Overcurrent_Limiting_in_Grid-Forming_Inverters_A_Comprehensive_Review_and_Discussion
Overcurrent_Limiting_in_Grid-Forming_Inverters_A_Comprehensive_Review_and_Discussion
Abstract—Grid-forming (GFM) inverters are increasingly rec- is increasing in modern power grids. Additional examples of
ognized as a solution to facilitate massive grid integration of grid-connected inverters include battery energy storage, STAT-
inverter-based resources and enable 100% power-electronics- COMs, and high-voltage dc. Today, most installed inverters act
based power systems. However, the overcurrent characteristics of
GFM inverters exhibit major differences from those of conven- as grid-following (GFL) units whose ac outputs mimic a current
tional synchronous machines. Accordingly, an in-depth character- source by following the measured grid voltage with the use of a
ization of GFM current-limiting strategies is needed to ascertain phase-locked loop (PLL) [1]. As the share of GFL inverter-based
their performance during off-nominal conditions. Although GFM resources (IBRs) grow and fossil-fuel generation is retired, so do
current-limiting controls are primarily necessary to protect the the concerns for power system integrity since grids were initially
inverter power stage, they determine the inverter behavior during
and after an off-nominal system disturbance. As a result, they can predicated on the use of synchronous generators (SGs) for
profoundly impact device-level stability, transient system stability, system stabilization. This has triggered increased interest from
power system protection, and fault recovery. This article offers the power system industry to incorporate grid-forming (GFM)
a comprehensive review of state-of-the-art current-limiting tech- capabilities in grid-connected inverters to provide grid services
niques for GFM inverters and outlines open challenges where in- that enhance reliability and stability [2]. In recent years, inverters
novative solutions are needed. One key contribution of this article is
the use of graphical methods that allow for intuitive understanding with GFM capabilities have been recognized as a pathway to
and visually aided comparisons of current-limiting methods. With facilitate the transition to a sustainable power grid. Many lead-
this approach, we evaluate various performance criteria for dif- ing research organizations, transmission system operators, and
ferent limiting methods, such as fault current contribution, voltage multinational consortia around the world are working towards
support, stability, and post-fault recovery. We also discuss the latest incorporating GFM capabilities into grid-connected inverters
standards and trends as they require inverter dynamics under off-
nominal conditions and outline pathways for future developments. and streamlining grid codes for GFM technologies [3], [4], [5],
[6], [7].
Index Terms—Current limiting, fault ride-through, grid- Despite significant interest in this area, many questions related
forming (GFM) inverters, stability.
to GFM inverter control remain unanswered [8]. Open questions
are particularly centered around the behavior of GFM control dy-
I. INTRODUCTION namics during off-nominal and contingency conditions [2], [3].
The physical origin of the problem is the inherent limits in the
HE presence of inverter-based renewable energy resources,
T such as wind turbines, solar photovoltaics, and fuel cells,
overcurrent capabilities of power semiconductor devices within
an inverter. Generally, converter size and thermal management
costs increase as the magnitude and duration that the converter
Manuscript received 10 January 2024; revised 6 April 2024 and 29 May 2024; must reliably tolerate increase. This tradeoff results in inverter
accepted 1 July 2024. Date of publication 18 July 2024; date of current version
11 September 2024. This work was authored in part by the National Renewable designs that can only tolerate overcurrents marginally exceeding
Energy Laboratory, operated by Alliance for Sustainable Energy, LLC, for the the nominal value for inverter cost reduction. SGs, on the other
U.S. Department of Energy (DOE) under Contract No. DE-AC36-08GO28308. hand, can deliver 5–10× their rated current for a certain period
This material is based upon work supported by the Laboratory Directed Research
and Development Program at NREL and the U.S. Department of Energy’s Office of time without damage, and this property has been leveraged to
of Energy Efficiency and Renewable Energy (EERE) under the Solar Energy enhance power system robustness during disturbances. The high
Technologies Office Award Number 38637. Recommended for publication by overcurrent capabilities and rotational inertia associated with
Associate Editor M. Saeedifard. (N. Baeckeland and D. Chatterjee contributed
equally to this work). (Corresponding author: Gab-Su Seo.) machines lie at the heart of existing power system reliability and
Nathan Baeckeland and Gab-Su Seo are with the Power Systems Engineer- protection schemes [9]. Given the aforementioned differences
ing Center, National Renewable Energy Laboratory, Golden, CO 80401 USA between SGs and IBRs, it is clear that the transition to an
(e-mail: [email protected]; [email protected]).
Debjyoti Chatterjee and Brian Johnson are with the Chandra Family Depart- inverter-based system will bring many challenges [10], [11]. On
ment of Electrical and Computer Engineering, University of Texas at Austin, the upside, inverters offer immense flexibility due to their use
Austin, TX 78712 USA (e-mail: [email protected]; b.johnson@ of programmable digital controls, which shape their dynamics,
utexas.edu).
Minghui Lu is with the Pacific Northwest National Laboratory, Seattle, WA and high switching frequencies that far exceed the dynamics of
98109 USA (e-mail: [email protected]). interest in power systems and, therefore, provide fast actuation.
Color versions of one or more figures in this article are available at Accordingly, the GFM inverter behavior is primarily determined
https://doi.org/10.1109/TPEL.2024.3430316.
Digital Object Identifier 10.1109/TPEL.2024.3430316 by the inverter control software design giving flexibility [12].
© 2024 The Authors. This work is licensed under a Creative Commons Attribution 4.0 License. For more information, see
https://creativecommons.org/licenses/by/4.0/
14494 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
Fig. 2. Overview of direct and indirect current-limiting methods for GFM inverters.
where |ii | denotes the magnitude of the reference current and en-
tails a separate calculation [22]. In the literature, various types of
limiters are used to track and curtail the magnitude of the current,
Fig. 4. Generic control structure of a direct switch-level current limiter.
such as root mean square (RMS) limiters, circular limiters, and
elliptical limiters. Mahamedi et al. [23] used a magnitude calcu-
lator to individually monitor phase RMS currents and limit phase
currents. In [24], [25], a circular current limiter is proposed to switching command fed into the semiconductor switching
limit the peak of the sinusoidal signal without causing distortion bridge is blocked as soon as the instantaneous inverter output
in the output currents, which could be caused by an instantaneous currents exceed the maximum current threshold. Because this
hard current limiter, such as clipping the sinusoidal current. method directly affects the switching command signals, i.e.,
Moawwad et al. [26] proposed an elliptical current limiter, bypassing other control blocks in series, rapid and accurate
which represents the locus for the total instantaneous current current limitations can be achieved. Du et al. [38], [39] proposed
(i.e., positive and negative-sequence currents). The limits of a switch-level current-limiting control strategy that immediately
the direct and quadrature components of the converter current suppresses the currents during overloading using a hysteresis
are adaptively defined to fully use the overloading capability. loop. By directly controlling the switching command signals,
Baeckeland et al. [27] used a resonant integrator to track the this method can limit the overcurrent in a few switching cycles,
line-current amplitudes. In that work, the reference currents are which is significantly faster than any other limiting method
proportionally scaled, referring to the maximum phase current discussed in this work. Gurule et al. [40] and [41] demonstrated
if the limiter is activated. Computing the current magnitude can- this method through experimental results; however, bypassing
not be achieved instantaneously; therefore, this step can cause the entire GFM control structure and directly manipulating the
delays in detecting an overcurrent and thus affect the response switching command signals can cause controller instability and
time, likely causing a momentary overcurrent and affecting the severely degrade power quality due to waveform peak clipping,
stability margins of the inverter [27]. More explanation on this as illustrated in Fig. 4. More so, this can lead to integrator windup
is found in Sections V-A and V-B. in the hierarchical control loops. (More discussion on integrator
With the current-reference limiter in place, the limited refer- windup phenomena during current limiting in Section V-D.)
ence signal feeding into the inner-current control loop, ρ ii , can For those reasons, switch-level current-limiting methods are
never surpass the maximum allowable current, Imax , as shown rarely proposed in the literature as the primary current-limiting
in (1). Because of the high bandwidth of the inner-current control technique in inverters. In conjunction with a primary current-
loop, the output current closely tracks the reference, ρ ii , and limiting method, the switch-level current limiter can provide
with that, quick and accurate current limiting is acquired. Many quick backup protection to secure the inverter hardware against
works have described various implementations, depending on high and fast-rising transient currents.
the type of reference frame used in the controls [23], [25],
[27], [28], [29], [30], [31], [32]. (More discussion on reference B. Indirect Current-Limiting Methods
frames is found in Section V-E.) As illustrated in Fig. 3(a), the This section introduces and reviews methods that indirectly
current-reference saturation gain, ρ, rescales the magnitude of limit the inverter output current by 1) modulating the power set
ii without manipulating the current-phasor angle. This retains points that feed into the primary GFM controller; 2) incorporat-
the current-phasor angle demanded by the voltage controller. ing a virtual impedance (VI) in the voltage feedback loop; or 3)
This type of limiting is presented in [24], [25], [27]; however, as implementing a voltage limiter. Each category is discussed in
shown in Fig. 3(b), it is possible—after saturating the magnitude detail.
of the reference signal—to manipulate and prioritize the active 1) Power Set Point Modulation Current Limiting: This
or reactive current during the disturbance [23], [31], [33], [34], current-limiting method aims to curtail the output current by
[35], [36], [37]. Manipulating the current-phasor angle, φ, can adaptively reducing the power set points during overcurrent
provide a tightly controlled output current during disturbances; conditions. This method is studied in [42] and [43], where the
however, it is worth contemplating whether this method retains power set points, P and Q , are dynamically rescaled as a
the voltage-source behavior of the GFM inverter during limiting function of the magnitude of the output voltage, E (see Fig. 5). In
as desired (more discussion is found in Section V-C). addition, by prioritizing reactive power during grid voltage drop
2) Switch-Level Current Limiting: Switch-level current- conditions, the GFM inverter can support the grid voltage and
limiting methods directly modulate the switching command straightforwardly comply with the grid codes requiring reactive
signals feeding into the semiconductor switching bridge to current provision, e.g., IEEE 1547 (more discussion is found in
curtail the output current, as illustrated in Fig. 4. The Section VI). As illustrated in Fig. 5, the power set points feeding
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14497
into the primary controller, Plim and Qlim , can be modified as Fig. 6. Generic control structure of a (a) static and (b) threshold VI current
limiter.
follows:
P if E > 0.9 pu
Plim =
2
(2) increasing the inverter output impedance. By redirecting the
(E Sr ) −(Q )2 if E ≤ 0.9 pu
sensed output current through a VI and subtracting the VI voltage
⎧
⎨Q if E > 0.9 pu drop from the voltage-reference signal, current limiting can be
Qlim = k Sr (1−E) if 0.5 pu < E ≤ 0.9 pu (3) achieved [45], [46], [47], [48]. Note that, compared to direct
⎩
E Sr if E ≤ 0.5 pu current-limiting methods that modulate the current reference,
VI current-limiting methods modulate the voltage reference,
where E denotes the inverter output voltage in per unit, Sr thereby preventing the voltage controller from commanding an
denotes the rated apparent output power in per unit, and k excessive inverter output current. This concept is illustrated by
denotes the ratio of the voltage drop at which the reactive power the generic VI current-limiting control structure shown in Fig. 6.
is injected into the grid, as often defined in grid codes [42], [43]. With the switch S4 , one can choose to enable a static VI, as
It is not clear, however, how power set point modulation current shown in Fig. 6(a) [48], [49], or a threshold VI, illustrated in
limiters can retain the GFM properties during faults and ensure Fig. 6(b) [50], [51], [52], [53]. A static VI limiter activates a
effective, accurate, and quick current limiting. This method has constant VI in a fault with a short rise time [48]. Since it handles
the potential to improve transient stability by achieving equality overcurrents in an ON/OFF fashion, the static VI excessively
of the power injection with the power set point during prolonged limits the output current, even during light overloading con-
faults (more discussion is found in Section V-A); however, sig- ditions, yielding under-utilization of the inverter’s fault current
nificant overcurrent cannot be avoided during the initial few fun- capabilities. Because the fault current provision is an essential
damental cycles after fault inception due to the low-bandwidth metric for system protection and recovery, a static VI is often not
outer controls (e.g., up to 10 fundamental cycles in [43]), which a preferred limiting method [44]. Moreover, a static VI can lead
would require significant overcurrent headroom in the inverter to latch-up, in which the inverter stays in current limiting and
hardware design and thermal management to avoid potential cannot return to normal operation even after the fault clears [49].
reliability issues and damage to the inverter. Further, note that Several of these drawbacks can be circumvented. First, one can
power set point current-limiting methods are based on arbitrary multiply the current signal with a threshold function, as denoted
criteria that only partially relate to the current magnitude, e.g., by ψ in Fig. 6(b). This threshold function only enables the VI
a voltage drop of 10%, as shown in Fig. 5. Equations (2) and current limiter when the inverter output current exceeds a certain
(3) have no dependency on the maximum rated current, Imax . threshold, Ith , and it gradually increases the VI magnitude as
Therefore, current limiting within the inverter boundaries cannot a function of the output current. This technique resolves the
be ensured. In addition, it is questionable whether this method latch-up issue and limits the output currents closer to Imax . For
works effectively during unbalanced faults, frequency drops, the threshold VI limiter, the VI voltage drop, vvi , can be described
or phase jumps while retaining stability. These concerns make by
this method unsuitable as a stand-alone limiting method, and,
therefore, should be combined with another limiting approach. vvi = (sLvi + Rvi ) ii ψ (4)
2) VI Current Limiting: During normal conditions, a GFM where Lvi and Rvi denote the inductive and resistive parts of
inverter can be represented as a voltage source behind an the VI, respectively. As illustrated in Fig. 6(b), the threshold
impedance, which remains small for voltage regulation. During function, ψ, can be defined by [52]
overcurrent conditions, on the other hand, the inverter output
impedance cannot remain the same. As the output current 0 if |ii | ≤ Ith
of the inverter is curtailed by a current limiter (independent ψ = |ii |−Ith (5)
Imax −Ith if |ii | > Ith .
of the limiter type) the equivalent output impedance of the
inverter modulates as a function of fault severity and other The function ψ can take various forms, ranging from a discon-
conditions [44]. A VI current limiter curtails the current by tinuous linear function of the inverter output current, such as
14498 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
sure that the inverter output impedance, during current-limiting Notice that the GFM inverter becomes a controlled current
operation, is primarily reactive from a droop control perspec- source during current limiting, similar to a GFL inverter, which
tive [53]; however, some resistance in the VI is required for can have a destabilizing effect in weak grids [62], [63]. By-
damping and, as such, to retain small-signal stability [10], [45]. passing the primary controller for current limiting can lead
(More on the effect of current limiting on small-signal stability to frequency windup in the primary controller and complicate
in Section V-B.) Denis et al. [55] proposed a tradeoff where the fault recovery process. Complementing the voltage-based
Xvi Xvi current limiter with a power set point current limiter can alle-
Rvi = 5. In Section V-A, we delve into the effect of the Rvi on
large-signal stability. viate frequency windup to a certain extent; however, instability
Despite these advanced VI current-liming methods, some challenges due to frequency disturbances remain. The intricate
inherent disadvantages must be considered. Because this type interplay between voltage regulation and frequency stability
of current-limiting method uses the reference of the voltage underscores the need for comprehensive solutions that simul-
controller, its current-limiting bandwidth is smaller than a direct taneously address both aspects. Further, detecting overcurrent
current-limiting method that uses a faster, inner control loop; is a straightforward criterion to engage the limiter; however,
therefore, a VI current limiting can be too slow to limit the deactivating the limiter cannot be commanded based on cur-
fast-rising transient peak current during the initial stage of a fault. rent measurements because the current is being fixed to Imax .
Also, although making ψ an exponential function can help, it is Deactivating the limiter, therefore, requires an additional logic.
not possible to limit the overcurrent to Imax with VI impedance All these phenomena can make it challenging to implement a
limiting. The inverter’s fault current provisioning capabilities, voltage-based current limiter.
as a result, can remain underused by a few percentages [27]. 4) Others: Taking inspiration from the concept of VI current
3) Voltage-Based Current Limiting: The voltage-based cur- limiters, [64], [65], [66], [67] propose a nonlinear modified
rent limiter curtails the inverter output current by decreasing droop controller with current-limiting properties. The proposed
the voltage reference feeding into the voltage controller during controllers can limit the inverter current under normal or fault
overcurrent. Though this is similar to VI current limiting, the conditions without external limiters, additional switches, or
voltage curtailment is computed in a different manner. During monitoring devices. In [68], a fast symmetrical fault ride-through
overcurrent, the limiter computes the voltage curtailment, elim , method is proposed using a hysteresis control. During the fault,
such that the output current matches Imax . This concept is illus- new power references are calculated, and the synchro-converter
trated in Fig. 7. During normal operation, e , generated by the switches to the hysteresis control to restrain inrush fault current.
primary controller, feeds into the outer-voltage controller. Once In [69], the output current of the inverter is limited by control-
an overcurrent is detected, switch S2 is activated, and the limited ling the power angle. This approach ensures synchronization
reference voltage can be computed as follows: stability after a voltage sag or a frequency jump. In [70], [71],
a frequency feed-forward term is incorporated into the ac-
elim = vg + (Lg s + Rg )Imax ejφ (7) tive power-frequency droop controller; however, the technique
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14499
TABLE I
OVERVIEW OF DIRECT, INDIRECT, AND HYBRID CURRENT-LIMITING METHODS
Fig. 10. Circuit equivalent of the considered GFM inverter during (a) normal
Fig. 11. Conceptual P − δ curves for the current-reference saturation limiter
operation and (b) current-reference saturation limited operation with current-
and the angle trajectory during a generic voltage drop fault with (a) φ = 0 and
phasor angle priority.
(b) φ = π3 .
can still remain in current limiting after the fault clearing due
to latch-up, resulting from the primary controller behavior (see
Section V-A), which prevents the inverter from a successful fault
recovery [131].
In contrast to current-reference saturation limiters, VI cur-
rent limiters have a fundamentally different post-fault behav-
Fig. 14. Integrator windup issue during faults. ior. Rather than manipulating the current reference, they are
designed to adjust the voltage reference as a function of the
output current. At the cost of responsiveness and limiting ac-
One typical issue is the windup of control integrators during curacy, reducing the voltage reference naturally limits the fault
current limiting. A common example is wind-up in the voltage current without winding up the inner control loops, allowing
controller; the current-reference saturation limiter curtails the the GFM inverter to retain control over the voltage and current
signal feeding into the inner-current controller due to which the independent of the limiting conditions [35], [45], [74]. Notice
inverter cannot inject the required current to build up the output that the primary controller, which governs the voltage and angle
voltage, e, to satisfy the reference, e (see Fig. 2). The integrator reference, can still be affected by integrator windup, which
of the inverter voltage controller continues to integrate the error can cause transient instability, as discussed in Section V-A.
due to the unregulated output voltage. If no countermeasures Moreover, the results in [111] reveal that a GFM inverter with
are taken, the integrator will accumulate a substantial error circular current limiters can also avoid these phenomena since
throughout the duration of the fault, as illustrated in Fig. 14. the inverter behaves similarly to those with virtual resistors.
Note that this phenomenon can occur in any instance of cascaded Hybrid current-limiting solutions can be sought to circumvent
control loops where reference signals in the inner loops are being the issue of outer-voltage integrator windup while alleviating the
curtailed. negative effects typically seen with VI current-limiting methods.
Once the fault clears and the grid returns to nominal opera- The hybrid limiter described in [44], for example, saturates the
tion, the voltage control loop of a GFM inverter must quickly reference current signal and implements a VI in the antiwindup
regain control over the terminal voltage; however, due to the feedback loop. This way, no windup of the outer-voltage loop
accumulated error in the integrator, the reference commands can occurs, the voltage-behind-impedance behavior is retained, and
take a significant amount of time to return to a value within the the current-reference saturation ensures quick and accurate cur-
normal range. Unless it immediately returns to normal operation, rent limiting. Moreover, the VI in the antiwindup feedback loop
the inverter can continue to inject its maximum rated current gives control over the internal inverter impedance, which can
into a healthy grid, which can lead to overvoltage at the termi- drastically improve grid synchronization in the face of faults,
nals. This can be followed by premature and aggressive control fault recovery, and overloaded black starts [129].
corrections, leading to excessive oscillations in the current and In addition, integrator windup in the outer-voltage loop di-
voltage outputs. All of which can compromise the stability of minishes the control over the output voltage and current-phasor
the system immediately after fault clearance. More discussion on angles, which can compromise postfault synchronization with
the post-fault instability caused by the windup is found in [131] the grid. With current-reference saturation limiting without an-
and [110]. tiwindup measures, the output voltage becomes uncontrolled,
Integrator windup can be prevented by using proper anti- which can aggravate a loss of synchronization. Adding anti-
windup techniques. They are designed to avoid integrator accu- windup measures can help regain control of the output voltage,
mulation that results from the discrepancy between the controller but the angle remains uncontrolled. In fact, [44] illustrates that
output and the actual control action realized, which can cause the internal impedance of the GFM inverter becomes purely
undesirable control behavior [52]. By reflecting the amount of resistive when employing a current-reference saturation limiter
unrealized control effort due to the limit in the preceding control with a conventional anti-windup feedback loop with a constant
signal (i.e., the amount of current exceeding the limit in the gain, without manipulating or prioritizing current-reference an-
GFM application), the states of the outer-loop control can stay gles. VI current-limiting methods and hybrid solutions can cir-
within a reasonable range to improve the post-fault control per- cumvent this issue. They retain control over the output voltage
formance [132]. Note that the implementation of an antiwindup and phasor angle, and as such, the internal impedance of the
varies and modulates the dynamic control behavior [31], [111], inverter. Nonetheless, integrator windup of the internal angle
[133], [134], [135], [136]. Pawar et al. [133] and Ghoshal and reference in the primary controller can still occur, which can lead
John [136] used conditional integration, and Ghoshal and John to a loss of synchronization and transient instability. (Measures
[136], Teodorescu et al. [134], and Richter and Doncker [135] to avoid primary-control integrator windup are further discussed
used tracking integration. In [137] a two-axis antiwindup PI in Section V-A.) Gu and Green [139] and Sepehr et al. [140] dis-
regulator is proposed to limit the current commands within a cir- cussed the synchronization principle after faults in light of angle
cular boundary. Even when antiwindup techniques are employed dynamics in an inverter-heavy power grid. In [33], a theoretical
to address this problem, they require knowledge of the system approach is proposed to explain the post-fault behavior of GFM
parameters to ensure closed-loop system stability, which may inverters with VIs.
not be available or may vary in practical situations [138]. Also Post-fault transients caused by inverter-current limiting
note that, equipped with an integrator antiwindup, the inverter can also cause system-wide issues [141], [142]. They can
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14507
in each phase independently. In [75] and [76], a hybrid current capabilities under off-nominal grid conditions. In the revised
limiter is proposed where the inner control loop utilizes three codes, inverters must stay connected to and remain synchronized
separate Kalman filters to estimate the magnitude and phase to the grid over an extended range of off-nominal grid conditions,
of three single-phase currents, and then saturation blocks are such as voltage and frequency excursions, for longer periods of
used to limit each phase currents independently. The proposed time without tripping. This type of requirement directly relates
approach can also flexibly limit the negative-sequence current as to the current-limiting control discussed in this article [166],
a percentage of positive-sequence currents based on grid code re- [167]. In addition, proactive actions during those off-nominal
quirements. In [23], the current controllers work in the decoupled conditions should be implemented to benefit the entire system
synchronous reference frame, while the current limiter operates operation. They can include injecting short-circuit currents dur-
in the natural reference frame, therefore, limiting each phase cur- ing a voltage drop to support the grid voltage and to avoid a
rent independently under faults. By limiting each phase current total blackout by facilitating the fault detection and protection
separately, under an asymmetric fault, only the affected phase(s) mechanisms [167], [168]. In case of unbalanced faults, some
will be current limited, while the healthy phase(s) can continue grid codes require the injection of reactive current into positive
to operate normally, as illustrated in Fig. 17(c). This operation and negative sequences [147], [167], [168], [169]. The required
can be beneficial in, for example, grids with single-phase loads, amount of current injection is defined as a function of the amount
because it can provide continuous service in healthy phases. of positive-sequence voltage drop or negative-sequence voltage
Note that independently controlling and limiting each phase rise during a fault.
can induce the flow of zero-sequence currents [82], [146]. This As of today, most grid codes are primarily drafted within
type of individual phase control is, therefore, only truly possible the paradigm of GFL inverter controls, in which the inverter
for three-phase, four-wire inverters. The three-phase, four-wire behaves as a controlled current source during both normal and
topology may have an extra switch leg and a dedicated zero- abnormal conditions. Programming specific active or reactive
sequence controller to regulate the zero-sequence current [162]. current injection during off-nominal grid voltage or frequency
For three-phase, three-wire inverters, limiting the phase currents conditions in GFL inverters, as a result, can be straightforwardly
in the natural reference frame can cause overvoltage issues [82], implemented by modifying the current-reference saturation lim-
[87], [146]. References Pokharelet al. [163] and Roh [164] iter. Since this type of modification does not affect the cur-
suggested that four-wire inverters are more effective than three- rent source nature, the inverter can continue using a PLL to
wire topologies in terms of harmonic distortion, leakage current, maintain synchronism with the grid. In GFM inverters, on the
capacitor voltage fluctuation rate, and total loss, particularly other hand, mandating a specific amount of current injection or
during faults and unbalanced conditions. rendering the inverter control into a current source contradicts
Conclusively, considering asymmetrical fault ride-through is the GFM principle of retaining the voltage-source behavior. For
imperative for practical current limiter designs. Each reference example, specific reactive current injection requirements can
frame presents distinct advantages and limitations. The selection be programmed with the current-reference saturation limiter
depends on requirements and tradeoffs regarding control accu- with fixed current-phasor angle, as discussed in Section III-A
racy, computational burden, controller design complexity, stabil- and illustrated in Fig. 3; then, the inverter may not retain the
ity, and overall system performance during faults. Requirements voltage-source behavior that likely provides more benefits to the
imposed by grid codes, such as specific sequence injection, power system operation under contingencies and the post-fault
should also be considered in the reference frame selection and recovery, especially in weak grids. How to unlock and exploit
control design owing to the frame-specific merits and limits the GFM capabilities under fault conditions and how to drive
discussed. Further technological advancements in this area will and reflect them in grid codes, however, is not clear as of today.
help overcome the challenges. Significant study is necessary to obtain a better understanding of
GFM inverter operation under faults and to facilitate standard-
ization. To fill this gap, we review the latest grid codes related
VI. GRID CODES FOR IBR OPERATION UNDER CURRENT to the fault and current limiting of IBRs. Though some are not
LIMITING specific to GFM inverters, understanding the motivation of the
For reliable power system operation and to safeguard the needs and trends in code changes would illuminate the pathways.
stability and continuity of the power supply under various grid First, we discuss recently developed GFM inverter grid codes.
conditions, grid operators enforce rules and requirements on In 2022, National Grid issued GC0137 for Great Britain’s system
generator units operating in their grids. These requirements operation [7], [170]. This code is designed to address technical
are based on the characteristics of SGs and decades of op- issues in the grid with the increasing share of IBRs with GFM ca-
erational experience; however, with the proliferation of IBRs pabilities. Although not mandatory, this code would facilitate the
in the grid, the need for inverter-oriented fault ride-through integration of GFM IBRs by enhancing the understanding of the
and dynamic voltage-support requirements has become promi- new technology and encouraging stakeholders to integrate GFM
nent [12], [165]. Grid codes for IBR-heavy systems must evolve, functionalities into their products. Related to current limiting,
considering the distinct merits and limitations of IBRs. In recent GC0137 specifies GFM-IBR operation under large frequency
years, this has led to world-wide revisions and creations of excursions (2 Hz/s) and short-circuit current injection under
grid codes. One significant change in many grid codes re- terminal voltage drops (down to 0 pu), both of which are likely
lated to overcurrent limiting is the requirement for operation to drive a GFM inverter into current limiting. These require
14510 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
GFM inverters to ride through (i.e., maintain synchronism) and understanding of this underexplored topic and will be founda-
proactively react to faults in an extended operational range, tional in the development of widely accepted grid codes.
which is well beyond what is typically required for non-GFM
IBRs. The Universal Interoperability for Grid-Forming Inverters
(UNIFI) consortium issued “Specifications for Grid-forming VII. SYSTEM PROTECTION IN IBR-HEAVY GRIDS
Inverter-based Resources Version 1” in 2022 and Version 2 in Over decades of operating SG-driven power grids, tradi-
March 2024 [3]. Although it does not provide numeric perfor- tional power system protection methods have proven reliable
mance metrics by design, it specifies GFM-IBR capabilities in by leveraging the typical voltage-source-behind-impedance
abnormal conditions, including retaining GFM characteristics behavior of an SG. A few typical SG fault attributes used to
under faults, contributing to system-wide stability, and recovery that end include high fault currents supplied by the SG and a
after events, all of which depend on the current limiting design. near-constant internal SG impedance that tends to be highly
It reconfirms the importance of the current-limiting design. inductive. Overcurrent, distance, and directional protection are
In addition, the UNIFI specification discusses the response to some examples of protection methods that employ these SG
asymmetrical faults that requires a GFM inverter to regulate a characteristics; however, IBRs in the system—of any type—
balanced internal voltage by allowing unbalanced currents, i.e., complicate the reliable detection and clearing of faults. Inverters
negative-sequence current injection. In addition, the European cannot provide high overcurrents, and the internal impedance
Network of Transmission System Operators [5], the Australian angle is predominantly dictated by the controls and the design
Energy Market Operator [4], and the North American Electric of the current limiter. As such, many questions circulate in the
Reliability Corporation [2] are leading the way to draft require- community about the protection of inverter-dominated grids,
ments for GFM inverters. e.g., should inverter controls or hardware be modified to comply
We provide more specifics in the latest codes related to GFM with existing protection schemes, or should protection schemes
operation under abnormal conditions. National Grid GC0137 [7] be adapted for inverters [8]. In this section, we discuss common
introduces a fault current injection requirement mandating GFM protection schemes, focusing on how they are affected by in-
inverters to exhibit a fast current response compared to GFL verters and how GFM inverters with current limits can provide
inverters against faults. In this code, the GFM inverter is re- solutions.
quired to inject the reactive current into the grid within 5 ms The most common protection scheme, particularly in low-
following a grid voltage drop below 0.9 pu. Complying with voltage and medium-voltage grids, is overcurrent protection.
this short time frame can pose a challenge if the response is This type of protection, and by extension directional overcur-
not inherent to the GFM IBR, i.e., voltage-source nature. On rent protection as well, relies on the presence of significant
the other hand, the grid code also requires that the active power overcurrents to detect a fault in a power system dominated by
response must not be faster than 5 Hz to avoid system resonance. SGs [171]. In an inverter-heavy system, however, detecting a
To satisfy this requirement, the control dynamics during faults fault by scanning for overcurrent can become arduous due to the
should be carefully designed while respecting the inverter’s limited overcurrent capabilities of inverters whose short-circuit
hardware limits. Also, notable are the latest IEEE standards, currents barely exceed their rating [172]. Deploying GFM IBRs
IEEE 1547-2018 [166] and 2800-2022 [167], since they detail can potentially alleviate this issue because they can proactively
the advanced functionalities needed from IBRs. In both stan- respond to faults, i.e., by providing the maximum current avail-
dards, inverters should not trip but maintain synchronism with able to facilitate the protection mechanism rather than providing
the grid during grid faults for an extended period of time, unless reduced current or early tripping that may appear in GFL invert-
they are allowed or required to trip [166], [167]. Compared to ers. Because it originates from the inverter hardware limits, how-
GC0137, which requires power injection even during a total ever, this issue cannot be fully solved by simply implementing
voltage collapse (Vg = 0 pu), the inverters under IEEE 1547 GFM controls in the IBRs replacing SGs, especially in the areas
Category II, which is the most demanding category for abnormal of weak system strength. Oversizing the inverters is a straightfor-
operations, for example, are mandated to temporarily cease to ward solution and can enable extended GFM funtionalities [4],
energize under a voltage drop below 0.3 pu [166]. This can lead [7], but additional value streams for the overdesign should be
to under-utilization of the GFM inverter’s capability if applied clearly defined and implemented by system operators to justify
and can affect system stability in certain conditions. Future the additional costs [173]. In an attempt to address the issue of
standards should establish requirements for GFM inverters that detecting overcurrent, advanced adaptive overcurrent protection
are engineered to offer extended ride-through capabilities to schemes have been proposed [174], [175], [176], [177]; however,
fully benefit from inverter-heavy power systems. selectivity is a major challenge [178].
As discussed, new grid code developments are in progress, Another widely employed protection scheme is distance pro-
and revisions of current standards are ongoing; however, so tection, which is primarily used in medium- and high-voltage
far no standard has been established that clarifies GFM-IBR distribution and transmission grids. Based on local voltage and
performance under fault conditions, which would allow the full current measurements, distance protection schemes compute
utilization of the potential of GFM inverters. This is because the impedance between lines and estimate the relative distance
the fundamental understanding of GFM inverter behavior is still to a fault on that line [179]. Conceptually, distance protection
being established. Research, development, demonstration, and works well when the sources at both ends of the protected line
deployment activities are paramount to establishing a deeper have a similar fault behavior [179]; however, with a mix of
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14511
TABLE III
ADVANTAGES AND LIMITATIONS OF CURRENT LIMITERS
IBRs and SGs, where the IBR current limiter can—intentionally In summary, the presence of IBRs can complicate the pro-
or unintentionally, as discussed in Section III—manipulate the tection of power systems due to known challenges, such as low
phase angle of the current, the distance protection can make a fault current levels, as well as unknown factors that arise from
wrong impedance-estimation decision [12]. Previous simulation the unpredictability of IBR behavior. Compared to GFL IBRs,
and hardware-in-the-loop studies have shown that distance pro- GFM IBRs can alleviate concerns and benefit system protection
tection is prone to failure in lines with (GFL) inverters, especially by proactively responding to faults with fault current provision,
during unbalanced line-to-line faults [180], [181], [182], [183], but their benefits could be limited due to the hardware limit,
[184], [185], [186], [187]. On the other hand, studies that inves- which motivates inverter oversizing [173]. The compatibility
tigate the interplay between GFM inverters and distance protec- of inverter controls and current limiter topologies with existing
tion remain sparse. Baeckeland [12] and Baeckeland et al. [128] protection schemes is often overlooked but deserves attention in
demonstrated through simulations and hardware validation that the inverter design process. On the other hand, advancements in
traditional distance protection can properly function with GFM protection technology, aided by novel communication methods
inverters equipped with certain control and current limiter design and developed information technologies, can enable a paradigm
considerations. The study illustrates that with a highly inductive shift in power system protection. Detailed electromagnetic tran-
VI current limiter, the GFM inverter behaves similarly to an SG sient modeling and simulation studies are essential to under-
(as illustrated in Fig. 12), which benefits distance protection, standing changes in protection system behavior under faults in
especially in a grid where IBRs and SGs coexist. inverter-heavy grids and to guide the energy mix transition while
Last, we discuss the effect of IBRs on line-differential pro- ensuring reliable system protection.
tection. Line-differential protection computes the sum of the
current flowing into and out of a line. According to Kirchoff’s
current law, this sum must always equal zero if there is no fault
VIII. CONCLUSION
on the line [188]. When there is a fault on the line, this criterion is
not met. This makes line-differential protection highly reliable. This article explored various aspects of the current-limiting
On the other hand, it requires reliable communication links to methods employed in GFM inverters. This final section consol-
exchange the measurement data from both ends of the line, and idates key points, provides a cohesive narrative, and offers our
it cannot provide remote backup protection. Unlike overcurrent perspective on the findings and existing research gaps presented
and distance protection, which rely on specific attributes of in the review.
SGs, the concept of line-differential protection is agnostic to The primary objective of current limiters is to curtail the
the source type (either SGs or IBRs) feeding the line. For the output current of the inverter, protecting the inverter hardware
same reason, line-differential protection is, conceptually, not from overloading and thermal damage. Although seemingly
affected by the control type of inverters, i.e., whether they are straightforward, the design intricacies of current limiters ripple
GFL or GFM. Though, some studies report that line-differential through the power network, impacting many aspects of the
protection, especially the alpha plane differential protection power system, including stability, grid support during distur-
scheme, can be affected by the altered fault current behavior bances, protection, post-fault recovery, and more. This paper
of inverters [189], [190]. Nevertheless, with some modifications highlighted the challenges of developing GFM current limiters
in the relay settings and high-bandwidth communication, line- and inverter controls that perform well on all these fronts. Al-
differential protection remains a reliable protection system for though no one-size-fits-all solution exists, the review identified
IBR-heavy grids [191], [192]. specific design aspects that confer distinct advantages. In the
14512 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
following, we highlight the most notable ones (a summary is of GFM inverters would require more effort within the
provided in Table III). community.
A well-established method to limit the inverter output currents 3) This article has shown that there are many different ways
is curtailing the reference signal feeding into the current con- to achieve effective current limiting in GFM inverters;
troller. Current-reference saturation limiting provides respon- however, we do not yet understand how well these different
sive and accurate limiting; however, if left untreated, it can GFM current limiting methods will interoperate with each
create integrator windups in the outer control loops and does other. While this study provides a fundamental basis,
not provide control over the current and voltage phasor angles. future power grids will feature thousands, if not millions,
The latter is particularly important for improving transient sta- of GFM inverters coexisting with other generation assets.
bility and grid synchronization, boosting the voltage during grid Understanding how these various GFM current-limiting
voltage sags and faults, and facilitating power system protection. and fault-behavior strategies interact with each other and
Adding antiwindup feedback loops and prioritizing reactive or other sources in terms of system stability and protection
active current in the limiter block can help alleviate some of is critical but mostly unknown.
these issues. 4) Arguably one of the most pressing gaps in the devel-
VI current-limiting methods, on the other hand, do not cre- opment and deployment of GFM technology is the lack
ate the windup of the outer-voltage loop control integrators of GFM inverter-tailored grid codes. In fact, many of
and can provide control over the current and voltage output the aforementioned GFM challenges could be overcome
phasors during faults and disturbances. For that reason, they with well-designed grid codes that clearly outline the re-
report better performance in terms of transient stability, voltage quired behavior of GFM inverters under off-nominal con-
support, and power system protection. On the downside, VI ditions. Novel GFM-tailored grid standards can streamline
current limiting curtails the voltage-reference input fed into the GFM developments, build clarity and common ground
outer-voltage loop, which, therefore, is inherently slower than among stakeholders, and facilitate field deployment of this
the current-reference saturation limiting methods, potentially promising technology.
causing momentary overcurrents and thus requiring an increased In summary, more efforts are necessary to understand GFM
design margin or use in combination with an additional method inverter behavior under current limiting and to illuminate the
for inverter protection and reliability. Also, VI current limiting pathway to well-defined and widely acceptable grid codes for
cannot fully use the overcurrent capability of the inverter. Careful GFM IBRs and IBR-heavy grids. Research, development, and
consideration of these tradeoffs is essential when using a VI demonstration activities are crucial to clearly defining how GFM
current limiter. inverters should behave under current-limiting and off-nominal
This review also discussed recent works that propose hy- conditions.
brid current-limiting solutions that combine the merits of two
methods. Although more research is needed, these papers show
promising results regarding reliable current limiting, angle con- REFERENCES
trol, stability, black start, and system protection. Although trade-
[1] B. Kroposki et al., “Achieving a 100% renewable grid: Operating electric
offs are unavoidable because of the hardware constraint of lim- power systems with extremely high levels of variable renewable energy,”
ited inverter currents, hybrid current-limiting methods elucidate IEEE Power Energy Mag., vol. 15, no. 2, pp. 61–73, Mar./Apr. 2017.
a pathway for future developments. [2] NREC, “Grid forming functional specifications for BPS-connected
battery energy storage systems,” North American Electric Relia-
Last, throughout this work, several gaps in the current state bility Corporation (NERC), Atlanta, GA, USA, 2023. [Online].
of research became apparent. Hereafter, we list the most notable Available: https://www.nerc.com/comm/RSTC_Reliability_Guidelines/
points for further research and remaining challenges in the space White_Paper_GFM_Functional_Specification.pdf
[3] B. Kroposki et al., “UNIFI specifications for grid-forming inverter-based
of GFM inverters during current-limited operations: resources (V. 2),” Nat. Renewable Energy Lab. (NREL), Golden, CO,
1) Although the effect of current limiting on the transient USA, Tech. Rep. NREL/TP-5D00-89269, 2024. [Online]. Available:
stability of GFM inverters during disturbances is covered https://www.nrel.gov/docs/fy24osti/89269.pdf
[4] AEMO, “Voluntary specifications for grid-fomring inverters,” Australian
extensively in this article, very few references take small- Energy Market Operator (AEMO), Melbourne, Victoria, Australia,
signal stability into consideration. Since engineering im- 2023. [Online]. Available: https://aemo.com.au/-/media/files/initiatives/
proved current-limiting behavior in large-signal response primary-frequency-response/2023/gfm-voluntary-spec.pdf
[5] I. Theologitis et al., “High penetration of power electronic interfaced
can trigger small-signal stability issues, mapping out the power sources and the potential contribution of grid forming converters,”
sweet spot between optimizing for small- and large-signal ENTSO-E Tech. Group High Penetration Power Electron. Interfaced
stability in GFM inverters during current-limited opera- Power Sources, Brussels, Belgium, 2020. [Online]. Available: https:
//euagenda.eu/upload/publications/untitled-292051-ea.pdf
tion is a point for further research. [6] EU, ”Migrate consortium,” 2020. [Online]. Available: https://www.
2) In this article, we outlined a general picture of the chal- h2020-migrate.eu/
lenges associated with protecting GFM inverter-driven [7] National Grid ESO, “Workgroup consultation GC0137: Minimum spec-
ification required for provision of GB grid forming (GBGF) capabil-
grids (or IBR-driven grids, for that matter); however, ity (formerly virtual synchronous machine/VSM capability),” London,
solid and widespread solutions both from power-system U.K., Mar. 2021. [Online]. Available: https://www.nationalgrideso.com/
and power-electronics perspectives are lacking in the document/189381/download
[8] Y. Lin et al., “Research roadmap on grid-forming inverters,” Nat. Renew-
current literature. Developing solutions for power sys- able Energy Lab., Golden, CO, USA, Tech. Rep. NREL/TP-5D00-73476,
tem protection incorporating the current-limiting behavior 2020.
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14513
[9] P. S. Kundur and O. P. Malik, Power System Stability and Control. New [32] D. Zmood and D. Holmes, “Stationary frame current regulation of PWM
York City, NY, USA: McGraw-Hill Educ., 2022. inverters with zero steady state error,” IEEE Trans. Power Electron.,
[10] Q. Taoufik, H. Wu, X. Wang, and I. Colak, “Variable virtual impedance- vol. 18, no. 3, pp. 814–822, May 2003.
based overcurrent protection for grid-forming inverters: Small-signal, [33] E. Rokrok, T. Qoria, A. Bruyere, B. Francois, and X. Guillaud, “Transient
large-signal analysis and improvement,” IEEE Trans. Smart Grid, vol. 14, stability assessment and enhancement of grid-forming converters em-
no. 5, pp. 3324–3336, Sep. 2023. bedding current reference saturation as current limiting strategy,” IEEE
[11] B. Fan, T. Liu, F. Zhao, H. Wu, and X. Wang, “A review of current-limiting Trans. Power Syst., vol. 37, no. 2, pp. 1519–1531, Mar. 2022.
control of grid-forming inverters under symmetrical disturbances,” IEEE [34] A. Pal, D. Pal, and B. K. Panigrahi, “A current saturation strategy
Open J. Power Electron., vol. 3, pp. 955–969, 2022. for enhancing the low voltage ride-through capability of grid-forming
[12] N. Baeckeland, “Design and modeling of inverter control for fault behav- inverters,” IEEE Trans. Circuits Syst. II: Exp. Briefs, vol. 70, no. 3,
ior and power system protection analysis,” Ph.D. dissertation, Fac. Eng. pp. 1009–1013, Mar. 2023.
Technol., KU Leuven, Belgium, 2022. [35] B. Fan and X. Wang, “Fault recovery analysis of grid-forming inverters
[13] G. Liang, G. N. B. Yadav, E. Rodriguez, G. G. Farivar, and J. Pou, “Fault with priority-based current limiters,” IEEE Trans. Power Syst., vol. 38,
ride-through control of cascaded H-bridge converter-based battery energy no. 6, pp. 5102–5112, Nov. 2023.
storage systems with redundant submodules,” in Proc. IEEE Southern [36] L. Zhang, L. Harnefors, and H.-P. Nee, “Power-synchronization control
Power Electron. Conf., 2022, pp. 1–5. of grid-connected voltage-source converters,” IEEE Trans. Power Syst.,
[14] C. Hirsching, M. Goertz, S. Wenig, A. Bisseling, M. Suriyah, and T. vol. 25, no. 2, pp. 809–820, May 2010.
Leibfried, “On fault-ride-through performance in MMC-HVDC applica- [37] L. Huang et al., “A virtual synchronous control for voltage-source
tions controlled as a virtual synchronous machine,” IEEE Trans. Energy converters utilizing dynamics of DC-link capacitor to realize self-
Convers., vol. 37, no. 4, pp. 2803–2812, Dec. 2022. synchronization,” IEEE Trans. Emerg. Sel. Topics Power Electron., vol. 5,
[15] D. W. Spier, C. Collados-Rodriguez, E. Prieto-Araujo, and O. Gomis- no. 4, pp. 1565–1577, Dec. 2017.
Bellmunt, “Analysis of equilibrium points and optimal grid support of [38] W. Du, Q. Nguyen, Y. Liu, and S. M. Mohiuddin, “A current limiting
grid-forming modular multilevel converter for balanced and unbalanced control strategy for single-loop droop-controlled grid-forming inverters
faults,” Int. J. Elect. Power Energy Syst., vol. 153, 2023, Art. no. 109281. under balanced and unbalanced faults,” in Proc. IEEE Energy Convers.
[16] M. C. Chandorkar, D. M. Divan, and R. Adapa, “Control of parallel Congr. Expo., 2022, pp. 1–7.
connected inverters in standalone ac supply systems,” IEEE Trans. Ind. [39] W. Du and S. M. Mohiuddin, “A two-stage current limiting control
Appl., vol. 29, no. 1, pp. 136–143, Jan./Feb. 1993. strategy for improved low-voltage ride-through capability of direct-
[17] H.-P. Beck and R. Hesse, “Virtual synchronous machine,” in Proc. Int. droop-controlled, grid-forming inverters,” in Proc. IEEE Energy Convers.
Conf. Elect. Power Qual. Utilisation, 2007, pp. 1–6. Congr. Expo., 2023, pp. 2886–2890.
[18] G.-S. Seo, M. Colombino, I. Subotic, B. Johnson, D. Groß, and F. Dör- [40] N. S. Gurule, J. Hernandez-Alvidrez, M. J. Reno, A. Summers, S.
fler, “Dispatchable virtual oscillator control for decentralized inverter- Gonzalez, and J. Flicker, “Grid-forming inverter experimental testing of
dominated power systems: Analysis and experiments,” in Proc. IEEE fault current contributions,” in Proc. IEEE Photovolt. Specialists Conf.,
Appl. Power Electron. Conf. Expo., 2019, pp. 561–566. 2019, pp. 3150–3155.
[19] M. Lu, S. Dutta, V. Purba, S. Dhople, and B. Johnson, “A grid-compatible [41] N. S. Gurule, J. Hernandez-Alvidrez, R. Darbali-Zamora, M. J. Reno,
virtual oscillator controller: Analysis and design,” in Proc. IEEE Energy and J. D. Flicker, “Experimental evaluation of grid-forming inverters
Convers. Congr. Expo., 2019, pp. 2643–2649. under unbalanced and fault conditions,” in Proc. Annu. Conf. IEEE Ind.
[20] M. Lu, “Virtual oscillator grid-forming inverters: State of the art, mod- Electron. Soc., 2020, pp. 4057–4062.
eling, and stability,” IEEE Trans. Power Electron., vol. 37, no. 10, [42] T. Liu, X. Wang, F. Liu, K. Xin, and Y. Liu, “A current limiting method
pp. 11579–11591, Oct. 2022. for single-loop voltage-magnitude controlled grid-forming converters
[21] W. Du et al., “A comparative study of two widely used grid-forming during symmetrical faults,” IEEE Trans. Power Electron., vol. 37, no. 4,
droop controls on microgrid small-signal stability,” IEEE Trans. Emerg. pp. 4751–4763, Apr. 2022.
Sel. Topics Power Electron., vol. 8, no. 2, pp. 963–975, Jun. 2020. [43] M. G. Taul, X. Wang, P. Davari, and F. Blaabjerg, “Current limiting
[22] M. Lu, R. Mallik, B. Johnson, and S. Dhople, “Dispatchable virtual- control with enhanced dynamics of grid-forming converters during fault
oscillator-controlled inverters with current-limiting and MPPT capabili- conditions,” IEEE Trans. Emerg. Sel. Topics Power Electron., vol. 8, no. 2,
ties,” in Proc. IEEE Energy Convers. Congr. Expo., 2021, pp. 3316–3323. pp. 1062–1073, Jun. 2020.
[23] B. Mahamedi, M. Eskandari, J. E. Fletcher, and J. Zhu, “Sequence-based [44] N. Baeckeland and G.-S. Seo, “Novel hybrid current limiter for grid-
control strategy with current limiting for the fault ride-through of inverter- forming inverter control during unbalanced faults,” in Proc. IEEE Int.
interfaced distributed generators,” IEEE Trans. Sustain. Energy, vol. 11, Conf. Power Electron. ECCE Asia, 2023, pp. 1517–1522.
no. 1, pp. 165–174, Jan. 2020. [45] A. D. Paquette and D. M. Divan, “Virtual impedance current limiting for
[24] C. Liu, X. Cai, R. Li, and R. Yang, “Optimal short-circuit current control inverters in microgrids with synchronous generators,” IEEE Trans. Ind.
of the grid-forming converter during grid fault condition,” IET Renewable Appl., vol. 51, no. 2, pp. 1630–1638, Mar./Apr. 2015.
Power Gener., vol. 15, no. 10, pp. 2185–2194, 2021. [46] X. Wang, Y. W. Li, F. Blaabjerg, and P. C. Loh, “Virtual-impedance-based
[25] I. Sadeghkhani, M. E. Hamedani Golshan, J. M. Guerrero, and A. control for voltage-source and current-source converters,” IEEE Trans.
Mehrizi-Sani, “A current limiting strategy to improve fault ride-through Power Electron., vol. 30, no. 12, pp. 7019–7037, Dec. 2015.
of inverter interfaced autonomous microgrids,” IEEE Trans. Smart Grid, [47] W. Zhang, J. Rocabert, J. I. Candela, and P. Rodriguez, “Synchronous
vol. 8, no. 5, pp. 2138–2148, Sep. 2017. power control of grid-connected power converters under asymmetrical
[26] A. Moawwad, M. S. El Moursi, and W. Xiao, “A novel transient control grid fault,” Energies, vol. 10, no. 7, 2017, Art. no. 950.
strategy for VSC-HVDC connecting offshore wind power plant,” IEEE [48] X. Lu, J. Wang, J. M. Guerrero, and D. Zhao, “Virtual-impedance-based
Trans. Sustain. Energy, vol. 5, no. 4, pp. 1056–1069, Oct. 2014. fault current limiters for inverter dominated AC microgrids,” IEEE Trans.
[27] N. Baeckeland, D. Venkatramanan, M. Kleemann, and S. Dhople, Smart Grid, vol. 9, no. 3, pp. 1599–1612, May 2018.
“Stationary-frame grid-forming inverter control architectures for unbal- [49] C. Luo, Y. Chen, Y. Xu, Z. Wang, and Q. Li, “Transient stability
anced fault-current limiting,” IEEE Trans. Energy Convers., vol. 37, no. 4, analysis and enhancement for VSG with virtual impedance based cur-
pp. 2813–2825, Dec. 2022. rent limitation,” in Proc. Annu. Conf. IEEE Ind. Electron. Soc., 2022,
[28] Z. Li, K. W. Chan, J. Hu, and S. W. Or, “An adaptive fault ride-through pp. 1–6.
scheme for grid-forming inverters under asymmetrical grid faults,” IEEE [50] F. Salha, F. Colas, and X. Guillaud, “Virtual resistance principle for the
Trans. Ind. Electron., vol. 69, no. 12, pp. 12912–12923, Dec. 2022. overcurrent protection of PWM voltage source inverter,” in Proc. IEEE
[29] M. Marwali and A. Keyhani, “Control of distributed generation systems- PES Innov. Smart Grid Technol. Conf. Europe, 2010, pp. 1–6.
Part I: Voltages and currents control,” IEEE Trans. Power Electron., [51] M. Zubiaga et al., “Enhanced TVI for grid forming vsc under unbalanced
vol. 19, no. 6, pp. 1541–1550, Nov. 2004. faults,” Energies, vol. 14, pp. 1–19, 2021.
[30] C. Liu et al., “Grid-Forming converter overcurrent limiting strategy [52] A. Gkountaras, S. Dieckerhoff, and T. Sezi, “Evaluation of current lim-
based on additional current loop,” Electronics, vol. 12, no. 5, 2023, iting methods for grid forming inverters in medium voltage microgrids,”
Art. no. 1112. in Proc. IEEE Energy Convers. Congr. Expo., 2015, pp. 1223–1230.
[31] T. Erckrath, P. Unruh, and M. Jung, “Voltage phasor based current limiting [53] J. He and Y. W. Li, “Analysis, design, and implementation of virtual
for grid-forming converters,” in Proc. IEEE Energy Convers. Congr. impedance for power electronics interfaced distributed generation,” IEEE
Expo., 2022, pp. 1–8. Trans. Ind. Appl., vol. 47, no. 6, pp. 2525–2538, Nov./Dec. 2011.
14514 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
[54] A. Gkountaras, S. Dieckerhoff, and T. Sezi, “Evaluation of current lim- [76] R. Rosso, S. Engelken, and M. Liserre, “On the implementation of an FRT
iting methods for grid forming inverters in medium voltage microgrids,” strategy for grid-forming converters under symmetrical and asymmetrical
in Proc. IEEE Energy Convers. Congr. Expo., 2015, pp. 1223–1230. grid faults,” IEEE Trans. Ind. Appl., vol. 57, no. 5, pp. 4385–4397,
[55] G. Denis, T. Prevost, M.-S. Debry, F. Xavier, X. Guillaud, and A. Menze, Sep./Oct. 2021.
“The migrate project: The challenges of operating a transmission grid [77] S. F. Zarei, H. Mokhtari, M. A. Ghasemi, and F. Blaabjerg, “Reinforcing
with only inverter-based generation. a grid-forming control improvement fault ride through capability of grid forming voltage source converters
with transient current-limiting control,” IET Renewable Power Gener., using an enhanced voltage control scheme,” IEEE Trans. Power Del.,
vol. 12, no. 5, pp. 523–529, 2018. vol. 34, no. 5, pp. 1827–1842, Oct. 2019.
[56] T. Erckrath, P. Unruh, and M. Jung, “Voltage phasor based current limiting [78] G. Lou, Q. Yang, W. Gu, and J. Zhang, “An improved control strategy of
for grid-forming converters,” in Proc. IEEE Energy Convers. Congr. virtual synchronous generator under symmetrical grid voltage sag,” Int.
Expo., 2022, pp. 1–8. J. Elect. Power Energy Syst., vol. 121, 2020, Art. no. 106093.
[57] J. Chen, F. Prystupczuk, and T. O’Donnell, “Use of voltage limits for [79] A. Narula, P. Imgart, M. Bongiorno, M. Beza, J. R. Svensson, and J.-
current limitations in grid-forming converters,” CSEE J. Power Energy P. Hasler, “Voltage-based current limitation strategy to preserve grid-
Syst., vol. 6, no. 2, pp. 259–269, 2020. forming properties under severe grid disturbances,” IEEE Open J. Power
[58] J. M. Bloemink and M. R. Iravani, “Control of a multiple source microgrid Electron., vol. 4, pp. 176–188, 2023.
with built-in islanding detection and current limiting,” IEEE Trans. Power [80] Z. Zeng, P. Bhagwat, M. Saeedifard, and D. Groß, “Hybrid threshold
Del., vol. 27, no. 4, pp. 2122–2132, Oct. 2012. virtual impedance for fault current limiting in grid-forming converters,”
[59] K. Shi, H. Ye, P. Xu, D. Zhao, and L. Jiao, “Low-voltage ride through in Proc. IEEE Energy Convers. Congr. Expo., 2023, pp. 913–918.
control strategy of virtual synchronous generator based on the analysis [81] T. Kim et al., “Blackstart of unbalanced microgrids using grid-forming
of excitation state,” IET Gener., Transmiss. Distrib., vol. 12, no. 9, inverter with voltage balancing capability,” in Proc. IEEE PES Transmiss.
pp. 2165–2172, 2018. Distrib. Conf. Expo., 2022, pp. 1–5.
[60] W. Du, Y. Liu, F. K. Tuffner, R. Huang, and Z. Huang, “Model specifica- [82] M. plet, T. C. Green, and J. D. McDonald, “Modelling and analysis of
tion of droop-controlled, grid-forming inverters (GFMDRP_A),” Pacific fault behaviour of inverter microgrids to aid future fault detection,” in
Northwest Nat. Lab., Richland, WA, USA, Tech. Rep., PNNL-32278, Proc. IEEE Int. Conf. Syst. Syst. Eng., 2007, pp. 1–6.
2021. [83] M. A. Zamani, A. Yazdani, and T. S. Sidhu, “A control strategy for
[61] W. Du, Y. Liu, R. Huang, F. K. Tuffner, J. Xie, and Z. Huang, “Positive- enhanced operation of inverter-based microgrids under transient distur-
sequence phasor modeling of droop-controlled, grid-forming inverters bances and network faults,” IEEE Trans. Power Del., vol. 27, no. 4,
with fault current limiting function,” in Proc. IEEE Power Energy Soc. pp. 1737–1747, Oct. 2012.
Innov. Smart Grid Technol. Conf., 2022, pp. 1–5. [84] K. G. Saffar, S. Driss, and F. B. Ajaei, “Impacts of current limiting on
[62] S. Jeong and G. Jang, “Stability analysis of a weak-grid-connected the transient stability of the virtual synchronous generator,” IEEE Trans.
voltage-sourced rectifier considering the phase-locked loop dynamics,” Power Electron., vol. 38, no. 2, pp. 1509–1521, Feb. 2023.
IEEE Trans. Power Syst., vol. 38, no. 1, pp. 436–446, Jan. 2023. [85] C. Luo, X. Ma, T. Liu, and X. Wang, “Controller-saturation-based
[63] H. Gong, X. Wang, and L. Harnefors, “Rethinking current controller transient stability enhancement for grid-forming inverters,” IEEE Trans.
design for PLL-synchronized VSCs in weak grids,” IEEE Trans. Power Power Electron., vol. 38, no. 2, pp. 2646–2657, Feb. 2023.
Electron., vol. 37, no. 2, pp. 1369–1381, Feb. 2022. [86] J. Erdocia, A. Urtasun, and L. Marroyo, “Dual voltage–current control
[64] Q.-C. Zhong and G. C. Konstantopoulos, “Current-limiting droop control to provide grid-forming inverters with current limiting capability,” IEEE
of grid-connected inverters,” IEEE Trans. Ind. Electron., vol. 64, no. 7, Trans. Emerg. Sel. Topics Power Electron., vol. 10, no. 4, pp. 3950–3962,
pp. 5963–5973, Jul. 2017. Aug. 2022.
[65] S. Dedeoglu and G. C. Konstantopoulos, “PLL-less three-phase droop- [87] C. A. Plet and T. C. Green, “A method of voltage limiting and distortion
controlled inverter with inherent current-limiting property,” in Proc. avoidance for islanded inverter-fed networks under fault,” in Proc. Eur.
Annu. Conf. IEEE Ind. Electron. Soc., 2019, pp. 4013–4018. Conf. Power Electron. Appl., 2011, pp. 1–8.
[66] A. G. Paspatis, G. C. Konstantopoulos, and J. M. Guerrero, “Enhanced [88] X. Lin, Z. Liang, Y. Zheng, Y. Lin, and Y. Kang, “A current limiting
current-limiting droop controller for grid-connected inverters to guaran- strategy with parallel virtual impedance for three-phase three-leg inverter
tee stability and maximize power injection under grid faults,” IEEE Trans. under asymmetrical short-circuit fault to improve the controllable capa-
Control Syst. Technol., vol. 29, no. 2, pp. 841–849, Mar. 2021. bility of fault currents,” IEEE Trans. Power Electron., vol. 34, no. 8,
[67] A. G. Paspatis and G. C. Konstantopoulos, “SRF-based current-limiting pp. 8138–8149, Aug. 2019.
droop controller for three-phase grid-tied inverters,” in Proc. Annu. Conf. [89] G.-S. Seo, J. Sawant, and F. Ding, “Black start of unbalanced microgrids
IEEE Ind. Electron. Soc., 2018, pp. 282–287. harmonizing single- and three-phase grid-forming inverters,” in Proc.
[68] Z. Shuai, W. Huang, C. Shen, J. Ge, and Z. J. Shen, “Characteristics and IEEE Power Energy Soc. Gen. Meeting, 2023, pp. 1–6.
restraining method of fast transient inrush fault currents in synchronvert- [90] M. Karimi-Ghartemani, R. Sharma, A. Zakerian, and S. A. Khajehoddin,
ers,” IEEE Trans. Ind. Electron., vol. 64, no. 9, pp. 7487–7497, Sep. 2017. “A single-phase enhanced grid-forming controller with converter current
[69] L. Huang, C. Wu, D. Zhou, and F. Blaabjerg, “A power-angle-based limiting,” in Proc. IEEE Energy Convers. Congr. Expo., 2021, pp. 37–44.
adaptive overcurrent protection scheme for grid-forming inverter under [91] M. Ciobotaru, R. Teodorescu, and F. Blaabjerg, “A new single-phase PLL
large grid disturbances,” IEEE Trans. Ind. Electron., vol. 70, no. 6, structure based on second order generalized integrator,” in Proc. IEEE
pp. 5927–5936, Jun. 2023. Power Electron. Specialists Conf., 2006, pp. 1–6.
[70] L. Huang, H. Xin, Z. Wang, L. Zhang, K. Wu, and J. Hu, “Transient [92] F. Xiao, L. Dong, L. Li, and X. Liao, “A frequency-fixed SOGI-based
stability analysis and control design of droop-controlled voltage source PLL for single-phase grid-connected converters,” IEEE Trans. Power
converters considering current limitation,” IEEE Trans. Smart Grid, Electron., vol. 32, no. 3, pp. 1713–1719, Mar. 2017.
vol. 10, no. 1, pp. 578–591, Jan. 2019. [93] M. Saitou and T. Shimizu, “Generalized theory of instantaneous active
[71] W. Du, R. H. Lasseter, and A. S. Khalsa, “Survivability of autonomous and reactive powers in single-phase circuits based on hilbert transform,”
microgrid during overload events,” IEEE Trans. Smart Grid, vol. 10, in Proc. Annu. IEEE Power Electron. Specialists Conf. Proc., 2002,
no. 4, pp. 3515–3524, Jul. 2019. pp. 1419–1424.
[72] A. J. G. Abrantes-Ferreira, A. C. Oliveira, and A. M. N. Lima, “Dispatch- [94] M. Saitou, N. Matsui, and T. Shimizu, “A control strategy of single-
able virtual oscillator inverter: Fault mitigation in weak grids,” in Proc. phase active filter using a novel D-Q transformation,” in Proc. IAS Annu.
IEEE Energy Convers. Congr. Expo., 2023, pp. 1059–1066. Meeting Conf. Rec. Ind. Appl. Conf., 2003, pp. 1222–1227.
[73] D. Groß and F. Dörfler, “Projected grid-forming control for current- [95] S. Gautam, W. Hassan, A. Bhatta, D. D.-C. Lu, and W. Xiao, “A compre-
limiting of power converters,” in Proc. Annu. Allerton Conf. Commun., hensive study of orthogonal signal generation schemes for single phase
Control, Comput., 2019, pp. 326–333. systems,” in Proc. Int. Conf. Power Electron. Energy, 2021, pp. 1–8.
[74] T. Qoria, F. Gruson, F. Colas, X. Kestelyn, and X. Guillaud, “Current lim- [96] Z. Xin, X. Wang, Z. Qin, M. Lu, P. C. Loh, and F. Blaabjerg, “An
iting algorithms and transient stability analysis of grid-forming VSCs,” improved second-order generalized integrator based quadrature signal
Electric Power Syst. Res., vol. 189, 2020, Art. no. 106726. generator,” IEEE Trans. Power Electron., vol. 31, no. 12, pp. 8068–8073,
[75] R. Rosso, S. Engelken, and M. Liserre, “Current limitation strategy Dec. 2016.
for grid-forming converters under symmetrical and asymmetrical grid [97] M. S. Reza, M. Ciobotaru, and V. G. Agelidis, “Accurate estimation of
faults,” in Proc. IEEE Energy Convers. Congr. Expo., 2020, pp. 3746– single-phase grid voltage parameters under distorted conditions,” IEEE
3753. Trans. Power Del., vol. 29, no. 3, pp. 1138–1146, Jun. 2014.
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14515
[98] Y. Wang, Y. Kuang, and Q. Xu, “A current-limiting scheme for [118] N. Baeckeland and G.-S. Seo, “Enhanced large-signal stability method for
voltage-controlled inverter using instantaneous current to generate virtual grid-forming inverters during current limiting,” in Proc. IEEE Workshop
impedance,” IEEE Trans. Emerg. Sel. Topics Circuits Syst., vol. 13, no. 2, Control Model. Power Electron., 2023, pp. 1–8.
pp. 524–535, Jun. 2023. [119] L. Huang, C. Wu, D. Zhou, and F. Blaabjerg, “A power angle limiting
[99] G. C. Konstantopoulos, Q.-C. Zhong, and W.-L. Ming, “PLL-less non- method for improving stability of grid-forming inverter under overcurrent
linear current-limiting controller for single-phase grid-tied inverters: condition,” in Proc. IEEE Energy Convers. Congr. Expo., 2022, pp. 1–6.
Design, stability analysis, and operation under grid faults,” IEEE Trans. [120] P. Hart and B. Lesieutre, “Energy function for a grid-tied, droop-
Ind. Electron., vol. 63, no. 9, pp. 5582–5591, Sep. 2016. controlled inverter,” in Proc. North Amer. Power Symp., 2014, pp. 1–6.
[100] Q.-C. Zhong and G. C. Konstantopoulos, “Nonlinear current-limiting [121] M. Kabalan, P. Singh, and D. Niebur, “Nonlinear Lyapunov stability
control for grid-tied inverters,” in Proc. Amer. Control Conf., 2016, analysis of seven models of a DC/AC droop controlled inverter connected
pp. 7472–7477. to an infinite bus,” IEEE Trans. Smart Grid, vol. 10, no. 1, pp. 772–781,
[101] G. C. Konstantopoulos, Q.-C. Zhong, B. Ren, and M. Krstic, “Bounded Jan. 2017.
integral control of input-to-state practically stable nonlinear systems to [122] I. Subotić, D. Groß, M. Colombino, and F. Dörfler, “A Lyapunov frame-
guarantee closed-loop stability,” IEEE Trans. Autom. Control, vol. 61, work for nested dynamical systems on multiple time scales with appli-
no. 12, pp. 4196–4202, Sep. 2016. cation to converter-based power systems,” IEEE Trans. Autom. Control,
[102] P. Unruh, M. Nuschke, P. Strauß, and F. Welck, “Overview on grid- vol. 66, no. 12, pp. 5909–5924, Dec. 2020.
forming inverter control methods,” Energies, vol. 13, no. 10, 2020, [123] P. J. Hart, M. Gong, H. Liu, Z. Chen, Y. Zhang, and Y. Wang, “Provably-
Art. no. 2589. stable overload ride-through control for grid-forming inverters using
[103] O. Ajala, N. Baeckeland, B. Johnson, S. Dhople, and A. Domínguez- system-wide lyapunov function analysis,” IEEE Trans. Energy Convers.,
García, “Model reduction and dynamic aggregation of grid-forming in- vol. 37, no. 4, pp. 2761–2776, Apr. 2022.
verter networks,” IEEE Trans. Power Syst., vol. 38, no. 6, pp. 5475–5490, [124] H. Wu and X. Wang, “Small-signal modeling and controller param-
Nov. 2023. eters tuning of grid-forming VSCs with adaptive virtual impedance-
[104] O. Ajala, M. Lu, B. Johnson, S. V. Dhople, and A. Domínguez-García, based current limitation,” IEEE Trans. Power Electron., vol. 37, no. 6,
“Model reduction for inverters with current limiting and dispatchable pp. 7185–7199, Jun. 2021.
virtual oscillator control,” IEEE Trans. Energy Convers., vol. 37, no. 4, [125] M. Miranbeigi, P. M. Gajare, J. Benzaquen, P. Kandula, and D. Divan,
pp. 2250–2259, Dec. 2021. “On the passivity of grid-forming converters – role of virtual impedance,”
[105] M. Lu, V. Purba, S. Dhople, and B. Johnson, “Comparison of droop con- in Proc. IEEE Appl. Power Electron. Conf. Expo., 2022, pp. 650–656.
trol and virtual oscillator control realized by andronov-hopf dynamics,” [126] J. Sawant, G.-S. Seo, and F. Ding, “Resilient inverter-driven black start
in Proc. 46th Annu. Conf. IEEE Ind. Electron. Soc., 2020, pp. 4051–4056. with collective parallel grid-forming operation,” in Proc. IEEE Power
[106] L. Huang, L. Zhang, H. Xin, Z. Wang, and D. Gan, “Current limiting Energy Soc. Innov. Smart Grid Technol. Conf., 2023, pp. 1–5.
leads to virtual power angle synchronous instability of droop-controlled [127] M. A. Awal, M. R. K. Rachi, H. Yu, S. Schröder, J. Dannehl, and I.
converters,” in Proc. IEEE Power Energy Soc. Gen. Meeting, 2016, pp. 1– Husain, “Grid-forming nature retaining fault ride-through control,” in
5. Proc. IEEE Appl. Power Electron. Conf. Expo., 2023, pp. 2753–2758.
[107] H. Xin, L. Huang, L. Zhang, Z. Wang, and J. Hu, “Synchronous in- [128] N. Baeckeland, D. Venkatramanan, S. Dhople, and M. Kleemann, “On the
stability mechanism of PF droop-controlled voltage source converter distance protection of power grids dominated by grid-forming inverters,”
caused by current saturation,” IEEE Trans. Power Syst., vol. 31, no. 6, in Proc. IEEE PES Innov. Smart Grid Technol. Conf. Europe, 2022, pp. 1–
pp. 5206–5207, Jun. 2016. 6.
[108] T. Qoria, F. Gruson, F. Colas, G. Denis, T. Prevost, and X. Guillaud, [129] N. Baeckeland and G.-S. Seo, “Large-signal stability improvement of
“Critical clearing time determination and enhancement of grid-forming parallel grid-forming inverter-driven black start,” in Proc. IEEE Power
converters embedding virtual impedance as current limitation algo- Energy Soc. Innov. Smart Grid Technol. Conf., 2024, pp. 1–5.
rithm,” IEEE Trans. Emerg. Sel. Topics Power Electron., vol. 8, no. 2, [130] N. Baeckeland and M. Kleemann, “Novel fault distance estimation
pp. 1050–1061, Feb. 2019. method for lines connected to converter-based generation,” in Proc. IEEE
[109] H. Zhang, W. Xiang, W. Lin, and J. Wen, “Grid forming converters PES Innov. Smart Grid Technol. Europe, 2021, pp. 01–06.
in renewable energy sources dominated power grid: Control strategy, [131] N. Bottrell and T. C. Green, “Comparison of current-limiting strate-
stability, application, and challenges,” J. Modern Power Syst. Clean gies during fault ride-through of inverters to prevent latch-up and
Energy, vol. 9, no. 6, pp. 1239–1256, 2021. wind-up,” IEEE Trans. Power Electron., vol. 29, no. 7, pp. 3786–3797,
[110] K. V. Kkuni and G. Yang, “Effects of current limit for grid forming Jul. 2014.
converters on transient stability: Analysis and solution,” Int. J. Electr. [132] S.-K. Sul, Control of Electric Machine Drive Systems. Hoboken, NJ,
Power Energy Syst., vol. 158, pp. 109919, 2024. USA: Wiley, 2011.
[111] B. Fan and X. Wang, “Equivalent circuit model of grid-forming converters [133] B. Pawar, E. I. Batzelis, S. Chakrabarti, and B. C. Pal, “Grid-forming
with circular current limiter for transient stability analysis,” IEEE Trans. control for solar PV systems with power reserves,” IEEE Trans. Sustain.
Power Syst., vol. 37, no. 4, pp. 3141–3144, Apr. 2022. Energy, vol. 12, no. 4, pp. 1947–1959, Apr. 2021.
[112] Y. Zhang, C. Zhang, R. Yang, M. Molinas, and X. Cai, “Current- [134] R. Teodorescu, F. Blaabjerg, U. Borup, and M. Liserre, “A new control
constrained power-angle characterization method for transient stability structure for grid-connected LCL PV inverters with zero steady-state
analysis of grid-forming voltage source converters,” IEEE Trans. Energy error and selective harmonic compensation,” in Proc. Annu. IEEE Appl.
Convers., vol. 38, no. 2, pp. 1338–1349, Jun. 2023. Power Electron. Conf. Expo., 2004, pp. 580–586 Vol.1.
[113] C. Shen, W. Gu, and E. Luo, “Transient performance comparison of [135] S. A. Richter and R. W. De Doncker, “Digital proportional-resonant (PR)
grid-forming converters with different FRT control strategies,” Front. control with anti-windup applied to a voltage-source inverter,” in Proc.
Energy, vol. 17, no. 2, pp. 239–250, 2023. Eur. Conf. Power Electron. Appl., 2011, pp. 1–10.
[114] T. Qoria, X. Wang, and R. Kadri, “Grid-forming control VSC-based [136] A. Ghoshal and V. John, “Anti-windup schemes for proportional integral
including current limitation and re-synchronization functions to deal with and proportional resonant controller.” 2010.
symmetrical and asymmetrical faults,” Electric Power Syst. Res., vol. 223, [137] H. P. Dang and H. N. Villegas Pico, “Blackstart and fault ride-through
2023, Art. no. 109647. capability of DFIG-based wind turbines,” IEEE Trans. Smart Grid,
[115] C. Collados-Rodriguez, D. W. Spier, M. Cheah-Mane, E. Prieto-Araujo, vol. 14, no. 3, pp. 2060–2074, Mar. 2023.
and O. Gomis-Bellmunt, “Preventing loss of synchronism of droop- [138] S. Tarbouriech and M. Turner, “Anti-windup design: An overview of
based grid-forming converters during frequency excursions,” Int. J. Elect. some recent advances and open problems,” IET Control Theory Appl.,
Power Energy Syst., vol. 148, 2023, Art. no. 108989. vol. 3, no. 1, pp. 1–19, 2009.
[116] M. Awal, M. R. K. Rachi, H. Yu, S. Schröder, J. Dannehl, and I. Husain, [139] Y. Gu and T. C. Green, “Power system stability with a high penetration
“Grid-forming nature retaining fault ride-through control,” in Proc. IEEE of inverter-based resources,” Proc. IEEE, vol. 111, no. 7, pp. 832–853,
Appl. Power Electron. Conf. Expo., 2023, pp. 2753–2758. Jul. 2023.
[117] X. Zhao and D. Flynn, “Freezing grid-forming converter virtual angu- [140] A. Sepehr, O. Gomis-Bellmunt, and E. Pouresmaeil, “Employing ma-
lar speed to enhance transient stability under current reference limit- chine learning for enhancing transient stability of power synchronization
ing,” in Proc. IEEE Workshop Control Model. Power Electron., 2020, control during fault conditions in weak grids,” IEEE Trans. Smart Grid,
pp. 1–7. vol. 13, no. 3, pp. 2121–2131, Mar. 2022.
14516 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 39, NO. 11, NOVEMBER 2024
[141] Z. Zhang, C. Lehmal, P. Hackl, and R. Schuerhuber, “Transient stability [163] S. P. Pokharel, S. M. Brahma, and S. J. Ranade, “Modeling and simulation
analysis and post-fault restart strategy for current-limited grid-forming of three phase inverter for fault study of microgrids,” in Proc. North Amer.
converter,” Energies, vol. 15, no. 10, 2022, Art. no. 3552. Power Symp., 2012, pp. 1–6.
[142] M. Mahdi and V. I. Genc, “Post-fault prediction of transient instabilities [164] C. Roh, “Performance comparisons of three-phase/four-wire model pre-
using stacked sparse autoencoder,” Electric Power Syst. Res., vol. 164, dictive control-based dc/ac inverters capable of asymmetric operation for
pp. 243–252, 2018. wave energy converters,” Energies, vol. 15, no. 8, 2022, Art. no. 2839.
[143] X. Lin, Y. Zheng, Z. Liang, and Y. Kang, “The suppression of volt- [165] M. Dietmannsberger and D. Schulz, “Impacts of low-voltage distribu-
age overshoot and oscillation during the fast recovery process from tion grid codes on ancillary services and anti-islanding detection of
load short-circuit fault for three-phase stand-alone inverter,” IEEE inverter-based generation,” IEEE Trans. Energy Convers., vol. 31, no. 4,
Trans. Emerg. Sel. Topics Power Electron., vol. 9, no. 1, pp. 858–871, pp. 1287–1294, Apr. 2016.
Jan. 2020. [166] IEEE Standard for Interconnection and Interoperability of Distrib. En-
[144] X. Wang, J. Gao, X. Wei, Z. Zeng, Y. Wei, and M. Kheshti, “Single ergy Resour. With Assoc. Electric Power Syst. Interfaces, IEEE Stan-
line to ground fault detection in a non-effectively grounded distribu- dard 1547-2018 (Revision of IEEE Standard 1547-2003), 2018.
tion network,” IEEE Trans. Power Del., vol. 33, no. 6, pp. 3173–3186, [167] IEEE Standard for Interconnection and Interoperability of Inverter-
Jun. 2018. Based Resour. (IBRs) Interconnecting With Assoc. Transmiss. Electric
[145] N. Tleis, Power Systems Modelling and Fault Analysis: Theory and Power Syst., IEEE Standard 2800-2022, 2022.
Practice. Amsterdam, The Netherlands: Elsevier, 2007. [168] EirGrid, “Eirgrid grid code, version 8,” 2019. [Online]. Available: http:
[146] C. A. Plet, M. Brucoli, J. D. McDonald, and T. C. Green, “Fault models //www.eirgridgroup.com/site-files/library/EirGrid/GridCodeVersion6.
of inverter-interfaced distributed generators: Experimental verification pdf
and application to fault analysis,” in Proc. IEEE Power Energy Soc. Gen. [169] VDE, “Technical requirements for the connection and operation of cus-
Meeting, 2011, pp. 1–8. tomer installations to the high voltage network (VDE-Ar-N 4120),” 2018.
[147] ENTSO-E, “Fault current contribution from PPMs & HVDC,” [170] N. G. ESO, Great Britain Grid Forming Best Practice Guide. Boca Raton,
ENTSO-E, Brussels, Belgium, Mar. 2017. [Online]. Available: https: FL, USA:CRC Press, 2023.
//consultations.entsoe.eu/system-development/entso-e-connection- [171] S. H. Horowitz, A. G. Phadke, and C. F. Henville, Power System Relaying,
codes-implementation-guidance-d-3/user_uploads/igd-fault-current- 5th ed. Hoboken, NJ, USA: Wiley, 2022.
contribution.pdf [172] N. Baeckeland, B. Herteleer, and M. Kleemann, “Impact of converter-
[148] D. B. Rathnayake et al., “Grid forming inverter modeling, control, and based distributed generation units on fault behaviour of distribution
applications,” IEEE Access, vol. 9, pp. 114781–114807, 2021. grids,” in Proc. Int. Conf. Develop. Power Syst. Protection, 2020, pp. 1–7.
[149] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Systems: [173] S. Cherevatskiy et al., “Grid forming energy storage system addresses
Modeling, Control, and Applications. Hoboken, NJ, USA: Wiley, 2010. challenges of grids with high penetration of renewables (a case study),”
[150] P. Rodríguez, J. Pou, J. Bergas, J. I. Candela, R. P. Burgos, and D. in Proc. CIGRÉ Session, 2020, Art. no. 322.
Boroyevich, “Decoupled double synchronous reference frame PLL for [174] M. Amaratunge, D. Edirisuriya, A. Ambegoda, M. Costa, W. Peiris, and
power converters control,” IEEE Trans. Power Electron., vol. 22, no. 2, K. Hemapala, “Development of adaptive overcurrent relaying scheme for
pp. 584–592, Feb. 2007. iidg microgrids,” in Proc. Int. Conf. Elect. Eng., 2018, pp. 71–75.
[151] D. Chatterjee, N. G. Barry, T. Kim, W. Kim, and S. Santoso, “Voltage [175] P. Mishra, A. K. Pradhan, and P. Bajpai, “Adaptive voltage restrained
balancing of grid-forming inverters in unbalanced, islanded microgrids,” overcurrent relaying for protection of distribution system with PV plant,”
in Proc. IEEE Power Energy Soc. Gen. Meeting, 2023, pp. 1–5. in Proc. IEEE Int. Conf. Power Syst., 2021, pp. 1–5.
[152] J. Svensson, M. Bongiorno, and A. Sannino, “Practical implementation [176] H. Muda and P. Jena, “Real time simulation of new adaptive overcurrent
of delayed signal cancellation method for phase-sequence separation,” technique for microgrid protection,” in Proc. Nat. Power Syst. Conf.,
IEEE Trans. Power Del., vol. 22, no. 1, pp. 18–26, Jan. 2006. 2016, pp. 1–6.
[153] E. Avdiaj, J. Are Suul, S. D’Arco, and L. Piegari, “A current controlled [177] A. Ghoor and S. Chowdhury, “Design of adaptive overcurrent protec-
virtual synchronous machine adapted for operation under unbalanced tion scheme for a grid-integrated solar PV microgrid,” in Proc. IEEE
conditions,” in Proc. Int. Conf. Renewable Energy Res. Appl., 2020, PES/IASPowerAfrica, 2020, pp. 1–5.
pp. 263–270. [178] J. Y. R. Wong et al., “Selectivity problem in adaptive overcurrent pro-
[154] J. Freytes, J. Li, G. de Préville, and M. Thouvenin, “Grid-forming tection for microgrid with inverter-based distributed generators (IBDG):
control with current limitation for MMC under unbalanced fault ride- Theoretical investigation and hil verification,” IEEE Trans. Power Del.,
through,” IEEE Trans. Power Del., vol. 36, no. 3, pp. 1914–1916, vol. 37, no. 4, pp. 3313–3324, Apr. 2021.
Mar. 2021. [179] G. Ziegler, Numerical Distance Protection: Principles and Applications.
[155] M. Awal, M. R. K. Rachi, H. Yu, I. Husain, and S. Lukic, “Double Hoboken, NJ, USA: Wiley, 2011.
synchronous unified virtual oscillator control for asymmetrical fault [180] C. Brantl, P. Ruffing, and R. Puffer, “The application of line protection
ride-through in grid-forming voltage source converters,” IEEE Trans. relays in high voltage Ac transmission grids considering the capabilities
Power Electron., vol. 38, no. 6, pp. 6759–6763, Jun. 2022. and limitations of connected MMCs,” 2020.
[156] R. Teodorescu, M. Liserre, and P. Rodriguez, Grid Converters for Pho- [181] A. Hooshyar, M. A. Azzouz, and E. F. El-Saadany, “Distance protection
tovoltaic and Wind Power Systems. Hoboken, NJ, USA: Wiley, 2011. of lines emanating from full-scale converter-interfaced renewable energy
[157] P. Bhagwat and D. Groß, “Three-phase grid-forming droop control for power plants–part i: Problem statement,” IEEE Trans. Power Del., vol. 30,
unbalanced systems and fault ride through,” in Proc. IEEE Power Energy no. 4, pp. 1770–1780, Apr. 2014.
Soc. Gen. Meeting, 2023, pp. 1–5. [182] R. Chowdhury and N. Fischer, “Transmission line protection for systems
[158] N. A. Ninad and L. A. C. Lopes, “Per-phase vector (dq) controlled three- with inverter-based resources–Part I: Problems,” IEEE Trans. Power Del.,
phase grid-forming inverter for stand-alone systems,” in Proc. IEEE Int. vol. 36, no. 4, pp. 2416–2425, Apr. 2020.
Symp. Ind. Electron., 2011, pp. 1626–1631. [183] A. Banaiemoqadam, A. Azizi, A. Hooshyar, M. Kanabar, and E. F.
[159] M. Shirazi, D. Gross, D. Light, J. VanderMeer, and T. Morgan, “Evalu- El-Saadany, “Impact of inverter-based resources on different implemen-
ation of current-limiting strategies for grid-forming inverters,” in Proc. tation methods for distance relays–Part I: Phase comparators,” IEEE
IEEE Energy Convers. Congr. Expo., 2023, pp. 1067–1074. Trans. Power Del., vol. 38, no. 6, pp. 4090–4102, Dec. 2023.
[160] G. Zeng and T. W. Rasmussen, “Design of current-controller with PR- [184] E. Martinez, M. Villén, S. Borroy, D. López, M. Popov, and H. Grasset,
regulator for LCL-filter based grid-connected converter,” in Proc. Int. “Effects of type-4 wind turbine on present protection relaying algo-
Symp. Power Electron. Distrib. Gener. Syst., 2010, pp. 490–494. rithms,” in Proc. 9th Protection Automat. Control (PAC) World Conf.,
[161] J. He, P. Liu, B. Liu, and S. Duan, “An asymmetric short-circuit fault 2018, pp. 1–9.
ride-through strategy providing current limiting and continuous voltage [185] J. Jia, G. Yang, A. H. Nielsen, and P. Rønne-Hansen, “Impact of VSC
supply for three-phase three-wire stand-alone inverters,” IEEE Access, control strategies and incorporation of synchronous condensers on dis-
vol. 8, pp. 211063–211073, 2020. tance protection under unbalanced faults,” IEEE Trans. Ind. Electron.,
[162] F. H. Md Rafi, M. J. Hossain, M. S. Rahman, and J. Lu, “Impact of vol. 66, no. 2, pp. 1108–1118, Feb. 2018.
controlling zero sequence current in a three-phase four-wire LV network [186] N. Baeckeland and M. Kleemann, “Influence of reactive current settings
with PV units,” in Proc. IEEE Power Energy Soc. Gen. Meeting, 2016, of converters on distance protection,” in Proc. Int. Colloq. Intell. Grid
pp. 1–5. Metrol., 2020, pp. 79–84.
BAECKELAND et al.: OVERCURRENT LIMITING IN GFM INVERTERS 14517
[187] M. Kleemann and N. Baeckeland, “Converter meets distance protection: Brian Johnson (Senior Member, IEEE) received the
A good match?,” in Proc. Eur. Conf. Power Electron. Appl., 2021, pp. 1– M.S. and Ph.D. degrees in electrical and computer
10. engineering from the University of Illinois at Urbana-
[188] G. Ziegler, Numerical Differential Protection: Principles and Applica- Champaign, Champaign, IL, USA, in 2010 and 2013,
tions. Hoboken, NJ, USA: Wiley, 2012. respectively. He is currently an Assistant Professor
[189] A. Haddadi, E. Farantatos, I. Kocar, and U. Karaagac, “Impact of inverter and a Fellow of the Jack Kilby/Texas Instruments En-
based resources on system protection,” Energies, vol. 14, no. 4, 2021, dowed Faculty Fellowship in Computer Engineering
Art. no. 1050. in the Chandra Family Department of Electrical and
[190] N. George, O. Naidu, and A. K. Pradhan, “Differential protection for Computer Engineering, University of Texas at Austin,
lines connected to inverter-based resources: Problems and solution,” in Austin, TX, USA. Previously, he was the Washington
Proc. Nat. Power Syst. Conf., 2022, pp. 419–424. Research Foundation Innovation Assistant Professor
[191] R. Chowdhury, R. McDaniel, and N. Fischer, “Applying line current dif- within the Department of Electrical and Computer Engineering at the University
ferential protection in systems with inverter-based resources,” Schweitzer of Washington in Seattle. Prior to joining the University of Washington in
Eng. Lab., Inc., Charlotte, NC, USA, 2022. [Online]. Available: http: 2018, he was an Engineer with the National Renewable Energy Laboratory.
//dx.doi.org/10.2139/ssrn.4058823 . His research interests are in renewable energy systems, power electronics, and
[192] S.K. Al-sachit and N. K. Nair, “Transmission line protection algo- control systems.
rithm based on voltage sequence component under high penetration of Dr. Johnson work was recognized with a National Science Foundation CA-
inverter-based resources,” Electric Power Syst. Res., vol. 201, 2021, REER Award in 2022 as well as prize paper awards from IEEE TRANSACTIONS
Art. no. 107504. [Online]. Available: https://www.sciencedirect.com/ ON ENERGY CONVERSION and IEEE TRANSACTIONS ON POWER ELECTRONICS.
science/article/pii/S0378779621004855 He is currently co-leading the multi-institutional Universal Interoperability
for Grid-Forming Inverters (UNIFI) Consortium which is funded by the U.S.
Department of Energy.