6.

ElevatorLogic and Parameters

Function Description Setting range (default value)

Hall call fire input logic


LF0.66 0:normally open 0
1:normally closed

Function Description Setting range (default value)

Hall call fire switch floor setting


LF0.67 0:normally open 1
1:normally closed

Function Description Setting range (default value)

LF0.68 UPS distance of operation cancel 0~65535【40】


UPS distance of operation cancel :mm。

Function Description Setting range (default value)

LF0.69 Door dwell time duringearthuake operation 0~65535【0】


Door dwell time duringearthuake operation :s。

Function Description Setting range (default value)

LF0.70 PM contactor release delay 0~65535【0】


PM contactor release delay :ms.

Function Description Setting range (default value)

Hall call lock input logic


LF0.71 0:normally open 0
1:normally closed

Function Description Setting range (default value) 6. ElevatorLogic and Parameters

Hall call lock switch floor setting


LF0.72 0:normally open 1
1:normally closed

Function Description Setting range (default value)

LF0.76 Minimum distance of connected to the two 0~65535【300】


door zone
Set minimum distance of connected to the two door zone, unit:mm.

Function Description Setting range (default value)

LF0.77 Response time of nixie tube and button 0~65535【15】


unit:ms。

Function Description Setting range (default value)

-97-
6. ElevatorLogic and Parameters

LF0.83 Pulse number limit when stationary 0~65535【0】


0:Within 5 pulse ..
N:Within N+5 pulse.

Function Description Setting range (default value)

LF0.84 DWELLspeed on start 0~65535mm/s【0】

LF0.85 DWELLtime on start 0~65535ms【0】


DWELL function DESCRIPTION:
Maintain output frequency in a short time when load is bigger, avoid motor stalling.
Function Description Setting range (default value)
LF0.89 Er54# detection time 0~65535【0】
Setting Er54# detection time:
Default value:0ms=200ms unit:ms。

 Not docked within stated time:


Step 1. Using this function。

Function Description Setting range (default value)


LF0.38 Not docked within stated time 0~65535【0】
Choice timed blind floor 。
0:Cancel this function.
1:Using this function.
Step 2. Set starting time of floor that need the function

Function Description Setting range (default value)


st
LF2.01 1 floor starting time hh-mm【00-00】
st
LF2.02 2 floor starting time hh-mm【00-00】

…… …… ……
st
LF2.64 64 floor starting time hh-mm【00-00】
6. ElevatorLogic and Parameters

Step 3. Set end time of floor that need the function

Function Description Setting range (default value)


st
LF3.01 1 floor end time hh-mm【00-00】
st
LF3.02 2 floor end time hh-mm【00-00】

…… …… ……
st
LF3.64 64 floor end time hh-mm【00-00】

 Password setting

Function Description Setting range (default value)

P0.00 Nidec only pass code 00000 – 99999 [*****]

P0.01 Intermediate pass code 00000 – 99999 [12345]

-98-
6. ElevatorLogic and Parameters

P0.02 Basic pass code 00000 – 99999 [00000]


The above parameters are used to set system pass codes. Fusion provides 3 different
permissions for pass code configuration.
P0.00 Advanced pass code, used by manufacturer.
P0.01 Read and change parameters. Default is 12345.
P0.02 Monitor/Read only. Default is 00000.。

 Restore Default Values

Function Description Setting range (default value)

P1.00 Restore default values 0000 – 9999 [valid after power off]
[1118]
1118: No operation (returns to this after default has been activated by below settings)
2227: Restore control parameters
3336: Restore motor control parameters
5554: Restore all parameters。
Other setting values: reserved

 Power off after restoring default values

 Clear fault records

Function Description Setting range (default value)

6. ElevatorLogic and Parameters


P1.01 Clear fault records 0 - 2 [0]
0: No operation
1: Clear control faults
2: Clear motor control related faults.

 Elevator with door open stayed in door zone. Spin inspection and normal
button 3 times within 5s ,can clear fault record.

 Clock setting

-99-
6. ElevatorLogic and Parameters

Function Description Setting range (default value)

P2.00 Year setting yyyy [2000]

P2.01 Day /month setting mm-dd [00-00]

P2.02 Minute / hour setting hh-mm [00-00]

P2.03 Second setting ss [00]

 When the clock setted , P2 parameters will be saved.,Please press the ENTER to
change P2, then review P2 , avoid storage unsuccessful
6. ElevatorLogic and Parameters

-100-
7. Fusion Installation in an Enclosure

7. Fusion Installation in an Enclosure

Please refer to Chapter 3

7. Fusion Installation in an Enclosure

-101-
7. Fusion Installation in an Enclosure

 COP & LOP Installation , wiring ,and adjustment


 K-06T Funcitional Specification

No. Function Description

1. Status Display Display status graphics according to controller

2. Background display Standard or user-provided graphic。

3. Time display User settable.

Advertisement
4. Display advertisement by time-cycle or floor number
display

5. Temperature display Display current temperature if desired.

6. LOGO diaplay Custom LOGO as needed

7. LElevator locking Elevator locking input

8. Fire service Fire recall input

Arrival chime &


9. Four outputs support arrival chime & direction preference
direction preference

10. Hall call Hall call UP and DOWN support

 K-06T Alphanumeric Display Characters


7. Fusion Installation in an Enclosure

 K-06T Status Display Indicators

Up Down Inspection ERR Over Load Fire

Full Load Attendant Earthquake VIP UPS Locking

-102-
7. Fusion Installation in an Enclosure

 K-06T installation
1. Caution

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.
• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials

• Install in place that absence of harmful gases and liquids.


• Install in place less salt and vibration.

• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter
• Make sure that electronic devices do not collide with other things.

2. Install direction

Arrow to
vertical
installation

Arrow to
Horizontal
installation

7. Fusion Installation in an Enclosure

-103-
7. Fusion Installation in an Enclosure

3. Mounting dimension
W H W1 H1 Mounting hole diameter PCBA thickness
168mm 135mm 160mm 127mm 3.5mm 25mm

 K-06T Description

Content Schema

Term Sym Terminal description (Default) Default


CN1 V- COMM
7. Fusion Installation in an Enclosure

UP Up call signal input


V+ Output +
L0 Output -
CN2 V- COMM
DN Down call signal input
V+ Output +
L1 Output -
CN3 V- COMM
LK Elevator locking signal input
V+ Output +
L2 Output -

CN4 V- COMM
FR Fire service signal input

-104-
7. Fusion Installation in an Enclosure

Term Sym Terminal description (Default) Default


V+ Output +
L3 Output -
CN6 V+ Output + Interface: XH-6
T3 Reserved When load current is less than 400mA.
If the load is greater than 400mA, use
Up indicator output
T2 K- 07K.
T1 Down indicator output
T0 Arrival chime output
V- Output -
CN7 —— PC programming
CN8 —— Programming terminal
CN9 —— Programming terminal
CN10 —— Spare
CN11 —— SWD interface
CN13 CANH CAN interface + Interface: XH-5
CANL CAN interface -
——
GND DC 24V-
24V DC 24V+ DC24V±15%
CN14 —— SD Card
S2 —— Function selection
RUN MODE CONFIGURATION
Mode 1 2 3 4 Power
Set On Off On
Run Off Off - On
ISP On Off - On
Demo Off Off On On
Term Resistor On On

D1 —— UP Call Indicator N/A


D4 —— Down Call Indicator N/A
D7 —— Spare N/A
D10 —— Spare N/A
D14 —— Output Indicator(T0) N/A
D16 —— Output Indicator(T1) N/A
—— Output Indicator(T2) N/A
7. Fusion Installation in an Enclosure
D17
D18 —— Output Indicator(T3) N/A
Serial port receives the signal,
D24 —— N/A
flashing after power on
Serial port receives the signal, flashing
D25 —— after power on N/A

D26 —— CAN port receives the signal, flashing N/A


D27 —— after power
Signal on ,port sends the signal N/A
Indicator
D32 —— Power Indicator 5V indicator
D33 —— Power Indicator 3.3V indicator

-105-
7. Fusion Installation in an Enclosure

 K-06T Wiring
1. Description

No. Function Description Remark


Supply and communication XH-5 terminal+shielded twisted
1. standard configuration
bus interface pair extension cable
XH-4 terminal +four-core 0.3mm2
2. UP-call button standard configuration
extension cable
XH-4 terminal + four-core 0.3mm2
3. DOWN-call button standard configuration
extension cable
Arrival chime & direction XH-6 terminal + six-core 0.3mm2
4. standard configuration
preference interface extension cable
XH-4 terminal + two-core 0.3mm2
5. Elevator locking interface standard configuration
extension cable
XH-4 terminal + two-core 0.3mm2
6. Fire service interface standard configuration
extension cable

2. Caution

CAUTION
• Wiring according to the manual , otherwise ,there may be lead to risk of controller damage.

• Power and CAN communication interface must use shielded twisted pair cable, otherwise it
will lead to the display controller does not work.

• Power and CAN communication connection cables should as bold as possible, otherwise it
will lead to the display controller does not work.

• Ground terminal must be standardized and reliable, otherwise ,there may be lead to risk of
damage to the controller and the system does not work.

INDICATE
• Ensure all terminals must be reliable , otherwise it will lead to the display controller does
not work.
• Avoid something falling into the controller box , otherwise ,there may be lead to risk of
controller damage.

• Do not sharethe grounding wire and power equipment.


7. Fusion Installation in an Enclosure

• Power and communication shielded twisted pair cable must be grounded, and to the control
cabinet PE port.

• COP / LOP must be grounded.

• Shorten the grounding wires as much as possible .

-106-
7. Fusion Installation in an Enclosure

3. K-06T Wiring Description


a) Power and CAN wiring description

K-03T & K-06T


24V
GND

CANL
CANH Shielded Twisted Cable cable shield

Power & CAN wiring mode

b) Call control and fire service and Elevator locking explanation

K-03T & K-06T K-03T & K-06T K-03T & K-06T


V- UP V+ L0 V- DN V+ L0 V- UP V+ L0 V- DN V+ L0 V- LK V+ L0 V- FR V+ L0

Wiring type of four-wire Wiring type of three-wire Wiring type of fire


button button service & locking

c) Parallel wiring instructions

L0 L0
K-03T & K-06T

K-03T & K-06T

V+ V+
DN DN
V- V-

L0 L0
V+ V+
UP UP
V- V-

Wiring type of sharing button


7. Fusion Installation in an Enclosure

d) Arrival chime & direction preference wiring instructions


K-03T & K-06T

V-

T0

T1

T2

T3

V+

Wiring type of hall arrival chime /direction


preference 1

If the current demand of the arrival chime/ lantern exceeds 400 mA , Using K-07K:

-107-
7. Fusion Installation in an Enclosure

V-
External

K-03T & K-06T


V-
V- V+ power
T0

K-07K
T0 V-
T1
T1 T0
T2
T2 T1
T3
V+ T2
V+
V+

Wiring type of hall arrival chime /direction


preference 2

 K-06T Configuration
1. Programming Interface

No. Interface Description

DIP switch Enter Parameter setting interface:


Switch 1 ON – all others OFF
1.
Exit parameter setting interface:
All switches OFF
Menu Selection:
Increment menus
2. UP call button
Parameter Selection:
Increase numeric parameter value
Menu Selection:
Decrement menus
3. Down call button
Parameter Selection:
Decrease numeric parameter value
Elevator locking Change on/off or enable/disable settings.
4.
button
Enter selected menu.
5. Fire service button
Exit and save.
7. Fusion Installation in an Enclosure

-108-
7. Fusion Installation in an Enclosure

2. Programming Interface
Language Selection:
Menu Display Parameters setting and descripition
K-06T CONFIG • Select Chinese or English by briefly
shorting Lock input LK to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING
<2>F:FUNCTION SELECT
• Please saved parameters and power off.
<3>G:GROUP NUMBER SETTING
<4>V:VERSION NUMBER • There will introduce in English.
<5>E:SPECIFIC FUNCTION
<6>B:CANBUS BAUDRATE SETTING • K-O6T as an example
<7>T:CHIME TIME SETTING
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH
<10>ADVERTISING MODE
<11>DATE&TIME SETTING
<12>FACTORY RESET
<13>SAVE&QUIT

MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Floor Number Setting:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN
ENGLISH(英文)/中文简体(Chinese) input DN or UP to V-.
<1>K:FLOOR NUMBER SETTING
<2>F:FUNCTION SELECT • Enter menu by briefly shorting Fire input FR
<3>G:GROUP NUMBER SETTING
<4>V:VERSION NUMBER
to V-. A box with a floor number in it will
<5>E:SPECIFIC FUNCTION appear.
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING • Briefly short UP or DOWN input UP or DN to
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH V- to set to appropriate floor for hall call
<10>ADVERTISING MODE
<11>DATE&TIME SETTING fixture or to 7. Fusion Installation in an Enclosure
<12>FACTORY RESET
<13>SAVE&QUIT • Zero (0) is the unit is to be used as a position
indicator.
FLOOR NUMBER
ME 0 • Exit menu by briefly shorting Fire input FR to
V-.
NU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-109-
7. Fusion Installation in an Enclosure

Function Select:
Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN
input DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION
<1>LIFT LOCK SELECT [DISABLE]
<3>G:GROUP NUMBER SETTING
<2>FIRE SERVICE [DISABLE] V-.
<4>V:VERSION NUMBER
<3>BUZZLE ENABLE [DISABLE]
<5>E:SPECIFIC FUNCTION
<4>INSPECTION ENERGY SAVE • Briefly short UP or DOWN input UP or DN to V-
<6>B:CANBUS BAUDRATE SETTING
[DISABLE]
<7>T:CHIME TIME SETTING
<5>FIRE [NORMAL OPEN]
to move to desired selections.
<8>DISPLAY
<6>LOCK DIRECTION
ENERGY SAVE SETTING
[DISABLE]
<9>UPDATE FLASH [NORMAL OPEN]
<7>LOCK • Briefly short Lock input LK to V- to change
<10>ADVERTISING MODE [DISABLE]
<8>FIRE OUTSIDE DISP
<11>DATE&TIME SETTING value.
<12>FACTORY RESET
<13>SAVE&QUIT • When all settings are as desired, briefly short
Fire input FR to V- to exit.

MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Group Number Setting:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN
input DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Briefly short UP or DOWN input UP or DN to V-
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING to increment/decrement group assignment.
7. Fusion Installation in an Enclosure

<8>DISPLAY DIRECTION SETTING


<9>UPDATE FLASH • Exit menu by briefly shorting Fire input FR to V-.
<10>ADVERTISING MODE
<11>DATE&TIME SETTING
<12>FACTORY RESET
<13>SAVE&QUIT

GROUP NUMBER
0

ENU DIRECTIONS
[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-110-
7. Fusion Installation in an Enclosure

Version Number:
Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN
input DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Software versions will be displayed.
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING • Exit menu by briefly shorting Fire input FR to
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH V-.
<10>ADVERTISING MODE
<11>DATE&TIME SETTING
K-06T VER 1.0 RESET
<12>FACTORY
<13>SAVE&QUIT
<1>P:Software Version:1.0
<2>D:Software Version:1.0

MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Specific Function:
Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input
DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to V-.
<2>F:FUNCTIONINDICATION
<1>DIRECTION SELECT
<3>G:GROUP NUMBER SETTING
<4>V:VERSIONFUNCTION
[DISABLE]
NUMBER [DISABLE]
• Briefly short UP or DOWN input UP or DN to V- to
<2>HANDICAP
<5>E:SPECIFIC FUNCTION [DISABLE]
<3>RESERVE move to desired selections.
<6>B:CANBUS BAUDRATE SETTING
<4>RESERVE [DISABLE]
• Briefly short Lock input LK to V- to change value.
7. Fusion Installation in an Enclosure
<7>T:CHIME TIME SETTING[DISABLE]
<5>RESERVE
<8>DISPLAY DIRECTION SETTING
<6>RESERVE [DISABLE]
<9>UPDATE FLASH
<7>RESERVE [DISABLE]
<10>ADVERTISING MODE [DISABLE]
<8>RESERVE • When all settings are as desired, briefly short Fire
<11>DATE&TIME SETTING input FR to V- to exit.
<12>FACTORY RESET
<13>SAVE&QUIT

MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-111-
7. Fusion Installation in an Enclosure

Chime Time Setting:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input
DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Briefly short UP or DOWN input UP or DN to V- to
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING move to desired time setting (mS).
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH • Briefly short LK to V- to select associated Chime
<10>ADVERTISING MODE
<11>DATE&TIME SETTING Time (duration) or Time Space (interval between
‘T’ ARRIVAI CHIME
<12>FACTORY RESET
TIME chimes).
<13>SAVE&QUIT
<1>CHIME TIME [3000ms]
<2>TIME SPACE [3000ms]
• With both selection and time setting highlighted,
short UP or DOWN input UP or DN to V- to
increase or decrease time value.
MENU DIRECTIONS
• Briefly short Fire input FR to V- to exit.
[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Display Direction Setting:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN
input DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Set Horizontal or Vertical by briefly shorting UP
<6>B:CANBUS BAUDRATE SETTING
or DOWN input DN or UP to V-. Note that, on the
7. Fusion Installation in an Enclosure

<7>T:CHIME TIME SETTING


<8>DISPLAY DIRECTION SETTING back of the circuit board there are arrows
<9>UPDATE FLASH
<10>ADVERTISING MODE indicating the board edge that will be on top to
<11>DATE&TIME SETTING
<12>FACTORY RESET
help you orient the display.
<13>SAVE&QUIT
• Briefly short Fire input FR to V- to exit.
DISPLAY MODE [VERTICAL]

MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-112-
7. Fusion Installation in an Enclosure

Advertising Mode:
Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input
DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Briefly short UP or DOWN input UP or DN to V- to
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING change the numeric value.
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH 0 = display single pictures without switching
<10>ADVERTISING MODE
<11>DATE&TIME SETTING 1 = pictures switches according the floors
<12>FACTORY RESET
<13>SAVE&QUIT
2 = pictures switch according to destination floor
ADVERTISING MODE 5
3 – 5000 = pictures switch to the corresponding
numerical cycle, Unit = sec, Default = 5.
MENU DIRECTIONS
• Briefly short Fire input FR to V- to exit
[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Update Flash:
Menu Display Parameters setting and descripition
K-06T CONFIG • If you are using an SD card to update software,
first insert the card into the board slot, then:
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Go to entry by briefly shorting UP or DOWN input
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING DN or UP to V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Enter menu by briefly shorting Fire input FR to V-.
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING • The update from the SD card will proceed
<8>DISPLAY DIRECTION SETTING 7. Fusion Installation in an Enclosure
<9>UPDATE FLASH automatically.
<10>ADVERTISING MODE
<11>DATE&TIME SETTING
<12>FACTORY RESET
<13>SAVE&QUIT

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-113-
7. Fusion Installation in an Enclosure

Date & Time Setting:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input
DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Enter menu by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Briefly short UP or DOWN input UP or DN to V- to
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING select time increment.
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH • When desired time increment is highlighted,
<10>DATE&TIME SETTING
<11>FACTORY RESET briefly short LK to V- to select corresponding
<12>SAVE&QUIT
DATE & TIME SETTING (year,
YEAR [2014]
M ONTH
DATE
[ 01]
[ 08]
• month, date, etc.).
D AY [ 03]
HOUR [ 2 0] • Briefly short UP or DOWN input UP or DN to V- to
MINUTE [ 42[ set desired value.
• Briefly short Fire input FR to V- to exit.
MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

Factory Reset::
Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input DN
or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Initiate Reset by briefly shorting Fire input FR to V-.
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING • Board will automatically reset to factory values.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION
7. Fusion Installation in an Enclosure

<6>B:CANBUS BAUDRATE SETTING


<7>T:CHIME TIME SETTING
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH
<10>ADVERTISING MODE
<11>DATE&TIME SETTING
<12>FACTORY RESET
<13>SAVE&QUIT

Factory Reset
MENU DIRECTIONS

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

-114-
7. Fusion Installation in an Enclosure

Save and Quit:


Menu Display Parameters setting and descripition
K-06T CONFIG • Go to entry by briefly shorting UP or DOWN input
DN or UP to V-.
ENGLISH(英文)/中文简体(Chinese)
<1>K:FLOOR NUMBER SETTING • Initiate Save by briefly shorting Fire input FR to
<2>F:FUNCTION SELECT
<3>G:GROUP NUMBER SETTING V-.
<4>V:VERSION NUMBER
<5>E:SPECIFIC FUNCTION • Board will automatically save setting values.
<6>B:CANBUS BAUDRATE SETTING
<7>T:CHIME TIME SETTING
<8>DISPLAY DIRECTION SETTING
<9>UPDATE FLASH
<10>ADVERTISING MODE
<10>DATE&TIME SETTING
<11>FACTORY RESET
<12>SAVE&QUIT

MENU DIRECTIONS
Save Successful!

[Down:3-4][Up:3-4]:Select Item
[F i r e:3-4][Lock:3-4]:Enter/Quit

Fire Lock Down Up


[3-4] [3-4] [3-4] [3-4]

7. Fusion Installation in an Enclosure

-115-
7. Fusion Installation in an Enclosure

 K-03T Installation , wiring ,and adjustment


 K-03T Funcitional Specification

No. Function Description

1. Status Display Display status graphics according to controller

2. Background display Standard or user-provided graphic。

3. LOGO diaplay Custom LOGO as needed

4. Elevator locking Elevator locking input

5. Fire service Fire recall input

Arrival chime &


6. Four outputs support arrival chime & direction preference
direction preference

7. Hall call Hall call UP and DOWN support

 K-03T Alphanumeric Display Characters

 K-03T Status Display Indicators

Up Down Inspection ERR Over Load Fire


7. Fusion Installation in an Enclosure

Full Load Attendant Earthquake VIP UPS Locking

-116-
7. Fusion Installation in an Enclosure

 K-03T installation
1. Caution
CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.

• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials


• Install in place that absence of harmful gases and liquids.

• Install in place less salt and vibration.


• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter

• Make sure that electronic devices do not collide with other things.

2. Install direction

Arrow to
vertical
installation

7. Fusion Installation in an Enclosure

Arrow to
Horizontal
installation

-117-
7. Fusion Installation in an Enclosure

3. Mounting dimension
W H W1 H1 Mounting hole diameter PCBA thickness
160mm 84mm 150mm 74mm 3.5mm 12mm

 K-03T Description

Content Schema

Term Sym Terminal description (Default) Default


CN1 —— Spare NA
CN2 CANH CAN interface + Interface: XH-5
CANL CAN interface -
——
GND DC 24V-
24V DC 24V+ DC24V±15%
CN3 V+ Output + Interface: XH-6
7. Fusion Installation in an Enclosure

T3 Spare When load current is less than 400mA.


T2 Up arrival output If the load is greater than 400mA, use K-
T1 Down arrival output 07K.
T0 Arrival chime output
V- Output -
CN4 —— SWD programming interface
CN6 —— Programming interface
CN7 —— Spare
CN8 —— Programming interface
CN10 —— SD card socket
CN11 V- COMM
FR Fire service signal input
V+ Output +
L3 Output -
CN12 V- COMM

-118-
7. Fusion Installation in an Enclosure

Term Sym Terminal description (Default) Default


LK Elevator locking signal input
V+ Output +
L2 Output -
CN13 V- COMM
DN Down call signal input
V+ Output +
L1 Output -
CN14 V- COMM
UP Up call signal input
V+ Output +
L0 Output -
RST —— RST
S2 —— Function selection RUN MODE CONFIGURATION
Mode 1 2 3 4 Power
Set On Off On
Run Off Off - On
ISP On Off - On
Demo Off Off On On
Term Resistor On On

D5 Power Indicator 5V indicator


D6 Power Indicator 3.3V indicator
Serial port receives the signal, flashing
D7 Signal Indicator
after power on
Serial port receives the signal, flashing
D8 Signal Indicator
after power on
CAN port receives the signal, flashing after
D9 Signal Indicator
power on
D10 Signal Indicator Signal Indicator ,port sends the signal
D13 Output Indicator Output Indicator(T0)
D14 Output Indicator Output Indicator(T1)
D15 Output Indicator Output Indicator(T2)
D16 Output Indicator Output Indicator(T3)
D27 Spare Spare
D28 Spare Spare 7. Fusion Installation in an Enclosure
D29 Down Call Indicator
D30 UP Call Indicator

 K-03T Wiring
1. Description
No
Function Description Remark
.
Supply and communication XH-5 terminal+shielded twisted pair Standard
1.
bus interface extension cable configuration
UP-call button XH-4 terminal +four-core 0.3mm2 Standard
2.
extension cable configuration
DOWN-call button XH-4 terminal + four-core 0.3mm2 Standard
3.
extension cable configuration

-119-
7. Fusion Installation in an Enclosure

Arrival chime & direction XH-6 terminal + six-core 0.3mm2 Standard


4.
preference interface extension cable configuration
Elevator locking interface XH-4 terminal + two-core 0.3mm2 Standard
5.
extension cable configuration
Fire service interface XH-4 terminal + two-core 0.3mm2 Standard
6.
extension cable configuration

2. Caution

CAUTION
• Wiring according to the manual , otherwise ,there may be lead to risk of controller damage.

• Power and CAN communication interface must use shielded twisted pair cable, otherwise it
will lead to the display controller does not work.

• Power and CAN communication connection cables should as bold as possible, otherwise it
will lead to the display controller does not work.

• Ground terminal must be standardized and reliable, otherwise ,there may be lead to risk of
damage to the controller and the system does not work.

INDICATE

• Ensure all terminals must be reliable , otherwise it will lead to the display controller does
not work.

• Avoid something falling into the controller box , otherwise ,there may be lead to risk of
controller damage.

• Do not sharethe grounding wire and power equipment.

• Power and communication shielded twisted pair cable must be grounded, and to the control
cabinet PE port.

• COP / LOP must be grounded.

• Shorten the grounding wires as much as possible .


7. Fusion Installation in an Enclosure

3. K-03T wiring
Please refer to K-06T wiring

 K-03T adjusting
Please refer to K-06T adjusting

-120-
7. Fusion Installation in an Enclosure

 K-PI1000 Installation , wiring ,and adjustment


 K-PI1000 Funcitional Specification

No. Function Description

1. Dot matrix display Set floor or character according to controller

2. Status Display Display status graphics according to controller

3. Elevator locking Elevator locking input

4. Fire service Fire recall input

Arrival chime &


5. Four outputs support arrival chime & direction preference
direction preference

6. Hall call Hall call UP and DOWN support

Slim COP and LOP


7. Thickness of PCBA Is 13mm.
control

 K-PI1000 Alphanumeric Display Characters

0 1 2 3 4 5 6 7 8 9

A B C D E F G H I J

K L M N O P Q R S T

U V W X Y Z
7. Fusion Installation in an Enclosure

 K-PI1000 Status Display

UP DOWN INSPECTION EARTHQUAKE OVER LOAD UPS

FIRE
LOCKING Err VIP ATTENDANT FULL LOAD
SERVICE

-121-
7. Fusion Installation in an Enclosure

 K-PI1000 installation
1. Caution

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.
• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials


• Install in place that absence of harmful gases and liquids.

• Install in place less salt and vibration.


• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter
• Make sure that electronic devices do not collide with other things.

2. Install direction

Install direction as
arrow:

3. Mounting dimension
7. Fusion Installation in an Enclosure

W H W1 H1 Mounting hole diameter PCBA thickness


140mm 60mm 130mm 50mm 4mm 13mm

 K-PI1000 Description

-122-
7. Fusion Installation in an Enclosure

Content Schema

Term Sym Terminal description (Default) Default


JP1 —— CAN
JP2 V- COMM
UP Up call signal input
V+ Output +
L1 Output -
JP3 V- COMM
DN Down call signal input
V+ Output +
L2 Output -
JP4 LK Elevator locking signal input
V- COMM
JP5 FR Fire service signal input
V- COMM

JP6 V+ Output + When load current is less than 400mA.


T3 Reserved If the load is greater than 400mA, use
T2 Up indicator output K- 07K.
T1 Down indicator output
T0 Arrival chime output
V- Output -
7. Fusion Installation in an Enclosure

JP7 —— Programming
JP8 —— Firmware upgrade
JP9 CANH CAN interface H Interface: VH-4
CANL CAN interface L
GND DC 24V- DC24V±15%
24V DC 24V+
SW1 —— Double-click for menu entry
LE1 —— CAN Indicator
LE2 —— Multifunctional Indicator (optional)
LE3 —— Multifunctional Indicator (optional)
LE4 —— Up Call Indicator
LE5 —— Down Call Indicator

-123-
7. Fusion Installation in an Enclosure

 K-PI1000 Wiring
1. Description
No. Function Description Remark
Supply and
1. XH-5 terminal+shielded twisted pair Standard
communication bus
extension cable configuration
interface
XH-4 terminal +four-core 0.3mm2 Standard
2. UP-call button interface
extension cable configuration
DOWN-call button XH-4 terminal + four-core 0.3mm2 Standard
3.
interface extension cable configuration
Arrival chime & direction XH-6 terminal + six-core 0.3mm2 Standard
4.
preference interface extension cable configuration
Elevator locking XH-4 terminal + two-core 0.3mm2 Standard
5.
interface extension cable configuration
XH-4 terminal + two-core 0.3mm2 Standard
6. Fire service interface
extension cable configuration

2. Caution

CAUTION
• Wiring according to the manual , otherwise ,there may be lead to risk of controller damage.

• Power and CAN communication interface must use shielded twisted pair cable, otherwise it
will lead to the display controller does not work.

• Power and CAN communication connection cables should as bold as possible, otherwise it
will lead to the display controller does not work.

• Ground terminal must be standardized and reliable, otherwise ,there may be lead to risk of
damage to the controller and the system does not work.

INDICATE
• Ensure all terminals must be reliable , otherwise it will lead to the display controller does
not work.
• Avoid something falling into the controller box , otherwise ,there may be lead to risk of
controller damage.

• Do not sharethe grounding wire and power equipment.


7. Fusion Installation in an Enclosure

• Power and communication shielded twisted pair cable must be grounded, and to the control
cabinet PE port.

• COP / LOP must be grounded.

• Shorten the grounding wires as much as possible .

-124-
7. Fusion Installation in an Enclosure

3. Wiring
a) Power and CAN wiring description

K-PI1000
24V
GND

CANL
CANH
Shieidd Twisted Cable cable shield

Power & CAN wiring mode

b) Call control and fire service and Elevator locking explanation

K-PI1000 K-PI1000 K-PI1000


V- UP V+ L0 V- DN V+ L0 V- UP V+ L0 V- DN V+ L0 V- LK V+ L0 V- FR V+ L0

wiring type of four- wiring type of three- wiring type of fire


wire button wire button service & locking

c) Parallel wiring instructions

L0 L0
V+ V+
DN DN
K-PI1000

K-PI1000

V- V-

L0 L0
V+ V+
UP UP
V- V-

wiring type of sharing button

7. Fusion Installation in an Enclosure


V-
K-PI1000

T0

T1

T2

T3

V+

wiring type of hall arrival chime &


direction preference 1
If the current demand of the arrival chime/ lantern exceeds 400 mA , Using K-07K:

-125-
7. Fusion Installation in an Enclosure

V-
external
V-
V- V+ power

K-PI1000
T0

K-07K
T0 V-
T1
T1 T0
T2
T2 T1
T3
V+ T2
V+
V+

wiring type of hall arrival chime & direction preference 2

 K-PI1000 adjustment
1. Programming Interface Definitions

No. Interface Description


Click Enter Parameter setting interface:
Click 2 times(double click)within 1s
1. Exit and save parameter setting interface
Press 3s to 10s without any operation, the display flashes for
3s and then automatically save & exit
Menu Selection:
2. UP call button
Increase numeric parameter value
Menu Selection:
3. DOWN call button
Decrease numeric parameter value
Menu Selection:
4. Fire service button
UP to select the menu;
Menu Selection:
5. Elevator locking button
Down to select the menu;

2. Programming Interface Description


Floor address setting:
Display Parameters setting and Description
K: sert as floor adderss menu, 0 = floor address
7. Fusion Installation in an Enclosure

A. Switch to floor setting menu by clicking Elevator locking or fire


service

B. Switch to floor setting menu be clicking or pressing UP or


DOWN,after 10s,display" S OK " setting successfully

C. K: Default 0,range:0~64。

floor address K=0,is car diplay controller


floor address K≠0,is hall diplay controller .

-126-
7. Fusion Installation in an Enclosure

Front door / Rear door Configuration:


Display Parameters setting and Description

A. Switch to Baud rate menu by clicking Elevator locking or fire service

B. Click or press UP or DOWN to set parameters


C. Press button of onboard 10s,display" S OK " setting successfully

D. parameter description:Default 0。

0: Front door Configuration 1: Rear door Configuration

(Spare)
Group Number Setting:
Display Parameters setting and Description

A. Switch to Baud rate menu by clicking Elevator locking or fire service

B. Click or press UP or DOWN to set parameters ;

C. Press button of onboard 10s,display" S OK " setting successfully ;

D. parameter description:Default 0。

0:Simplex; 1:elevator 1; 2: elevator 2


And so on。

 K-07L Installation , wiring ,and adjustment


 K-07L Function Description

No. Function Description

1. Segment code display Set floor or character according to controller


7. Fusion Installation in an Enclosure
2. Elevator status display Display status graphics according to controller

3. Elevator locking Elevator locking input

4. Fire service Fire recall input

Arrival chime & direction


5. Four outputs support arrival chime & direction preference
preference

6. Hall call Hall call UP and DOWN support。

Monochrome
7. Monochrome seven-segment LCD
seven-segment LCD

-127-
7. Fusion Installation in an Enclosure

 K-07L Installation
1. Caution

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.

• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials

• Install in place that absence of harmful gases and liquids.

• Install in place less salt and vibration.

• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter

• Make sure that electronic devices do not collide with other things.

2. Mounting dimension

 K-07LDescription

Content Schema
7. Fusion Installation in an Enclosure

Term Sym Terminal description Default Term Sym


J1 V+ Output + When load current is less than 400mA.
T0 Up arrival indicator If the load is greater than 400mA, use K-07K.

T1 Down arrival indicator


T2 Arrival chime output
V- Output -

-128-
7. Fusion Installation in an Enclosure

Term Sym Terminal description Default Term Sym


J2 V- COMM
FR Fire service signal input
J3 V- COMM
LK Elevator locking signal
input

J4 V- COMM
DN Down call signal input
V+ Output +
L1 Output -
J5 V- COMM
UP Up call signal input
V+ Output +
L0 Output -
JP6 —— Firmware upgrade
J7 CANH CAN interface H Interface:VH-4
CANL CAN interface L
GND DC 24V-
24V DC 24V+
S1 —— Function jumper DC24V±15%
RUN
BOT

RUN
SET

RUN
BOT

BOT
SET

SET
? ? ? ? ? ? ? ? ? ? ? ?
S2 —— CAN Resistance

 K-07LWiring
1. Description

No. Function Description Remark


1 Supply and communication XH-5 terminal+shielded twisted Standard
bus interface pair extension cable configuration
2 UP-call button XH-4 terminal +four-core 0.3mm2 Standard 7. Fusion Installation in an Enclosure
extension cable configuration
3 DOWN-call button XH-4 terminal + four-core 0.3mm2 Standard
extension cable configuration
4 Arrival chime & direction XH-6 terminal + six-core 0.3mm2 Standard
preference interface extension cable configuration
5 Elevator locking interface XH-4 terminal + two-core 0.3mm2 Standard
extension cable configuration
6 Fire service interface XH-4 terminal + two-core 0.3mm2 Standard
extension cable configuration

2. Caution

-129-
7. Fusion Installation in an Enclosure

CAUTION
• Wiring according to the manual , otherwise ,there may be lead to risk of controller damage.

• Power and CAN communication interface must use shielded twisted pair cable, otherwise it
will lead to the display controller does not work.

• Power and CAN communication connection cables should as bold as possible, otherwise it
will lead to the display controller does not work.

• Ground terminal must be standardized and reliable, otherwise ,there may be lead to risk of
damage to the controller and the system does not work.

INDICATE
• Ensure all terminals must be reliable , otherwise it will lead to the display controller does
not work.

• Avoid something falling into the controller box , otherwise ,there may be lead to risk of
controller damage.
• Do not sharethe grounding wire and power equipment.

• Power and communication shielded twisted pair cable must be grounded, and to the control
cabinet PE port.

• COP / LOP must be grounded.

• Shorten the grounding wires as much as possible .

3. Wiring Description
a) Power and CAN wiring description

24V
K-07L

GND

CANL
CANH
Shieidd Twisted Cable cable shield

Power & CAN wiring mode

b) Call control and fire service and Elevator locking explanation


7. Fusion Installation in an Enclosure

K-07L K-07L K-07L


V- UP V+ L0 V- DN V+ L0 V- UP V+ L0 V- DN V+ L0 V- LK V- FR

wiring type of four- wiring type of three- wiring type of fire


wire button wire button service & locking

c) Parallel wiring instructions

-130-
7. Fusion Installation in an Enclosure

L0 L0
V+ V+
DN DN
V- V-

K-07L

K-07L
L0 L0
V+ V+
UP UP
V- V-

wiring type of sharing button

d) If the current demand of the arrival chime/ lantern exceeds 400 mA , Using K-07K

V-

T2
K-07L

T1

T0

V+

wiring type of hall arrival chime &


direction preference 1

V-
external
power
V-
V- V+
T2
K-07K
K-07L

T0 V-
T1
T1 T0
T0
T2 T1

V+ V+ T2

V+

wiring type of hall arrival chime & direction preference 2

 K-07L Configuration
1. Programming Interface Definitions 7. Fusion Installation in an Enclosure

No. Interface Description


RUN

RUN

RUN
BOT

BOT

BOT
SET

SET

SET

S1 Functional
1.
jumper
Parameter Operate Firmware
setting normally Upgrade
Parameter setting interface:
2. UP call button
increase numeric parameter value
Parameter setting interface:
3. DOWN call button
Decrease numeric parameter value
Menu Selection:
4. Fire service button
UP to select the menu;
Elevator locking Menu Selection:
5.
button Down to select the menu

-131-
7. Fusion Installation in an Enclosure

2. Programming Interface Description


Steps Dot matrix displays Description

⑴ Jumper terminals set “F1” sets floor numbers if used as a


of S1 to access hall landing indicator (1 through 64
parameters setting of serviced floors).

⑵ Momentarily short
UP and V- to
increment
parameters ,
F2 – FC Refer to the following table
Momentarily short
for F2 – FC parameter descriptions
DN and V- to
decrement
parameters

⑶ Momentarily short
LK and V- to selsct a
“0”= the parameters of menu
digit ,the selected
digit will flash.

⑷ Momentarily short
UP and V- to
increment
parameters ,Moment Changed value
arily short DN and
V- to decrement
parameters
7. Fusion Installation in an Enclosure

⑸ When all parameters


are set , temporarily
short FR and V- on
fire service to exit the
menu.

-132-
7. Fusion Installation in an Enclosure

Steps Dot matrix displays Description

⑹ Temporarily short
RUN jumper of S1 to
exit parameters
setting mode and OK = all the parameters were
save. If all the saved successfully
parameters were
saved successfully ,
Ok will be display.

⑺ If all the parameters


were not properly If ER is display , repeat the
saved , ER will be parameter entry and save process
display

⑻ Reset the board to The board will display the


entry the appropriate appropriate operating value for its
operating. position and status

3. K-07L parameters
Para.# Value Description
F1 0-64 0 is car call ,others are hall call,floor numbers from 1-64
F2 (SPARE)must be 0
choice for front / rear door
F3 0-1 =0 front door configuration;
=1 rear door configuration
=0 Arrow flashes when Elevator is operation
F4 0-1
=1 Arrow does not flash when Elevator is operation 7. Fusion Installation in an Enclosure
=0 Display functions under Fire service
F5 0-1
=1 No display under Fire service
=0 No display during Inspection operation, displays the floor number
and “Maintenance”
F6 0-1
=1 During Inspection operation, displays the floor number and
“Maintenance”
=0 Special status display invalid
F7 0-1
=1 Special status display valid
=0 Special status display Chinese
F8 0-1
=1 Special status display English

-133-
7. Fusion Installation in an Enclosure

 K-03D Installation , wiring ,and adjustment


 K-03D Funcitional Specification

No. Function Description

1. Dot matrix display Set floor or character according to controller

2. Status Display Display status graphics according to controller

3. Elevator locking Elevator locking input

4. Fire service Fire recall input

Arrival chime &


5. Four outputs support arrival chi me & direction preference
direction preference

6. Hall call Hall call UP and DOWN support

Lateral dot matrix


7. Lateral dot matrix display
display

 K-03D installation
1. Caution

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.

• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials


• Install in place that absence of harmful gases and liquids.

• Install in place less salt and vibration.

• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter
• Make sure that electronic devices do not collide with other things.
7. Fusion Installation in an Enclosure

-134-
7. Fusion Installation in an Enclosure

2. Mounting dimension:mm

 K-03D Description

Content Schema

7. Fusion Installation in an Enclosure


Term Sym Terminal description Default
P1 CANH CAN(Default)
+ Interface: VH-4
CANL CAN -
24V- DC 24V- DC24V±15%
24V+ DC 24V+
P2 V- COMM
UP Up call signal input
V+ Output +
L0 Output -
P3 V- COMM
DN Down call signal input
V+ Output +
L1 Output -
P4 V- COMM
LK Elevator locking signal input

-135-
7. Fusion Installation in an Enclosure

Term Sym Terminal description Default


P5 V- (Default)
Signal common
FR Fire service signal input

P6 —— Function jumper

RUN

RUN
SET

SET
? ? ? ? ? ? ? ?

J7 V+ Output + When load current is less than 400mA.


T0 Up arrival indicator If the load is greater than 400mA, use
T1 Down arrival indicator K- 07K.
T2 Arrival chime output
V- Output -
J1 —— CAN Terminal resistance

 K-03D Wiring
1. Description

No. Function Description Remark


1 Supply and communication XH-4 terminal+shielded twisted standard configuration
bus interface pair extension cable
2 UP-call button XH-4 terminal +four-core standard configuration
0.3mm2 extension cable
3 DOWN-call button XH-4 terminal + four-core standard configuration
0.3mm2 extension cable
4 Arrival chime & direction XH-5 terminal + six-core standard configuration
preference interface 0.3mm2 extension cable
5 Elevator locking interface XH-2 terminal + two-core standard configuration
0.3mm2 extension cable
6 Fire service interface XH-2 terminal + two-core standard configuration
0.3mm2 extension cable

2. Caution

CAUTION
7. Fusion Installation in an Enclosure

• Wiring according to the manual , otherwise ,there may be lead to risk of controller damage.

• Power and CAN communication interface must use shielded twisted pair cable, otherwise it
will lead to the display controller does not work.
• Power and CAN communication connection cables should as bold as possible, otherwise it
will lead to the display controller does not work.

• Ground terminal must be standardized and reliable, otherwise ,there may be lead to risk of
damage to the controller and the system does not work.

INDICATE
• Ensure all terminals must be reliable , otherwise it will lead to the display controller does
not work.

• Avoid something falling into the controller box , otherwise ,there may be lead to risk of

-136-
7. Fusion Installation in an Enclosure

controller damage.

• Do not sharethe grounding wire and power equipment.

• Power and communication shielded twisted pair cable must be grounded, and to the control
cabinet PE port.

• COP / LOP must be grounded.

• Shorten the grounding wires as much as possible .

3. Wiring Description
Please refer to K-07Lwiring

 K-03D adjustment
1. Programming Interface Definitions

No. Interface
RUN
Description

RUN
SET

SET
1. P6 Functional jumper

Operate normally Menu setting


Parameter setting interface:
2. UP call button
increase numeric parameter value
Parameter setting interface:
3. DOWN call button
Decrease numeric parameter value
Menu Selection:
4. Fire service button
UP to select the menu;
Menu Selection:
5. Elevator locking button
Down to select the menu

2. K-03D Parameters

PARA.# Value Description


K 0~64 Set floor addressof controller
7. Fusion Installation in an Enclosure
value Definitions
3 2 1 0 (X=:0 or 1)
X X X 1 Arrow select
Inspection button display enable
X X 1 X =0,display floor number
F Function Select =1,not display floor number
=0, Elevator locking button has
remind
X 1 X X
=1, Elevator locking button has no
remind
=0 hall dislay floor number
1 X X X
=1 hall not dislay floor number
G Group Number spare
V —— Version, have no need to set

-137-
7. Fusion Installation in an Enclosure

value Definitions
2 1 0 (X=:0 or 1)
direction preference
X X 1
Specific default : 1
E
Function =0 scroll to display
X 1 X
=1 have no scroll to display
=0 have no icon of prohibited entering
1 X X
=1 have icon of prohibited entering
Set front / rear =0 front door
B
door =1 rear door
Display function 0 No output
of 1 Inspection
X
BGL1(backlight 2 Bypass
module) 3 Overload
Display function 4 Attendant
of 5 Full load
Y
BGL2(backlight 6 Fire service
module) 7 Err
Display function 8 Earthquake
of 9 Earthquake
Z
BGL3(backlight 10 Independent run
module) 11 IC Enable

 MC-VAB Voice Announcement


 MC-VAB Installation , wiring ,and adjustment
 MC-VAB Funcitional Specification

No. Funcitional Description


Floor voice
1. Play the information of floor number。
reminding
Elevator status voice Play Elevator status:UP , DOWN , open / close the door ,
2.
reminding inspection , err, overload , fullload .etc
7. Fusion Installation in an Enclosure

Compatible
3. multi-format audio Support mp3,WAV.etc
files
Play background
4. Play background music while waiting for or during operation
music

5. Update voice file Update voice file by SD card

-138-
7. Fusion Installation in an Enclosure

 MC-VAB installation
1. Caution

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.

• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials

• Install in place that absence of harmful gases and liquids.


• Install in place less salt and vibration.

• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter

• Make sure that electronic devices do not collide with other things.

2. Mounting dimension (unit:mm)

7. Fusion Installation in an Enclosure

-139-
7. Fusion Installation in an Enclosure

 MC-VAB Description

Content Schema

Term Sym Terminal description Default


J1 24V+ (Default)
DC 24V+ Interface: XH-4
24V- DC 24V-
CANH CAN +
CANL CAN -
DC24V±15%
J2 —— SD card slot Contains annunciated signal for board
J3 —— USB Reserved
J4 —— Programming interface Firmware upgrade Port
J5 IN1 Multifunction input 1 Background music
IN2 Multifunction input 2 Reserved
IN3 Multifunction input 3 Reserved
IN4 Multifunction input 4 Reserved
IN5 Multifunction input 5 Reserved
GND Signal common
S1 —— BOOT Jumper Firmware upgrade Port
S2 —— Reset
S3 —— CAN Resistance
S4 —— Programming jumper
VR1 —— Volume adjust Left Channel
VR2 —— Volume adjust Right Channel
7. Fusion Installation in an Enclosure

 MC-VAB Wiring

-140-
7. Fusion Installation in an Enclosure

 GCL group control board

CAUTION
• Be installed in clean space ,have no non-oil mist, dust,.
• Do not make metal powder, oil, water . etc into the controller.

• Do not install in place there are some inflammable materials

• Install in place that absence of harmful gases and liquids.


• Install in place less salt and vibration.

• Avoid foreign matter falling into the surface of controller.

INDICATE
• Install according to the controller dimension, mounting hole distance , and diameter
• Make sure that electronic devices do not collide with other things.

1. Mounting dimension \ unit:mm

Width Length Thickness


76 123 <10

7. Fusion Installation in an Enclosure

-141-
7. Fusion Installation in an Enclosure

 GCL description

Content Schema

Term Sym Terminal description Default


J1 —— (Default)
Firmware upgrade
J2 CANL2
CAN Communcation Port 2
CANH2
J3 CANL1
CAN Communcation Port 1
CANH1
J4 24V+ DC 24V+ DC24V±15%
24V- DC 24V-
GND Ground
X0 Multifunction 1
X1 Multifunction2
X2 Multifunction3
COM0 Common
T0 Multifunction 1
COM1 Common
T1 Multifunction 2
S1 —— Firmware upgrade
S2 RST Reset
S3 —— CAN Resistance
S4 —— CAN Resistance
DS1 —— Display Code
DS2 ——
7. Fusion Installation in an Enclosure

K1 DN Function set 1
K2 UP Function set 2
K3 FUN Function set 3

-142-
7. Fusion Installation in an Enclosure

 GCL wiring

7. Fusion Installation in an Enclosure

-143-
7. Fusion Installation in an Enclosure

 GCL adjustment
Before setting group control parameters, complete all simplex adjustments. When making
simplex parameter settings, note Elevator total floors, lower offset floor, door zone layout of
front door (non-stop floor), and rated speed settings.

System group number setting:


Set L0.00 group number value to 0 to prevent a Elevator from entering into group control.

Underground floor setting:


If a Elevator has underground floors, you should set lower offset value on the main board.
An upper offset is not required.
Group control board parameter settings:

1. To enter parameter setting mode, press UP and DN at the same time until the menu is
displayed.

2. To switch menus, press the UP or DN button.


3. To select parameters, press the FUN button to select a menu parameter. It will flash.
4. To change a selected parameter, press UP or DN to increase/decrease value.

5. To return to the menu, press the FUN button.


6. To exit the menu, press UP and DN buttons at the same time.

7. Parameter saving: While exiting the menu, if display shows “Or”, it means the parameter
values are saved. If it shows “Er”, it means a save fault occurred and settings must be
repeated.

1. GCL Parameters

code Meaning Range Remarks


Different group control
boards have different group
F1 Elevator group number 1-8
numbers, generally starting
with 1
F2 Elevator (lowest) return main floor 1 - 48 Sector parking, lower floor.
Middle return floor (the value should be larger than
F3 1 - 48 Sector parking, middle floor.
parameter F2 value)
Upper return floor (the value should larger than
F4 1 - 48 Sector parking, upper floor.
parameter F3 value)
7. Fusion Installation in an Enclosure

Waiting time Time the group should wait for an


F5 assigned elevator to close its doors and depart a 7 - 255 Each unit equals 4 seconds.
floor before re-assigning the call to another car.
If two fully loaded cars depart a floor within this 7 - 255
F6 Each unit equals 4 seconds.
time period, the group will begin peak operation
When traffic conditions allow, the group will wait for 7 - 255
F7 Each unit equals 4 seconds.
this period of time before exiting peak mode.
F8 Time to wait before exiting zoning. 7 - 255 Each unit equals 4 seconds.
The maximum amount of time the main floor will be Each unit equals 4 seconds.
F9 allowed to go without a Elevator before a car is 0 - 255 If set to 0, the Elevator will
automatically returned. not return to main floor.
The maximum amount of time the middle return Each unit equals 4 seconds.
FA floor will be allowed to go without a Elevator before 0 - 255 If set to 0, the Elevator will
a car is automatically returned. not return to main floor.
FB The maximum amount of time the upper return 0 - 255 Each unit equals 4 seconds.

-144-
7. Fusion Installation in an Enclosure

floor will be allowed to go without a Elevator before If set to 0, the Elevator will
a car is automatically returned. not return to main floor.
OC Test mode 0 - 1B

GCL Fault Code Table


When both the group control board and the Elevators are in normal operation, the display
will show a marquee. When a Elevator enters into different modes of operation (full-load,
bypass, attendant, inspection, fire, etc.), a code will be displayed as follows:
Code Meaning Troubleshooting Remarks
E1 CAN1 bus error interrupt Increase or decrease S4
terminal resistor
E2 CAN2 bus error interrupt Increase or decrease S3
terminal resistor
E3 Arbitration lost will occur when Re-set group control board
groups are incorrectly assigned the number
same number
E4 Non
E5 GCL and FUSION did not establish Set system group number
communication of main board as 3
E6 Cannot find main group control Check wiring among group
board control boards
A stands for enter into
Displayed when Elevator enters into
An N stands for group
group control
number
SF Elevator is returning to Simplex Elevator is in inspection or
mode. fault mode and is returning
to Simplex mode.
S1 Elevator fault Check the Elevator
S2 Elevator delayed Check close/open door
signal;
Elevator will enter delayed
status when door cannot
fully close within a certain
time
S3 Group control board independent Enter into simplex mode 7. Fusion Installation in an Enclosure
operation
S4 Car call board independent operation Enter into simplex mode
S5 Attendant In attendant mode
S6 Bypass In bypass mode
S7 Full load In full load mode
S8 Fire In fire mode
S9 Elevator lock In Elevator lock mode
SA Inspection In inspection mode
SB Input point 2 Spare
SC Input point 3 Spare
Ur Main group control board display
UP-peak
Dr Main group control board display
DOWN-peak

-145-
7. Fusion Installation in an Enclosure

 Door pre-opening board


 K-50A Description

Content Schema

Terminal Code Use Description


Inputs P1 MQS Upper door zone Upper, middle, and lower sensors are mounted
K1 sensor equidistantly (150 mm separation). The landing
P2 MQX Lower door zone vane is 300mm in length. When the car is precisely
P3 MQ sensor door zone
Middle leveled, all three sensors are active.
sensor
P4 LOW Low speed signal Active when low speed has been commanded (at or
input under 0.3 m/s).

P5 TK+ Stop contactor input Relay K1 control inputs.


P6 TK- Stop contactor input
P7 555 24V+ power
P8 551 24V - power
Outputs P1 551 24V - power
K2 P2 P25 Door pre-open
Outputs P1 A30 request
Door lock short
K3 P2 A22 circuitlock
Door 1 short
circuit 2
7. Fusion Installation in an Enclosure

-146-
8. Events/Troubleshooting

8. Events/Troubleshooting

8.1. Events/Troubleshooting
ZXK-6000-S- A has fault protection and fault memory functions. It monitors each input
signal and running condition, in addition to external feedback information. If an abnormal
situation occurs, the corresponding protective function is activated and the operator
displays the associated error code.

Fault information is divided into five categories. Please see the table below:

Fault Type Description Remarks


Running condition not
I Display fault code
affected
Display fault code
II Normal run in simplex mode
Exit the elevator group control (parallel) system
Display fault code
Brake drops, remain out of
Stop at the nearest floor; shut down.
III normal service until the
Car stops immediately if there is any other
fault is corrected
problem
Display fault code
Permit low-speed run
No output during remote control, brake drops.
IV under fault code
Allow to run on inspection mode, releveling
condition.
and other low-speed run.
Remain out of normal
Display fault code
V service until the fault is
The system blocks outputs, brake drops.
corrected

8.2. Fault/Error Conditions


Remark: All input logic refer to default setting.
Fault code Fault type Fault name
ZXK-6000-S- A low voltage input terminal function error
1 V
ZXK-6000-S- A low-voltage input set incorrectly.
Cause Troubleshooting
ZXK-6000-S- A P1.0 – P4.7input Verify ZXK-6000-S- A low voltage input terminal
terminal is in error or correctly assigned. If not, set correctly or set to
duplicated. default function.
Fault code Type Fault name
ZXK-6000-S- A output fault
2 V
8. Events/Troubleshooting

ZXK-6000-S- A output terminal incorrectly configured


Cause Troubleshooting
ZXK-6000-S- A Verify ZXK-6000-S- A output terminal
T6.0-T7.7output in error or correctly assigned. If not, set correctly or
duplicated. select the defaultfunction.
Code Type Fault name
3 V Drive is not ready
Cause Troubleshooting
Drive error detected Check the fault record; troubleshoot accordingly.
Code Type Fault name

-147-
8. Events/Troubleshooting

4 V Drive fault
Cause Troubleshooting
Drive faults during run Check the fault record; troubleshoot accordingly.
Code Type Fault name
Motor encoder signal not detected.
5 V ZXK-6000-S- A outputs run signal, but encoder not detected
after set delay.
Causes Troubleshooting
Elevator starting sequence Decrease starting “anti-vibration delay”, “brake pick
taking excessive time delay”, “rated speed delay” as required.
Motor stall Verify brake is picking correctly.
Code Type Fault name
6 V Encoder channels reversed
Cause Troubleshooting
Elevator run direction and Change the elevator running
encoder signal reversed direction. Change the encoder
channels.
Elevator roll-back Enable the position lock function.
Increase “starting proportional gain” setting
value. Decrease “starting integral time”
setting value.
Code Type Fault name
Car or cartop controller input terminal setting error
7 V
Car or cartop controller input terminal incorrect configuration
Cause Troubleshooting
Car or cartop controller input Verify each input terminal of the car controller.
terminal setting in error or If in error, set correctly or select default function.
duplicated.
Code Type Fault name
8 V Drive run signal stuck
Cause Troubleshooting
Controller damaged Verify drive parameters.
Code Type Fault name
9 III Motor overheat protection enabled
Cause Troubleshooting
Motor overheat Check fan function, if any. Check cooling vents.
Motor overheat protection Reset motor overheat protection monitoring signal logic
monitoring signal logic error (normally open/normally closed). Default is normally
open.
8. Events/Troubleshooting

Motor overheat protection Check wiring.


signal electrical wiring
incorrect
Motor overheat protection Short signal common V- to motor overheat protection
monitoring signal malfunction monitoring signal or disconnect the motor overheat
protection monitoring signal.
Verify level change is detected by ZXK-6000-S- A.
Code Type Fault name
Cartop controller CAN communication error
11 III
Controller and cartop controller CAN communication error

-148-