A400-Spec-Sheet
A400-Spec-Sheet
Incineration System
Unique Design Compliant with Air Quality Regulations
Specifications Summary
A400 Propane, Natural Gas, or Diesel Fired Incineration System complete with one burner, optional second burner and secondary burn
chamber, stainless and / or refractory lined stack and chambers, and manual operating timers.
WASTE CHAMBER
INSTALLATION
Chamber capacity
Must be installed in accordance with local codes and
(Type 4 waste-pathological) 400 lbs 182 kg
ordinances, subject to regulatory agencies. Outside
Chamber volume (approximate) 12.6 cu. ft. .36 cu. m. installation is recommended with a simple metal roof or
Chamber size (inside) Width 29” 74 cm three-sided metal shelter, providing a minimum of four
Height 22” 56 cm foot clearance from any combustible roof materials.
Length 42” 106 cm Minimum of 18” clearance is required for penetration of
Door opening 22”W x 29”L 56 cm x 74 cm combustible roof materials. Inside installations may
have special insurance requirements.
Height to door 30.5” 77 cm
Overall dim’s 1 burner, w/stack 132”H x 57”Wx 71”L 3.35 m x 145 cm x 180cm GENERAL
Overall dim’s 2 burner, w/stack 186”H x 57”Wx 71”L 4.7m x 145 cm x 180cm Electrical service
Suggested min. slab size (l x w x thick) 8’ x 6’ x 4” 1.8 m x 2.4m x 10cm Standard – 115 volt, 60 HZ, 20 amp
Also available – 220 volt, 50 HZ, 10 amp
STACK
Diameter 1 burner system 12” 30.5 cm, 2 burner system 14” 35.5 cm BURNERS
LP or Natural or Diesel burner(s) with spark ignition
Material 14 gauge (2 mm) lined Aluminized Steel and/or unlined stainless steel and flame safety shut-off.
REFRACTORY THICKNESS OPERATION
Primary 3.0”(2800F) 7.6 cm Manual timers
Secondary 1.5”(2800F) 3.8 cm TOTAL WEIGHT
Stack 1.5”(2800F) 3.8 cm 1975 lbs. (approximate) 896 kg
APP. FUEL CONSUMPTION A400 LP A400 NATURAL GAS A400 Diesel
Upper burner 0.83 GPH 83 CFH 0.5 GPH
Lower burner 3.0 GPH 275 CFH 2.5 GPH
* Fuel consumption approximate. Actual fuel use depends on BTU content of waste.