ion-lxhi-ds
ion-lxhi-ds
W
OPERATING ENVIRONMENT Feed Water Specifications
Installation should be indoors with no direct sunlight Feed Water Conductivity
< 40 μS/cm
and should have a maximum ambient room temperature Equivalent, including CO2 and Silica
of 113°F (45°C). Temperature 41 - 140° F (5 - 60° C)
pH 4 – 11
Halal certified. All Ionpure modules are manufactured in
accordance with the Islamic Food and Nutrition Council of Total Hardness (as CaCO3) < 1.0 ppm
America standards (IFANCA), and will carry the Crescent M Dissolved Organics (TOC as C) < 0.5 ppm
Halal logo. Silica (SiO2) < 1.0 ppm
Dimensions
Operating Parameters
Item Number L H W
Typical Recovery 90 – 95%
LXM04HI-3 11.81” 23.84” 12.54”
Maximum Feed Pressure 100 psi (6.9 bar)
(300.0 mm) (605.5 mm) (318.5 mm)
DC Voltage* 0 – 600
LXM10HI-3 15.29” 23.84” 12.54”
(388.6 mm) (605.5 mm) (318.5 mm) DC Amperage 0 - 10
LXM18HI-3 19.91” 23.84” 12.54” Pressure Drop Range
(505.7 mm) (605.5 mm) (318.5 mm) 20 - 30 psi (1.4 - 2.1 bar)
at Nominal Flow
LXM24HI-3 23.38” 23.84” 12.54” Maximum Feed Temperature 140°F (60°C)
(593.9mm) (605.5 mm) (318.5 mm)
Sanitization Temperature
LXM30HI-3 27.42” 23.84” 12.54” 185°F (85°C)
at 30 psi (2.0 bar)
(696.5mm) (605.5 mm) (318.5 mm)
All information presented herein is believed reliable and in accordance with accepted engineering practices. Evoqua makes
no warranties as to the completeness of this information. Users are responsible for evaluating individual product suitability
for specific applications. Evoqua assumes no liability whatsoever for any special, indirect or consequential damages arising
from the sale, resale or misuse of its products.
© 2018 Evoqua Water Technologies LLC Subject to change without notice ION-LXHI-DS-0818