Betriebsanleitung / Operating Instructions Ausgabe/Edition: AA

Previous

Bremseinheit / Braking Unit


11.2003 Allgemeines

Weitergabe sowie Vervielfältigung dieser Unterlage, Verwertung


und Mitteilung ihres Inhalts nicht gestattet, soweit nicht ausdrück-
lich zugestanden. Zuwiderhandlungen verpflichten zu Schadener-
satz. Alle Rechte vorbehalten, insbesondere für den Fall der
Patenterteilung oder GM-Eintragung.

Wir haben den Inhalt der Druckschrift auf Übereinstimmung mit


der beschriebenen Hard- und Software überprüft. Dennoch
können Abweichungen nicht ausgeschlossen werden, so dass wir
für die vollständige Übereinstimmung keine Garantie
übernehmen. Die Angaben in dieser Druckschrift werden jedoch
regelmäßig überprüft und notwendige Korrekturen sind in den
nachfolgenden Auflagen enthalten. Für Verbesserungsvorschläge SIMOVERT ist ein Warenzeichen von Siemens
sind wir dankbar.

The reproduction, transmission or use of this document or its con-


tents is not permitted without express written authority. Offenders
will be liable for damages. All rights, including rights created by
patent grant or registration of a utility model or design, are
reserved.
We have checked the contents of this document to ensure that
they coincide with the described hardware and software.
However, differences cannot be completely excluded, so that we
do not accept any guarantee for complete conformance.
However, the information in this document is regularly checked
and necessary corrections will be included in subsequent editions.
We are grateful for any recommendations for improvement. SIMOVERT Registered Trade Mark

6SE7087-6CX87-2DA1 Siemens AG
0-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
General 11.2003

Contents

1 Definitions and Warnings ..............................................................................1-1

2 Product Description .......................................................................................2-1

3 Mounting, Connecting-Up..............................................................................3-1

3.1 Dimension drawing ...........................................................................................3-3

3.2 Adaptor plate installation ..................................................................................3-4

3.3 Power terminals ................................................................................................3-5

3.4 Control terminal X38.........................................................................................3-6

3.5 Examples for connection ..................................................................................3-7

4 Braking Resistors...........................................................................................4-1

4.1 Definitions of the power ratings ........................................................................4-2

5 Monitoring .......................................................................................................5-1

6 Start-Up............................................................................................................6-1

6.1 Capacitor forming .............................................................................................6-5

7 Technical Data ................................................................................................7-1

6SE7087-6CX87-2DA1 Siemens AG
0-1 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Definitions and Warnings

1 Definitions and Warnings


Qualified personnel For the purpose of this documentation and the product warning labels,
a "Qualified person" is someone who is familiar with the installation,
mounting, start-up, operation and maintenance of the product. He or
she must have the following qualifications:
♦ Trained or authorized to energize, de-energize, ground and tag
circuits and equipment in accordance with established safety
procedures.
♦ Trained or authorized in the proper care and use of protective
equipment in accordance with established safety procedures.
♦ Trained in rendering first aid.

DANGER indicates an imminently hazardous situation which, if not avoided, will


result in death, serious injury and considerable damage to property.

WARNING indicates a potentially hazardous situation which, if not avoided, could


result in death, serious injury and considerable damage to property.

CAUTION used with the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, may result in minor or moderate injury.

CAUTION used without safety alert symbol indicates a potentially hazardous


situation which, if not avoided, may result in property damage.

NOTICE NOTICE used without the safety alert symbol indicates a potential
situation which, if not avoided, may result in an undesireable result or
state.

NOTE For the purpose of this documentation, "Note" indicates important


information about the product or about the respective part of the
documentation which is essential to highlight.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 1-1
Definitions and Warnings 11.2003

WARNING Hazardous voltages are present in this electrical equipment during


operation.
Non-observance of the warnings can thus result in severe personal
injury or property damage.
Only qualified personnel should work on or around the equipment
This personnel must be thoroughly familiar with all warning and
maintenance procedures contained in this documentation.
The successful and safe operation of this equipment is dependent on
correct transport, proper storage and installation as well as careful
operation and maintenance.

NOTE This documentation does not purport to cover all details on all types of
the product, nor to provide for every possible contingency to be met in
connection with installation, operation or maintenance.
Should further information be desired or should particular problems
arise which are not covered sufficiently for the purchaser's purposes,
the matter should be referred to the local SIEMENS sales office.
The contents of this documentation shall not become part of or modify
any prior or existing agreement, commitment or relationship. The sales
contract contains the entire obligation of SIEMENS AG. The warranty
contained in the contract between the parties is the sole warranty of
SIEMENS AG. Any statements contained herein do not create new
warranties or modify the existing warranty.

6SE7087-6CX87-2DA1 Siemens AG
1-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Definitions and Warnings

CAUTION
Components which can be destroyed by electrostatic
discharge (ESD)
The converters contain components which can be destroyed by electrostatic discharge. These
components can be easily destroyed if not carefully handled. If you have to handle electronic
boards please observe the following:
♦ Electronic boards should only be touched when absolutely necessary
♦ The human body must be electrically discharged before touching an electronic board
♦ Boards must not come into contact with highly insulating materials - e.g. plastic foils,
insulated desktops, articles of clothing manufactured from man-made fibers
♦ Boards must only be placed on conductive surfaces
♦ When soldering, the soldering iron tip must be grounded
♦ Boards and components should only be stored and transported in conductive packaging
(e.g. metalized plastic boxes, metal containers)
♦ If the packing material is not conductive, the boards must be wrapped with a conductive
packaging material, e.g. conductive foam rubber or household aluminum foil.
The necessary ECB protective measures are clearly shown in the following diagram:
a = Conductive floor surface d = ESD overall
b = ESD table e = ESD chain
c = ESD shoes f = Cubicle ground connection

d
b d b d

e e

f f f f f

a c c a c a
Sitting Standing Standing / Sitting

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 1-3
11.2003 Product Description

2 Product Description
When a motor brakes, it feeds electrical energy back to the SIMOVERT
MASTERDRIVES, causing the DC link voltage to rise. The braking unit
is connected in parallel to the DC link and limits the DC link voltage
increase to an acceptable level. The braking unit converts the
generated braking energy to heat in an external braking resistor. The
appropriate resistor must always be connected to the braking unit.
Braking energy cannot be converted without one.
The braking unit is connected to the converter or inverter via the DC
link terminals. When the DC bus voltage reaches a pre-defined limit,
the braking unit automatically turns on and prevents the DC bus voltage
from continuing to increase.
The braking unit operates autonomously of the converter or inverter.
The braking unit electronics are supplied from the DC link voltage.
Braking units can be connected in parallel to enhance braking
performance.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 2-1
11.2003 Mounting, Connecting-Up

3 Mounting, Connecting-Up
Mounting ♦ Using M6 screws or adapter plate on G-type mounting rail (adapter
plate is not included in scope of supply).

Connecting-up ♦ Braking unit:


Connect the terminals C/L+ and D/L- (top side of the braking unit) to
the terminals C/L+ and D/L- of the drive (see Fig. 3-2).
• Connecting cables to DC link must be twisted-pair and max. 3 m
long
• In the case of several parallel inverters with a common DC link,
the braking unit must be connected to the inverter with the
highest output.
♦ Connecting braking units in parallel:
• To increase the braking power, braking units can be connected
in parallel. The switch for the response threshold (see Fig. 6-2)
must be set identically on all units connected in parallel. The total
continuous braking power CBP is calculated from the total
continuous braking power of the individual units. For a definition
of braking power, see Fig. 4-1.
• Each braking unit must have its own twisted-pair feeder cable,
max. 3 m in length, to the DC link. Feeder cables of the same
length must be used for all paralleled braking units to ensure a
symmetrical distribution of current.
• Each braking unit requires its own braking resistor
♦ External braking resistors (selection list see chapter "Braking
Resistors")
• Connect braking resistor to terminals G and H.
• Length of the connecting cables between braking unit and
external braking resistor < 15 m.

WARNING Mis-connecting or shorting the DC bus terminals will destroy the drive
and the braking unit, respectively.
The exit air from the braking units can reach a temperature of > 80 °C.
The housing surface can reach a temperature of > 65 °C.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 3-1
Mounting, Connecting-Up 11.2003

A shield plate is included in the scope of supply of the braking unit.


When using shielded control cables or a shielded cable for the external
braking resistor, the shield of these cables can be connected to the
shield plate. This plate is also used for strain relief.
The shield plate is mounted via two bolts and the nuts supplied on the
bottom of the braking unit as shown in Fig. 3-1.

Fig. 3-1 Braking unit with shield plate

X3

X1 X3
DC link
CD
SIEMENS SIEMENS

Braking Unit
Braking Unit

SIMOVERT Overcurr. Overcurrent


Overload
Overcurrent
Overload Braking
Overload
MASTERDRIVES
Overtemp. Overtemp.
Ready

Resistor
Ready

Overtemp.
Ready
Ext.
Braking
Resistor

X2 X6
Parallel connection of braking units

Fig. 3-2 Connection of the braking unit

6SE7087-6CX87-2DA1 Siemens AG
3-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Mounting, Connecting-Up

3.1 Dimension drawing


View from above: C/L+ D/L- PE

10.5
115
Bolt M5x10
45
DC link 247
terminal X3

360
414

426

Braking
46

resistor
terminal X6

6.5 View from below:


135.9
X38
12

G H PE
1

Fig. 3-3 Dimension drawing

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 3-3
Mounting, Connecting-Up 11.2003

3.2 Adaptor plate installation


263

G-type Adapter plate

15
22
mounting rail
EN 50035
Braking Unit

478.2
360

500

Shield plate

G-type
mounting rai
Adapter plate

Hexagon nut M6

Adapter plate order number: 6SX7010-0KC01


Fig. 3-4

6SE7087-6CX87-2DA1 Siemens AG
3-4 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Mounting, Connecting-Up

3.3 Power terminals


DC link terminal X3
Terminal / meaning Remark
C/L+ Input (Plus DC link) Terminal strip (top of unit)
D/L- Input (Minus DC link) Terminal strip (top of unit)
PE Protective earth Terminal strip (top of unit)
Shield connection M5 bolt on housing at top
Braking resistor terminal X6
Terminal / meaning Remark
G External braking resistor Terminal strip (bottom of unit)
H External braking resistor Terminal strip (bottom of unit)
PE Protective earth Terminal strip (bottom of unit)
Shield connection M5 bolt on housing at bottom (via shield plate)

NOTE
Connectable cross section:
Multi-core 1.5 to 16 mm2
Stranded 1.5 to 16 mm2
AWG 16 to 6

Table 3-1 Power connections on braking unit

WARNING The braking unit may be connected to the DC bus bar with or without
using fuses. The connections between the drive converter or inverter
and braking unit must be short-circuit- and ground-fault proof.
The dielectric strength rating of the cable must be selected according to
the line voltage.

Fuses ♦ Fuses are recommended for multi-motor systems with a common


DC link (incoming power >> braking unit rating).
♦ High voltage fuses (1000 V) must be used in the positive and
negative branches (fuses type see Table 7-1).
♦ Fuses are not required for single-motor drives (one braking unit on
converter).

NOTE These fuses only provide protection in "critical situations". They do not
protect the braking unit or external braking resistor.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 3-5
Mounting, Connecting-Up 11.2003

3.4 Control terminal X38


Terminal / Remark
meaning
1 Inhibit input The braking unit is inhibited when + 24 V DC to reference potential (pin 2) is applied.
All active error messages are acknowledged at the same time. For an error to be
acknowledged, high level must be applied to this input for at least 2 ms (for
information about error acknowledgement, see also chapter 5 "Monitoring").
To enable the braking unit, remove the 24 V DC supply again (low level).

High level: > 15 V


Low level: < 5 V
Inhibition and acknowledgement are possible only if the external 24 V DC supply is
connected to pins 4 and 2.
2 M Ground for external 24 V supply and reference potential for signals
3 Not assigned No function
4 P24 Positive pole of external 24V supply
20 V – 30 V DC / 0.5 A
5 Fault output Output transistor conductive → No fault
(output voltage > P24 – 3 V)
Output transistor blocked → Fault
(0 V) or
braking unit inhibited
or
no DC link voltage
or
no external 24 V supply
The fault output has a maximum current-carrying capacity of 300 mA.
The fault output is referred to the potential at ground terminal X38, pin 2

NOTE The braking unit will work even if control terminal strip X38 is not
connected.
When the DC link voltage is disconnected and the internal voltage
supply drops (fault LEDs go out), errors are cleared automatically.
The cables for connecting control terminal strip X38 must be installed
separately from the power cables.
Length of control cables < 10 m.

6SE7087-6CX87-2DA1 Siemens AG
3-6 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Mounting, Connecting-Up

3.5 Examples for connection


PE
C/L+ D/L-
24 V DC
-X3: -X3: -X6:
Overcurrent C / L+ C/L+ G
O
V Overload SIMOVERT H
E Overtemp MASTER- Load
R
1 3
Ready DRIVES resistor
D / L- D/L-
X38 Braking unit
1
-X38
1 2 4
-X9 -X101.2 2
2 3
-X101.1 4
3
4 24 V
5
5
-X101.7

G H PE
P586 = 18

Fig. 3-5 General schematic Fig. 3-6 Converter – braking unit with braking resistor and
diagram shutdown of converter on faults via digital input 5

24 V DC
-X3: -X3: -X6:
C / L+ C/L+ G

SIMOVERT H
MASTER- 1 3 Load
DRIVES resistor
D / L- D/L-
X38 Braking unit
1
2 4
-X9 -X101.2 2
3
-X101.1 4
24 V
-X101.8 5

-X101.7

For MASTERDRIVES parameter setting,


see section "Start-up"

Fig. 3-7 Converter – braking unit with braking resistor and shutdown of converter on faults;
braking unit fault message to converter;
acknowledgement of braking unit fault via pushbutton

CAUTION The braking unit may not be connected to the live DC bus via a
contactor.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 3-7
11.2003 Braking Resistors

4 Braking Resistors
The braking resistors listed in chapter 7 "Technical Data" match the
braking units and allow full utilization of the braking capability.

WARNINGS When braking resistors and braking units are combined, it must be
guaranteed that the resistance of a resistor is not less than the
minimum allowed resistance, otherwise the braking unit may be
destroyed!
Higher values of the resistors are allowed. The higher the resistance
value, however, the lower the braking power. The braking power varies
indirectly in proportion to the resistance value (double the resistance
value → half the braking power).
During operation the surface of the braking resistors may have
temperatures of several hundred degrees C. Therefore cooling air must
not contain flammable or explosive items or gases.
If a resistor is wall-mounted, the wall must not be flammable.

WARNINGS The external braking resistor must be mounted separately and


connected to the plant supply.
The braking resistors recommended by Siemens have a thermocontact
(NC contact) which trips when the resistor overloads. In this event, the
converter must be disconnected from the supply via a main contactor.
If the main contactor is controlled via the appropriate output of the
converter or inverter (X9), the thermocontact can be connected to a
binary input that is parameterized as a fault input (see Fig. 3-6).

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 4-1
Braking Resistors 11.2003

4.1 Definitions of the power ratings


Braking unit with external resistor
P20 = Rated Power
P3 = Peak Power = 1.5 × P20
PDB = 0.25 × P20 = Steady State Power Rating
P

The following applies with respect to


P3 1.5
paralleled braking units:
P20 total = 0.9 x aggregate P20
P20 1 of individual units
P3 total = aggregate P3 of
individual units
PDB 0.25 PDB total = aggregate CBP of
individual units
0
03 20 23 90 t[s]

Fig. 4-1 Load characteristics of the braking units

6SE7087-6CX87-2DA1 Siemens AG
4-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Monitoring

5 Monitoring
When faults occur, the braking unit is inhibited and the transistor at the
fault output blocked (see 3.4 "Control terminal X38"). The appropriate
operating state is indicated by the LEDs on the front panel.

Display elements Description of operating state State of Acknow-


(LED) output ledgeable?
transistor
♦ Overcurrent LED lights up with a short circuit at the output end. Blocked Yes
(fault) This fault is not self-acknowledging. You can
acknowledge it by applying and then removing the inhibit
signal.
Correct the short circuit before acknowledging the
fault!
♦ Overload LED lights up when the overload monitor responds (the Conductive Self-
ratio between load and off-load duration is monitored, I2t acknow-
monitoring); the pulse/pause ratio is limited when the ledging
specified duty cycle is exceeded.
The total continuous braking power (CBP) can be
displayed at any time regardless of the status of the
LED.
The duty cycles shown in Fig. 4-1 (P3/P20) can be
deselected complete only after the LED has gone out.
♦ Overtemp The LED lights up when the temperature monitor Blocked No
(fault) responds (ambient temperature too high or cooling air
inlet inhibited).
The fault is automatically acknowledged when the
temperature drops below the critical level again.
♦ Ready The LED lights up when operating voltage is connected Conductive Not
to the input terminals. applicable
It goes out if the braking unit is disabled via the "Inhibit"
input on control terminal strip X38 or if a temperature
fault (→ Overtemp) or short circuit (→ Overcurrent) has
occurred.
A flashing LED indicates an internal fault in the braking
unit, i.e. the unit is defective.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 5-1
11.2003 Start-Up

6 Start-Up

DANGER Do not remove the front cover when voltage is applied to the
braking unit!
The control circuit is directly connected to the DC bus voltage!
The unit must therefore be disconnected from the supply before the
setting of the response threshold switch is adjusted.
The units have hazardous voltage levels up to 5 min. after the unit has
been powered-down due to the DC link capacitors.

How to change setting of switch S1 for


the response threshold:
♦ Remove the two screws at the
bottom of the front plate, pull the
plate out forwards at the bottom
and push to one side (Fig. 6-1). Do
not remove the PE conductor
connection to the front cover!
♦ Use a suitable tool, e.g. small
screwdriver, to adjust the setting of
switch S1 (Fig. 6-2).
♦ Hook the top of the front panel into
Overcurrent
the slit in the housing and insert Overload
and tighten the two screws at the Overtemp.
Ready
bottom.

Fig. 6-1 Opening the front


cover

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 6-1
Start-Up 11.2003

Low
High

Fig. 6-2 Swith S1 for response threshold

Switch S1 for response threshold:


It is possible to switch over the response threshold on the braking units.
This can be useful for units operating on a supply system with 380 V /
400 V, 500 V or 660 V. In this case, the DC link voltage increases only
slightly in braking mode, thus reducing the voltage load on the motor
insulation.

NOTE For 1LA1/5/6/8/ type SIEMENS motors the voltage limit does not need
to be changed.
If the voltage limit switch S1 is set to the lower limit, the braking power
is reduced (P~V2).

6SE7087-6CX87-2DA1 Siemens AG
6-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Start-Up

The voltage limit switch S1 is located behind the front cover.


Braking unit Rated voltage Response threshold Switch position
6SE70__-_C.87-2DA1 208 V to 230 V 387 V (not adjustable) In both positions

6SE70__-_E.87-2DA1 380 V to 460 V 757 V (factory setting) L

H
380 V to 400 V 673 V L

6SE70__-_F.87-2DA1 500 V to 575 V 945 V (factory setting) L

H
500 V 841 V L

6SE70__-_H.87-2DA1 660 V to 690 V 1105 V (factory setting) L

H
660 V 1040 V L

Table 6-1 Setting the response thresholds

Set parameters on converter: (see section headed "Parameterization"


in operating manual for SIMOVERT MASTERDRIVES)
♦ Deactivate the Udmax controller in the converter or inverter. To do
this on units with Vector Control functionality, set parameter P515 to
"0". Units with Motion Control functionality do not possess this
controller and do not therefore require resetting.
♦ Parameterize the binary inputs and outputs for controlling the
braking unit (BICO technology). The specified setting values are
based on the assumption that the connections between the
MASTERDRIVES and braking unit have been made according to
Fig. 3-6 or Fig. 3-7. If different terminals have been used, the setting
values must be modified accordingly.
Assuming that the MASTERDRIVES parameters are set to their
defaults (factory state), the required parameter settings are as follows:
Example according to Fig. 3-6
P575 Index 001 = 18

Example according to Fig. 3-7


P575 Index 001 = 18
U064 Index 001 = 617
U237 Index 001 = 536
U237 Index 002 = 21
U302 Index 001 = 158
U303 Index 001= 3
U951 Index 099 = 8
U952 Index 054 = 8
U952 Index 062 = 8

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 6-3
Start-Up 11.2003

Dig.inp.5
-X101/7 24 V P575.1 = 18
B0018 B ext. fault 1
5V

[Sheet 780]
U303.1 Mode
3s U304 (0)
U951.99 = 8
T [Sheet 765] [Sheet 710]
ON delay
from status word 2 / bit 29 T 0 0
"Bypass contactor
energized" OFF delay
0 T 1 U952.54 = 8
U302 = 158 U237 U952.62 = 8
.01
B B0536 B U064 = 617
ON/OFF delay .02
T T 2 B
.03 & B0617 B 1 = "fault F151"
B (1)
Pulse generator 1 B0537
T 3

-X101/8 24 V
B0020 Dig.inp.6
5V
1 B0021
Dig.inp. 6 neg.

Fig. 6-3

NOTE When the DC link voltage is applied, fault output –X38/5 is "Low" for
about 2 seconds (self-test), i.e. in the fault state. The parameter
settings specified above conceal this state when the system is switched
on.

6SE7087-6CX87-2DA1 Siemens AG
6-4 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Start-Up

6.1 Capacitor forming


The DC link capacitors must be re-formed if the converter has been
non-operational for more than one year. If the converter was started-up
within one year after having been shipped (serial number on the rating
plate), it is not necessary to re-form the DC link capacitors.
Forming is realized by switching-in a rectifier and resistor, which is
connected to the DC link. The converter supply must be
disconnected (circuit: refer to Fig. 6-4)!
The forming period required depends on how long the braking unit has
been non-operational (see Fig. 6-5).

Position Example Significance / Example


1 and 2 F2 Site of manufacture: Chemnitz
3 R Manufacturing year: 2003
S 2004
T 2005
U 2006
4 1 to 9 Manufacturing month: Jan. to Sept.
O October
N November
D December
5 to 10 Not relevant for forming
(serial number)
Table 6-2 Serial number structure

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 6-5
Start-Up 11.2003

Forming
PE
C/L+ D/L-

O Overcurrent
V Overload
E Overtemp
R
Ready

R
G H PE

Recommended components
A R C
208 V < Un < 415 V SKD 50 / 12 220 Ω / 100 W 22 nF / 1600 V
380 V < Un < 460 V SKD 62 / 16 470 Ω / 100 W 22 nF / 1600 V
500 V < Un < 690 V SKD 62 / 18 680 Ω / 100 W 22 nF / 1600 V

Fig. 6-4 Circuit for forming

Forming
6 time in h
5
4
3
2
1

1 2 3 4 5
Non-operational
time in years

Fig. 6-5 Forming time as a function of how long braking unit has been non-
operational

6SE7087-6CX87-2DA1 Siemens AG
6-6 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Technical Data

7 Technical Data

Order Number Power Voltage Rated Weight Order Number Conductor Fuses
Rating Limit DC sizes for DC link
voltage DC link and
braking Type
resistor
Braking unit P20 Braking resistor Cu cable
6SE70... (kW) (V) (V) (kg) 6SE70... Ω)
(Ω mm2 AWG
21-6CS87-2DA1 5 387 280 to 310 3 21-6CS87-2DC0 20 1.5 14 3NE4101
18-0ES87-2DA1 5 757 510 to 620 3 18-0ES87-2DC0 80 1.5 16 3NE4101
16-4FS87-2DA1 5 945 675 to 780 3 16-4FS87-2DC0 124 1.5 16 3NE4101
23-2CS87-2DA1 10 387 280 to 310 3.3 23-2CS87-2DC0 10 2.5 14 3NE4102
21-6ES87-2DA1 10 757 510 to 620 3.1 21-6ES87-2DC0 40 1.5 16 3NE4101
21-3FS87-2DA1 10 945 675 to 780 3.1 21-3FS87-2DC0 62 1.5 16 3NE4101
26-3CS87-2DA1 20 387 280 to 310 4.1 26-3CS87-2DC0 5 10 6 3NE4120
23-2ES87-2DA1 20 757 510 to 620 3.3 23-2ES87-2DC0 20 2.5 14 3NE4102
28-0ES87-2DA1 50 757 510 to 620 4.1 28-0ES87-2DC0 8 10 6 3NE4121
26-4FS87-2DA1 50 945 675 to 780 4.1 26-4FS87-2DC0 12.4 10 6 3NE4120
25-3HS87-2DA1 50 1105 890 to 930 4.1 25-3HS87-2DC0 17.8 6 8 3NE4118

NOTE Braking resistor: Resistance value ± 10 %

Table 7-1 Technical data

NOTE The minimum conductor sizes apply to copper cable at an ambient


temperature of 40 °C (in accordance with DIN VDE 0298 Part 4 / 02.88
Group 5). For maximum possible conductor sizes, see section 3.3,
Table 3-1.

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 7-1
Technical Data 11.2003

Dimensions (mm) Width Height Depth


45 360 247
Cooling method Self cooling
Degree of protection IP20 nach EN 60529
Permissible ambient or coolant
temperature
• In operation 0° C to +40° C (32° F to 104° F)
• In storage -25° C to +55° C (-13° F to 131° F)
• In transport -25° C to +70° C (-13° F to 158° F)
Pollution severity Pollution severity 2 to DIN EN 50178
Environmental conditions Climate: 3K3
to DIN IEC 721-3-3 Chemically active substances: 3C2
Humidity rating Relative air humidity
≤ 95 % in transport and storage
≤ 85 % in operation (no condensation
permitted)

Table 7-2 Technical data

6SE7087-6CX87-2DA1 Siemens AG
7-2 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Technical Data

Cabinet - roof mounting A

145
PE

∅ 5.5 x 8

525 150
15 540 180

Wall mounting (electrical connection to the left)

Mulit-element resistor MF2

Airflow
(convection)

Braking resistor for Type


5 kW; 20 Ω 6SE7021-6CS87-2DC0
5 kW; 80 Ω 6SE7018-0ES87-2DC0
5 kW; 124 Ω 6SE7016-4FS87-2DC0

Fig. 7-1 Mounting diagram, braking resistor

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 7-3
Technical Data 11.2003

Cabinet - roof mounting A

145
PE

∅5.5 x 8

525 330
15 540 360

Wall mounting (electrical connection to the left)

Mulit-element resistor MF4

Airflow
(convection)

Braking resistor for Type


10 kW; 10 Ω 6SE7023-2CS87-2DC0
10 kW; 40 Ω 6SE7021-6SE87-2DC0
10 kW; 62 Ω 6SE7021-3FS87-2DC0

Fig. 7-2 Mounting diagram, braking resistor

6SE7087-6CX87-2DA1 Siemens AG
7-4 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
11.2003 Technical Data

Floor mounting
430
View A

M20

M25

305
M6
ground
terminal

400

View A
∅9

T1/T2 pillar
terminal
380
485

2.5 mm2

2 M6 pin
terminals
400

430

Wall mounting
400
∅9
380

The minimum clearance to other


components must be 100 mm on all sides
with ventilation slots!

Braking resistor for Type Weight, approx.


20 kW; 20 Ω 6SE7023-2ES87-2DC0 17 kg
20 kW; 5 Ω 6SE7026-3CS87-2DC0 15 kg

Fig. 7-3 Mounting diagram, braking resistor for floor and wall mounting

Siemens AG 6SE7087-6CX87-2DA1
SIMOVERT MASTERDRIVES Bremseinheit / Braking Unit 7-5
Technical Data 11.2003

Floor mounting
740
View A

M20

M25

305
M6
ground
terminal

710

∅9
480

380

T1/T2 pillar
terminal
2.5 mm2
View A
Wall mounting 400
∅9

380

2 M6 pin
terminals
710

729 The minimum clearance to other components must be


100 mm on all sides with ventilation slots!

Braking resistor for Type Weight, approx.


50 kW; 8 Ω 6SE7028-0ES87-2DC0 27 kg
50 kW; 12,4 Ω 6SE7026-4FS87-2DC0 27 kg
50 kW; 17,8 Ω 6SE7025-3HS87-2DC0 28 kg

Fig. 7-4 Mounting diagram, braking resistor for floor and wall mounting

6SE7087-6CX87-2DA1 Siemens AG
7-6 Bremseinheit / Braking Unit SIMOVERT MASTERDRIVES
Bisher sind folgende Ausgaben erschienen: Ausgabe interne Sachnummer
AA A5E00236283

Ausgabe AA besteht aus folgenden Kapiteln:

Kapitel Änderungen Seitenzahl Ausgabedatum


1 Definitionen und Warnungen Erstausgabe 3 11.2003
2 Produktbeschreibung Erstausgabe 1 11.2003
3 Montieren, Anschließen Erstausgabe 7 11.2003
4 Bremswiderstände Erstausgabe 2 11.2003
5 Überwachung Erstausgabe 1 11.2003
6 Inbetriebsetzen Erstausgabe 6 11.2003
7 Technische Daten Erstausgabe 6 11.2003

The following versions have been published so far: Version Internal item number
AA A5E00236283

Version AA consists of the following chapters:

Chapter Changes Pages Version date


1 Definitions and Warnings first edition 3 11.2003
2 Product Description first edition 1 11.2003
3 Mounting, Connecting-Up first edition 7 11.2003
4 Braking Resistors first edition 2 11.2003
5 Monitoring first edition 1 11.2003
6 Start-Up first edition 6 11.2003
7 Technical Data first edition 6 11.2003

Siemens AG
Automatisierungs- und Antriebstechnik
Motion Control Systems
Postfach 3180, D – 91050 Erlangen © Siemens AG 2003
Änderungen vorbehalten
Bundesrepublik Deutschland Bestell-Nr./Order No.: 6SE7087-6CX87-2DA1

www.ad.siemens.de Gedruckt in der Bundesrepublik Deutschland