Calculation of Stable Controller Values for Single Area Isolated Power System using Boundary Locus Method
Calculation of Stable Controller Values for Single Area Isolated Power System using Boundary Locus Method
ISSN No:-2456-2165
Abstract:- The power system's operating point fluctuates is provided. Plotting the stability boundary locus in the (kp;
constantly due to its extremely nonlinear nature. As a ki) plane and then determining the stabilising values of a PI
result, both actual and reactive power are impacted by the controller's parameters form the basis of the suggested
extremely low system performance. Real power shifts approach. By solving a series of inequalities without the use
mostly impact the Changes in voltage magnitude are the of linear programming, the method does not need sweeping
primary determinant of changes in reactive power and over the parameters or the Pade approximation. As a result, it
system frequency. Reactive and real capabilities can provides a number of significant benefits above the current
therefore be managed independently. The Automatic findings in this area. In addition to stabilisation, stabilising PI
Voltage Regulator (AVR) regulates the voltage magnitude controllers that meet predetermined gain and phase margins
and, therefore, the reactive power, whereas the Load are calculated using this technique. PID controllers for
Frequency Control (LFC) controls the actual power. The control systems with and without time delay are also designed
regulating of generator power output is known as load using the suggested methodology. The (kp; ki), (kp; kd), and
frequency control, or LFC, in an interconnected system. (ki; kd) planes yield the limiting values of a PID controller
Generally speaking, fixed gain controllers are made for that stabilise a particular system with time delay.
nominal operating settings and don't offer the optimal
control performance under a variety of operating II. BOUNDARY LOCUS METHOD
circumstances. Therefore, it is preferable to monitor
operating circumstances and compute the control using A. Design of Pi Controller
updated parameters in order to maintain system Examine Figure 1's single-input single-output (SISO)
performance close to optimal. Using the "Boundary Locus control system.
Method," a novel approach to identifying stabilising PID
controllers for the LFC control system loop has been put
forth in this study.
I. INTRODUCTION
The system's characteristic polynomial ∆(s) is shown in Hurwitz stability is 1. The characteristic equation from
Fig. Fig. 1 may be expressed as ∆(s)=1+G(s).C(s)
The system's closed loop characteristic polynomial may be
expressed as
The real and imaginary components of ∆(s) are thus equal to zero, yielding
And
Let
Q(ω) = -ω 2N0(-ω 2 ), R(ω) = Ne(-ω 2 ) B. Design of Pid Controllers:
S(ω) = ωNe(-ω 2 ), U(ω) = ωN0(-ω 2 ) Assume that Fig. 1's C(s) is a PID controller of type
X(ω) = ωD0(-ω 2 ), Y(ω) = -ωDe(-ω 2 ) (7)
𝐾𝑖
𝐶(𝑆) = 𝐾𝑝 𝐾𝑑 𝑆 (11)
𝑆
Equations (5) and (6) may therefore be expressed as
The stability boundary locus in the (Kp, Ki) plane can
𝐾𝑝 𝑄(𝜔) + 𝐾𝑖 𝑅(𝜔) = 𝑋(𝜔)
be found by following the steps in Section 1. be readily
produced in the (kp, kd)-plane for a fixed value of ki, or it can
𝐾𝑝 𝑆(𝜔) + 𝐾𝑖 𝑈(𝜔) = 𝑌(𝜔) (8) be acquired for a fixed value of Kd. For a given value of kp,
however, the stability boundary locus in the (ki, kd)-plane
From these equations cannot be obtained because will, in this instance, equal zero.
While the stability area in the (ki,kd) plane for a fixed value
𝑋(𝜔)𝑈(𝜔)−𝑌(𝜔)𝑅(𝜔)
𝐾𝑝 = 𝑄(𝜔)𝑈(𝜔)−𝑅(𝜔)𝑆(𝜔) (9) of Kp is a convex polygon, it is not a convex polygon and
might not even be a convex set in the (kp, li)-plane for a fixed
value of kd or in the (kp,kd)-plane for a fixed value of ki.
And
However, by employing the stability region found in the (kp,
𝑌(𝜔)𝑄(𝜔)−𝐾(𝜔)𝑆(𝜔) ki) plane and (kp, kd)-plane as follows, the stability region in
𝐾𝑖 = 𝑄(𝜔)𝑈(𝜔)−𝑅(𝜔)𝑆(𝜔) (10) the (ki, kd)-plane may be determined for a fixed value of kp.
Substituting Ki in terms of Kd
𝜔2 𝑁0 𝐷𝑒 − 𝑘𝑑 𝜔4 𝑁02 − 𝜔2 𝑁𝑒 𝐷0 − 𝐾𝑑 𝜔2 𝑁𝑒2
𝐾𝑖 =
−𝜔 2 𝑁02 − 𝑁𝑒2
Thus, the stability areas in the (kp, ki) and (kp, kd) planes may be found using these equations.
III. BASIC GENERATION CONTROL LOOPS moment of inertia-time constant, the power frequency control
is slow acting and the excitation control is rapid acting. As a
Each generator in an integrated power system has its result, the load frequency and excitation voltage control are
own LFC and AVR control loop. Fig. 2 shows the schematic examined separately, and there is very little cross coupling
representation of the voltage and frequency control loop. The between the LFC loop and the AVR. Active and reactive
frequency and voltage magnitude are kept within the power demands in a power system are never constant; they
designated bounds by the controllers, which are configured fluctuate constantly in response to growing or dropping
for a certain operating state and handle slight variations in trends.
load demand. Variations in the rotor angle δ and,
consequently, the frequency f, are the primary determinants While reactive power is primarily dependent on changes
of slight variations in actual power. The magnitude of the in voltage magnitude and less sensitive to frequency
voltage, or the generator excitation, is the primary variations, changes in actual power have an impact on the
determinant of reactive power [4]. A brief variation in system frequency. System generation control's primary goal
generator speed results in a change in angle . For minor is to maintain the intended frequency and power exchanges
variations, load frequency and excitation voltage controls are across adjacent systems by balancing system generation
therefore non-interactive and amenable to separate modelling against load and losses. The Automatic Voltage Regulator
and analysis. Additionally, because the generating field's time (AVR) and the Load Frequency Controller (LFC) are a
constant is significantly less than the turbine's and generator's generation's two primary control loops.
IV. LOAD FREQUENCY CONTROL It could not be cost-effective to send all of the data over
great distances. The control, which depends on load demand,
In the design and operation of electrical power systems, is a function of the states. Realising the ideal controller may
load frequency management is crucial. depend on an accurate load demand prediction.
Furthermore, an LFC system that controls generator By controlling the system frequency, LFC seeks to
loading based on frequency must be designed in order to preserve the system's actual power balance. There is a
guarantee the quality of the power supply. For the following frequency variation whenever the actual power demand
reasons, conventional controllers are frequently impractical varies. The turbine governor receives this frequency error
for implementation. All of the system's states influence the after it has been amplified, combined, and converted into a
ideal control. In reality, not every state could be accessible. It command signal. By altering the turbine's output, the
is necessary to assess the states that are unavailable or absent. governor works to bring the input and output back into
balance.
Table 1: LFC
S.No Block Gain Time Constant
1 Governor Kg=1 Tg=0.2 Sec
2 Turbine Kt=1 Tt=0.5 Sec
3 Generator Inertia Constant H=5 Sec
4 Governor Speed Regulation R=0.05 Per Unit
5 The load varies by 0.8 percent for a 1 percent change in frequency, i.e D=0.8
A. Design of Pi Controller
Single Area Load Frequency Control's analogous transfer function is provided by
△ 𝜴(𝑆) (1 + 𝑇𝑔 𝑠)(1 + 𝑇𝑡 𝑠)
𝐺(𝑆) = =
△ 𝑷𝑳 (𝑺) (2𝐻𝑠 + 𝐷)(1 + 𝑇 𝑆)(1 + 𝑇 𝑆) + 1
𝑔 𝑡 𝑅
(1 + 0.2𝑠)(1 + 0.5𝑠)
𝐺(𝑆) =
1
(2 ∗ 5𝑠 + 0.8)(1 + 0.2𝑆)(1 + 0.5𝑆) +
0.05
0.1𝑆 2 + 0.7𝑆 + 1
𝐺(𝑆) =
𝑆3 + 7.08𝑆 2 + 10.56𝑆 + 20.8
Substituting S = j ω;
(−0.1𝜔2 + 1) + 𝑗𝜔(0.7)
𝐺(𝑆) =
(−7.08𝜔 3 + 20.8) + 𝑗𝜔(−𝜔 2 + 10.56)
𝑎1 𝜔7 + 𝑎2 𝜔5 + 𝑎3 𝜔3
𝐾𝑖 =
−0.01𝜔 5 −0.29𝜔 3 − 𝜔
Fig 4: Stability Region in the (Kp, Ki) plane for Kd=0 and Kd=1
Fig 5: Stability Region in the (Kp, Ki) Plane for Ki=0 and Ki=1
From the above two graphs we obtain 8 points for Kp= 𝐾𝑑 = 0.015𝐾𝑖 c -5.71, 𝐾𝑑 =0
0 are (36.57, 0), (42.97, 1), (0, 0), (0, 1), (0, - 5.71), (1, -5.55),
(0, 0), (1, 0) 𝐾𝑑 = 0.016𝐾𝑖 c -5.71, 𝐾𝑑 =0
From these we obtain 4 straight lines Now, sketch these lines' patch shape. Plots for Kp, Ki,
and Kd are now available.
Fig 8: Plot for Change in Frequency for a Step Load Change of 0.1 p.u
Fig 9: Plot for Change in Frequency for a Step Load Change of 0.1 p.u
REFERENCES