.01 GnDmdSrc Reason for requesting None (1) No request ✖ ✓
generator:
Bat (2) State-of-charge-dependent request
Lod (3) Load-dependent request
Tim (4) Time-controlled request
Run1h (5) Requested for 1 hour
Start (6) Manually started
ExtSrcReq (7) External generator request
133.02 GnStt Generator state Off (1) Deactivated generator operation ✖ ✓
Init (2) Detecting generator
Ready (3) Waiting for request (ready)
Warm (4) Warming up
Connect (5) Connecting
Run (6) Operation
Retry (7) Restarting
Disconnect (8) Split
Cool (9) Cooling down
Lock (10) Locked after operation
Fail (11) Error
FailLock (12) Locked after error
Reinit (13) Re-detection of the generator
133.03 GnRmgTm Remaining minimum run ‒ ‒ ✖ ✓
time of the generator
in hh:mm:ss
133.04 GnRnStt Status of the digital input Off (1) Off ✖ ✓
for generator feedback
On (2) On ✖ ✓
(expert mode)

134# Device
No. Name Description
134.01 ExtPwrAt Total active power of the external grid connection at line conductor L1 in kW ✖ ✓
134.02 ExtVtg Voltage of the external grid connection at line conductor L1 in V ✖ ✓
134.03 ExtCur Current of the external grid connection at line conductor L1 in A ✖ ✓
134.04 ExtFrq Frequency of the external grid connection in Hz ✖ ✓
134.05 ExtPwrRt Reactive power of the external grid connection at line conductor L3 in kVAr (expert ✖ ✓
mode)
134.07 ExtLkRmgTm Minimum stop time in hh:mm:ss ✖ ✓

Operating Manual SI30M-44M-60H-80H-BE-en-32 103


13 Parameters in Sunny Remote Control SMA Solar Technology AG

135# Slave1
No. Name Description
135.01 ExtPwrAtSlv1 Total active power of the external grid connection at Slave 1 / line conductor L2 ✖ ✓
in kW
135.02 ExtVtgSlv1 Voltage of the external grid connection at Slave 1 / line conductor L2 in V ✖ ✓
135.03 ExtCurSlv1 Current of the external grid connection at Slave 1 / line conductor L2 in A ✖ ✓
135.04 ExtPwrRtSlv1 Reactive power of the external grid connection at Slave 1 line conductor L2 ✖ ✓
in kVAr (expert mode)

136# Slave2
No. Name Description
136.01 ExtPwrAtSlv2 Total active power of the external grid connection at Slave 2 / line conductor L3 ✖ ✓
in kW
136.02 ExtVtgSlv2 Voltage of the external grid connection at Slave 2 / line conductor L3 in V ✖ ✓
136.03 ExtCurSlv2 Current of the external grid connection at Slave 2 / line conductor L3 in A ✖ ✓
136.04 ExtPwrRtSlv2 Reactive power of the external grid connection at Slave 2 line conductor L3 ✖ ✓
in kVAr (expert mode)

13.2.1.4 Charge Controller (140#)

141# SIC50 Total


No. Name Description
141.01 TotSicEgyCntIn Total PV energy: This is the total energy of all Sunny Island Charger charge ✖ ✓
controllers in kWh
141.02 TSicDyEgyCntIn Total PV energy today: This is the total energy of all Sunny Island Charger ✖ ✓
charge controllers in kWh
141.03 TotSicPvPwr Total PV power of all Sunny Island Charger charge controllers in W ✖ ✓
141.04 TotSicBatCur Total output current of all Sunny Island Charger charge controllers in A ✖ ✓

142# SIC50 1
No. Name Description
142.01 Sic1EgyCntIn Total PV energy of Sunny Island Charger charge controller 1 in kWh ✖ ✓
142.02 Sic1TdyEgyCntIn Daily energy of Sunny Island Charger charge controller 1 in kWh ✖ ✓
142.03 Sic1PvPwr PV power of Sunny Island Charger charge controller 1 in W ✖ ✓
142.04 Sic1PvVtg PV voltage of Sunny Island Charger charge controller 1 in V ✖ ✓
142.05 Sic1BatVtg Battery voltage of Sunny Island Charger charge controller 1 in V ✖ ✓
(expert mode)
142.06 Sic1BatCur Battery current of Sunny Island Charger charge controller 1 in A ✖ ✓
(expert mode)
142.07 Sic1HsTmp Heat sink temperature of Sunny Island Charger charge controller 1 in °C ✖ ✓
(expert mode)

104 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

143# SIC50 2
No. Name Description
143.01 Sic2EgyCntIn Total PV energy of Sunny Island Charger charge controller 2 in kWh ✖ ✓
143.02 Sic2TdyEgyCntIn Daily energy of Sunny Island Charger charge controller 2 in kWh ✖ ✓
143.03 Sic2PvPwr PV power of Sunny Island Charger charge controller 2 in W ✖ ✓
143.04 Sic2PvVtg PV voltage of Sunny Island Charger charge controller 2 in V ✖ ✓
143.05 Sic2BatVtg Battery voltage of Sunny Island Charger charge controller 2 in V ✖ ✓
(expert mode)
143.06 Sic2BatCur Battery current of Sunny Island Charger charge controller 2 in A ✖ ✓
(expert mode)
143.07 Sic2HsTmp Heat sink temperature of Sunny Island Charger charge controller 2 in °C ✖ ✓
(expert mode)

144# SIC50 3
No. Name Description
144.01 Sic3EgyCntIn Total PV energy of Sunny Island Charger charge controller 3 in kWh ✖ ✓
144.02 Sic3TdyEgyCntIn Daily energy of Sunny Island Charger charge controller 3 in kWh ✖ ✓
144.03 Sic3PvPwr PV power of Sunny Island Charger charge controller 3 in W ✖ ✓
144.04 Sic3PvVtg PV voltage of Sunny Island Charger charge controller 3 in V ✖ ✓
144.05 Sic3BatVtg Battery voltage of Sunny Island Charger charge controller 3 in V ✖ ✓
(expert mode)
144.06 Sic3BatCur Battery current of Sunny Island Charger charge controller 3 in A ✖ ✓
(expert mode)
144.07 Sic3HsTmp Heat sink temperature of Sunny Island Charger charge controller 3 in °C ✖ ✓
(expert mode)

145# SIC50 4
No. Name Description
145.01 Sic4EgyCntIn Total PV energy of Sunny Island Charger charge controller 4 in kWh ✖ ✓
145.02 Sic4TdyEgyCntIn Daily energy of Sunny Island Charger charge controller 4 in kWh ✖ ✓
145.03 Sic4PvPwr PV power of Sunny Island Charger charge controller 4 in W ✖ ✓
145.04 Sic4PvVtg PV voltage of Sunny Island Charger charge controller 4 in V ✖ ✓
145.05 Sic4BatVtg Battery voltage of Sunny Island Charger charge controller 4 in V ✖ ✓
(expert mode)
145.06 Sic4BatCur Battery current of Sunny Island Charger charge controller 4 in A ✖ ✓
(expert mode)
145.07 Sic4HsTmp Heat sink temperature of Sunny Island Charger charge controller 4 in °C ✖ ✓
(expert mode)

Operating Manual SI30M-44M-60H-80H-BE-en-32 105


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.1.5 Compact (150#)


The menu 150# Compact displays multiple parameters from the following areas at a glance:
• Battery
• AC measured values of the Sunny Island inverter
• Electric generator or utility grid
• Status of the Sunny Island inverter

Battery (Bat)

Figure 15: Overview of the menu Meters Compact for the battery

Position Description Parameters


A Battery state of charge (SOC) as % 120.01 BatSoc ✓ ✓
B Estimated error of the battery state of charge (SOC) in % 120.11 BatSocErr ✓ ✓
(expert mode)
C Battery temperature in °C 120.07 BatTmp ✓ ✓
D Charging voltage target value in V 120.03 BatChrgVtg ✓ ✓
E Battery voltage in V 120.02 BatVtg ✓ ✓
F Total battery current of the cluster in A 120.06 TotBatCur ✓ ✓

AC measured values of the Sunny Island inverter (Inv)

Figure 16: Overview of the menu Meters Compact for the AC measured values of the Sunny Island inverter

Position Description Parameters


A Voltage of the Sunny Island inverter in V 112.03 InvVtg ✓ ✓
B Voltage frequency of the Sunny Island inverter in Hz 112.05 InvFrq ✓ ✓
C Reactive power of the inverter in kVAr 112.06 InvPwrRt ✓ ✓
D Active power of the inverter in kW 112.02 InvPwrAt ✓ ✓

106 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

Generator or utility grid (Ext)

Figure 17: Overview of the menu Meters Compact for the generator or the battery backup grid

Position Description Parameters


A Voltage of generator or utility grid in V 134.02 ExtVtg ✓ ✓
B Frequency of generator or utility grid in Hz 134.04 ExtFrq ✓ ✓
C Reactive power of generator or utility grid in kVAr 134.05 ExtPwrRt ✓ ✓
D Active power of generator or utility grid in kW 134.01 ExtPwrAt ✓ ✓

Status of the Sunny Island inverter (OpStt)

Figure 18: Overview of the menu Meters Compact for the status of the Sunny Island inverter

Position Description Value Explanation Parameters


A Operating state of the Init Initialization 112.01 InvOpStt ✓ ✓
Sunny Island
Standby Standby
Run Operation
EmChargeMod Emergency
charge mode
Error Error

Operating Manual SI30M-44M-60H-80H-BE-en-32 107


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.1.6 SlfCsmp (160#)

161# Power
No. Name Description
161.01 TotPvPwrAt Power PV generation in kW ✓ ✖
161.02 TotLodPwrAt Total power of the loads in kW ✓ ✖
161.03 SlfCsmpPwrAt Current self-consumption in kW ✓ ✖
161.04 SlfCsmpIncPwr Current increased self-consumption in kW ✓ ✖
161.05 GdCsmpPwrAt Power drawn from the utility grid in kW ✓ ✖
161.06 GdFeedPwrAt Power fed into the utility grid in kW ✓ ✖

162# Energy
No. Name Description
162.01 TotLodEgyCnt Consumption meter reading in kWh ✓ ✖
162.02 SlfCsmpIncEgy Total increased self-consumption in kWh ✓ ✖
162.03 SlfCsmpIncTdy Today's increased self-consumption in kWh ✓ ✖
162.04 SlfCsmpEgy Energy consumed internally in kWh ✓ ✖
162.05 GdCsmpEgyMtr Purchased electricity meter reading in kWh ✓ ✖
162.06 GdCsmpEgyTdy Today's purchased electricity in kWh ✓ ✖
162.07 GdFeedEgyMtr Feed-in meter reading in kWh ✓ ✖
162.08 PvEgyMtr PV production meter reading in kWh ✓ ✖
162.09 GdFeedEgyTdy Today's grid feed-in in kWh ✓ ✖

163# State
No. Name Description Value Explanation
163.01 BatMntStt Battery maintenance On Charge with solar ✓ ✖
charge status: If full charge power: Full charge or
or equalization charge equalization charge active;
with PV energy has not energy is drawn from the
ended after 24 hours, utility grid
163.01 BatMntStt
Wait Charge with solar
automatically switches to
power: If sufficient PV
On.
energy is available, full
charge or equalization
charge active
Off Inactive: No full charge or
equalization charge active

108 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation


163.02 SlfCsmpSOCArea Status of the battery SlfCsmpSOC Range for increased ✓ ✖
utilization range self-consumption
In systems for increased PVResSOC Range for maintenance of
self-consumption and in the battery state of charge
battery backup systems,
this parameter shows the BUResSOC Range for the battery
range currently occupied backup system function
by the state of charge of BatResSOC Range for protection
the battery. against deep discharge
ProtResSOC Range for protection in the
event of deep discharge
163.03 SlfCsmpSOCLim Lower discharge limit for 5% … 90% ‒ ✓ ✖
self-consumption range as
%
With this updated display
value, the Sunny Island
inverter informs of the state
of charge up to which the
battery for increased
self-consumption is
discharged (expert mode).

13.2.1.7 Multicluster (170#)

171# Total
The menu 171# Total is visible until firmware version 3.5 of the Sunny Island. The firmware version 3.5 of Sunny Island
can be used only in multicluster systems with Multicluster Box 12 of the device type MC-BOX-12.3-20.
No. Name Description
171.01 MCBatSOC Battery state of charge of the multicluster systems as % ✓ ✓

172# Ext.Cluster
The menu 172# Ext.Cluster is visible until firmware version 3.5 of the Sunny Island. The firmware version 3.5 of
Sunny Island can be used only in multicluster systems with Multicluster Box 12 of the device type MC-BOX-12.3-20.
No. Name Description Value Explanation
(plain text no.)
172.01 BatSOCExt1 Battery state of charge of extension cluster – – ✓ ✓
1 as %
172.02 BatSOCExt2 Battery state of charge of extension cluster ✓ ✓
2 as %
172.03 BatSOCExt3 Battery state of charge of extension cluster ✓ ✓
3 as %
172.04 BatSOCExt4 Battery state of charge of extension cluster ✖ ✓
4 as %
172.05 BatSOCExt5 Battery state of charge of extension cluster ✖ ✓
5 as %

Operating Manual SI30M-44M-60H-80H-BE-en-32 109


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation


(plain text no.)
172.06 BatSOCEx6 Battery state of charge of extension cluster – – ✖ ✓
6 as %
172.07 BatSOCExt7 Battery state of charge of extension cluster ✖ ✓
7 as %
172.08 BatSOCExt8 Battery state of charge of extension cluster ✖ ✓
8 as %
172.09 BatSOCExt9 Battery state of charge of extension cluster ✖ ✓
9 as %
172.10 BatSOCExt10 Battery state of charge of extension cluster ✖ ✓
10 as %
172.11 BatSOCExt11 Battery state of charge of extension cluster ✖ ✓
11 as %
172.13 TotInvPwrAtExt1 Active power of extension cluster 1 in kW ✓ ✓
172.14 TotInvPwrAtExt2 Active power of extension cluster 2 in kW ✓ ✓
172.15 TotInvPwrAtExt3 Active power of extension cluster 3 in kW ✓ ✓
172.16 TotInvPwrAtExt4 Active power of extension cluster 4 in kW ✖ ✓
172.17 TotInvPwrAtExt5 Active power of extension cluster 5 in kW ✖ ✓
172.18 TotInvPwrAtExt6 Active power of extension cluster 6 in kW ✖ ✓
172.19 TotInvPwrAtExt7 Active power of extension cluster 7 in kW ✖ ✓
172.20 TotInvPwrAtExt8 Active power of extension cluster 8 in kW ✖ ✓
172.21 TotInvPwrAtExt9 Active power of extension cluster 9 in kW ✖ ✓
172.22 TotInvPwrAtExt10 Active power of extension cluster 10 in kW ✖ ✓
172.23 TotInvPwrAtExt11 Active power of extension cluster 11 in kW ✖ ✓
172.25 TotInvPwrRtExt1 Reactive power of extension cluster 1 ✓ ✓
in kVAr
172.26 TotInvPwrRtExt2 Reactive power of extension cluster 2 ✓ ✓
in kVAr
172.27 TotInvPwrRtExt3 Reactive power of extension cluster 3 ✓ ✓
in kVAr
172.28 TotInvPwrRtExt4 Reactive power of extension cluster 4 ✖ ✓
in kVAr
172.29 TotInvPwrRtExt5 Reactive power of extension cluster 5 ✖ ✓
in kVAr
172.30 TotInvPwrRtExt6 Reactive power of extension cluster 6 ✖ ✓
in kVAr
172.31 TotInvPwrRtExt7 Reactive power of extension cluster 7 ✖ ✓
in kVAr
172.32 TotInvPwrRtExt8 Reactive power of extension cluster 8 ✖ ✓
in kVAr

110 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation


(plain text no.)
172.33 TotInvPwrRtExt9 Reactive power of extension cluster 9 – – ✖ ✓
in kVAr
172.34 TotInvPwrRtExt10 Reactive power of extension cluster 10 ✖ ✓
in kVAr
172.35 TotInvPwrRtExt11 Reactive power of extension cluster 11 ✖ ✓
in kVAr
172.37 OpSttExt1 Operating state of extension cluster 1 Operating (1) Operation ✓ ✓
Warning (2) Warning
Failure (3) Error
172.38 OpSttExt2 Operating state of extension cluster 2 Values and explanations see ✓ ✓
172.37 OpSttExt1
172.39 OpSttExt3 Operating state of extension cluster 3 ✓ ✓
172.40 OpSttExt4 Operating state of extension cluster 4 ✖ ✓
172.41 OpSttExt5 Operating state of extension cluster 5 ✖ ✓
172.42 OpSttExt6 Operating state of extension cluster 6 ✖ ✓
172.43 OpSttExt7 Operating state of extension cluster 7 ✖ ✓
172.44 OpSttExt8 Operating state of extension cluster 8 ✖ ✓
172.45 OpSttExt9 Operating state of extension cluster 9 ✖ ✓
172.46 OpSttExt10 Operating state of extension cluster 10 ✖ ✓
172.47 OpSttExt11 Operating state of extension cluster 11 ✖ ✓

13.2.2 Adjustable Parameters

13.2.2.1 Inverter (210#)


No. Name Description Value Explanatio Default
n value
210.01 InvVtgNom Nominal voltage of the 202.0 V … 230 V/ ✓ ✓ 230.0 V
Sunny Island inverter in V 253.0 V 50 Hz
202.0 V … 220 V/ 220.0 V
242.0 V 60 Hz
210.02 InvFrqNom Nominal frequency of the 45.0 Hz to 230 V/ ✓ ✓ 50.0 Hz
Sunny Island inverter in Hz 55.0 Hz 50 Hz
(expert mode)
55.0 Hz to 220 V/ 60.0 Hz
65.0 Hz 60 Hz
210.03 InvChrgCurMax Maximum AC battery charging 0 A to 26.1 A SI 8.0H ✓ ✓ 26.1 A
current (expert mode)
0 A to 20.0 A SI 6.0H 20.0 A
The actual AC current can be
limited due to normative 0 A to 14.3 A SI 4.4M 14.3 A
requirements. 0 A to 10 A SI 3.0M 10 A

Operating Manual SI30M-44M-60H-80H-BE-en-32 111


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.2.2 Battery (220#)

/05*$&
Damage to the battery due to incorrect settings
The set battery parameters influence the charging behavior of the Sunny Island inverter. The battery can be damaged
by incorrect settings for the battery type, nominal voltage and capacity parameters.
• Ensure that the values recommended by the battery manufacturer are set (refer to the technical data for the battery
in the manufacturer documentation). Note that the battery charging behavior names used by
SMA Solar Technology AG and the battery manufacturer may, in some cases, differ in meaning (for the battery
charging behavior of the Sunny Island inverter, see technical information "Battery Management").
• Set the battery capacity for a ten-hour electric discharge (C10). The battery manufacturer specifies the battery
capacity in relation to discharge time.

221# Property
No. Name Description Value Explanation Default
value
221.01 BatTyp Battery type VRLA Valve-regulate ✓ ✓ ‒
d lead–acid
battery with
immobilized
electrolyte in
gel or glass
mat
FLA Valve-regulate
d lead–acid
battery with
liquid
electrolyte
LiIon Lithium-ion
battery
221.02 BatCpyNom Battery nominal capacity 100 Ah to VRLA, FLA ✓ ✓ 166 Ah
C10 in Ah 10,000 Ah
50 Ah to 10,000 Ah Lithium-ion
221.03 BatVtgNom Battery nominal voltage 40.0 V … 48.0 V ‒ ✓ ✓ ‒
in V
221.04 BatTmpMax Maximum battery 221.05 BatTmpStr … ‒ ✓ ✓ 40°C
temperature in °C 50°C
(expert mode)
221.05 BatTmpStr Battery temperature as 0°C to ‒ ✓ ✓ 35°C
connection limit after 221.04 BatTmpMax
overtemperature
disconnection in °C
(expert mode)
221.06 BatWirRes Cable resistance of the 0 m Ω … 100 m Ω ‒ ✓ ✓ 0mΩ
battery connection, in m Ω
(expert mode)

112 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
221.07 BatFanTmpStr Temperature limit for 20°C to ‒ ✓ ✓ 40°C
multifunction relay with 221.04 BatTmpMax
battery room fan (BatFan
function) in °C

222# Chargemode
No. Name Description Value Explanatio Default
n value
222.01 BatChrgCurMax Maximum battery charging 10 A … ‒ ✓ ✓ ‒
current in A 900 A
222.02 AptTmBoost Absorption time of the boost 1 min to For VRLA ✓ ✓ 180 min
charge in minutes (expert mode) 600 min
For FLA 90 min
222.03 AptTmFul Absorption time for full charge 1.0 h … ‒ ✓ ✓ 6.0 h
in hours (expert mode) 20.0 h
222.04 AptTmEqu Absorption time for equalization 1.0 h … ‒ ✓ ✓ 12.0 h
charge in hours (expert mode) 48.0 h
222.05 CycTmFul Cycle time of full charge in days 1 d … 180 d ‒ ✓ ✓ 14 d
(expert mode)
222.06 CycTmEqu Cycle time of equalization 7 d … 365 d ‒ ✓ ✓ 90 d
charge in days (expert mode)
222.07 ChrgVtgBoost Setpoint of the cell voltage at 2.20 V … VRLA ✓ ✓ 2.40 V
boost charge in V (expert mode) 2.70 V
FLA, off-grid ✖ ✓ 2.40 V
FLA, on-grid ✓ ✖ 2.55 V
222.08 ChrgVtgFul Cell voltage setpoint for full 2.30 V … Off-grid ✖ ✓ 2.45 V
charge in V (expert mode) 2.70 V
On-grid ✓ ✖ 2.50 V
222.09 ChrgVtgEqu Cell voltage setpoint for 2.30 V … Off-grid ✖ ✓ 2.45 V
equalization charge in V 2.70 V
VRLA, on-grid ✓ ✖ 2.55 V
(expert mode)
FLA, on-grid ✓ ✖ 2.50 V
222.10 ChrgVtgFlo Cell voltage setpoint for float 2.20 V … ‒ ✓ ✓ 2.25 V
charge in V (expert mode) 2.40 V
222.11 BatTmpCps Battery temperature 0.0 mV⁄°C … ‒ ✓ ✓ 4.0 mV⁄°C
compensation in mV/°C 10.0 mV⁄°C
(expert mode)
222.12 AutoEquChrgEna Automatic equalization charge Disable Disable ✓ ✓ Enable
(expert mode)
Enable Enable

Operating Manual SI30M-44M-60H-80H-BE-en-32 113


13 Parameters in Sunny Remote Control SMA Solar Technology AG

223# Protection
No. Name Description Value Default
value
223.01 BatPro1TmStr Start time of battery protection mode level 1 00:00:00 … ✖ ✓ 22:00:00
in hh:mm:ss (expert mode) 23:59:59
223.02 BatPro1TmStp End time of battery protection mode level 1 00:00:00 … ✖ ✓ 06:00:00
in hh:mm:ss (expert mode) 23:59:59
223.03 BatPro2TmStr Start time of battery protection mode level 2 00:00:00 … ✖ ✓ 17:00:00
in hh:mm:ss (expert mode) 23:59:59
223.04 BatPro2TmStp End time of battery protection mode level 2 00:00:00 … ✖ ✓ 09:00:00
in hh:mm:ss (expert mode) 23:59:59
223.05 BatPro1Soc Battery SOC for protection mode level 1 as % 0% … 70% ✖ ✓ 20%
(expert mode)
223.06 BatPro2Soc Battery SOC for protection mode level 2 as % 0% … 70% ✖ ✓ 15%
(expert mode)
223.07 BatPro3Soc Battery SOC for protection mode level 3 as % 0% … 70% ✖ ✓ 10%
(expert mode)
223.08 BatProTmm Minimum time (in minutes) during which there is 1 min to ✖ ✓ 5 min
no battery current for switching to battery 20 min
protection mode (expert mode)
If the minimum time has elapsed and no battery
current was present, the Sunny Island can switch
to battery protection mode.

224# BatSilent
No. Name Description Value Explanation Default
value
224.01 BatSilentEna Energy-saving mode Enable Enable ✖ ✓ Disable
Disable Disable
224.02 BatSilentTmFlo Time until switchover to 1 h … 48 h – ✖ ✓ 3h
energy-saving mode (h)
224.03 BatSilentTmMax Maximum duration of 1 h … 168 h – ✖ ✓ 12 h
energy-saving mode (h)

225# Current Sensor


No. Name Description Value Explanation Default value
225.01 BatCurSnsTyp Type of battery current None No sensor is ✓ ✓ None
sensor connected.
60 mV 60 mV type
50 mV 50 mV type
225.02 BatCurGain60 60 mV type in A⁄60 mV 0 A⁄60 mV … ‒ ✓ ✓ 100 A⁄60 mV
1,800 A⁄60 mV

114 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default value


225.03 BatCurGain50 50 mV type in A⁄50 mV 0 A⁄50 mV … ‒ ✓ ✓ 100 A⁄50 mV
1,800 A⁄50 mV
225.04 BatCurAutoCal Automatic calibration Start Start automatic ✓ ✓ ‒
of external battery calibration
current sensor

13.2.2.3 External/Backup (230#)

231# General
No. Name Description Value Explanation Default
value
231.01 PvFeedTmStr Start time for PV grid 00:00:00 ‒ ✖ ✓ 04:00:00
feed-in in hh:mm:ss …
(expert mode) 23:59:59
231.02 PvFeedTmStp Stop time for PV grid 00:00:00 ‒ ✖ ✓ 22:00:00
feed-in in hh:mm:ss …
(expert mode) 23:59:59
231.03 ExtLkTm Lock time until connection 0 min to ‒ ✖ ✓ 20 min
to the external grid after 60 min
reverse power or relay
protection in minutes
(expert mode)
231.06 ExtSrc External energy sources in PvOnly Only AC sources in the ✖ ✓ ‒
Off-Grid mode stand-alone grid, no
generator in the off-grid
system
Gen Generator
Grid Utility grid
GenGrid Electric generator or utility
grid
231.12 ClstPwrNom Nominal power of the ‒ ‒ ✓ ✓ ‒
cluster in kW

232# Grid Control


No. Name Description Value Explanation Default
value
232.01 Country Set country standard Other Individual setting ✓ ✓ ‒
(protected by
VDE-AR-4105 Code of Practice −
SMA Grid Guard)
VDE-AR-N 4105
AS4777 Standard
AS4777

Operating Manual SI30M-44M-60H-80H-BE-en-32 115


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


value
232.02 GdVtgMin Lower minimum threshold 172.50 V to 230 V/50 Hz ✓ ✓ 184.00 V
of line voltage for voltage 210.01
220 V/60 Hz 194.00 V
monitoring in V (expert InvVtgNom
mode, protected by
SMA Grid Guard)
232.03 GdVtgMax Upper maximum 210.01 230 V/50 Hz ✓ ✓ 264.50 V
threshold of line voltage InvVtgNom to
220 V/60 Hz 242.00 V
for voltage monitoring 264.50 V
in V (expert mode,
protected by
SMA Grid Guard)
232.04 GdCurNom Maximum current from 0.0 A to 50.0 A 1 inverter ✖ ✓ 16A
the utility grid (A) SI 3.0M / 4.4M
(expert mode, protected (single-phase)
by SMA Grid Guard) 1 inverter ✖ ✓ 16A
SI 6.0H / 8.0H
(single-phase)
0.0 A to 100.0 A 2 inverters ✖ ✓ 16A
SI 6.0H / 8.0H
(single-phase)
0.0 A to 150.0 A 3 inverters ✖ ✓ 16A
SI 6.0H / 8.0H
(single-phase)
0.0 A to 50.0 A 3 inverters ✖ ✓ 16A
SI 3.0M / 4.4M
(three-phase)
3 inverters ✖ ✓ 16A
SI 6.0H / 8.0H
(three-phase)
232.05 GdFrqNom Nominal grid frequency 232.05 230 V/50 Hz ✓ ✓ 50.00 Hz
in Hz (expert mode, GdFrqMin to
220 V/60 Hz 60.00 Hz
protected by SMA Grid 232.06
Guard) GdFrqMax
232.06 GdFrqMin Lower minimum threshold 40.00 Hz to 230 V/50 Hz ✓ ✓ 47.50 Hz
of power frequency for 232.04
220 V/60 Hz 59.30 Hz
frequency monitoring GdFrqNom
in V (expert mode,
protected by
SMA Grid Guard)
232.07 GdFrqMax Upper maximum 232.4 GdFrqNo 230 V/50 Hz ✓ ✓ 51.50 Hz
threshold of power m to 70.00 Hz
220 V/60 Hz 60.50 Hz
frequency for frequency
monitoring in V (expert
mode, protected by
SMA Grid Guard)

116 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
232.08 GdVldTm Minimum observation 5 s to 900 s VDE-AR-N 4105 ✓ ✓ 60 s
time for line voltage and AS4777
frequency in the
220 V/60 Hz 300 s
permissible range for
connection in s (expert
mode, protected by SMA
Grid Guard)
232.09 GdMod Type of reverse feeding GridCharge Charge on utility ✓ ✓ −
into the utility grid (expert grid
mode, protected by
GridFeed Charge and
SMA Grid Guard)
feedback on utility
grid
232.10 GdRvPwr Maximum grid reverse 0 W to 5,000 W 1 Sunny Island or ✖ ✓ 100 W
power in W (expert single-cluster
mode) system
0 W to Multicluster 100 W
20,000 W system
232.11 GdRvTm Permissible time for 0 s to 60 s ‒ ✖ ✓ 5s
maximum grid reverse
power in s (expert mode)
232.12 GdVtgMinDel Lower voltage difference 0.0 V … 20.0 V VDE_AR_4105 ✓ ✓ 11.5 Hz
for valid grid connection
AS4777 2.0 Hz
in V
(expert mode, protected Off-grid 2.0 Hz
by SMA Grid Guard) Other 2.0 Hz
220 V/60 Hz 2.0 Hz
232.13 GdVtgMaxDel Upper voltage difference 0.0 V … 12.0 V VDE_AR_4105 ✓ ✓ 11.5 Hz
for valid grid connection
AS4777 2.0 Hz
in V
(expert mode, protected Off-grid 2.0 Hz
by SMA Grid Guard) Other 2.0 Hz
220 V/60 Hz 2.0 Hz
232.14 GdVtgMinDel Lower frequency 0.00 Hz to − ✓ ✓ 0.02 Hz
difference for valid grid 2.50 Hz
connection in Hz
(expert mode, protected
by SMA Grid Guard)
232.15 GdFrqMaxDel Upper frequency 0.00 Hz to VDE_AR_4105 ✓ ✓ 1.45 Hz
difference for valid grid 2.50 Hz
connection in Hz
0.00 Hz to 230 V/50 Hz 0.02 Hz
(expert mode, protected 0.20 Hz
by SMA Grid Guard)
0.00 Hz to 220 V/60 Hz 0.02 Hz
0.20 Hz

Operating Manual SI30M-44M-60H-80H-BE-en-32 117


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


value
232.16 GdAlSns Sensitivity of the Low Low ✓ ✓ Normal
anti-islanding detection
Medium Medium
(expert mode, protected
by SMA Grid Guard) Normal Normal
High High
232.40 GdRtCurSrc Place of reactive current External Sunny Island ✓ ✖ External
compensation in grid compensates all
operation (expert mode) reactive currents.
Inverter Sunny Island does
not compensate
reactive currents.
Shared Sunny Island
partially
compensates
reactive currents.
232.41 P-WCtlHzMod Operating mode of Off Disable ✓ ✖ −
active power reduction in
WCtlHz Enable
case of overfrequency
P(f) (expert mode,
protected by
SMA Grid Guard)
232.42 P-HzStr Difference between 0.0 Hz to 5.0 Hz This value defines ✓ ✖ 0.2 Hz
starting frequency and how many Hz
grid frequency, linear above
instantaneous power 210.02 InvFrqN
gradient configuration om the active
(protected by power limitation
SMA Grid Guard) starts.
232.43 P-HzStop Difference between reset 0.0 Hz to 5.0 Hz This values defines ✓ ✖ 0.2 Hz
frequency and grid how many Hz
frequency, linear above
instantaneous power 210.02 InvFrqN
gradient configuration om the active
(protected by power limitation
SMA Grid Guard) stops.
232.44 P-WGra Active power gradient, 10%⁄Hz to ‒ ✓ ✖ 40%⁄Hz
linear instantaneous 130%⁄Hz
power gradient
configuration (expert
mode, protected by
SMA Grid Guard)
232.46 WGraRecon Power gradient following 1% … 100% ‒ ✓ ✖ 10%
grid error in % (expert
mode, protected by
SMA Grid Guard)

118 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
232.48 Q-VArMod Operating mode of static Off Disable ✓ ✖ −
voltage stability,
PFCnst Constant
configuration of static
displacement
voltage stability (expert
power factor
mode, protected by
cos φ
SMA Grid Guard)
PFCtlW Automatic
adaptation of the
displacement
power factor
according to the
current active
power
232.49 PF-PF cosPhi setpoint, cosPhi 0.8 … 1 Code of Practice ✓ ✖ 0.9
configuration, direct VDE-AR-N 4105
specification (expert
Standard 1
mode, protected by
AS-4777
SMA Grid Guard)
232.50 PF-PFExt cosPhi excitation type, OvExt Lagging ✓ ✖ UnExt
cosPhi configuration,
UnExt Leading
direct specification
(expert mode, protected
by SMA Grid Guard)
232.51 PF-PFStr cosPhi of the start point, 0.8 … 1 ‒ ✓ ✖ 1
configuration of
cos Phi(P) characteristic,
direct specification
(expert mode, protected
by SMA Grid Guard)
232.52 PF-PFExtStr Excitation type of the start OvExt Lagging ✓ ✖ OvExt
point, configuration of
UnExt Leading
cos Phi(P) characteristic,
direct specification
(expert mode, protected
by SMA Grid Guard)
232.53 PF-WNomStr Active power of the start 0% to 232.56 ‒ ✓ ✖ 50%
point, configuration of PF-WNomStop
cos Phi(P) characteristic,
direct specification
(expert mode, protected
by SMA Grid Guard)
232.54 PF-PFStop cosPhi of the end point, 0.8 … 1.0 ‒ ✓ ✖ 0.9
configuration of
cos Phi(P) characteristic,
direct specification
(expert mode, protected
by SMA Grid Guard)

Operating Manual SI30M-44M-60H-80H-BE-en-32 119


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


value
232.55 PF-PFExtStop Excitation type of the end OvExt Lagging ✓ ✖ UnExt
point, configuration of
UnExt Leading
cos Phi(P) characteristic,
direct specification
(expert mode, protected
by SMA Grid Guard)
232.56 PF-WNomStop Active power of the end 232.52 ‒ ✓ ✖ 100%
point, configuration of PF-WNomStr to
cos Phi(P) characteristic, 100%
direct specification
(expert mode, protected
by SMA Grid Guard)
232.58 GdAIFac Anti-islanding factor in 0.00 … 3.00 − ✓ ✓ 0.50
current-controlled grid
operation with I-Loop
(expert mode)
232.59 MsPhSel Line conductor to which L1 Line conductor L1 ✓ ✖ −
the Sunny Island is
L2 Line conductor L2
connected (expert mode)
L3 Line conductor L3
232.60 EZATyp Type of PV system feed-in Asymmetric At least one PV ✓ ✖ −
(expert mode) inverter is
single-phase and
feeds in
asymmetrically.
Symmetric All PV inverters are
three-phase and
feed in
symmetrically.

233# Grid Start, for off-grid systems only


No. Name Description Value Explanatio Default
n value
233.01 GdSocEna Enable grid request Disable Disable ✖ ✓ Disable
based on battery state of
Enable Enable
charge (expert mode)
233.02 GdSocTm1Str Battery state of charge 1% to ‒ ✖ ✓ 40%
limit for connection to the 233.03 GdSocTm1Stp
utility grid in the standard
additional time period
in % (expert mode)
This is the valid threshold
without the additional
time period.

120 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanatio Default


n value
233.03 GdSocTm1Stp Battery state of charge 233.02 GdSocTm1Str ‒ ✖ ✓ 80%
limit for disconnection to 95%
from the utility grid in the
standard additional time
period as % (expert
mode)
This is the valid threshold
without the additional
time period.
233.04 GdSocTm2Str Battery state of charge 1% to ‒ ✖ ✓ 40%
limit for connection to the 233.05 GdSocTm2Stp
utility grid in the
additional time period as
% (expert mode)
233.05 GdSocTm2Stp Battery state of charge 233.04 GdSocTm2Str ‒ ✖ ✓ 80%
limit for disconnection to 95%
from the utility grid in the
additional time period as
% (expert mode)
233.06 GdTm1Str Start of standard 00:00:00 … 23:59:59 ‒ ✖ ✓ ‒
additional time period for
grid request in hh:mm:ss
(expert mode)
233.07 GdTm2Str Start of additional time 00:00:00 … 23:59:59 ‒ ✖ ✓ ‒
period for grid request
in hh:mm:ss (expert
mode)
233.08 GdPwrEna Grid request based on Disable Disable ✖ ✓ Disable
power (expert mode)
Enable Enable
233.09 GdPwrStr Grid request for 233.10 GdPwrStp to ‒ ✖ ✓ 4.0 kW
connection power limit 300 kW
in kW (expert mode)
233.10 GdPwrStp Grid request for 0 kW to ‒ ✖ ✓ 2.0 kW
disconnection power limit 233.09 GdPwrStr
in kW (expert mode)
233.11 GdStrChrgMod Grid request based on Off Off ✖ ✓ Equal
charge mode (expert
Full Full charge
mode)
Equal Equalization
charge
Both Full and
equalization
charge

Operating Manual SI30M-44M-60H-80H-BE-en-32 121


13 Parameters in Sunny Remote Control SMA Solar Technology AG

234# Gen Control


No. Name Description Value Explanation Default
value
234.01 GnVtgMin Lower minimum threshold 172.5 V to ‒ ✖ ✓ 172.50 V
of PV array voltage for 210.01 InvVtgNom
voltage monitoring in V
(expert mode, protected
by SMA Grid Guard)
234.02 GnVtgMax Upper maximum 210.01 InvVtgNom ‒ ✖ ✓ 250.0 V
threshold of PV array to 264.5 V
voltage for voltage
monitoring in V (expert
mode, protected by
SMA Grid Guard)
234.03 GnCurNom Nominal generator 0.0 A to 50.0 A 1 Sunny Island ✖ ✓ 16.0 A
current in A
0.0 A to 100.0 A Two Sunny Island 16.0 A
inverters, parallel
0.0 A to 150.0 A Three 16.0 A
Sunny Island
inverters, parallel
0.0 A to 50.0 A Three-phase 16.0 A
0.0 A to 80.0 A Multicluster Box 6 60.0 A
0.0 A to 160.0 A Multicluster Box 160.0 A
12
0.0 A to 500.0 A Multicluster Box 435.0 A
36
234.04 GnFrqNom Nominal generator 234.05 GnFrqMin 230 V/50 Hz ✖ ✓ 50.00 Hz
frequency under nominal to
220 V/60 Hz 60.00 Hz
load in Hz (expert mode) 234.06 GnFrqMax
234.05 GnFrqMin Lower minimum threshold 40.00 Hz to 230 V/50 Hz ✖ ✓ 44.64 Hz
of generator frequency 234.04 GnFrqNom
for frequency monitoring
50.00 Hz to 220 V/60 Hz 50.00 Hz
in V (expert mode,
234.04 GnFrqNom
protected by
SMA Grid Guard)
234.06 GnFrqMax Upper maximum 234.04 GnFrqNo 230 V/50 Hz ✖ ✓ 60.00 Hz
threshold of generator to 70.00 Hz
220 V/60 Hz 70.00 Hz
frequency for frequency
monitoring in V (expert
mode, protected by
SMA Grid Guard)
234.07 GnStrMod Generator interface Manual Manual ✖ ✓ Autostart
Autostart Automatic
234.08 GnOpTmMin Minimum run time of 0 min to 360 min ‒ ✖ ✓ 15 min
generator in minutes

122 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
234.09 GnStpTmMin Minimum idle time of the 0 min to 360 min ‒ ✖ ✓ 15 min
generator in minutes
234.10 GnCoolTm Cooling time of the 0 min to 60 min ‒ ✖ ✓ 5 min
generator in minutes
234.11 GnErrStpTm Idle time after generator 0 h to 24 h ‒ ✖ ✓ 1h
error in hours (expert
mode)
234.12 GnWarmTm Warm-up time in seconds 5 s to 900 s ‒ ✖ ✓ 60 s
234.13 GnRvPwr Maximum reverse power 0 W to 5,000 W 1 Sunny Island or ✖ ✓ 100 W
for voltage monitoring of single-cluster
generator in W (expert system
mode)
0 W to 20,000 W Multicluster 100 W
system
234.14 GnRvTm Time for reverse power or 0 s to 900 s ‒ ✖ ✓ 30 s
reverse current for
voltage monitoring of
generator in s (expert
mode)
234.15 GnCtlMod Type of generator current Cur Fixed threshold for ✖ ✓ Cur
limitation (expert mode) current limitation
The generator control CurFrq Frequency-depen
limits the consumption of dent current
generator current. limitation
234.20 GnAlSns Anti-islanding Sensitivity Low Low ✖ ✓ Normal
of the generator fault
Medium Medium
recognition (expert mode)
Normal Normal
High High
234.41 GnCurCtlMod Enable I-Loop in Droop Standard ✖ ✓ Droop
generator operation generator
(expert mode, only with operation without
SI6.0H-11 and I-Loop
SI8.0H-11)
CurCtl Current-controlled
I-Loop enables generator
generators with operation with
inadequate voltage I-Loop
regulation to be used in
the system.
234.42 GnAIFac Anti-islanding factor in 0.00 … 1.00 − ✖ ✓ 0.10
current-controlled
generator operation with
I-Loop (expert mode)

Operating Manual SI30M-44M-60H-80H-BE-en-32 123


13 Parameters in Sunny Remote Control SMA Solar Technology AG

235# Gen Start


No. Name Description Value Explanation Default
value
235.01 GnAutoEna Automatic generator start Off Disable ✖ ✓ On
during disturbances
On Enable
235.02 GnAutoStr Number of attempts to carry 0 … 10 ‒ ✖ ✓ 3
out automatic restart of
generator (expert mode)
235.03 GnSocTm1Str Battery state of charge limit 1% to 235.04 ‒ ✖ ✓ 40%
for generator request in the GnSocTm1Stp
standard additional time
period as %
This is the valid threshold
without the additional time
period.
235.04 GnSocTm1Stp Battery state of charge limit 235.03 GnSocTm ‒ ✖ ✓ 80%
for end of generator request 1Str to 95%
in the standard additional
time period as %
This is the valid threshold
without the additional time
period.
235.05 GnSocTm2Str Battery state of charge limit 1% to 235.06 ‒ ✖ ✓ 40%
for generator request in GnSocTm2Stp
additional time period as %
235.06 GnSocTm2Stp Battery state of charge limit 235.05 GnSocTm ‒ ✖ ✓ 80%
for end of generator request 2Str to 95%
in the additional time period
as %
235.07 GnTm1Str Start time of the standard 00:00:00 … ‒ ✖ ✓ 00:00:00
additional time period for 23:59:59
generator request in
hh:mm:ss; corresponds to the
end time of the additional
time period
235.08 GnTm2Str Start time of additional time 00:00:00 … ‒ ✖ ✓ 00:00:00
period for generator request 23:59:59
in hh:mm:ss
235.09 GnPwrEna Generator request based on Disable Disable ✖ ✓ Enable
power (expert mode)
Enable Enable
235.10 GnPwrStr Load limit: Generator start 235.11 GnPwrSt ‒ ✖ ✓ 4.0 kW
for generator request based p to 300.0 kW
on power in kW (expert
mode)

124 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
235.11 GnPwrStp Load limit: Generator 0.0 kW to ‒ ✖ ✓ 2.0 kW
shutdown for end of 235.10 GnPwrStr
generator request based on
power in kW (expert mode)
235.12 GnPwrAvgTm Averaging time for 1 s to 900 s ‒ ✖ ✓ 60 s
load-dependent generator
request based on power in s
(expert mode)
235.13 GnTmOpEna Time-controlled generator Disable Disable ✖ ✓ Disable
operation
Enable Enable
235.14 GnTmOpStrDt Start date for time-controlled ‒ ‒ ✖ ✓ 2011-01-
generator operation 01
in dd.mm.yyyy
235.15 GnTmOpStrTm Time at the start of 00:00:00 … ‒ ✖ ✓ 00:00:00
time-controlled generator 23:59:59
operation in hh:mm:ss
235.16 GnTmOpRnDur Run time for time-controlled 00:00:00 … ‒ ✖ ✓ 00:00:00
generator operation 99:59:00
in hh:mm:ss
235.17 GnTmOpCyc Repeat cycle for Single Once ✖ ✓ Single
time-controlled generator
Daily Daily
operation
Weekly Weekly
235.18 GnStrChrgMod Generator request in Off Off ✖ ✓ Both
configured charge mode
Full Full charge
(expert mode)
Equal Equalization
charge
Both Full and
equalization
charge
235.19 GnStrDigIn Generator request in Disable Disable ✖ ✓ Disable
response to signal on
Enable Enable
activated digital input
(expert mode)

Operating Manual SI30M-44M-60H-80H-BE-en-32 125


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.2.4 Relay (240#)

241# General
No. Name Description Value Explanation Default
value
241.01 Rly1Op Operating mode Off Off; the multifunction relay is always ✓ ✓ AutoGn
of the in idle mode.
multifunction
On On; the multifunction relay is
relay 1
permanently activated.
AutoGn Automatic generator request; the
Sunny Island automatically requests
the generator. In case of a generator
request, the multifunction relay is
activated.
AutoLodExt 1-level load shedding
When the generator is connected, the
Sunny Island stops the load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
AutoLod1Soc 1-level load shedding or first level of
2-level load shedding
When the upper SOC threshold is
reached, the Sunny Island ends load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
AutoLod2Soc Second level of 2-level load shedding
When the upper SOC threshold is
reached, the Sunny Island ends load
shedding. When the loads are to be
shed, the multifunction relay is
deactivated.
Tm1 Timer 1
The Sunny Island controls external
processes time-dependently. When
the set time #243 Timer is reached,
the multifunction relay is activated.
Tm2 Timer 2
The Sunny Island controls external
processes time-dependently. When
the set time #243 Timer is reached,
the multifunction relay is activated.

126 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
241.01 Rly1Op Operating mode ExtPwrDer Control of additional loads; the ✓ ✓ AutoGn
multifunction Sunny Island controls additional
relay 1 loads in order to put excess energy to
(continued) practical use. When excessive energy
can be used, the multifunction relay is
activated.
GnRn Relay is activated when generator is
running: When the generator is in
operation, the multifunction relay is
activated.
ExtVfOk Relay is activated when external
source is present: When the voltage
and frequency of the external energy
source are within the valid range for
the connection, the multifunction relay
is activated.
GdOn Relay is activated when utility grid is
present: When the utility grid is
connected, the multifunction relay is
activated.
Error Relay is deactivated during error:
When an error message is pending,
the multifunction relay is deactivated.
Warn Relay is activated during warning:
When a warning is pending, the
multifunction relay is activated.
Run Relay is activated when cluster is
running: When the Sunny Island or
the cluster is in operation, the
multifunction relay is activated.
BatFan Relay is activated when battery room
fan is running: The Sunny Island
controls the battery room fan for all
clusters together. When the battery
room is to be ventilated, the
multifunction relay is activated.
AcdCir Relay is activated when the
electrolyte pump is running: The
Sunny Island controls the electrolyte
pump of the battery. When the
electrolyte is to be circulated, the
multifunction relay is activated.

Operating Manual SI30M-44M-60H-80H-BE-en-32 127


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


value
241.01 Rly1Op Operating mode MccBatFan Relay is activated when battery room ✓ ✓ AutoGn
multifunction fan is running: The Sunny Island
relay 1 controls the battery room fan for all
(continued) clusters together. When the battery
room is to be ventilated, the
multifunction relay is activated.
MccAutoLod Load shedding in a multicluster
system
When all batteries have reached the
upper SOC threshold, the
Sunny Island ends load shedding.
When the loads are to be shed, the
multifunction relay is deactivated.
CHPReq No function
CHPAdd No function
SiComRemote Multifunction relay is controlled via
ComSync.
Overload When the Sunny Island limits its
power, the multifunction relay is
deactivated.
GriSwt Triggering of contactors for grid
disconnection in the battery backup
system
GndSwt Triggering of the grounding in the
battery backup system
GriRdtSwt Triggering of redundant contactor for
grid disconnection in the battery
backup system
241.02 Rly2Op Operating mode See 241.01 Rly1Op, page 126 for value and ✓ ✓ AutoLodExt
multifunction explanation
relay 1 function

No. Name Description Value Default


value
241.07 ExtPwrDerMinTm Minimum time for the ExtPwrDer function of the 0 min to ✓ ✓ 10 min
multifunction relay in minutes 600 min
241.08 ExtPwrDerDltVtg Voltage difference for the ExtPwrDer function of 0V… ✓ ✓ 0.15 V
the multifunction relay in V 0.40 V
The voltage difference corresponds to the cell
voltage of the battery.

128 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

242# Load
No. Name Description Value Default
value
242.01 Lod1SocTm1Str Battery state of charge limit for start of 1% to 242.02 ✓ ✓ 30%
load shedding 1 in the standard Lod1SocTm1Stp
additional time period as %
This is the valid threshold without the
additional time period.
242.02 Lod1SocTm1Stp Battery state of charge limit for end of 242.01 ✓ ✓ 50%
load shedding 1 in the standard Lod1SocTm1Str to 90%
additional time period as %
This is the valid threshold without the
additional time period.
242.03 Lod1SocTm2Str Battery state of charge limit for start of 1%… ✓ ✓ 30%
load shedding 1 in additional time 242.04 Lod1SocTm2Stp
period as %
242.04 Lod1SocTm2Stp Battery state of charge limit for end of 242.03 ✓ ✓ 50%
load shedding stop in additional time Lod1SocTm2Str to 90%
period as %
242.05 Lod1Tm1Str Start time of the standard additional 00:00:00 … 23:59:59 ✓ ✓ ‒
time period for load shedding 1 in
hh:mm:ss; corresponds to the end time
of the additional time period
242.06 Lod1Tm2Str Start time of the additional time period 00:00:00 … 23:59:59 ✓ ✓ ‒
for load shedding 1 in hh:mm:ss
242.07 Lod2SocTm1Str Battery state of charge limit for start of 1% to 242.08 ✓ ✓ 30%
load shedding 1 in the standard Lod2SocTm1Stp
additional time period as %
This is the valid threshold without the
additional time period.
242.08 Lod2SocTm1Stp Battery state of charge limit for end of 242.07 ✓ ✓ 50%
load shedding 1 in the standard Lod2SocTm1Str to 90%
additional time period as %
This is the valid threshold without the
additional time period.
242.09 Lod2SocTm2Str Battery state of charge limit for start of 1% … ✓ ✓ 30%
load shedding 1 in the standard 242.10 Lod2SocTm2Stp
additional time period as %
242.10 Lod2SocTm2Stp Battery state of charge limit for end of 242.09 ✓ ✓ 50%
load shedding 2 in additional time Lod2SocTm2Str to 90%
period as %
242.11 Lod2Tm1Str Start time of the standard additional 00:00:00 … 23:59:59 ✓ ✓ 00:00:00
time period for load shedding 2 in
hh:mm:ss; corresponds to the end time
of the additional time period

Operating Manual SI30M-44M-60H-80H-BE-en-32 129


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Default


value
242.12 Lod2Tm2Str Start time of the additional time period 00:00:00 … 23:59:59 ✓ ✓ 00:00:00
for load shedding 2 in hh:mm:ss;
corresponds to the start time of the
additional time period

243# Timer
No. Name Description Value Explanation Default
value
243.01 RlyTmr1StrDt Start date for timer 1 in ‒ ‒ ✓ ✓ 2011-01-01
dd.mm.yyyy
243.02 RlyTmr1StrTm Start time at which the 00:00:00 … ‒ ✓ ✓ ‒
multifunction relay is 23:59:59
activated for timer 1
in hh:mm:ss
243.03 RlyTmr1Dur Duration for which the 00:00:00 … ‒ ✓ ✓ ‒
multifunction relay remains 99:59:00
activated for timer 1
in hh:mm:ss
243.04 RlyTmr1Cyc Repetition cycle time for timer Single Once ✓ ✓ Single
1
Daily Daily
Weekly Weekly
243.05 RlyTmr2StrDt Start date timer 2 ‒ ‒ ✓ ✓ 2011-01-01
243.06 RlyTmr2StrTm Start time at which the 00:00:00 … ‒ ✓ ✓ ‒
multifunction relay is 23:59:59
activated for timer 2
in hh:mm:ss
243.07 RlyTmr2Dur Duration for which the 00:00:00 … ‒ ✓ ✓ ‒
multifunction relay remains 99:59:00
activated for timer 2
in hh:mm:ss
243.08 RlyTmr2Cyc Repetition cycle time for timer Single Once ✓ ✓ Single
2
Daily Daily
Weekly Weekly

244# Slave1
No. Name Description Value Explanation Default
value
244.01 Rly1OpSlv1 Operating mode of See 241.01 Rly1Op, page 126 for value ✓ ✓ Off
the multifunction and explanation
relay 1 of Slave 1
244.02 Rly2OpSlv1 Operating mode of See 241.01 Rly1Op, page 126 for value ✓ ✓ Off
the multifunction and explanation
relay 2 of Slave 1

130 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

245# Slave2
No. Name Description Value Explanation Default
value
245.01 Rly1OpSlv2 Operating mode of See 241.01 Rly1Op, page 126 for value ✓ ✓ Off
the multifunction and explanation
relay 1 of Slave 2
245.02 Rly2OpSlv2 Operating mode of See 241.01 Rly1Op, page 126 for value ✓ ✓ Off
the multifunction and explanation
relay 2 of Slave 2

13.2.2.5 System (250#)


No. Name Description Value Explanation Default
value
250.01 AutoStr Number of autostarts 0 … 10 0 indicates that autostart ✓ ✓ 3
is disabled.
250.02 Dt Date in dd.mm.yyyy ‒ ‒ ✓ ✓ ‒
250.03 Tm Time in hh:mm:ss ‒ ‒ ✓ ✓ ‒
250.04 BeepEna Button sound Off Disable ✓ ✓ On
On Enable
250.06 ComBaud Baud rate in Bd 1 200 Default value for RS485 ✓ ✓ ‒
This value cannot be communication.
changed with 4 800 ‒
Speedwire.
9 600 ‒
19 200 ‒
115k Default value for
Speedwire
communication.
250.09 ComAdr Communication 0 … 65 535 ‒ ✓ ✓ 1
address (cannot be
adjusted)
250.11 AfraEna Automatic frequency Disable Disable ✖ ✓ ‒
synchronization (AFRA)
Enable Enable
(expert mode)
250.23 Box Type of AC None None ✖ ✓ ‒
subdistribution: /
MC-Box-6-1x Multicluster Box 6.3
Multicluster Box
MC-Box-9-1x Multicluster Box 9.3
MC-Box-12-1x Multicluster Box 12.3
MC-Box-12-2x Multicluster Box 12.3 of
the type
MC-BOX-12.3-20
MC-Box-36-1x Multicluster Box 36.3

Operating Manual SI30M-44M-60H-80H-BE-en-32 131


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


value
250.24 ClstMod Cluster type (adjustable SingleClst Single cluster ✓ ✓ ‒
in QCG)
MainClst Main cluster
ExtnClst Extension cluster
250.28 ChrgCtlOp Type: other DC sources Auto AC sources and DC ✖ ✓ Auto
(expert mode) charge controllers
NoFrq 2620 = Other DC ✓
charge controllers
The DC charge
controllers are not
Sunny Island Charger
devices and there are no
AC sources in the system.
SMA Communicative coupled ✓
DC charge controllers,
e.g.
Sunny Island Charger
No AC sources in the
system.
250.30 RnMod Run Mode RunAlways In the event of a slave ✓ ✓ RunAlwa
Behavior of the cluster device error, the cluster ys
in the event of a device remains in operation
fault StopAlways In the event of a device
error, the cluster stops
operation
250.31 ChLstSel Selection of short or Short Short ✓ ✓ Normal
normal channel list
Normal Normal
(expert mode)
The length must be
compatible with the
communication device.
250.32 UpdMode Type of firmware Manual Update must be ✓ ✓ Auto
update confirmed on the
Sunny Remote Control.
Auto Update will be
performed automatically
at the set time
250.33 UpdAutoTime.
Never Deactivation of all
updates
250.33 UpdAutoTime Point in time for 00:00:00 … ‒ ✓ ✖ 05:00:00
performing the 23:59:59
automatic firmware
update in hh:mm:ss

132 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

13.2.2.6 SlfCsmpBackup (#260)

261# General
No. Name Description Value Explanation Default
(plain text value
no.)
261.01 SlfCsmpIncEna Increased Disable Disable ✓ ✖ −
self-consumption
Enable Enable ✓ ✖
261.02 SlfCsmpPosSel Highest-yielding month for North Highest PV yield in ✓ ✖ −
battery utilization range: June
South Highest PV yield in ✓ ✖
December
261.03 Saisonenable Seasonal operation No Disable ✓ ✖ Yes
(expert mode)
Yes Enable ✓ ✖
Automatic adjustment of
the battery depth of
discharge: In seasons with
fewer hours of sunlight, the
electric discharge of the
battery will be lower.
261.04 SlfCsmpSpnt Specification of the control ≤ 0W Negative value: grid ✓ ✖ 0W
target at active feed-in
self-consumption in W*
0W No grid feed-in and
purchased electricity
≥ 0W Positive value:
purchased electricity
261.05 SlfCsmpLodShed Activation of load Disable Load shedding during ✓ ✖ Enable
shedding during self-consumption is
self-consumption.* deactivated.
Enable Load shedding during
self-consumption is
activated.
* The parameter is visible until firmware version 3.5 of the Sunny Island. The firmware version 3.5 of Sunny Island can only be used in
multicluster systems with Multicluster Box 12 of the device type MC-BOX-12.3-20.

262# BatUsage
No. Name Description Value Explanation Default
(plain text value
no.)
262.01 ProtResSOC Lower limit of the 10% … 20% Lead-acid batteries ✓ ✖ 10%
deep-discharge
3% … 20% Lithium-ion batteries ✓ ✖ 3%
protection range for
disconnection (%) of the
battery capacity (expert
mode)

Operating Manual SI30M-44M-60H-80H-BE-en-32 133


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation Default


(plain text value
no.)
262.02 BatResSOC Minimum width of the 2% … 50% Lithium-ion battery, ✓ ✖ 2%
deep-discharge self-consumption only
protection range (%) of
Lithium-ion battery, ✓ ✖ 10%
the battery capacity
battery backup
(expert mode)
system
Lead-acid battery, ✓ ✖ 30%
self-consumption only
Lead-acid battery, ✓ ✖ 5%
battery backup
system
262.03 BUResSOC Minimum width of the 0% … 100% ‒ ✓ ✖ 0%
backup power supply
range on the longest day
of the year as a
percentage of the battery
capacity (expert mode)
262.04 PVResSOC Width of the range for the 4% … 20% ‒ ✓ ✖ 5%
maintenance of the
battery state of charge
(%) of the nominal
capacity (expert mode)
262.05 MinSlfCsmpSOC Minimum width of the 9% … 100% Lithium-ion battery ✓ ✖ 70%
self-consumption range
Lead-acid battery ✓ ✖ 35%
on the shortest day of the
year as a percentage of
the battery capacity
(expert mode)

13.2.2.7 Authent (270#)


No. Name Description
270.01 Auth.Code Entry of the SMA Grid Guard code ✓ ✖

13.2.3 Information (300#)

13.2.3.1 Inverter (310#)

311# Total
No. Name Description
311.01 EgyCntIn Energy consumed by the Sunny Island inverter in kWh ✓ ✓
311.02 EgyCntOut Energy supplied by the Sunny Island inverter in kWh ✓ ✓
311.03 EgyCntTm Run time of the energy meter in hours ✓ ✓

134 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

312# Device
No. Name Description Value Explanation
(plain text no.)
312.01 Adr Device address Master (1) Address ✓ ✓
Slave1 (2) Address
Slave2 (3) Address
312.03 ApplSel Operating mode of the Offgrid Sunny Island is operating in ✓ ✓
Sunny Island (expert the stand-alone grid.
mode)
OnGrid Sunny Island is connected to
the utility grid.
312.05 SysFncSel Selection of the on-grid SelfConsOnly Increased self-consumption ✓ ✖
system only
BackupOnly Battery backup only
SelfConsBackup Battery backup with increased
self-consumption
312.06 FwVer Firmware version of the ‒ ‒ ✓ ✓
central processing unit
of the master
312.07 SN Serial number of the ‒ ‒ ✓ ✓
master
312.08 OnTmh Operating hours ‒ ‒ ✓ ✓
312.09 ClstCfgAt Set configuration of 1Phase1 Single-phase, one ✓ ✓
cluster Sunny Island
1Phase2 Single-phase, two
Sunny Island inverters
1Phase3 Single-phase, three
Sunny Island inverters
3Phase Three-phase, three
Sunny Island inverters
312.10 OpStt Operating state of the Operating (1) Operation ✓ ✓
Sunny Island inverter
Warning (2) Warning
Failure (3) Error

Operating Manual SI30M-44M-60H-80H-BE-en-32 135


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description Value Explanation


(plain text no.)
312.11 CardStt SD memory card status Off (1) No SD memory card inserted ✓ ✓
message
Operational (2) Ready for operation
Mount (3) Initialization
OutOfSpace (4) No storage space available
BadFileSys (5) No file system detected
Incomp (6) File system incompatible
Parameter (7) Parameter set write access
ParamFailed (8) Parameter set write access
failed
WriteLogData (9) Log data write access
312.12 FwVer2 Firmware version of the ‒ ‒ ✓ ✓
logic component
(digital signal
processor)
312.13 FwVer3 Boot loader of the ‒ ‒ ✓ ✓
operation control unit
312.14 FwVer4 Boot loader of the ‒ ‒ ✓ ✓
digital signal processor
312.18 ComMod1 Type of interface in the ‒‒‒ No interface inserted ✖ ✓
interface slot SISysCan
SI-SysCan SI-SYSCAN.BGx inserted
(multicluster system)
312.19 ComMod2 Type of interface in the ‒‒‒ No interface inserted ✓ ✓
interface slot
SI-ComSma SI-COMSMA.BGx inserted
SiComSma
(RS485)
SI-SW-DM SWDMSI-NR inserted
(Speedwire)
312.21 MmcUpdFmVer OCU firmware version − − ✓ ✓
of the update file on the
SD memory card
312.22 MmcUpdFmVer2 DSP firmware version of − − ✓ ✓
the update file on the
SD memory card
312.23 MmcFileSys File system of the SD FAT16 − ✓ ✓
memory card
FAT32 −

313# Slave1
No. Name Description Value Explanation
313.01 FwVerSlv1 Firmware version of slave 1 ‒ ‒ ✓ ✓
313.02 SNSlv1 Serial number of slave 1 (line conductor L2) ‒ ‒ ✓ ✓

136 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation


313.03 OnTmhSlv1 Operating hours of slave 1 in hours ‒ ‒ ✓ ✓
313.04 PhSlv1 Line conductor assignment of slave 1 L1 Line conductor
L1
L2 Line conductor
L2
L3 Line conductor
L3
313.05 OpSttSlv1 Operating state of slave 1 (line conductor L2) Operating Operation ✓ ✓
Warning Warning
Failure Error
313.06 FwVer2Slv1 DSP firmware version of slave 1 ‒ ‒ ✓ ✓
313.07 FwVer3Slv1 OCU boot loader of slave 1 ‒ ‒ ✓ ✓
313.08 FwVer4Slv1 DSP boot loader of slave 1 ‒ ‒ ✓ ✓

314# Slave2
No. Name Description Value Explanation
314.01 FwVerSlv2 Firmware version of slave 2 ‒ ‒ ✓ ✓
314.02 SNSlv2 Serial number of slave 2 (line conductor L3) ‒ ‒ ✓ ✓
314.03 OnTmhSlv2 Operating hours of slave 2 in hours ‒ ‒ ✓ ✓
314.04 PhSlv2 Line conductor assignment of slave 2 L1 Line conductor ✓ ✓
L1
L2 Line conductor
L2
L3 Line conductor
L3
314.05 OpSttSlv2 Operating state of slave 2 (line conductor L3) Operating Operation ✓ ✓
Warning Warning
Failure Error
314.06 FwVer2Slv2 Firmware version of the digital signal processor ‒ ‒ ✓ ✓
of slave 2
314.07 FwVer3Slv2 Boot loader of the operation control unit of ‒ ‒ ✓ ✓
slave 2
314.08 FwVer4Slv2 Boot loader of the digital signal processor of ‒ ‒ ✓ ✓
slave 2

13.2.3.2 Battery (320#)


No. Name Description
320.01 Soh Current battery capacity (SOH) in % ✓ ✓
Ratio of currently usable capacity to the rated value of the battery
320.02 StatTm Run time of statistics counter in days ✓ ✓

Operating Manual SI30M-44M-60H-80H-BE-en-32 137


13 Parameters in Sunny Remote Control SMA Solar Technology AG

No. Name Description


320.03 ChrgFact Charging factor ✓ ✓
320.04 BatEgyCntIn Energy meter for battery charging in kWh ✓ ✓
320.05 BatEgyCntOut Energy meter for battery discharging in kWh ✓ ✓
320.06 AhCntIn Battery charging counter in Ah ✓ ✓
320.07 AhCntOut Battery discharging counter in Ah ✓ ✓
320.08 BatTmpPkMin Minimum battery temperature in °C ✓ ✓
320.09 BatTmpPkMax Maximum battery temperature in °C ✓ ✓
320.10 EquChrgCnt Number of equalization charges of the battery ✓ ✓
320.11 FulChrgCnt Number of full charges of the battery ✓ ✓
320.12 BatCurOfsErr Estimated offset error of battery current in A (expert mode) ✓ ✓
320.13 OcvPointCnt Open-circuit voltage points meter (expert mode) ✓ ✓
320.15 AhCntFul Relative battery discharging since the last full charge in Ah⁄100 Ah ✓ ✓
320.16 AhCntEqu Ampere-hour meter for battery discharging since the last equalization charge ✓ ✓
in Ah⁄100 Ah
320.17 BatVtgPk Maximum battery voltage reached since the last start in V ✓ ✓
320.18 BatCurPkIn Maximum battery current reached since the last start in charge direction in A ✓ ✓
320.19 BatCurPkOut Maximum battery current reached since the last start in discharge direction in A ✓ ✓
320.20 SocHgm100 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 100% to and including 90%, based on time in % (expert mode)
320.21 SocHgm090 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 90% to and including 80%, based on time as % (expert mode)
320.22 SocHgm080 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 80% to and including 70%, based on time as % (expert mode)
320.23 SocHgm070 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 70% to and including 60%, based on time as % (expert mode)
320.24 SocHgm060 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 60% to and including 50%, based on time as % (expert mode)
320.25 SocHgm050 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 50% to and including 40%, based on time as % (expert mode)
320.26 SocHgm040 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 40% to and including 30%, based on time as % (expert mode)
320.27 SocHgm030 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 30% to and including 20%, based on time as % (expert mode)
320.28 SocHgm020 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 20% to and including 10%, based on time as % (expert mode)
320.29 SocHgm010 Percentage frequency distribution of battery state of charge (SOC) when SOC is ✓ ✓
in the range of 10% to and including 0%, based on time as % (expert mode)
320.30 SocHgm000 Frequency distribution of the battery state of charge in relation to time, when SOC ✓ ✓
is equal to 0%, as % (expert mode)

138 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description


320.31 SocVtgCal Recalibration of the battery state of charge based only on open-circuit voltage as ✓ ✓
% (expert mode)
320.32 ErrSocVtgCal Estimated error of the voltage-calibrated battery state of charge as % (expert ✓ ✓
mode)
320.33 SocChrgCal Recalibration of the battery state of charge based only on full charge as % ✓ ✓
(expert mode)
320.34 ErrSocChrgCal Estimated error of the full-charge-calibrated battery state of charge as % (expert ✓ ✓
mode)
320.35 OcvGra Gradient of the open-circuit voltage characteristic curve in Ah⁄V (expert mode) ✓ ✓
320.36 OcvMax Maximum open-circuit voltage in V (expert mode) ✓ ✓

13.2.3.3 External (330#)

331# Grid
No. Name Description
331.01 GdEgyCntIn Energy meter for grid feed-in in kWh ✓ ✓
331.02 GdEgyCntOut Energy meter for purchased electricity in kWh ✓ ✓
331.03 GdEgyTmh Duration for which energy exchange with the utility grid is possible, in hours ✓ ✓
331.04 GdOpTmh Operating hours counter for grid operation in hours ✓ ✓
331.05 GdCtcCnt Number of grid connections ✓ ✓
331.06 TotTmh Feed-in hours ✓ ✓
331.07 GdFailTms Power outage time (s) ✓ ✓

332# Generator
No. Name Description
332.01 GnEgyCnt Released energy from generator in kWh ✖ ✓
332.02 GnEgyTm Duration of energy measurement for the generator in hours ✖ ✓
332.03 GnOpTmh Operating hours counter for generator in hours ✖ ✓
332.04 GnStrCnt Number of generator starts ✖ ✓

13.2.4 Report (400#)


410# Error active
Display of currently pending warnings and errors (see Section 10 "Troubleshooting", page 42).
420# Error history
History of warnings and errors (see Section 10 "Troubleshooting", page 42).

430# Event history


History of events (see Section 10 "Troubleshooting", page 42).

440# Error grid


History of the last five grid errors (see Section 10 "Troubleshooting", page 42).

Operating Manual SI30M-44M-60H-80H-BE-en-32 139


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.5 Operation (500#)

13.2.5.1 Inverter (510#)


No. Name Description Value Explanation Default
value
510.01 InvRs Initiate device restart No Do not restart ✓ ✓ ‒
Yes Restart
510.02 InvTmOpEna Time-controlled inverter Disable Disable ✖ ✓ Disable
operation:
Enable Enable
510.03 InvTmOpStrDt Start date for time-controlled ‒ ‒ ✖ ✓ ‒
inverter operation
in dd.mm.yyyy
510.04 InvTmOpStrTm Time for the start of 00:00:00 … ‒ ✖ ✓ ‒
time-controlled operation 23:59:59
in hh:mm:ss
510.05 InvTmOpRnDur Run time for time-controlled 00:00:00 … ‒ ✖ ✓ ‒
inverter operation in hh:mm:ss 99:59:00
510.06 InvTmOpCyc Repetition cycle for Single Once ✖ ✓ Single
time-controlled inverter
Daily Daily
operation
Weekly Weekly

140 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 13 Parameters in Sunny Remote Control

No. Name Description Value Explanation Default


value
510.07 CntRs Delete energy meter Inv Sunny Island ✓ ✓ ‒
The value indicates which Bat Battery
energy meter is to be deleted.
Gn Generator
Gd Utility grid
All All energy
meters
Sic1 Sunny Island
Charger 1
charge
controller
Sic2 Sunny Island
Charger 2
charge
controller
Sic3 Sunny Island
Charger 3
charge
controller
Sic4 Sunny Island
Charger 4
charge
controller
SicAll All Sunny Island
Charger charge
controllers
510.08 TstClstCom Activation of communication test Off Off ✖ ✓ ‒
between individual clusters
Transmit Enable
(expert mode)
510.09 ClstComStt Status of communication test Wait Waiting ✖ ✓ ‒
(expert mode)
OK Completed

13.2.5.2 Battery (520#)


No. Name Description Value Explanation Default
value
520.01 ChrgSelMan Manual equalization Idle Waiting until conditions are met ✓ ✓ Idle
charge
Start Starting
Stop Stop

Operating Manual SI30M-44M-60H-80H-BE-en-32 141


13 Parameters in Sunny Remote Control SMA Solar Technology AG

13.2.5.3 Generator (540#)


No. Name Description Value Explanation Default
value
540.01 GnManStr Manual generator start Auto Automatic ✖ ✓ Auto
Stop Stop
Start Starting
Run1h Start for 1 hour
540.02 GnAck Acknowledgment of generator Ackn Acknowledge ✖ ✓ ‒
errors

13.2.5.4 MMC card (550#)


No. Name Description Value Explanation
550.01 ParaSto Save parameter settings Set1 Parameter set 1 ✓ ✓
Set2 Parameter set 2
550.02 ParaLod Load parameter settings Set1 Parameter set 1 ✓ ✓
(expert mode)
Set2 Parameter set 2
Factory Load default settings
550.03 CardFunc Functions of the SD ForcedWrite Forced write ✓ ✓
memory card
StoEvtHis Storing event memory
StoFailHis Save error log
StoHis Storing event and fault memory

13.2.5.5 Grid (560#)


No. Name Description Value Explanation Default
value
560.01 GdManStr Manual control of the utility grid Auto Automatic ✖ ✓ Auto
Visible if the parameter Stop Stop
233.01 GdSocEna or
233.08 GdPwrEna is enabled. Start Starting

142 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 14 Parameters in the Communication Product

14 Parameters in the Communication Product


Most parameters of the Sunny Island inverter can be called up and set on the communication product (e.g.
Sunny Explorer or Sunny Portal). Links to additional information can be found at www.SMA-Solar.com:
Document title and content Document type
SUNNY EXPLORER User manual
Call up and set the parameters in Sunny Portal
SUNNY HOME MANAGER in SUNNY PORTAL User manual
Call up and set the parameters in Sunny Portal
SUNNY ISLAND – Comparison of the same parameters for Speedwire Technical information
(e.g. Sunny Explorer) and RS485 (e.g. Sunny Remote Control)

Operating Manual SI30M-44M-60H-80H-BE-en-32 143


15 Sunny Remote Control Menu Structure SMA Solar Technology AG

15 Sunny Remote Control Menu Structure


15.1 User Mode

Figure 19: Menu structure: user mode

144 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 15 Sunny Remote Control Menu Structure

15.2 Installer Mode and Expert Mode

Figure 20: Menu structure: installer mode and expert mode

Operating Manual SI30M-44M-60H-80H-BE-en-32 145


16 Contact SMA Solar Technology AG

16 Contact
If you have technical problems with our products, please contact the SMA Service Line. We need the following
information in order to provide you with the necessary assistance:
• Sunny Island inverter type
• Sunny Island inverter serial number
• Sunny Island inverter firmware version
• Error message displayed
• Type of battery connected
• Nominal battery capacity
• Nominal battery voltage
• Type of the communication products connected
• Type and size of additional energy sources

Australia SMA Australia Pty Ltd. Belgien SMA Benelux BVBA/SPRL


Sydney Belgique Mechelen
Toll free for Australia: 1800 SMA AUS België +32 15 286 730
(1800 762 287) Luxemburg
International: +61 2 9491 4200 Luxembourg
Nederland
Argentina SMA South America SPA Česko SMA Central & Eastern Europe s.r.o.
Brasil Santiago Magyarország Praha
Chile +562 2820 2101 Polska +420 235 010 417

Perú România
Slovensko
Danmark SMA Solar Technology AG France SMA France S.A.S.
Deutschland Niestetal Lyon
Österreich SMA Online Service Center: Sunny Boy, Sunny Mini Central,
www.SMA.de/Service Sunny Tripower : +33 472 09 04 40
Schweiz
Monitoring Systems :
Sunny Boy, Sunny Mini Central, +33 472 09 04 41
Sunny Tripower: +49 561 9522-1499 Sunny Island : +33 472 09 04 42
Monitoring Systems Sunny Central : +33 472 09 04 43
(Kommunikationsprodukte): +49 561
9522-2499
Fuel Save Controller (PV-Diesel Hybrid-
systeme): +49 561 9522-3199
Sunny Island, Sunny Backup,
Hydro Boy: +49 561 9522-399
Sunny Central: +49 561 9522-299
España SMA Ibérica Tecnología Solar, S.L.U. India SMA Solar India Pvt. Ltd.
Portugal Barcelona Mumbai
+34 935 63 50 99 +91 22 61713888

146 SI30M-44M-60H-80H-BE-en-32 Operating Manual


SMA Solar Technology AG 16 Contact

South Africa SMA Solar Technology Ελλάδα SMA Hellas AE


South Africa Pty Ltd. Κύπρος Αθήνα
Centurion (Pretoria) Kıbrıs +30 210 9856666
08600 SUNNY (08600 78669) България
International: +27 (12) 622 3000
Italia SMA Italia S.r.l. United Kingdom SMA Solar UK Ltd.
Milano Milton Keynes
+39 02 8934-7299 +44 1908 304899
SMA Solar (Thailand) Co., Ltd. 대한민국 SMA Technology Korea Co., Ltd.
서울
+66 2 670 6999 +82-2-520-2666
 SMA Middle East LLC Other countries International SMA Service Line
    !   Niestetal
+971 2 234-6177 Toll free worldwide:
00800 SMA SERVICE
(+800 762 7378423)

Operating Manual SI30M-44M-60H-80H-BE-en-32 147


SMA Solar Technology

www.SMA-Solar.com

You might also like