0% found this document useful (0 votes)
17 views142 pages

GA 90+-160 (2018) AIB EN Wuxi 9829317862-Compressed

Uploaded by

anhdungro1986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views142 pages

GA 90+-160 (2018) AIB EN Wuxi 9829317862-Compressed

Uploaded by

anhdungro1986
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 142

GA 90+, GA 110, GA 132, GA 160

Instruction book
Atlas Copco

GA 90+, GA 110, GA 132, GA 160

Instruction book
Original instructions

COPYRIGHT NOTICE
Any unauthorized use or copying of the contents or any part thereof is prohibited.
This applies in particular to trademarks, model denominations, part numbers and
drawings.

2019 - 12
No. 9829 3178 62

www.atlascopco.com
Instruction book

Table of contents

1 Safety precautions..........................................................................................................5

1.1 SAFETY ICONS................................................................................................................................... 5

1.2 GENERAL SAFETY PRECAUTIONS............................................................................................................5

1.3 SAFETY PRECAUTIONS DURING INSTALLATION........................................................................................... 6

1.4 SAFETY PRECAUTIONS DURING OPERATION.............................................................................................. 7

1.5 SAFETY PRECAUTIONS DURING MAINTENANCE OR REPAIR........................................................................... 8

1.6 DISMANTLING AND DISPOSAL...............................................................................................................10

2 General description...................................................................................................... 11

2.1 INTRODUCTION.................................................................................................................................11

2.2 AIR AND OIL SYSTEM.........................................................................................................................13

2.3 COOLING AND CONDENSATE SYSTEM.................................................................................................... 16

2.4 REGULATING SYSTEM........................................................................................................................ 17

2.5 ENERGY RECOVERY SYSTEM...............................................................................................................20

3 Elektronikon™ Touch controller................................................................................. 29

3.1 CONTROLLER...................................................................................................................................29

3.2 CONTROL PANEL.............................................................................................................................. 31

3.3 ICONS USED.................................................................................................................................... 32

3.4 MAIN SCREEN..................................................................................................................................36

3.5 QUICK ACCESS SCREEN.....................................................................................................................37

3.6 MENU SCREEN.................................................................................................................................38

3.7 DATA MENU.....................................................................................................................................40

3.8 SERVICE MENU................................................................................................................................ 42

3.9 WEEK TIMER MENU...........................................................................................................................44

3.10 EVENT HISTORY MENU.......................................................................................................................45

3.11 MACHINE SETTINGS MENU.................................................................................................................. 46

3.12 CONTROLLER SETTINGS MENU.............................................................................................................49

2 9829 3178 62
Instruction book

3.13 ACCESS LEVEL.................................................................................................................................52

4 Installation.....................................................................................................................54

4.1 DIMENSION DRAWING........................................................................................................................ 54

4.2 INSTALLATION PROPOSAL................................................................................................................... 60

4.3 ELECTRICAL CONNECTIONS.................................................................................................................63

4.4 QUALITY OF SAFETY COMPONENTS.......................................................................................................71

4.5 PICTOGRAPHS................................................................................................................................. 71

4.6 COOLING WATER REQUIREMENTS.........................................................................................................72

5 Operating instructions................................................................................................. 78

5.1 INITIAL START-UP..............................................................................................................................78

5.2 BEFORE STARTING............................................................................................................................81

5.3 STARTING....................................................................................................................................... 82

5.4 DURING OPERATION.......................................................................................................................... 84

5.5 CHECKING THE DISPLAY.....................................................................................................................85

5.6 MANUAL LOADING/UNLOADING.............................................................................................................87

5.7 STOPPING.......................................................................................................................................88

5.8 TAKING OUT OF OPERATION................................................................................................................89

5.9 USE OF AIR RECEIVER....................................................................................................................... 90

6 Maintenance.................................................................................................................. 91

6.1 PREVENTIVE MAINTENANCE SCHEDULE..................................................................................................91

6.2 OIL SPECIFICATIONS..........................................................................................................................92

6.3 OIL SPECIFICATIONS..........................................................................................................................93

6.4 OIL CHANGE....................................................................................................................................93

6.5 OIL FILTER CHANGE.......................................................................................................................... 95

6.6 OIL SEPARATOR CHANGE................................................................................................................... 96

6.7 STORAGE AFTER INSTALLATION........................................................................................................... 97

6.8 SERVICE KITS.................................................................................................................................. 97

9829 3178 62 3
Instruction book

7 Integrated dryer............................................................................................................ 98

7.1 INTRODUCTION.................................................................................................................................98

7.2 AIR AND REFRIGERANT SYSTEM.........................................................................................................101

7.3 AUTOMATIC REGULATION SYSTEM...................................................................................................... 105

7.4 CONDENSATE DRAIN SYSTEM............................................................................................................ 107

7.5 ELECTRICAL SYSTEM.......................................................................................................................109

7.6 REGULATION ................................................................................................................................ 109

7.7 MAINTENANCE INSTRUCTIONS........................................................................................................... 110

7.8 PROBLEM SOLVING......................................................................................................................... 111

8 Adjustments and servicing procedures................................................................... 113

8.1 AIR FILTERS.................................................................................................................................. 113

8.2 COOLERS..................................................................................................................................... 113

8.3 SAFETY VALVE...............................................................................................................................115

9 Problem solving..........................................................................................................117

9.1 PROBLEM SOLVING......................................................................................................................... 117

10 Technical data.............................................................................................................119

10.1 READINGS ON DISPLAY.................................................................................................................... 119

10.2 REFERENCE CONDITIONS................................................................................................................. 120

10.3 LIMITS..........................................................................................................................................120

10.4 SETTINGS OF SAFETY VALVE.............................................................................................................121

10.5 SETTINGS OF OVERLOAD RELAYS, FUSES AND CIRCUIT BREAKERS............................................................ 121

10.6 COMPRESSOR DATA........................................................................................................................126

4 9829 3178 62
Instruction book

1 Safety precautions

1.1 Safety icons

Explanation

Danger to life

Warning

Important note

1.2 General safety precautions


1. The operator must employ safe working practices and observe all related work safety
requirements and regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter
of the two shall apply.
3. Installation, operation, maintenance and repair work must only be performed by authorized,
trained, specialized personnel. The personnel should apply safe working practices by use of
personal protection equipment, appropriate tools and defined procedures.
4. The compressor is not considered capable of producing air of breathing quality. For air of
breathing quality, the compressed air must be adequately purified according to the
applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks:
• Stop the machine
• Press the emergency stop button
• Switch off the voltage
• Depressurize the machine
• Lock Out - Tag Out (LOTO):
• Open the power isolating switch and lock it with a personal lock
• Tag the power isolating switch with the name of the service technician.
• On units powered by a frequency converter, wait 10 minutes before starting any
electrical repair.
• Never rely on indicator lamps or electrical door locks before maintenance work, always
disconnect and check with measuring device.

If the machine is equipped with an automatic restart after voltage failure function and if
this function is active, be aware that the machine will restart automatically when the
power is restored if it was running when the power was interrupted!

6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at
people. Never use the air to clean dirt from your clothes. When using the air to clean
equipment, do so with extreme caution and wear eye protection.
7. The owner is responsible for maintaining the unit in safe operating condition. Parts and
accessories shall be replaced if unsuitable for safe operation.
8. It is prohibited to walk or stand on the unit or on its components.

9829 3178 62 5
Instruction book

9. If compressed air is used in the food industry and more specifically for direct food contact, it
is recommended, for optimal safety, to use certified Class 0 compressors in combination
with appropriate filtration depending on the application. Please contact your customer center
for advice on specific filtration.

1.3 Safety precautions during installation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during installation


1. The machine must only be lifted using suitable equipment in accordance with the applicable
safety regulations. Loose or pivoting parts must be securely fastened before lifting. It is
strictly forbidden to dwell or stay in the risk zone under a lifted load. Lifting acceleration and
deceleration must be kept within safe limits. Wear a safety helmet when working in the area
of overhead or lifting equipment.
2. The unit is designed for indoor use. If the unit is installed outdoors, special precautions must
be taken; consult your supplier.
3. In case the device is a compressor, place the machine where the ambient air is as cool and
clean as possible. If necessary, install a suction duct. Never obstruct the air inlet. Care must
be taken to minimize the entry of moisture at the inlet air.
4. Any blanking flanges, plugs, caps and desiccant bags must be removed before connecting
the pipes.
5. Air hoses must be of correct size and suitable for the working pressure. Never use frayed,
damaged or worn hoses. Distribution pipes and connections must be of the correct size and
suitable for the working pressure.
6. In case the device is a compressor, the aspirated air must be free of flammable fumes,
vapors and particles, e.g. paint solvents, that can lead to internal fire or explosion.
7. In case the device is a compressor, arrange the air intake so that loose clothing worn by
people cannot be drawn in.
8. Ensure that the discharge pipe from the compressor to the aftercooler or air net is free to
expand under heat and that it is not in contact with or close to flammable materials.
9. No external force may be exerted on the air outlet valve; the connected pipe must be free of
strain.
10. If remote control is installed, the machine must bear a clear sign stating: DANGER: This
machine is remotely controlled and may start without warning.
The operator has to make sure that the machine is stopped and depressurized and that the
electrical isolating switch is open, locked and labelled with a temporary warning before any
maintenance or repair. As a further safeguard, persons switching on or off remotely
controlled machines shall take adequate precautions to ensure that there is no one checking
or working on the machine. To this end, a suitable notice shall be affixed to the start
equipment.
11. Air-cooled machines must be installed in such a way that an adequate flow of cooling air is
available and that the exhausted air does not recirculate to the compressor air inlet or
cooling air inlet.

6 9829 3178 62
Instruction book

12. The electrical connections must correspond to the applicable codes. The machines must be
earthed and protected against short circuits by fuses in all phases. A lockable power
isolating switch must be installed near the compressor.
13. On machines with automatic start/stop system or if the automatic restart function after
voltage failure is activated, a sign stating "This machine may start without warning" must be
affixed near the instrument panel.
14. In multiple compressor systems, manual valves must be installed to isolate each
compressor. Non-return valves (check valves) must not be relied upon for isolating pressure
systems.
15. Never remove or tamper with the safety devices, guards or insulation fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure must be protected by a pressure relieving device or devices as
required.
16. Piping or other parts with a temperature in excess of 70˚C (158˚F) and which may be
accidentally touched by personnel in normal operation must be guarded or insulated. Other
high temperature piping must be clearly marked.
17. For water-cooled machines, the cooling water system installed outside the machine has to
be protected by a safety device with set pressure according to the maximum cooling water
inlet pressure.
18. If the ground is not level or can be subject to variable inclination, consult the manufacturer.
19. If the device is a dryer and no free extinguishing system is present in the air net close to the
dryer, safety valves must be installed in the vessels of the dryer.

Also consult following safety precautions: Safety precautions during operation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.4 Safety precautions during operation


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during operation


1. Never touch any piping or components of the machine during operation.
2. Use only the correct type and size of hose end fittings and connections. When blowing
through a hose or air line, ensure that the open end is held securely. A free end will whip
and may cause injury. Make sure that a hose is fully depressurized before disconnecting it.
3. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
4. Never operate the machine when there is a possibility of taking in flammable or toxic fumes,
vapors or particles.
5. Never operate the machine below or in excess of its limit ratings.

9829 3178 62 7
Instruction book

6. Keep all bodywork doors shut during operation. The doors may be opened for short periods
only, e.g. to carry out routine checks. Wear ear protectors when opening a door.
On machines without bodywork, wear ear protection in the vicinity of the machine.
7. People staying in environments or rooms where the sound pressure level reaches or
exceeds 80 dB(A) shall wear ear protectors.
8. Periodically check that:
• All guards are in place and securely fastened
• All hoses and/or pipes inside the machine are in good condition, secure and not
rubbing
• No leaks occur
• All fasteners are tight
• All electrical leads are secure and in good order
• Safety valves and other pressure relief devices are not obstructed by dirt or paint
• Air outlet valve and air net, i.e. pipes, couplings, manifolds, valves, hoses, etc. are in
good repair, free of wear or abuse
• Air cooling filters of the electrical cabinet are not clogged
9. If warm cooling air from compressors is used in air heating systems, e.g. to warm up a
workroom, take precautions against air pollution and possible contamination of the breathing
air.
10. On water-cooled compressors using open circuit cooling towers, protective measures must
be taken to avoid the growth of harmful bacteria such as Legionella pneumophila bacteria.
11. Do not remove any of, or tamper with, the sound-damping material.
12. Never remove or tamper with the safety devices, guards or insulations fitted on the machine.
Every pressure vessel or auxiliary installed outside the machine to contain air above
atmospheric pressure shall be protected by a pressure relieving device or devices as
required.
13. Yearly inspect the air receiver. Minimum wall thickness as specified in the instruction book
must be respected. Local regulations remain applicable if they are more strict.

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during maintenance.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.5 Safety precautions during maintenance or repair


All responsibility for any damage or injury resulting from neglecting these precautions, or
non observance of the normal caution and care required for installation, operation,
maintenance and repair, even if not expressly stated, will be disclaimed by the
manufacturer.

Precautions during maintenance or repair


1. Always use the correct safety equipment (such as safety glasses, gloves, safety shoes,
etc.).
2. Use only the correct tools for maintenance and repair work.

8 9829 3178 62
Instruction book

3. Use only genuine spare parts for maintenance or repair. The manufacturer will disclaim all
damage or injuries caused by the use of non-genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "Work in progress; do not start" shall be attached
to the starting equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to
ensure that there is no one checking or working on the machine. To this end, a suitable
notice shall be affixed to the remote start equipment.
7. Close the compressor air outlet valve and depressurize the compressor before connecting
or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all
sources of pressure and relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety
precautions against toxic vapors of cleaning liquids.
10. Scrupulously observe cleanliness during maintenance and repair. Keep dirt away by
covering the parts and exposed openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Oil tanks must be
completely purged, e.g. by steam cleaning, before carrying out such operations. Never weld
on, or in any way modify, pressure vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is
overheated, the machine shall be stopped but no inspection covers shall be opened before
sufficient cooling time has elapsed; this to avoid the risk of spontaneous ignition of the oil
vapor when air is admitted.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure
vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they
function properly. They may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating
pressures, temperatures and time settings are correct. Check that all control and shut-down
devices are fitted and that they function correctly. If removed, check that the coupling guard
of the compressor drive shaft has been reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of
the oil separator vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture
from entering them, e.g. when steam cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on
the bodywork and in the air inlet and outlet systems of the compressor, is in good condition.
If damaged, replace it by genuine material from the manufacturer to prevent the sound
pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate
bowls.
21. Only if applicable, the following safety precautions are stressed when handling
refrigerant:
• Never inhale refrigerant vapors. Check that the working area is adequately ventilated; if
required, use breathing protection.
• Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin
with water. If liquid refrigerant contacts the skin through clothing, never tear off or
remove the latter; flush abundantly with fresh water over the clothing until all refrigerant
is flushed away; then seek medical first aid.

9829 3178 62 9
Instruction book

Also consult following safety precautions: Safety precautions during installation and
Safety precautions during operation.
These precautions apply to machinery processing or consuming air or inert gas.
Processing of any other gas requires additional safety precautions typical to the
application which are not included herein.
Some precautions are general and cover several machine types and equipment; hence
some statements may not apply to your machine.

1.6 Dismantling and disposal

Dismantling
Once the end of life of the machine is reached, please follow next steps:
1. Stop the machine.
2. Check all safety precautions mentioned in the previous chapters to secure safe handling
(e.g. LOTO, cool-down, depressurize, discharge, ...).
3. Separate the harmful from the safe components (e.g. drain oil from oil containing parts).
4. Refer to the disposal topic mentioned below.

Disposal of electrical and electronic appliances (WEEE)


This equipment falls under the provisions of the European Directive 2012/19/EU on waste
electrical and electronic appliances (WEEE) and may not be disposed as unsorted waste.

The equipment is labelled in accordance with the European Directive 2012/19/EU with the
crossed-out wheelie bin symbol.
At the end of life-time of the electric and electronic equipment (EEE) it must be taken to separate
collection.
For more information check with your local waste authority, customer center or distributor.

Disposal of other used material


Used filters or any other used material (e.g. desiccant, lubricants, cleaning rags, machine parts,
etc.) must be disposed of in an environmentally friendly and safe manner, and in line with the
local recommendations and environmental legislation.

10 9829 3178 62
Instruction book

2 General description

2.1 Introduction

General

General view

GA are oil-injected screw compressors, driven by an electric motor and enclosed in a sound-
insulated bodywork.
GA 90+ and GA 110 up to GA 160 are air-cooled compressors.
GA 90+ W and GA 110 W up to GA 160 W are water-cooled compressors.
GA are single-stage compressors.
The following features are available as an option:

Full-Feature
A refrigerant dryer is fully integrated into the bodywork of the compressor. This "all-in-one"
feature reduces the required space for installation and provides savings on piping installation
costs.

Energy recovery
The compressor is provided with an Atlas Copco energy recovery system to recover the major
part of the compression heat and heat losses of the drive motor gathered in hot water without any
influence on the compressor performance.

PT-1000 in windings and bearings


Five (PT-1000) temperature sensors are installed in the main motor of which 2 sensors are
monitoring the bearings and 3 sensors are monitoring the windings. The relevant temperatures
are shown on the controller display and alarms and shutdowns are programmed to protect the
compressor.

9829 3178 62 11
Instruction book

TT-TN or IT network
The compressor control panel is designed to be connected to either a TT-TN or IT electrical
power network. The design of these networks is described in the IEC 60950 standard.

Performance test certificate


The unit will be delivered with a performance test certificate. The certificate is included in the
documentation package delivered with the compressor.
The performance test certificate is mentioning the compressor serial number. Free air delivery
(English: Free Air Delivery (FAD)), specific energy requirement (English: Specific Energy
Requirement (SER)) are guaranteed according to ISO 1217:2009, annex “C” (fourth edition).

Witnessed performance test


Factory visit and witnessing of the standard performance test of the compressor can be attended
by the customer or a representative. The compressor is tested following the Atlas Copco
standard test procedure in accordance to the ISO 1217:2009, annex “C” (fourth edition).

12 9829 3178 62
Instruction book

2.2 Air and oil system

Flow diagram

Air-cooled version

9829 3178 62 13
Instruction book

Water-cooled version

Reference Description
1 Air inlet
2 Energy recovery circuit (optional)
3 Condensate drain, compressor
4 Condensate drain, Full-Feature compressor
5 Air outlet

14 9829 3178 62
Instruction book

Reference Description
6 Cooling water circuit

Position of components

Air flow
Air comes in through filter (AF) and unloader (UA) and is compressed in the compressor element
(E).
A mixture of compressed air and oil flows into the air receiver/oil separator (AR), where oil and air
are separated.
The air flows through the minimum pressure valve (Vp), the air cooler (Ca) and the condensate
trap to the air outlet.
Minimum pressure valve (Vp) prevents the receiver pressure from dropping below a minimum
pressure and includes a check valve which prevents blow-back of compressed air from the net.
Full-Feature compressors have a dryer after the air cooler.

Oil circuit
The air receiver (AR) removes most of the oil from the air/oil mixture by centrifugal action. The oil
collects in the lower part of the air receiver (AR) which serves as oil tank.
The oil separator removes the remaining oil.

9829 3178 62 15
Instruction book

The oil circuit has a thermostatic bypass valve that prevents that the oil flows through the oil
cooler (Co) when the oil temperature is low.
Air pressure forces the oil from air receiver (AR) through the oil filter (OF).
The filtered oil flows through the cooling channels of the drive motor to the compressor element
(E) and the lubrication points.
The oil circuit has an extra thermostatic bypass valve that will send extra oil to the compressor
element when the oil temperature is getting too high.

2.3 Cooling and condensate system

Condensate drain system

Condensate drains, Pack version

Condensate drains, Full-Feature version

Reference Designation
Dac Automatic condensate drain outlet
Dmc Manual condensate drain outlet

16 9829 3178 62
Instruction book

A condensate trap is installed downstream of the air cooler to prevent condensate from entering
the air outlet pipe. The trap is provided with a level sensor and solenoid valve for automatically
draining condensate and with a manual drain valve.
This condensate can contain small amounts of oil and should be processed according to local
environmental legislation.
On Full-Feature units, the condensate formed in the dryer collects in the lower part of the heat
exchanger/evaporator. When the condensate in the electronic drain reaches a certain level, it is
drained via the automatic drain outlet (Dac)

Cooling system
On air-cooled compressors, the air and oil coolers are cooled by dual-speed fans.
Water-cooled compressors are provided with a cooling water system, including oil and air
coolers.

2.4 Regulating system

Elektronikon
The compressor is controlled by the Elektronikon® regulator.
The regulator keeps the net pressure within programmable pressure limits by automatically
loading and unloading the compressor depending on the air consumption.

Unloader
The unloader is mounted on the compressor stage inlet and connected to the air filter outlet.
During the regulation of the compressor pressure, the unloader can appear in 4 modes:
1. Unload
2. Pre-load
3. Load
4. Delayed unload

Reference Designation
1 Element inlet
2 L/UL solenoid valve Y1
3 Controlled bypass valve Y11 (Blow-By)
4 Blow-off hole
5 Calibrated by-pass

9829 3178 62 17
Instruction book

Unload mode

The compressor starts in unload mode:


1. Load/Unload valve (Y1) is not powered (Y1 closed resulting in blow-off valve open).
2. The unloader closes.
3. A calibrated by-pass allows compression up to unload pressure level to guarantee the oil
injection pressure. Air is recirculated in the compressor to avoid constant pressure rise.
4. The Blow-By valve (Y11) is not powered (closed).

Pre-Load mode

The compressor starts in unload mode:


1. Load/Unload valve (Y1) is not powered (Y1 closed resulting in blow-off valve open).
2. The unloader is closed.
3. The Blow-By valve (Y11) is powered (open).
a. Extra air is sucked in
b. Vessel pressure goes up gradually
4. When the vessel pressure reaches +/- 2.5 bar, the unit will go to load mode.

18 9829 3178 62
Instruction book

Load mode

1. Load/Unload valve (Y1) is powered (Y1 opened resulting in blow-off valve closed).
2. The unloader opens and allows further pressure rise above 2.5 bar (36.3 psi).
3. The Blow-By valve (Y11) is not powered (closed).
When the air demand drops and the pressure reaches the unload level, the compressor switches
to unload mode, the oil separator pressure is expanded through blow-off hole (BO) and the above
sequence repeats.

Delayed unload mode

1. Load/Unload valve (Y1) is not powered (Y1 closed resulting in blow-off valve open).
2. The unloader closes.
3. The Blow-By valve (Y11) is powered (open).
a. Extra air is sucked in.
b. Vessel pressure is gradually decreasing.
4. When the vessel pressure reaches 6.5 bar (94.3 psi), the unit will go into unload mode.

Compressor stop mode


Both the pre-load hole between the compressor stage inlet and blow-by valve (Y11) and the load
activation (LA) hole are equipped with a ball check valve. At compressor stop (with the load/
unload valve (Y1) not powered (open) and the blow-by valve (Y11) not powered (closed)), these
two ball check valves, together with the closed unloader valve, ensure there is no backflow of air
from the compressor stage inlet to the unloader inlet.

9829 3178 62 19
Instruction book

2.5 Energy recovery system

General description

The maximum allowed pressure at the water side of the heat exchanger is 10 bar (145
psi).

The energy required in any compression process is mainly transformed into heat. The major part
of the compression heat is dissipated through the oil system. The Atlas Copco energy recovery
systems are designed to recover most of the above-mentioned heat as warm or hot water without
any adverse influence on the compressor performance.
After the compression stage, the oil is separated from the compressed air. The compressed air
flows to the aftercooler and the oil flows to the oil cooler. The energy in the oil can be recovered
by installing a heat exchanger in front of the oil cooler.
The energy recovery systems can be applied as low temperature rise / high water flow systems
(e.g. central heating in closed water circuits) or as high temperature rise / low water flow systems
(e.g. pre-heating of boiler feed water in open water circuits).

Main components
The system mainly comprises:
• Oil/water heat exchanger (HE)
• Energy recovery valve (Y152)
• Oil by-pass valve (Y151)
• Temperature sensors for water inlet and outlet
• The necessary pipes, brackets, bolts, etc.

Installation
The package includes:
• a general by-pass system, to shut down the energy recovery system
• a by-pass system to prevent the oil outlet temperature from dropping below the minimum
value.
When the Energy Recovery system is working, this by-pass system makes the oil flow
through the Energy Recovery heat exchanger instead of the normal oil cooler

20 9829 3178 62
Instruction book

Energy recovery system

Pressure drop, water side

Text on figure

(1) Pressure drop (kPa)


(2) Pressure drop (bar)
(3) Water flow (l/s)

pd = 4.23 F2 + 1.62 F
With:
• pd = pressure drop in kPa
• F = water flow in l/s

The pressure drops calculated with the formulas above are indicative.

9829 3178 62 21
Instruction book

Energy recovery system for air-cooled compressors

Energy recovery system for water-cooled compressors

22 9829 3178 62
Instruction book

Flow diagram

The recovery water enters the unit at the heat exchanger inlet connection. In the heat exchanger
the compression heat is transferred from the compressor to the water. The water leaves the heat
exchanger via the outlet connection.

Installation
The compressor frame is prepared for the Energy Recovery system. Before mounting the
installation, the two laser prepared holes in the canopy must be cut out.

Operation
The compressor oil flow is controlled by two thermostatic valves (Y151 and Y152). Y152 controls
the oil flow over the energy recovery cooler and Y151 controls the oil flow through the oil cooler
and thus the element outlet temperature. Ex factory the thermostat setting of Y151 is chosen in a
way that the element outlet temperature is 90 °C (194 °F) +/- 5 °C (9 °F).
Recoverable Energy
The graphs of the Principal data section below represent the performance for each power variant
at reference working pressure. The curves represent the limits of the energy recovery area and
were obtained with the temperature of the element outlet as indicated in the graph. All points
below the curve with Tc = 85 °C (185 °F) are possible working points where the recovered energy
is maximized for lower element outlet temperatures.
The formula to calculate the amount of recovered energy is:
Q (kW) = 4.2 x q (l/s) x dT (°C)
with
• q = water flow in l/s
• dT = temperature difference between water at inlet and outlet
Selection of the thermostatic valve
To avoid condensate in the oil circuit, it is very important that the element outlet temperature
always exceeds the condensation temperature. In worst case conditions (e.g. air inlet of 46 °C
(115 °F) and relative humidity (R.H.) of 50 %), tc (compressor outlet stage temperature) should
be above 85 °C (185 °F) for units with working pressures up to 10 bar (150 psi). This means that:
to prevent condensation in these worst case conditions, the curves with tc= 85 °C (185 °F) are

9829 3178 62 23
Instruction book

the lower limit of the energy recovery (for compressors with working pressure up to 10 bar (150
psi)).
If the air inlet temperature and R.H. are known, tc can be lower than the limits above and can be
calculated from the curves below. The compressor stage outlet temperature should exceed this
value by adapting the thermostatic valve Y151 in the thermostatic valve housing of the oil cooling
system of the standard compressor. To obtain a higher element outlet temperature (with a high
energy recovery water flow and/or low energy recovery water inlet temperature) (to get a higher
water outlet temperature), a thermostatic valve with an indicated temperature higher than the
standard factory mounted has to be mounted in the thermostatic valve housing of the oil cooling
system of the standard compressor. A list of standard thermostat settings for Y151 can be found
below.
The cooling water circuit of the energy recovery is by default protected against steam generation
by a compressor shut down at cooling water temperatures of the energy recovery of 95 °C (203
°F). When the thermostat valve selection is done for a compressor stage outlet temperature
running above 95 °C (203 °F), the compressor might trip at this limit value. This could happen
whenever the heat dissipation in the customer's installation stops (e.g. when the pump in the
customer's installation stops) or the heat dissipation is lower than the heat recovered from the
compressor. This results in a gradual temperature increase on the energy recovery cooling
medium system until the shut-down value has been reached. In this case following measures can
be taken to prevent an unwanted shut down:
• Manually switch off energy recovery by use of the hand wheel.
• Ask an Atlas Copco technician to increase the shut down value of the cooling water
temperature of the energy recovery in the Elektronikon controller. It is advised to choose a
temperature higher than the selected compressor element outlet temperature but at least 5
°C (9 °F) below the boiling point of the applied cooling medium and never higher than 120
°C (248 °F).

The thermostatic valve of the energy recovery (Y152) always needs to have an
indicated temperature equal to or higher than that of the thermostatic valve in the
thermostatic valve housing of the oil cooling system of the standard compressor.

24 9829 3178 62
Instruction book

Condensation point determination

Text on figure

(1) Air inlet temperature (°C)


(2) Condensation temperature (°C)
(3) Relative humidity (%)
(4) Working pressure (bar(e))

Set point of thermostatic valve Y151


Working pressure for 50 Hz Working pressure for 60 Hz
compressors compressors
Compressor 5.5 7.5 8.5 10 100 125 150
75 psi
type bar bar bar bar psi psi psi
GA 90+ 55 °C 65 °C 65 °C 75 °C 55 °C 65 °C 65 °C 75 °C
GA 110 55 °C 55 °C 65 °C 75 °C 55 °C 55 °C 65 °C 75 °C
GA 132 55 °C 55 °C 55 °C 65 °C 55 °C 55 °C 55 °C 65 °C
GA 160 N.A. 55 °C 55 °C 55 °C N.A. 55 °C 55 °C 55 °C

9829 3178 62 25
Instruction book

Calculation examples

Text on figure

(1) Water outlet temperature (°C)


(2) Water inlet temperature (°C)

Example point X
High temperature rise, low water flow application, e.g. pre-heating of boiler feed water in open
circuit:
• Compressor unit: GA 160 - 50 Hz
• Working pressure: 8 bar / 116 psi
• Water flow: 0.6 l/s / 1.27 cfm
• Water inlet temperature: 31 °C / 88 °F
• Water outlet temperature: 85 °C / 185 °F
The formula to calculate the amount of recovered energy results in (2):
• 4.2 x 0.6 x (85 - 31) = 136 kW ( ± as indicated on the curve)
The outlet temperature for a water flow of 0.6 l/s can be calculated backwards from formula (2):
• Toutlet = 31 + (136 / (4.2 x 0.6)) = 85 °C (185 °F)
Total pressure drop on waterside is (1):
• pd = (4.23 x 0.6²) + (1.62 x 0.6) = 2.5 kPa = 25 mbar (0.36 psi)
Example point Y
Low temperature rise, high water flow application, e.g. central heating in closed circuit:
• Compressor unit: GA 160 - 50 Hz
• Working pressure: 8 bar / 116 psi
• Water flow: 4 l/s / 0.87 cfm
• Water inlet temperature: 47.5 °C / 117.5 °F

26 9829 3178 62
Instruction book

• Water outlet temperature: 55.9 °C / 132.6 °F


The formula to calculate the amount of recovered energy results in (2):
• 4.2 x 4 x (55.9-47.5) = 141 kW ( ± as indicated on the curve of 85 °C)
The outlet temperatures for a water flow of 4 l/s can be calculated backwards from formula (2):
• Toutlet = 47.5 + (141 / (4.2 x 4)) = 55.9 °C (132.6 °F)
Total pressure drop on waterside is (1):
• pd = (4.23 x 4²) + (1.62 x 4) = 74 kPa = 0.74 bar (10.73 psi)
Example point Z
• Compressor unit: GA 160 -50 Hz
• Working pressure: 8 bar / 116 psi
• Water flow: 1 l/s / 2.12 cfm
• Water inlet temperature: 55 °C / 131 °F
• Water outlet temperature: 82.0 °C / 179.6 °F
The formula to calculate the amount of recovered energy results in (2):
• 4.2 x 1 x (82-55) = 113.4 kW
The outlet temperatures for a water flow of 1 l/s can be calculated backwards from formula (2):
• Toutlet = 55 + (113.4 / (4.2 x 1)) = 82 °C (179.6 °F)
Total pressure drop on waterside is (1):
• pd = (4.23 x 1²) + (1.62 x 1) = 5.85 kPa = 58.5 mbar (0.85 psi)
This proves that it is possible to work at higher temperatures, but with less heating power.
The temperature of the vessel can be set to 100 °C (212 °F) as well. The installation can
work in a higher curve, to obtain a higher water outlet temperature. This setting must be
done by a service technician of Atlas Copco.
• Compressor unit: GA 160
• Working pressure: 8 bar / 116 psi
• Water inlet temperature: 30 °C / 86 °F
• Water outlet temperature: 60 °C / 140 °F
The lowest curve is the maximum energy that can be recovered. If it is necessary to work in the
area below the lowest curve, you have to calculate with the 140.5 kW anyway.
dT = 30 °C/ 54 °F (60 °C - 30 °C / 140 °F - 86 °F)
c = 4.2 J/kgK (for water)
Q = 140.5 kW (lowest curve)
Formula for recovered energy is : ==> Q = m x c x dT
==> m = Q / (c x dT)
==> m = 140.5 / (4.2 x 30)
==> m = 1.115 l/s

Additional safety precautions


• The parts must only be lifted using suitable equipment in accordance with the applicable
safety regulations. Loose or pivoting parts must be securely fastened before lifting.

9829 3178 62 27
Instruction book

• Wear a safety helmet when working in the area of overhead or lifting equipment.
• Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
• Protection caps, bags, etc. must be removed before connecting the pipes.
• Water hoses must be of correct size and suitable for the working pressure.
• The water connections must be free of strain.
• Pipe work or other parts with a temperature in excess of 70 ˚C (158 ˚F) must be guarded or
insulated. Other high-temperature pipe work must be clearly marked.
• The water system installed outside the machine has to be protected by a safety device with
set pressure according to the maximum cooling water inlet pressure.
• All maintenance work shall only be undertaken when the machine has cooled down.
• Never weld or perform any operation involving heat near the oil system.

28 9829 3178 62
Instruction book

3 Elektronikon™ Touch controller

3.1 Controller

The Touch controller

Introduction
The controller has following functions:
• Controlling the unit
• Protecting the unit
• Monitoring components subject to service
• Automatic restart after voltage failure (ARAVF)

Automatic control of the unit


The controller maintains the net pressure between programmable limits by automatically loading
and unloading the unit (fixed speed units) or by adapting the motor speed (units with frequency
converter).
A number of programmable settings, e.g. the unloading and loading pressures (for fixed speed
units), the setpoint (for units with frequency converter), the minimum stop time, the maximum
number of motor starts and several other parameters are taken into account.
The controller stops the unit whenever possible to reduce the power consumption and restarts it
automatically when the net pressure decreases. If the expected unloading period is too short, the
unit is kept running to prevent too short standstill periods.

A number of time based automatic start/stop commands may be programmed. Take into
account that a start command will be executed (if programmed and activated), even after
manually stopping the unit.

9829 3178 62 29
Instruction book

Protecting the unit


Shutdown
Several sensors are provided on the unit. If one of the measured signals exceeds the
programmed shutdown level, the unit will be stopped.
Example: If the element outlet temperature exceeds the programmed shutdown level, the unit will
be stopped. This will be indicated on the display of the controller.
The unit will also be stopped in case of overload of the drive motor or fan motor.

Before remedying, consult the Safety precautions.


Before resetting a warning or shutdown message, always solve the problem. Frequently
resetting these messages without remedying may damage the unit.

Shutdown warning
A shutdown warning level is a programmable level below the shutdown level.
If one of the measurements exceeds the programmed shutdown warning level, a message will
appear on the display and the general alarm LED will light up to warn the operator before the
shutdown level is reached.
The message disappears as soon as the warning condition disappears.

Service warning
A number of service operations are grouped as a Service Plan. Each Service Plan has a
programmed time interval. If the service timer exceeds a programmed value, this will be indicated
on the display to warn the operator to carry out the service actions belonging to that Service Plan.

Automatic restart after voltage failure (ARAVF)


The controller has a built-in function to automatically restart the unit when the voltage is restored
after voltage failure. For units leaving the factory, this function is made inactive. If desired, the
function can be activated. Consult your supplier.

If the function is activated and provided the regulator was in the automatic operation
mode, the unit will automatically restart if the supply voltage to the module is restored.
The ARAVF label (see section Pictographs) shall be glued near to the controller.

30 9829 3178 62
Instruction book

3.2 Control panel

Control panel

Parts and functions

Reference Designation Function


1 Touchscreen Shows the unit operating condition and a number of
icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.
3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the unit is running in automatic operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the unit.
7 Start button This button starts the unit. The operation sign (4)
lights up. The controller is operative.

9829 3178 62 31
Instruction book

3.3 Icons used

Menu icons

Menu Icon Menu Icon Menu Icon


Data Status

Inputs

Outputs

Counters

Aux. Equipment Converters


Parameters

Service Service Overview

Service Plan

Service History

Service
functions

Clean Screen

Week Timer Week

Remaining
Running Time

Event History Saved Data

32 9829 3178 62
Instruction book

Menu Icon Menu Icon Menu Icon


Machine Alarms
Settings

Regulation

Control
Parameters

Aux. Equipment Converter(s)


Parameters

Fan

Internal
SmartBox

Auto Restart

Controller Network Ethernet


Settings Settings Settings

CAN Settings

Localisation Language

Date/Time

Units

User Password

Help

Information

Status icons

Icon Description
Motor Stopped

9829 3178 62 33
Instruction book

Motor Stopped Wait

Running Unloaded

Manual Unload

Running Unloaded Wait

Running Loaded

Failed to Load

Running Loaded Wait

Manual Stop

Machine Control Mode, Local

Machine Control Mode, Remote

Machine Control Mode, LAN

Automatic Restart After Voltage Failure

Week Timer Active

System icons

Icon Description
Basic User

Advanced User

Service User

Antenna 25%

34 9829 3178 62
Instruction book

Antenna 50%

Antenna 75%

Antenna 100%

Change between screens (indication)

Energy recovery

Dryer

Element

Drain(s)

Analogue Output

Menu

Reset

Auto Restart

Filter(s)

Cooler

Valve(s)

Power Meter

Input icons

Icon Description
Pressure

9829 3178 62 35
Instruction book

Temperature

Special Protection

Open

Closed

This chapter gives a general survey of available icons. Not all icons mentioned in this
chapter are applicable to every machine.

3.4 Main screen

Function
The Main screen is the screen that is shown automatically when the voltage is switched on. It is
switched off automatically after a few minutes when there is no touch input.

Description

Reference Designation Function


1 Home button The home button is always shown and can
be tapped to return to the main screen.
2 Screen information On the main screen, the screen information
bar shows the serial number of the machine.
When scrolling through menus, the name of
the current menu is shown.
3 Access level button The access level button is always shown and
can be tapped to change the current user
access level.

36 9829 3178 62
Instruction book

Reference Designation Function


4 Alarm button The alarm button can be tapped to show the
current alarms. If an alarm occurs, the icon
on the button will be red.
5 Service button The service button can be tapped to show
the service information.
6 Status This icon shows the current status of the unit.
7 Page indicator Indicates which page you currently see. The
middle indication is the main screen, left is
the menu screen and at the right the quick
access screen.
Swipe left or right to go to another screen.
8, 9, 10, 11 These fields can contain a history chart, an Tap the field to view the type of
input or a counter value, depending on the measurement. This will be shown in the
type of the machine. screen information bar.
Examples of inputs:
• Ambient temp
• Outlet
• Dryer dewpoint
Examples of counters:
• Running hours
• Load relay
• Loaded hours
12 Menu button The menu button is always shown and can
be tapped to go to the menu.

3.5 Quick access screen

Function
The screen is used to directly access some frequently used functions.

Procedure
The Quick access screen can be viewed by swiping left, starting from the main screen.

Description

Through this screen, several important settings can be viewed and modified.

9829 3178 62 37
Instruction book

Function Description
Setpoints Several setpoints can be modified by tapping this icon.
Control mode The control mode can be changed by tapping this icon.
• Local control via start/stop buttons
• Remote control via digital input(s)
• LAN control via the network.
When in Remote or LAN control, the start/stop buttons on the controller will not work.
Display language The display language of the controller can be changed by tapping this icon.
Manual unload (only When tapped, the machine will go in Manual unload mode until the icon is tapped
on fixed speed units) again.
Week timer Week timers can be set by tapping this icon.
Remaining running The Remaining running time can be set and modified by tapping this icon.
time
Internal SmartBox The reception quality of the internal antenna can be monitored.

Each bar represents 25% reception strength. If the four bars are filled, the reception
strength is 100%. If only one bar is filled, the reception strength is just 25%.
Auto restart Auto restart can be activated by tapping this icon.

3.6 Menu screen

Function
This screen is used to display the different menus where settings can be viewed or changed.

Procedure
The Menu screen can be viewed by tapping the Menu button or by swiping right, starting from the
main screen.

Description

Reference Designation Function


(1) Data The data menu contains the status of the unit, information about the
Inputs, Outputs and Counters. The Auxiliary equipment can also be
viewed through this menu.

38 9829 3178 62
Instruction book

Reference Designation Function


(2) Service The service menu contains the Service information. The ‘Clean
screen’ function can be used to clean the touchscreen.
(3) Week timer Multiple Week timers and a Remaining running time can be set
through this menu.
(4) Event history In case of an alarm, the Status information of the unit is saved and
can be viewed through this menu.
(5) Machine settings Alarms settings, Regulation settings and Control parameters can be
changed through this menu. Auxiliary equipment parameters can
also be changed.
The Auto restart function can be set through this menu. This function
is password protected.
(6) Controller settings Network settings, Localisation settings and a User password can be
set through this menu. There is also a Help page available and the
Controller information can be shown.

Menu structure
Operating the controller can be done by swiping through screens and tapping icons or menu
items.

This is the main menu structure. The structure can be different depending on the configuration of
the unit.

9829 3178 62 39
Instruction book

3.7 Data menu

Function
This screen is used to display the following submenus:
• Status
• Inputs
• Outputs
• Counters
• Aux. Equipment
These submenus can be entered by tapping the icons.

Procedure
To enter the Data menu screen:
1. Tap the Menu button
2. Tap the Data icon

Description

Reference Designation
(1) Status menu
(2) Inputs menu
(3) Outputs menu
(4) Counters menu
(5) Auxiliary equipment menu

Status menu
Tap the Status icon to enter the Status menu.

This menu shows the current status of the unit.

40 9829 3178 62
Instruction book

If an alarm is active, it can be viewed by tapping the alarm message. To reset an alarm, tap the
reset button (1).

Before remedying, consult the Safety precautions.


Before resetting a warning or shutdown message, always solve the problem. Frequently
resetting these messages without remedying may damage the unit.

Inputs menu
Tap the Inputs icon to enter the Inputs menu.

This menu shows information about all the inputs.

Outputs menu
Tap the Outputs icon to enter the Outputs menu.

This menu shows information about all the outputs.

Voltage-free outputs may only be used to control or monitor functional systems.


They should NOT be used to control, switch or interrupt safety related circuits.
Check the maximum allowed load on the label.
Stop the unit and switch off the supply before connecting external equipment. Check the
Safety precautions.

Counters menu
Tap the Counters icon to enter the Counters menu.

9829 3178 62 41
Instruction book

This menu shows an overview of all actual hours and counters of the unit and controller.

Auxiliary equipment menu


Tap the Aux. Equipment icon to enter the Aux. equipment menu.

This menu shows an overview of all auxiliary equipment fitted.

3.8 Service menu

Function
This screen is used to display the following submenus:
• Service
• Service functions (Only visible as advanced user)
• Clean screen
These submenus can be entered by tapping the icons.

Procedure
To enter the Service menu screen:
1. Tap the Menu button
2. Tap the Service icon

42 9829 3178 62
Instruction book

Description

Reference Designation
(1) Service
(2) Service functions (Only visible as advanced user)
(3) Clean screen

Service menu
Tap the Service icon to enter the Service menu.

This menu shows the remaining Running Hours and the remaining Real Time Hours until the next
service. The first row (A) shows the Running Hours when the first service is needed (green), the
second row shows the Real Time Hours (blue)
A service overview can be viewed by tapping icon (1).
The service plan can be viewed by tapping icon (2). Through this menu, the service plan can be
modified:
1. Tap the desired service plan. A selection screen will pop up.
2. Change the Running Hours by tapping ‘–’ or ‘+’.
3. Confirm by tapping ‘V’ or decline by tapping ‘X’.
The service history can be viewed by tapping icon (3).
When a service plan interval is reached, a message will appear on the screen. When service has
been performed, the service timer can be reset by tapping the reset button (4).

Service functions (Only visible as advanced user)


Tap the Service Functions icon to enter the Service Functions menu.

9829 3178 62 43
Instruction book

Depending on the machine, this menu can have a different set of functions. Many of them are
password protected, as they are only accessible for authorized personnel.

Clean screen
Tap the Clean Screen icon to start the 15 seconds countdown to perform cleaning of the
touchscreen.

The touchscreen and the start and stop button become inactive for 15 seconds.

3.9 Week timer menu

Function
This screen is used to set up to 4 different week timers with each up to 8 settings per day.
The week timers can be activated through this screen.
A Remaining Running Time can be set from 5 up to 240 minutes.

Procedure
To enter the Week Timer menu screen:
1. Tap the Menu button
2. Tap the Week Timer icon

44 9829 3178 62
Instruction book

Description

Reference Designation Function


(1) Add or select week If less than 4 weeks are programmed, tap the ‘+’ button to add a
week.
(2) Remove week Tap to remove a programmed week timer.
(3) Activate week timer A selection screen pops up. The user can choose the correct week
by tapping ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by
tapping ‘X’.
(4) Remaining running A selection screen pops up. The user can change the remaining time
time by tapping ‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by
tapping ‘X’.
(5) Add setting A selection screen pops up. The user can change the setting by
swiping up or down and confirm by tapping ‘V’ or decline by tapping
‘X’.

3.10 Event history menu

Function
This screen is used to display the saved data in case of an alarm.
These submenus can be entered by tapping the icons.

Procedure
To enter the Event history menu screen:
1. Tap the Menu button
2. Tap the Event History icon

Description

9829 3178 62 45
Instruction book

Reference Designation
(1) Saved Data

Saved data
Tap the Saved Data icon to enter the Saved Data menu.

Scroll through the items swiping up and down in this list. The event date and time is shown at the
right side of the screen.
Press on one of the items in the list for more information reflecting the status of the unit when the
shutdown occurred.

3.11 Machine settings menu

Function
This screen is used to display the following submenus:
• Alarms
• Regulation
• Control Parameters
Only visible if the machine has adaptable parameters.
• Aux. Equipment parameters
• Auto Restart
These submenus can be entered by tapping the icons.

Procedure
To enter the Machine settings menu screen:
1. Tap the Menu button
2. Tap the Machine Settings icon

46 9829 3178 62
Instruction book

Description

Reference Designation
(1) Alarms menu
(2) Regulation menu
(3) Control Parameters menu
(4) Aux. Equipment Parameters menu
(5) Auto Restart menu

Alarms menu
Tap the Alarms icon to enter the Alarms menu.

A list of all alarms is shown.


When pressing on one of the items in this list, the warning and/or shutdown levels are shown for
this alarm.

Regulation menu
Tap the Regulation icon to enter the Regulation menu.

Setpoints or pressure bands can be modified through this menu.


Modify a setting

9829 3178 62 47
Instruction book

When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

Control parameters menu


Tap the Control Parameters icon to enter the Control Parameters menu.

This menu shows information about the Control Parameters.


Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

Auxiliary equipment parameters menu


Tap the Aux. Equipment Parameters icon to enter the auxiliary equipment parameters menu.

This menu shows an overview of all the auxiliary equipment fitted.


Through this menu, the parameters of the auxiliary equipment can be changed.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

Auto restart menu


Tap the Auto restart icon to enter the Auto Restart menu.

48 9829 3178 62
Instruction book

Through this menu, the automatic restart can be activated. The activation is password protected.
The automatic restart settings can also be changed.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.
Modify a setting
When clicking a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.

3.12 Controller settings menu

Function
This screen is used to display the following submenus:
• Network Settings
• Localisation
• User Password
• Help
• Information
These submenus can be entered by tapping the icons.

Procedure
To enter the Controller Settings menu screen:
1. Tap the Menu button
2. Tap the Controller Settings icon

Description

9829 3178 62 49
Instruction book

Reference Designation
(1) Network Settings menu
(2) Localisation menu
(3) User Password menu
(4) Help menu
(5) Information menu

Network settings menu


Tap the Network Settings icon to enter the Network Settings menu.

Ethernet Settings
The list of Ethernet Settings is shown. When ethernet is turned off, the settings can be modified.
CAN Settings
The list of CAN Settings is shown. When CAN is turned off, the settings can be modified.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

Localisation menu
Tap the Localisation icon to enter the Localisation menu.

Language
The language setting of the controller can be modified through this menu.
Date/Time

50 9829 3178 62
Instruction book

The date and time settings of the controller can be modified through this menu.
Units
The units displayed can be modified through this menu.
Modify a setting
When tapping a list item, a selection screen pops up. The user can modify the setting by tapping
‘–’ or ‘+’ and can confirm by tapping ‘V’ or decline by tapping ‘X’.
Change a selection
When tapping a list item, a selection screen pops up. The user can change the selection by
swiping up or down and confirm by tapping ‘V’ or decline by tapping ‘X’.

User password menu


Tap the User Password icon to enter the User Password menu.

The user password can be activated or deactivated through this menu. Enter and confirm a user
password to activate, repeat to deactivate.
Enter a password
When tapping a password protected item, a selection screen pops up. The user can enter the
password by swiping up or down to select the desired number. Once the 4 digits are entered, the
user can confirm by tapping ‘V’ or decline by tapping ‘X’.

Help menu
Tap the Help icon to enter the Help menu.

This menu can show a link to the web page of your supplier, a helpdesk phone number or other
helpful information.

Information menu
Tap the Information icon to enter the Information menu.

9829 3178 62 51
Instruction book

This menu shows information about the controller.

3.13 Access level

Function
Through this pop-up screen the access level settings can be viewed or changed.

Procedure
The Access Level screen can be viewed or changed by tapping the Access Level button at the
upper right corner of the screen.

Description

Reference Designation Function


(1) User A basic set of parameters is visualized, no password required.
(2) Service A basic set of parameters can be modified, no password required.
(3) Full This access level is not accessible to end users.
(4) Decline Tap to decline the selected user level.
(5) Confirm Tap to confirm the selected user level.

52 9829 3178 62
Instruction book

Service access level

Tap the Service access level icon (1) and confirm (2).

The screen information bar (1) now shows the current status of the unit instead of the machine
serial number.
The Received Signal Strength Indicator (RSSI) value is now shown in the Internal SmartBox
menu. See Quick access screen.
In the service menu, an extra menu item is now available. See Service menu.

9829 3178 62 53
Instruction book

4 Installation

4.1 Dimension drawing

Compressor dimensions

Dimension drawing of Pack compressor, metric units

54 9829 3178 62
Instruction book

Dimension drawing of Pack compressor, imperial units

9829 3178 62 55
Instruction book

Dimension drawing of air-cooled Full-Feature compressor, metric units

56 9829 3178 62
Instruction book

Dimension drawing of air-cooled Full-Feature compressor, imperial units

9829 3178 62 57
Instruction book

Dimension drawing of water-cooled Full-Feature compressor, metric units

58 9829 3178 62
Instruction book

Dimension drawing of water-cooled Full-Feature compressor, imperial units

Reference table

Reference Description
(1) Data plate
(2) Electrical cable entry (cable box, optional CTS kit)
(3) Air-cooled compressor: Cooling air outlet
Air-cooled compressor: Dryer cooling air outlet
Water-cooled compressor: Canopy ventilation outlet
(4) Air-cooled compressor: Dryer cooling air inlet
(5) Cubicle ventilation inlet
(6) 4 slotted holes
(7) Compressor air inlet
Air-cooled compressor: Cooling air inlet
Water-cooled compressor: Canopy ventilation inlet
(8) Compressed air outlet
(9) Manual drain, compressor
(10) Automatic drain, compressor
(11) Automatic drain, dryer

9829 3178 62 59
Instruction book

Reference Description
(12) Energy recovery water outlet
(13) Energy recovery water inlet
(14) Water-cooled compressor: Cooling water inlet
Air-cooled compressor: Not used
(15) Water-cooled compressor: Cooling water outlet
Air-cooled compressor: Not used
(16) Centre of gravity
(17) Detail C

4.2 Installation proposal

Compressor room example

Compressor room example, metric units

60 9829 3178 62
Instruction book

Compressor room example, imperial units

Text on figures

Reference Description
(1) Install the compressor on a level floor suitable for taking its weight.
(2) Compressed air outlet valve (not in scope of supply).
(3) For SI units
Delivery pipe:
The maximum pipe length can be calculated as follows:
L = (dp x d5 x p) / (450 x Qc1.85)
L = Length of pipe in m
dp = Pressure drop (recommended maximum = 0.1 bar)
d = Inner diameter of the outlet pipe in mm
p = Absolute pressure at the compressor outlet in bar(a)
Qc = Free air delivery of the compressor in l/s
The connection of the air delivery pipe is made on top of the main air net pipe in order
to minimize carry-over of possible condensate residue.
(3) For British/American units:
Delivery pipe:
The maximum pipe length can be calculated as follows:
L = 1470 ( (dp x d5 x p) / (Qc1.85) )
L = Length of pipe in ft
dp = Pressure drop (recommended maximum = 1.45 psi)
d = Inner diameter of the outlet pipe in inch
p = Absolute pressure at the compressor outlet in psi
Qc = Free air delivery of the compressor in cfm
The connection of the air delivery pipe is made on top of the main air net pipe in order
to minimize carry-over of possible condensate residue.

9829 3178 62 61
Instruction book

Reference Description
(4) For SI units
Ventilation:
The inlet grid(s) and ventilation fan must be installed in such a way that any re-
circulation of cooling air to the compressor is avoided. The air velocity to the grid(s) has
to be limited to 5 m/s
The maximum allowable pressure drop over all cooling ducts together is 30 Pa
The maximum air temperature at the compressor intake opening is 46 °C (50 °C for
HAT version), minimum 0 °C
The required ventilation to limit the compressor room temperature can be calculated as
follows:
Qv = 0.92N / dT (air-cooled unit)
Qv = 0.1N / dT (water-cooled unit)
Qv= Required ventilation capacity in m3/s
N = Shaft input of the compressor in kW
dT = Compressor room temperature over the outdoor temperature in °C
(4) For British/American units:
Ventilation:
The inlet grid(s) and ventilation fan must be installed in such a way that any re-
circulation of cooling air to the compressor is avoided. The air velocity to the grid(s) has
to be limited to 5 m/s
The maximum allowable pressure drop over all cooling ducts together is 4.35 x 10 psi
The maximum air temperature at the compressor intake opening is 114.8 °F (122 °F for
HAT version), minimum 32 °F
The required ventilation to limit the compressor room temperature can be calculated as
follows:
Qv = 2845 x (0.92N) / dT (air-cooled unit)
Qv = 2845 x (0.1N) / dT (water-cooled unit)
Qv= Required ventilation capacity in cfm
N = Shaft input of the compressor in hP
dT = Compressor room temperature over the outdoor temperature in °F
(5) Drain pipes to condensate collector. The drain pipes may not enter in the collector.
Individual drain pipes may not be interconnected to avoid interference
Compressor condensate contains oil. Depending on local legislation, it is recommended
to install an oil/water separator (consult Atlas Copco)
(6) Control cubicle with monitoring panel
(7) Main cable entry
(8) Cooling water inlet pipe (only water-cooled unit)
(9) Cooling water outlet pipe (only water-cooled unit)
(10) Minimum free area to be reserved for the compressor installation
(11) Ventilation proposals
(12) Air-cooled compressor
(13) Water-cooled compressor
(A) Cooling air outlet (air-cooled unit)
Dryer cooling air outlet (air-cooled Full-Feature unit)
Canopy ventilation outlet (water-cooled unit)
(B) Compressor air inlet
Cooling air inlet (air-cooled unit)
Canopy ventilation inlet (water-cooled unit)
(C) Cubicle ventilation air inlet (high ambient temperature unit)
(D) Dryer cooling air inlet (only air-cooled Full-Feature unit)

62 9829 3178 62
Instruction book

4.3 Electrical connections

Reference Description
(1) Customer's installation
(2) Customer
(3) 6 fuses
(4) 3 fuses if possible
(5) Compressor

9829 3178 62 63
Instruction book

Reference Description
(6) Compressor motor

To preserve the protection degree of the electric cubicle and to protect its components
from dust from the environment, it is mandatory to use a proper cable gland when
connecting the supply cable to the compressor.

Warnings
• Obey local regulations if they are stricter than the regulations mentioned in this
document.
• Obey the applicable electrical directives when installing and connecting the
compressor to the power circuit:
• IEC 60204-1
• IEC 60364-5-52
• CSA/UL
• UL: UL508A
• CSA: C22.2
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage. It is however highly recommended to keep the voltage drop over
the supply cables at nominal current below 5% of the nominal voltage (IEC
60204-1).
• Use the original cable entry.
• Full load (compressor) package currents are calculated and available on Technical
data sheet. For cable section selection purposes, we suggest to add 10% to
compensate for any under-voltages that might occur in the installation.
• Use copper wires only.
• Caution
• Always double-check the fuse size versus the calculated cable size. If
required, reduce the fuse size or enlarge the cable size.
• Cable length should not exceed the maximum length according to IEC 60204
(table.10).
• Display the fuse type information next to the fuse holder of the mains branch.
• Connect the power cable with the correct cable lugs on the terminals in the
electrical cabinet.
• Do not connect more than one (1) cable lug at one side of a contactor terminal or
copper bar, unless specified otherwise.
• Respect a minimum of 10 mm IEC (1/2” CSA/UL branch circuit) between stripped
cable ends for low voltage installations.
• Fuses are maximum allowed values to protect installed compressor electrical
panel.
• Apply the listed cable sections on main supply cables AND earth cable.
• Do not exceed the ambient temperature listed in the Limits section to avoid cable
damage.
• Mount all cables on a horizontally ventilated cable tray.
• Do not stack or group cables as this avoids heat dissipation.
• Connect the power cable with the correct (CSA certified) cable lugs on the
terminals in the electrical cabinet.
• Respect a minimum distance of 10 mm (0.4") between stripped cable ends.
• Use only the prescribed cable types:
• IEC: XLPE 90 °C (194 °F)
• CSA-UL: (R, RW, T) multicore 110 °C (230 °F)
• Display the fuse type information next to the fuse holder of the mains branch.

64 9829 3178 62
Instruction book

Cable size and main fuses


Overview of fuse types

Electrical approval Fuse type


IEC aR
CSA/UL class RK5 1

1 Class RK5 according UL248-9

Electrical approval SSCCR 1


IEC gG/gL type 2 2
CSA HRC form II
UL (for TT/TN electrical nets) class RK5 3
UL (for IT electrical nets) Class J (LPJ)

1 SSCCR = Standard Short Circuit Current Rating


2 gG/gL type 2 according to IEC609471-4-1, IEC60269, DIN43620, VDE0636
3 Class RK5 according UL248-9

Maximum fuse size


• The pre-described fuses mentioned in the Technical Data Sheet (TDS) or on the service
diagram are the maximum main fuses to protect the installed compressor electrical panel.
• The pre-described fuse types are to be used.
• Final cable and fuse selection will depend on the customer’s installation and local legislation.
• Installing smaller fuses of the same type/class might lead to smaller main feeder cables.
• Always double-check the fuse size versus the calculated cable size. If required, reduce the
fuse size or enlarge the cable size.
• Cable length should not exceed the maximum length according to IEC 60204 (table 10).
• Obey local regulations if they are stricter than the examples mentioned in this document.

Package current
The Package current mentioned on the technical data sheet is defined as follows:
• Package current is the current the compressor uses:
• At reference conditions
• At 100 % load
• At maximum pressure
• At nominal voltage
• Before service interval (so including fouled filters, etc…)
The pre-described fuses on the technical data sheet are the maximum main fuses to protect the
installed compressor electrical panel.

9829 3178 62 65
Instruction book

Cable configuration

Single supply cables

Parallel supply cables

Phase supply cables (Only valid for Y-D versions)

Parallel phase supply cables (Only valid for Y-D versions)

66 9829 3178 62
Instruction book

(1): Power distribution panel


(2): Compressor starter panel
Fuse calculations for IEC are done according to IEC 60364–4–43 (Low voltage electrical
installations — Part 4–43: protection against overcurrent).
Fuse calculations for cUL, CSA and UL: The indicated fuse size is the maximum fuse size in
order to protect the motor.

Cable sizing according IEC


The tables below indicate the current carrying capacities of cables for commonly used installation
methods, calculated according to standard IEC 60364-5-52 (Electrical installations of buildings
part 5 - selection and erection equipment and section 52 - current carrying capacities in wiring
systems).
The allowed currents are valid for XLPE (Cross-linked polyethylene) insulated cables with three
loaded copper conductors and for maximum conductor temperature 90 °C, reference temperature
30 °C.

Installation method E or F, according table B.52.1;


Single-core or multi-core cables, touching in free air;
Clearance to wall not less than 0,3 times cable diameter for method E or one cable diameter for
method F.
Maximum allowable current in function of the ambient temperature for installation method E
(Multi-core cables with 3 loaded conductors and maximum conductor temperature 90 °C)

Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 127 A < 116 A < 110 A < 104 A < 97 A
35 mm² < 158 A < 144 A < 137 A < 130 A < 120 A
50 mm² < 192 A < 175 A < 167 A < 157 A < 146 A
70 mm² < 246 A < 224 A < 214 A < 202 A < 187 A
95 mm² < 298 A < 271 A < 259 A < 244 A < 226 A

9829 3178 62 67
Instruction book

Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
120 mm² < 346 A < 315 A < 301 A < 284 A < 263 A
150 mm² < 399 A < 363 A < 347 A < 327 A < 303 A
185 mm² < 456 A < 415 A < 397 A < 374 A < 347 A
240 mm² < 538 A < 490 A < 468 A < 441 A < 409 A
300 mm² < 621 A < 565 A < 540 A < 509 A < 472 A

Maximum allowable current in function of the ambient temperature for installation method F
(Single-core cables with 3 loaded conductors and maximum conductor temperature 90 °C)

Cable section 30 °C 40 °C 45 °C 50 °C 55 °C
25 mm² < 135 A < 123 A < 117 A < 110 A < 103 A
35 mm² < 169 A < 154 A < 147 A < 139 A < 128 A
50 mm² < 207 A < 188 A < 180 A < 170 A < 157 A
70 mm² < 268 A < 244 A < 233 A < 220 A < 204 A
95 mm² < 328 A < 298 A < 285 A < 269 A < 249 A
120 mm² < 383 A < 349 A < 333 A < 314 A < 291 A
150 mm² < 444 A < 404 A < 386 A < 364 A < 337 A
185 mm² < 510 A < 464 A < 443 A < 418 A < 388 A
240 mm² < 607 A < 552 A < 528 A < 498 A < 461 A
300 mm² < 703 A < 639 A < 611 A < 576 A < 534 A
400 mm² < 823 A < 749 A < 716 A < 674 A < 625 A

Cable calculation method for IEC


• Single supply cables (3 phases + PE):
• Add 10 % to the total package current (Package current from the technical data
sheets).
• Install fuses on each supply cable which are smaller than or equal to the Max. fuse
values from the technical data sheets or the instruction manual.
• Connection between contactors must be made by means of copper bars.
• Parallel supply cables and phase supply cables (2 x (3 phases + PE)):
• Add 10 % to the total package current (Package current from the technical data sheets)
and divide by √3.
• Multiply the ampacity of the cables with the reduction factors per table B.52.17 of IEC
60364-5-52 (Method E or F), (typically 0.8).
• Install fuses on each supply cable which are smaller than or equal to the Max. fuse
values from the technical data sheets or the instruction manual.
• Parallel phase supply cables (4 x (3 phases + PE)):
• Add 10 % to the total package current (Package current from the technical data sheets)
and divide by √3 and then by 2.
• Multiply the ampacity of the cables with the reduction factors per table B.52.17 of IEC
60364-5-52 (Method E or F), (typically 0.8).
• Install fuses which are smaller than or equal to the Max. fuse values of the technical
data sheets or the instruction manual.
• Size of the PE cable:
• For supply cables up to 16 mm²: same size as supply cables.

68 9829 3178 62
Instruction book

• For supply cables between 16 mm² and 35 mm²: 16 mm².


• For supply cables larger than 35 mm²: half the size of the supply wires.
Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).

Example of supply cable calculation


Itot = 407 A, maximum ambient temperature is 45 °C, recommended fuse = 500 A.
• Single supply cables (3 phases + PE):
• I = 407 A + 10 % = 407 x 1.1 = 447.7 A
The table for method E (multi-core cable), 90 °C cable temperature and ambient
temperature of 45 °C allows a maximum current of 468 A for a 240 mm² cable. So use a
multi-core cable of 3 x 240 mm² + 120 mm².
• Parallel supply cable and phase supply cable 2 x (3 phases + PE):
• I = (407 A + 10 %)/√3 = (407 x 1.1)/√3 = 259 A
For a single-core cable of 120 mm², method F, 90 °C cable temperature and ambient
temperature of 45°C, the maximum current is 333 A x 0.8 = 266 A. So two (2) parallel
(single-core) cables of 3 x 120 mm² + 70 mm² are sufficient.
For a multi-core cable of 120 mm², method E, 90 °C cable temperature and ambient
temperature of 45°C, the maximum current is 301 A x 0.8 = 240 A. This 120 mm² cable
would be too small, so you need to install a cable with a bigger section.
Looking at a multi-core cable of 150 mm², method E, 90 °C cable temperature and ambient
temperature of 45°C, the maximum current is 347 A x 0.8 = 277 A. The right selection in this
case would then be two (2) parallel cables of 3 x 150 mm² + 95 mm³.
• Parallel phase supply cable 4 x (3 phases + PE):
• I = (407 A + 10 %)/(√3 x 2) = (407 x 1.1)/(√3 x 2) = 130 A
For a single-core cable of 50 mm², method F, 90 °C cable temperature and ambient
temperature of 45°C, the maximum current is 180 A x 0.8 = 144 A. So two (4) parallel
(single-core) cables of 3 x 50 mm² + 25 mm² are sufficient.
For a multi-core cable of 50 mm², method E, 90 °C cable temperature and ambient
temperature of 45°C, the maximum current is 167 A x 0.8 = 133 A. So two (4) parallel (multi-
core) cables of 3 x 50 mm² + 25 mm² are sufficient.

Cable sizing according UL


The table below indicates the current carrying capacities of cables for commonly used installation
methods, according to standard UL 508A. Ampacities of insulated conductors, copper 75°C.

AWG or kcmil Ampacity


10 < 30 A
8 < 50 A
6 < 65 A
4 < 85 A
3 < 100 A
2 < 115 A
1 < 130 A
1/0 < 150 A
2/0 < 175 A
3/0 < 200 A

9829 3178 62 69
Instruction book

AWG or kcmil Ampacity


4/0 < 230 A
250 < 255 A
300 < 285 A
350 < 310 A
400 < 335 A
500 < 380 A

Note: The above table has been prepared for user convenience. Only the latest editions of the UL
standard and its amendment(s) are to be considered as the official documents.

Cable calculation method for UL


Calculation method according UL 508A
• Single supply cables (3 phases + PE)::
• Add 25 % to the total package current (Package current from the technical data
sheets).
• Install fuses on each supply cable which are smaller than or equal to the Max. fuse
values from the technical data sheets or instruction manual.
• Connection between contactors must be made by means of copper bars.
• Parallel supply cables and phase supply cables (2 x (3 phases + PE)):
• Add 25 % to the total package current (Package current from the technical data sheets)
and divide by √3.
• Install fuses on each supply cable which are smaller than or equal to the Max. fuse
values from the technical data sheets or instruction manual.
• Parallel phase supply cables (4 x (3 phases + PE)):
• Add 25 % to the total package current (Package current from the technical data sheets)
and divide by √3 and then by 2.
• Install fuses which are smaller than or equal to the Max. fuse values from the technical
data sheets or instruction manual.
• Size of the PE cable
• Use the maximum allowed ampacity of the selected supply cables and compare with
the value in the table below according to UL508A.

Ampacity Size of PE
< 90 A 8 AWG
< 125 A 6 AWG
< 150 A 6 AWG
< 200 A 4 AWG
< 225 A 2 AWG
< 400 A 1/0 AWG
< 500 A 1/0 AWG
< 800 A 2/0 AWG
< 1000 A 3/0 AWG

Note: The above table has been prepared for user convenience. Only the latest editions of
the UL standard and its amendment(s) are to be considered as the official documents.

70 9829 3178 62
Instruction book

Always check the voltage drop over the cable (less than 5 % of the nominal voltage is
recommended).

Example of supply cable calculation


IPackage = 128 A, maximum ambient temperature is 30 °C, maximum fuse = 200 A
• Single supply cables (3 phases + PE):
• I = 128 A + 25 % = 128 x 1.25 = 160 A
• For AWG2/0, the maximum current is 175 A, which is sufficient => use AWG2/0
• So use a cable of 3 x AWG2/0 + AWG4
• Parallel supply cable and phase supply cable 2 x (3 phases + PE):
• I = (128 A + 25 %)/√3 = (128 x 1.25)/√3 = 93 A
• For AWG3, the maximum current is 100 A, which is sufficient => use AWG3
• So use a cable of 2x (3 x AWG3 + AWG6)
• Parallel phase supply cable 4 x (3 phases + PE):
• I = (128 A + 25 %)/(√3 x 2) = (128 x 1.25)/(√3 x 2) = 47 A
• For AWG5, the maximum current is 50 A, which is sufficient => use AWG8
• So use a cable of 4x (3 x AWG8 + AWG8)

4.4 Quality of safety components


When installing a remote emergency button or a motor contactor, the following B10d values are
advised:
• Emergency stop button: 500 000
• Main contactor: 933 333

4.5 Pictographs

Control panel of Elektronikon controller


Refer to the chapter Controller panel for pictographs of the Elektronikon controller.

Other locations

9829 3178 62 71
Instruction book

Reference Description
13 Automatic condensate drain
14 Automatic condensate drain for optional oil/water separator (type OSD)
15 Manual condensate drain
16 Stop the compressor before maintenance or repair
17 Warning: under tension
18 Read Instruction book before starting the compressor
19 Switch off the voltage and depressurize the compressor before maintenance or repair
20 Before connecting the compressor electrically, consult the Instruction book for the motor
rotation direction
21 Torques for steel (Fe) or brass (CuZn) bolts
22 Consult the Instruction book before greasing
23 Switch off the voltage before removing the protecting cover inside the electric cabinet
24 Oil the gaskets, screw on the filters and tighten by hand (approx. one half turn)
25 Consult the Instruction book before maintenance or repair
26 Cooling water inlet
27 Cooling water outlet
28 Oil outlet

4.6 Cooling water requirements

General
Cooling water needs to fulfill requirements in order to avoid problems of scaling, fouling,
corrosion or bacterial growth. No general recommendation can encompass the effects of all
combinations of the various compounds, solids and gases typically found in cooling water in
interaction with different materials. Therefore the recommendations formulated in our cooling
water specifications are a general guide line for acceptable coolant quality. However, where strict
limits apply, a statement is made in the specification.
The water requirements refer to untreated water. When water is treated, some parameters will
change. Water treatments should be carried out by a specialized water treatment company,
taking the responsibility for the performance of the treated cooling water and the compatibility
with the materials in the cooling circuit. This includes not only the selection of the appropriate
additives, but also the correct application, monitoring of concentrations and properties, prevention
of sludge formation and maintenance of the system. This applies also to treatment with anti-
freeze products. They should be provided with suitable stabilizers and inhibitors.
Specifications also depend on the criteria mentioned below:
• the type of cooling circuit:
• open
• Single Pass

• recirculation with cooling tower

72 9829 3178 62
Instruction book

• closed loop

Reference Description
(1) Machine
(2) Heat exchanger
(3) Cooling tower
(4) Make up water
(5) Blowdown
(6) Standard Atlas Copco specification

• the application:
• standard (max water temperature 65°C / 149°F at the outlet)
• Energy Recovery (water temperature up to 95°C / 203°F)
A full instruction for handling cooling water data is available at Atlas Copco.
In case water is not in line with recommended values or if any doubt, please refer to Atlas Copco.

Technical specifications

Parameter Unit Single Pass Single Pass Recirculating Closed Closed


(65°C / (95°C / (65°C / 149°F) System System
149°F) 203°F) (65°C / (95°C /
149°F) 203°F)
1 pH 6.8 - 9.3 6.8 - 9.3 6.8 - 9.3 7.5 - 9.3 7.5 - 9.3
2 Conductivity µS / cm < 1500 < 600 < 4000 < 1500 50 - 600
3 Total Dissolved mg / L TDS to be measured for calculating RSI.
Solids
4 Ca-hardness ppm < 500 <2 < 500 < 1000 < 50
CaCO3
5 Total Alkalinity ppm No limits indicated. To be measured for calculating RSI.
CaCO3

9829 3178 62 73
Instruction book

Parameter Unit Single Pass Single Pass Recirculating Closed Closed


(65°C / (95°C / (65°C / 149°F) System System
149°F) 203°F) (65°C / (95°C /
149°F) 203°F)
6 Ryznar Stability 5.6 - 7.5 N.A. 5.6 - 7.5 5.6 - 7.5 5.6 - 7.5
Index (RSI)
7 Chlorine ppm < 0.5 — < 0.5 — —
8 Chlorides ppm < 500 (*) < 100 < 500 (*) < 500 (*) < 100
9 Nitrates ppm No limits indicated. To be measured for calculating RSI.
10 Sulphates ppm < 1000 < 200 < 1000 < 400 < 200
11 Chemical <5 <1 <5 <1 <1
Corrosion Index
12 Iron ppm <1 < 0.2 <1 <1 < 0.2
13 Manganese ppm < 0.2 < 0.05 < 0.2 < 0.2 < 0.05
14 Copper ppm <1 < 0.2 <1 <1 < 0.2
15 Ammonium ppm < 0.5 < 0.5 < 0.5 < 0.5 < 0.5
16 Suspended ppm < 10 <1 < 10 < 10 <1
Solids (max
10µ)
17 Oil or Grease ppm <1 <1 <1 <1 <1
18 Biology CFU / < 10 5 < 10 3 < 10 5 < 10 3 < 10 3
mL

Remarks on the technical specifications

Parameter Remarks
1 pH For stainless steel systems without other materials, pH can be
down to 6.
For closed loop systems, higher pH values are possible
2 Conductivity Conductivity and TDS linked with conversion factor (theoretical
factor possible, but practical determination recommended at
least once)
6 Ryznar Stability Index (RSI) Recommended actions : see table for RSI
7 Chlorine or shock treatment max. 2 ppm for 30 min/day
8 Chlorides (*) Limit 200 ppm applicable when RSI < 5.6 or RSI > 7.5
10 Sulphates Rejection < 2000 ppm. To be measured for calculating RSI.
11 Chemical Corrosion Index Index = (Chlorides + Sulphates + Nitrates) / (M-Alkalinity) (all
expressed in meq/l)
15 Ammonium limit not applicable for Cu-free systems
16 Suspended Solids (max No particles > 10µ allowed. (Particles <0.5µ not considered).
10µ)
18 Biology Anaerobic biology in closed system never allowed.

Ryznar Stability Index (RSI)


The Ryznar Stability Index (RSI) is a parameter for predicting whether water will tend to dissolve
or precipitate calcium carbonate. The adhesion of scaling deposits and their effect are different

74 9829 3178 62
Instruction book

on different materials, but the equilibrium of the water (scaling or corrosive) is only determined by
its actual pH value and by the saturation pH value (pHs).
The saturation pH value is determined by the relationship between the calcium hardness, the
total alkalinity, the total solids concentration and the temperature.
The Ryznar Stability Index is calculated as follows :
RSI = 2*pHs - pH

Symbol Explanation
pH Measured pH (at room temperature) of water sample
pHs pH at saturation

The pHs is calculated by using :


pHs = (9.3 + A + B) - (C + D)

Symbol Calculation
A (10log(TDS) - 1) / 10
B 13.12 x 10log(°C+273) + 34.55
C 10

log(Ca2+) - 0.4 (Ca2+ expressed as ppm CaCO3)


D 10

log(M-Alkalinity) (M-Alkalinity expressed as ppm CaCO3)

RSI and chloride limitation


Single Pass system

RSI Chloride Water condition Maximum 65°C / Maximum 95°C / 203


limit 149°F °F
RSI<3.9 200 ppm Very high scale formation Water cannot be used. Not applicable.
4.0<RSI<5.5 200 ppm High scale formation Regular control and Not applicable.
descaling operation
necessary.
Not recommended for
plate heat exchangers
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not Not applicable.
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not Water treatment not
necessary. necessary.
Occasional inspection Occasional inspection
recommended. recommended.
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not Water treatment not
necessary. necessary.
Occasional inspection Occasional inspection
recommended. recommended.

9829 3178 62 75
Instruction book

RSI Chloride Water condition Maximum 65°C / Maximum 95°C / 203


limit 149°F °F
7.6<RSI<9.0 200 ppm Strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation
9.1<RSI<11 200 ppm Very strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation
RSI>11 200 ppm Very strong corrosion Regular control Regular control
necessary. necessary.
Avoid interruption of Avoid interruption of
operation operation

Recirculating system, with cooling tower

RSI Chloride Water condition Maximum 65°C / 149°F


limit
RSI<3.9 200 ppm Very high scale formation Water cannot be used.
4.0<RSI<5.5 200 ppm High scale formation Regular control and descaling
operation necessary.
Not recommended for plate
heat exchangers
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not
necessary.
Occasional inspection
recommended.
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not
necessary.
Occasional inspection
recommended.
7.6<RSI<9.0 200 ppm Strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
9.1<RSI<11 200 ppm Very strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
RSI>11 200 ppm Very strong corrosion Water cannot be used.

Closed loop system

RSI Chloride Water condition Maximum 65°C / 149°F and


limit 95°C / 203°F
RSI<3.9 200 ppm Very high scale formation Water cannot be used.
4.0<RSI<5.5 200 ppm High scale formation Treat water to reduce scaling
character

76 9829 3178 62
Instruction book

RSI Chloride Water condition Maximum 65°C / 149°F and


limit 95°C / 203°F
5.6<RSI<6.2 350 ppm Slight scale formation Water treatment not
necessary.
Occasional inspection
recommended.
6.3<RSI<6.8 500 ppm Neutral water Water treatment not
necessary.
Occasional inspection
recommended.
6.9<RSI<7.5 350 ppm Slight corrosion Water treatment not
necessary.
Occasional inspection
recommended.
7.6<RSI<9.0 200 ppm Strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
9.1<RSI<11 200 ppm Very strong corrosion Regular control necessary.
Use of corrosion inhibitor
recommended
RSI>11 200 ppm Very strong corrosion Water cannot be used.

9829 3178 62 77
Instruction book

5 Operating instructions

5.1 Initial start-up

Warning

The operator must apply all relevant Safety precautions.

Switch off the voltage before making any adjustment.

Outdoor/altitude operation
If the compressor is installed outdoors or if the air inlet temperature can be below freezing point,
precautions must be taken. In this case, and also if operating at high altitude, consult Atlas
Copco.

Moving/lifting
The compressor can be moved by a lift truck using the slots in the frame. Make sure that the
forks protrude from the other side of the frame. The compressor can also be lifted after inserting
beams in the slots. Make sure that the beams cannot slide and that they protrude from the frame
equally. The chains must be held parallel to the bodywork by chain spreaders in order not to
damage the compressor. The lifting equipment must be placed in such a way that the
compressor is lifted perpendicularly. Lift gently and avoid twisting.

78 9829 3178 62
Instruction book

General preparations

Step Action
1 Install the compressor, see the sections Dimension drawing, Installation proposal and
Main fuses and supply cables.
2 Stick labels near the control panel to warn the operator that:
• the compressor may start automatically after a voltage failure
• the compressor is automatically started and stopped
• the compressor may be remotely controlled
3 A number of VCI (Volatile Corrosion Inhibitor) plates are provided inside the bodywork to
protect the compressor against corrosion. Remove the plates.
4 If the compressor has not run for the past 6 months, it is required to improve the
lubrication of the compressor element before starting. Fill up the compressor element as
described in section Oil change (paragraph: Filling the compressor element with oil).
5 Check the oil level. The oil level should reach the bottom of the oil filler neck (FC).

The minimum level should reach the oil sight-glass (GI) when the compressor is
stopped.
If needed, top up the oil.
Take care that no dirt drops into the oil system.
Refit and tighten the filler plug (FC).

Protection during transport

Transport fixtures

9829 3178 62 79
Instruction book

Step Action
1 The gear casing, motor support and air receiver supports are secured to the frame,
immobilizing the vibration dampers during transport.
2 Remove the bushes (1) from the gear casing supports and the motor support.
3 Remove the brackets fitted next to the air receiver supports.

Electric cabinet

Step Action
1 Check that the electrical connections correspond to the local codes. The installation
must be earthed and protected by fuses in all phases. An isolating switch must be fitted.
2 Check the wires on the transformers for correct connection.
3 Check the setting of the circuit breakers.

In the cabinet door, a filter is foreseen. Sufficient ventilation is guaranteed.

Water circuit

Step Action
1 Check that the cooling water drain valves (customer’s installation) in the inlet and outlet
lines are closed.
2 Check that the water shut-off valves (customer’s installation) are open.
3 Open the water regulating valve and check for water flow.

Start up

On Full-Feature compressors, switch on the voltage 4 hours before starting in order to


energize the crankcase heater of the refrigerant compressor.

Step Action
1 Close the drain valves (see the section Cooling and condensate system).
2 Switch on the voltage.
3 On air-cooled compressors, check the rotation direction of the fan motor. The fan is
visible through the grating in the air inlet panel (see section Dimension drawing). The
correct rotation direction is indicated by arrows on the fan inlet plate.
On Full-Feature compressors, open the door of the dryer compartment and check the
rotation direction of the fan motors of the condenser. The correct rotation direction is
indicated by an arrow.
4 If the rotation direction is wrong, press the emergency stop button, switch off the voltage
and reverse two incoming electric lines.
If the rotation direction of the fan motor is wrong, consult your Atlas Copco customer
centre.
5 Run the compressor for a few minutes and check that it is operating normally.

80 9829 3178 62
Instruction book

5.2 Before starting

Warning

The operator must apply all relevant safety precautions.


If the water system was drained, close the drain valves.

Control panel

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.
3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

9829 3178 62 81
Instruction book

Procedure

Step Action
1 Switch on the voltage. The voltage sign (5) lights up.
2 Close the condensate drain valves.
3 Open the air outlet valve.
4 Check the oil sight-glass. Minimum level should reach the oil sight-glass when the
compressor is stopped.
5 Open the water shut-off valves and the water regulating valve.

5.3 Starting

Warning

The operator must apply all relevant Safety precautions.

On Full-Feature compressors, switch on the voltage 4 hours before starting in order to


energize the crankcase heater of the refrigerant compressor.

Control panel

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.

82 9829 3178 62
Instruction book

Reference Designation Function


3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

Procedure

Step Action
1 Press the start button. The compressor starts running in unloaded condition. The
operation sign (4) lights up.
2 Approx. 10 seconds later (programmable), the compressor starts running loaded.
The status icon on the display of the controller changes from the running unloaded icon
to the running loaded icon.
3 On water-cooled compressors, regulate the cooling water flow with the compressor
running loaded. Adjust the water flow to obtain the most suitable air temperature at the
outlet of the compressor elements. The temperature must be between 2 and approx. 7
˚C (4 and approx. 13 ˚F) above the relevant temperature in the diagram.

9829 3178 62 83
Instruction book

Reference Name
A Air inlet temperature in ˚C
B Condensation temperature in ˚C
C Effective working pressure in bar
D Relative air humidity in %

5.4 During operation

Warning

The operator must apply all relevant Safety precautions.

The operator should immediately stop the machine in case of oil leaks internally in the
machine as well as externally and consult a competent technician to resolve the cause.
The machine should not be restarted before the problem has been remedied.
The load cycle of the compressor must be limited to maximum two cycles per minute.

Description

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.

84 9829 3178 62
Instruction book

Reference Designation Function


3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

1. Check the readings on the display.


2. When reaching the preset unloading pressure, shown on the display, the compressor will
start running unloaded. From now on, the electronic control module will calculate the
optimum moment to stop and restart the compressor motor automatically, depending on the
maximum permissible number of motor starts and on the air consumption.
3. To unload the compressor manually, press the manual load/unload button (1) on the display.
To put the compressor back into automatic operation, press the manual load/unload button
on the display again.

4. On Full-Feature compressors, regularly check the pressure dew-point on the display of the
control panel. The pressure dew-point will deviate from nominal if the air inlet conditions or
volume differ from nominal.

If the compressor is stopped, it may start automatically.

5.5 Checking the display

Warning

Before carrying out any maintenance, repair work or adjustment, stop the compressor,
press the emergency stop button and switch off the voltage. Close the air outlet valve
and open the manual condensate drain valve.

9829 3178 62 85
Instruction book

Description

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.
3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

1. Regularly check the display for readings and messages. Normally, the main display is
shown.
2. Always check the display and remedy the trouble if the warning sign (2) is alight or blinks.
The display will show a service message if a service plan interval has been exceeded or if a
service level for a monitored component has been exceeded. Carry out the service actions
of the indicated plans or replace the component and reset the relevant timer.
Regularly check the Inputs and Outputs menus for a quick look at the compressor status.

86 9829 3178 62
Instruction book

5.6 Manual loading/unloading

Description

Control panel

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.
3 Service sign Is lit when service is needed.
4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

General
Normally, the compressor runs in automatic operation, i.e. the electronic regulator loads, unloads,
stops and restarts the compressor automatically. Operation sign (4) is then alight.
If required, the compressor can be unloaded manually. In this case, the compressor is switched
out of automatic operation i.e. the compressor remains running unloaded unless it is loaded
again manually.
Manual unloading

9829 3178 62 87
Instruction book

To unload the compressor manually, touch the manual load/unload button (1) on the display.
When the button is touched, the compressor starts running unloaded and the operation sign (4)
fades. The manual load/unload icon starts blinking.

Manual loading
To put the compressor back into automatic operation, press the manual load/unload button (1) on
the display. When the button is touched, the operation sign (4) lights up and the compressor
starts running loaded in case the air net pressure drops below the programmed level. The
manual load/unload icon darkens.

If the Load or Unload icons are not displayed on the bottom line of the screen, make
sure to return to the Main screen first.

5.7 Stopping

Reference Designation Function


1 Touchscreen Shows the compressor operating condition and a
number of icons to navigate through the menu.
The screen can be operated by touch.
2 Warning sign Flashes in case of a shut-down, is lit in case of a
warning condition.
3 Service sign Is lit when service is needed.

88 9829 3178 62
Instruction book

Reference Designation Function


4 Operation sign Is lit when the compressor is running in automatic
operation.
5 Voltage sign Indicates that the voltage is switched on.
6 Stop button This button stops the compressor.
7 Start button This button starts the compressor. The operation
sign (4) lights up. The controller is operative.

Procedure

Frequently stopping the compressor using the emergency stop button may damage the
compressor. Only use the emergency stop button in case of emergency.

Step Action
1 Press stop button (6). The compressor will coast down and then stop.
2 To stop the compressor in case of emergency, press the emergency stop button. The
warning sign (2) starts flashing. After remedying the trouble, unlock the emergency stop
button by pulling it back.
3 Close the air outlet valve.
4 Open the condensate drain valves.
5 Switch off the voltage.
6 On water-cooled compressors, close the water shut-off valves.
7 On water-cooled compressors, if the compressor is installed in a room where freezing
temperatures are expected, drain the cooling system by opening the drain valves in the
water inlet and outlet pipes (customer's installation).

5.8 Taking out of operation

Disconnecting the compressor


At the end of the service life of the compressor, proceed as follows:

Step Action
1 Stop the compressor and close the air outlet valve.
2 Switch off the voltage and disconnect the compressor from the mains.
3 Depressurize the compressor by opening the drain valve and loosening the oil filler plug
one turn.
4 Shut off and depressurize the part of the air net which is connected to the outlet valve.
Disconnect the compressor air outlet pipe from the air net.
5 Drain the oil and condensate circuits.
On water-cooled compressors, drain the water circuits.
6 Disconnect the compressor condensate piping from the condensate drain net.
7 On water-cooled compressors, disconnect the cooling water pipes from the compressor.

9829 3178 62 89
Instruction book

5.9 Use of air receiver

Instructions
1. This vessel may only be used for separating oil from compressed air and this within the
limits of pressure and temperature as specified on the nameplate.
2. A safety valve must be installed by the user to protect the vessel against overpressure. The
protection must ensure that the pressure will not permanently exceed the maximum
allowable working pressure.
3. The user must take precautions to ensure that the vessel operates in the temperature range
between -10 °C (14 °F) and 120 °C (248 °F).
4. To guarantee a proper operation, the intake air must be filtered.
5. A draining valve must be foreseen by the user to protect the vessel against overfilling by oil.
6. The vessel must be mounted in an installation that will operate at atmospheric pressure.
7. The user must avoid storing/installing the separator in badly ventilated rooms, near heating
sources or inflammable substances. The user must protect the vessel by a casing in case of
outdoor erection.
8. Pipe connections must be mounted tension free by means of flexible couplings.
9. The vessel must be mounted with the foreseen attachment points. In areas with risk of
earthquakes or installations subjected to reaction forces and moments of inertia from
supporting constructions, anchor pads must be used.
10. The vessel must be foreseen with an earthing.
11. The user must make the customer aware of possible high surface temperature of the vessel.
12. The user must provide the customer with instructions regarding safe emptying, cleaning,
inspecting (also internally), maintenance and daily operation.
13. After the vessel has been opened, the original bolts must be used for closing. Herewith the
maximum torque has to be respected.
14. No modifications may be carried out on the vessel by welding, drilling or by any other way of
mechanical operation, without written permission of the manufacturer.
15. This vessel was designed and manufactured respecting the functional specifications. An
inspection of the inside is for this reason not really necessary as long as the vessel is used
within the limits and applications for which it has been designed. However it is possible that
local legislation requires an internal inspection.

90 9829 3178 62
Instruction book

6 Maintenance

6.1 Preventive maintenance schedule

Warning

Before carrying out any maintenance, repair work or adjustment, proceed


as follows:
• Stop the compressor.
• Press the emergency stop button.
• Close the air outlet valve and open the manual condensate drain valves.
• For compressors equipped with electronic water drains, press the test
buttons on top of the electronic drains until the air system between the air
receiver and the outlet valve is fully depressurized.
• Switch off the voltage.
• Open and lock the isolating switch.
The operator must apply all relevant Safety precautions.

Warranty - Product Liability


Use only authorized parts. Any damage or malfunction caused by the use of unauthorized parts
is not covered by Warranty or Product Liability.

General
When servicing, replace all removed gaskets, O-rings and washers.

Preventive maintenance schedule

The maintenance schedule is prior to the maintenance warnings displayed on the


controller. It is the responsibility of the owner to carry out the required maintenance at
the appropriate moment.

Period Running hours Operation


Daily 8 Check readings on display.
Daily 8 Check that condensate is discharged during loading.
Daily 8 Check oil level. Before starting, the level should be above the sight-
glass.
3-Monthly -- Check for air-, water- and oil leakages.
3-Monthly -- Check the contamination on the air- and oil-cooler surface, clean
externally if necessary.
3-Monthly -- Check the condition of the cooling fan assembly.
3-Monthly -- Check the condition of the air filters and cubicle filters, replace if
necessary.
See Oils -- Change oil.

Contact Atlas Copco to schedule the following maintenance intervals:


• Yearly or 8000 hours

9829 3178 62 91
Instruction book

• 2 Yearly or 16000 hours


• 5 Yearly or 40000 hours

When operating in a dusty atmosphere, inspect the air filters more frequently.
Always use Atlas Copco filters.
The separator element must also be replaced when the pressure difference over the
element exceeds 0.8 bar (12 psi). Check the pressure drop when the compressor is
running loaded and preferably with a stable working pressure.
Damaged flexibles must be replaced immediately.

Service agreements
Atlas Copco Customer Centres have a range of service agreements to suit your needs:
• An Inspection Plan
• A Preventive Maintenance Plan
• A Warranty+ Plan
• A Total Responsibility Plan
Contact your Customer Centre to set up a tailor-made service agreement. It will ensure optimum
operational efficiency, minimize downtime and reduce the total life cycle costs.

Service plan
A number of service operations are grouped (called Level A, Level B, Level C...). Each level
stands for a number of service actions to be carried out at the time intervals programmed in the
Elektronikon regulator.
When a level is reached, a message will appear on the screen. After carrying out all service
actions, the interval timers must be reset using the “Reset” key in the “Service” menu. Consult
your Atlas Copco Service Centre.

6.2 Oil specifications

Atlas Copco Roto-Xtend Duty Fluid


Atlas Copco Roto-Xtend Duty Fluid is a high-quality synthetic lubricant for oil-injected scroll and
screw compressors which keeps the compressor in excellent condition. Roto-Xtend Duty Fluid
can be used for compressors operating at ambient temperatures between 0 ˚C (32 ˚F) and 46 ˚C
(115 ˚F) (see section Service kits).

Foodgrade oil
Foodgrade oil is a unique high quality synthetic lubricant, specially created for oil-injected screw
compressors that provide air for the food industry. This lubricant keeps the compressor in
excellent condition. Foodgrade oil can be used for compressors operating at ambient
temperatures between 0 ˚C (32 ˚F) and 40 ˚C (104 ˚F).

92 9829 3178 62
Instruction book

Important

Never mix oils of different brands or types.

6.3 Oil specifications

Atlas Copco Roto-Xtend Duty Fluid


Atlas Copco Roto-Xtend Duty Fluid is a high-quality synthetic lubricant for oil-injected scroll and
screw compressors which keeps the compressor in excellent condition. Roto-Xtend Duty Fluid
can be used for compressors operating at ambient temperatures between 0 ˚C (32 ˚F) and 46 ˚C
(115 ˚F) (see section Service kits).

Important

Never mix oils of different brands or types.

6.4 Oil change

Warning

The operator must apply all relevant Safety precautions.

Vent, filler and drain plugs

Oil drain plugs on compressor elements, gearbox and drive motor

9829 3178 62 93
Instruction book

Vent and drain plugs on air-cooled compressors

Filler and drain plugs on water-cooled compressors

94 9829 3178 62
Instruction book

Procedure

Step Action
1 Run the compressor until warm.
Stop the compressor.
Close the air outlet valve.
Switch off the voltage.
Wait a few minutes.
Depressurize by unscrewing the plug only one turn to permit any pressure in the system
to escape.
2 Loosen the vent plugs on top of the oil coolers.
3 Drain the oil by removing the drain plugs.
Plugs are fitted on the:
• Air receiver / Oil separator with drain point
• Element outlet
• Drive motor
• Gearbox
• Oil coolers of air-cooled compressors
• Oil filter housing
• Hose between the oil filter housing and oil coolers of water-cooled compressors
Tighten the plugs after draining.
4 Remove the filler plug.
Fill the air receiver / oil separator with oil until the level reaches the filler opening.
Refit and tighten the plug.
Tighten the vent plug of the oil cooler.
5 Disconnect the air inlet hose from the inlet valve.
Pour 10 liter of oil into the compressor stage.
Reinstall the air inlet hose.
6 Run the compressor for a few minutes to allow the oil cooler by-pass valve to open.
Stop the compressor.
Wait a few minutes.
7 Depressurize the system by unscrewing the plug only one turn to permit any pressure in
the system to escape.
Remove the plug.
Fill the air receiver / oil separator with oil until the level reaches the filler opening.
Tighten the filler plug.
8 After carrying out all service actions in the relevant “Service Plan”, reset the service
warning.
Refer to the Service menu section.

6.5 Oil filter change

Warning

Stop the compressor and switch off the voltage. The operator must apply all relevant
Safety precautions.

9829 3178 62 95
Instruction book

Position of oil filters

Procedure

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage. Wait a few
minutes and depressurize the air receiver by unscrewing the oil filler plug (of the air
receiver) only one turn to permit any pressure in the system to escape.
2 Use an oil pan to avoid possible oil spillage. Unscrew the oil filters only one turn and
wait a few minutes to let the oil of the filter flow back into the oil separator. Remove the
oil filters.
3 Clean the filter seats on the manifold. Oil the gaskets of the new filters and screw the
filters into place until the gaskets contact their seats. Then tighten with a maximum
torque of 10 Nm.
4 Tighten the oil filler plug (of the air receiver).
5 Reset the service warning after carrying out all service actions in the relevant Service
Plan. Refer to the Service menu section.

6.6 Oil separator change

96 9829 3178 62
Instruction book

Procedure

Step Action
1 Stop the compressor, close the air outlet valve and switch off the voltage. Wait a few
minutes and depressurize the air receiver by unscrewing the oil filler plug (of the air
receiver) only one turn to permit any pressure in the system to escape.
2 Unscrew the bolts fixing the small vessel covers marked to have an oil separator
element below them.
3 Remove the oil separator cartridges and replace them by new cartridges. Mind correct
angular positioning of the cartridges.
4 Tighten the oil filler plug (of the air receiver).
5 Reset the service warning after carrying out all service actions in the relevant Service
Plan. Refer to the Service menu section.

6.7 Storage after installation

Procedure
Run the compressor, e.g. once a week, until warm plus 5–10 minutes. Load and unload the
compressor a few times to operate the components of the unloading/loading system.

If the compressor is going to be stored without running from time to time, protective
measures must be taken. Consult the Atlas Copco Customer Centre.

6.8 Service kits

General
Service kits comprise all parts needed for servicing components and offer the benefits of genuine
Atlas Copco parts while keeping the maintenance budget low. All service tools are in IQ2
Inteliquater and the Business Portal.

Atlas Copco Roto-Xtend Duty Fluid


Roto-Xtend Duty Fluid can be ordered in the following quantities:
• 5-litre can: 2901 1700 00
• 20-litre can: 2901 1701 00
• 209-litre drum: 2901 1702 00
See Oil specifications.

9829 3178 62 97
Instruction book

7 Integrated dryer

7.1 Introduction

Description
The air dryer removes moisture from compressed air by cooling the air to near freezing point.
This causes water to condense. The condensate is automatically drained. The air is warmed up
before leaving the dryer (approx. 5 ˚C (9 ˚F) below the incoming air temperature).
The air dryer cools down the compressed air to the preset temperature. Any formed condensate
is automatically drained.
The electronic regulator keeps the pressure dew-point stable at no load by opening or closing the
solenoid valve of the hot-gas by-pass.
On air-cooled dryers, the condenser has a cooling fan controlled by a pressure sensor.
Water-cooled dryers have a water regulating valve in the water outlet of the condenser.
The descriptions mentioned in this book are valid for both air-cooled and water-cooled dryers.

General view

Air-cooled dryer

98 9829 3178 62
Instruction book

Water-cooled dryer

Position of components

Water-cooled dryer

9829 3178 62 99
Instruction book

Air-cooled dryer

1 Heat exchanger
2 On air-cooled dryers, cooling fan(s)
On water-cooled dryers, water regulating valve
3 On air-cooled dryers, air-cooled condenser
On water-cooled dryers, water-cooled condenser
4 Sight-glass
5 Refrigerant compressor
6 Liquid separator
7 Thermostatic expansion valve
8 Refrigerant dryer/filter
9 Non-return valve

100 9829 3178 62


Instruction book

7.2 Air and refrigerant system

Flow diagram

Air-cooled dryer

9829 3178 62 101


Instruction book

Water-cooled dryer

Reference Name
301a Air/air heat exchanger
301b Air/refrigerant heat exchanger
111 Condensate separator
410 Non-return valve

102 9829 3178 62


Instruction book

Reference Name
403 Air-cooled condenser (air-cooled version)
Water-cooled condenser (water-cooled version)
408 Fan blower (air-cooled version)
Water regulating valve (water-cooled version)
407 Thermostatic expansion valve
90 Pressure shut-down switch
405 Refrigerant dryer/filter
401 Liquid separator
412 Hot-gas by-pass valve
402 Refrigerant compressor
411 Solenoid valve
406 Sight-glass
89, 90 Temperature sensor
90 Pressure sensor
413 Automatic drain

Description air system


Compressed air enters heat exchanger (301a) and is cooled by the outgoing, cold, dried air.
Water in the incoming air starts to condense. The air then flows through heat exchanger/
evaporator (301b) where the refrigerant evaporates causing the air to be further cooled to close
to the evaporating temperature of the refrigerant. More water in the air condenses. The cold air
then flows through separator (111) where all the condensate is separated from the air.
The condensate collects in the electronic water drain (413) and is automatically drained. The
cold, dried air flows through heat exchanger (301a), where it is warmed up by the incoming air to
approx. 5 ˚C (9 ˚F) below the incoming air temperature.
Condensation in the air net cannot occur unless the air is cooled to below the pressure dew-point
indicated on the control panel.

Description refrigeration system


Refrigerant compressor (402) delivers hot, high-pressure refrigerant gas, which flows through
condenser (202), where most of the refrigerant condenses.
The liquid flows through refrigerant dryer/filter (405) to thermostatic expansion valve (407) via
sight-glass (406). The refrigerant leaves the thermostatic expansion valve at evaporating
pressure.
The refrigerant enters evaporator (301b), where it withdraws heat from the compressed air by
further evaporation at constant pressure. The heated refrigerant leaves the evaporator and is
sucked in by refrigerant compressor (402) via liquid separator (401).
The dryers are provided with a sight-glass (406). The sight-glass allows the refrigerant flow in the
line to be checked. During normal operation, the liquid flow must be clear. In general, vapor
bubbles indicate a shortage of refrigerant. Note that fluctuations in the load may cause bubbles to
pass in the flow for a short time. The centre of the glass is provided with a moisture indicator
which is green when the liquid refrigerant is free of moisture. It will turn yellow when the

9829 3178 62 103


Instruction book

refrigerant contains moisture, indicating that the refrigerant dryer/filter (405) needs to be
replaced.

Refrigerant gas specifications


Please check the data plate of the integrated dryer for the type designation and refer to the table
below.

Dryer Cooling Refrigerant gas Global Amount Amount Tonnes of


method Warming (kg) (lbs) CO2
Potential equivalent
ID 365 air R410A 2088 3.8 8.4 7.9
ID 525 air R410A 2088 5.8 12.8 12.1
ID 365 water R410A 2088 4.2 9.3 8.8
ID 525 water R410A 2088 4.8 10.6 10.0

104 9829 3178 62


Instruction book

7.3 Automatic regulation system

Air and refrigerant flow diagram

Air and refrigerant flow diagram for air-cooled dryer

9829 3178 62 105


Instruction book

Air and refrigerant flow diagram for water-cooled dryer

Description
The condenser pressure must be kept as constant as possible to obtain stable operation,
therefore:
• For air-cooled versions, the regulator stops and starts the cooling fans
• For water-cooled versions, the water regulating valve in the water outlet regulates the
cooling water flow

106 9829 3178 62


Instruction book

When at partial or no load the dew-point pressure stays below the set-point, the regulator opens
solenoid valve (411) and hot, high-pressure gas is fed through hot-gas by-pass valve (412) to the
evaporator circuit to prevent the evaporator temperature from dropping below 0 ˚C (32 ˚F).

7.4 Condensate drain system

Description

Electronic water drain location

Electronic water drain functioning

1 Inlet
2 Supply line
3 Pilot valve
4 Diaphragm
5 Sensor
6 Collector
7 Valve seat
8 Outlet

9829 3178 62 107


Instruction book

The condensate enters the electronic water drain via inlet (1) and accumulates in collector (6). A
capacitive sensor (5) continuously measures the liquid level.
The pilot valve (3) is activated as soon as the collector is filled up to a certain level. Diaphragm
(4) opens outlet (8), discharging the condensate.
When the collector has been emptied, the outlet closes quickly without wasting compressed air.
When the controller registers a malfunction, the red alarm LED on the control panel of the
electronic water drain starts flashing, a warning appears on the display of the regulator and the
electronic drain valve will automatically change to the alarm mode, opening and closing the valve
according to a sequence as shown below . This condition continues until the fault is remedied. If
the fault is not remedied automatically, maintenance is required.

Drain frequency during alarm condition

Testing the Electronic water drain

Control panel

Briefly press the TEST button and check that the valve opens for condensate discharge.
Checking the alarm signal
• Press and hold the test button for at least 1 minute.
• Check that the alarm LED flashes.

108 9829 3178 62


Instruction book

• Check that a warning is generated on the display of the regulator.


• Release the test button.

7.5 Electrical system

Dryer protection
The high-pressure shut-down switch stops the compressor motor when the pressure in the
refrigerant circuit reaches the upper set-point of the switch.
After tripping:
• The switch must be reset manually by pressing its reset knob and by pressing the Cancel/
escape key on the controller.
The compressor motor has a built-in thermic protection. If the thermic protection trips, the
compressor motor will be stopped. The compressor will restart when the motor windings have
cooled down, which may take up to 3 hours.

7.6 Regulation

General description
The electronic regulator automatically controls the dryer, i.e.:
• keeps the pressure dew-point stable
• stops the dryer whenever necessary
• restarts the dryer when required
In general, the regulator has following functions:
• controlling the dryer
• protecting the dryer

Controlling the dryer


The regulator keeps the pressure dew-point stable at no load by opening or closing the solenoid
valve of the hot-gas by-pass.
In order to keep the condenser pressure constant:
• For air-cooled versions, the regulator starts and stops the fan motor(s) as necessary.
• For water-cooled versions, the water regulating valve regulates the cooling water flow.

Protecting the dryer


Shut-down
• In case the pressure in the refrigerant circuit is too high, the dryer will be stopped.
• For air-cooled versions, the dryer will also be stopped if there is an overload of a fan motor.
Warning
• A warning message appears if the electronic water drain is malfunctioning.

9829 3178 62 109


Instruction book

7.7 Maintenance instructions

Important

The dryers contain refrigerant HFC.


When the automatic operation LED is lit, starting and stopping of the dryer are controlled
automatically.
If the dryer start/stop timer is active, the dryer may start automatically, even if it was
stopped manually.

Safety precautions
When handling refrigerant R404A or R410A (refer to dryer data plate), all applicable safety
precautions must be observed. The following points are stressed:
• Contact of refrigerant with the skin will cause freezing. Special gloves must be worn and, if
there is contact with the skin, the skin should be rinsed with water. On no account may
clothing be removed.
• Fluid refrigerant will also cause freezing of the eyes; therefore, safety glasses must be worn.
• Refrigerants R404A and R410A are poisonous. Do not inhale refrigerant vapors. Check that
the working area is adequately ventilated.
When removing the side panels of the dryer, be aware that internal elements such as the pipes
can reach a temperature of 120 ˚C (248 ˚F). Therefore, wait until the dryer has cooled down
before removing the side panels.
Before starting any maintenance or repairs, switch off the voltage. Isolate the dryer from the air
net.

Local legislation
Local legislation may impose that:
• Work on the refrigerant circuit of the cooling dryer or on any equipment which influences its
function must be carried out by an authorized control body.
• The installation should be checked once a year by an authorized control body.

Warranty and product liability


Use only authorized genuine parts. Any damage or malfunction caused by the use of
unauthorized parts is not covered by Warranty or Product Liability.

Service agreements
Customer Centres have a range of service agreements to suit your needs:
• An Inspection Plan.
• A Preventive Maintenance Plan.
• A Total Responsibility Plan.
Contact your Customer Centre to arrange a tailor-made service agreement. This will ensure
optimum operational efficiency, minimize downtime and reduce the total life cycle costs.

110 9829 3178 62


Instruction book

General
The following remarks should be kept in mind:
• Keep the dryer clean.
• On air-cooled dryers, brush or blow off the finned surface of the condenser regularly.
On water-cooled dryers, regularly check for water leaks.
• Inspect and clean the electronic water drain once a year .

7.8 Problem solving

Attention

Use only authorized parts. Any damage or malfunction caused by the use of
unauthorized parts is not covered by Warranty or Product Liability.
Apply all relevant Safety precautions.
Before carrying out any maintenance or repairs on the dryer, stop the dryer and switch
off the voltage.
Open the isolating switch to prevent an accidental start.
Isolate the dryer from the air net.

Faults and remedies (general)

Condition Fault Remedy


- Pressure dew-point too high Ambient temperature too high Check and correct; if necessary,
draw cooling air via a duct from a
cooler place or relocate dryer
Shortage of refrigerant Have circuit checked for leaks and
recharged
Refrigerant compressor does See below
not run
Evaporator pressure too high See below
Condenser pressure too high See below
Automatic drain system Have the system cleaned
clogged
- Condenser pressure too high Fan control switch out of order Replace
or too low on air-cooled dryers
Fan or fan motor out of order Check fan/fan motor
Ambient temperature too high Check and correct; if necessary,
draw cooling air via a duct from a
cooler place or relocate dryer
Condenser externally clogged Clean condenser
- Condenser pressure too high Cooling water system clogged Have cooling water system cleaned
or too low on water-cooled
dryers
Cooling water temperature too Check and correct as necessary
high
- Compressor stops or does not Electric power supply to Check and correct as necessary
start compressor is interrupted

9829 3178 62 111


Instruction book

Condition Fault Remedy


Motor overload protection of Have motor checked
refrigerant compressor motor For resetting: see the section
has tripped Electrical system
High-pressure switch tripped See above
- Condensate drain remains Automatic drain system Flush the assembly by opening
inoperative clogged manual drain valve.
Have system inspected
- Condensate trap continuously Automatic drain system out of Have system checked. If necessary
discharges air and water order replace automatic drain
- Evaporator pressure is too Hot-gas by-pass valve Have hot-gas by-pass valve
high or too low at unload incorrectly set or out of order adjusted
Condenser pressure too high See above
or too low
Shortage of refrigerant Have circuit checked for leaks and
recharged

112 9829 3178 62


Instruction book

8 Adjustments and servicing procedures

8.1 Air filters

Warning

Stop the compressor, close the air outlet valve, press the emergency stop button and
switch off the voltage. The operator must apply all relevant Safety precautions.

Position of air filters

Air filters (1)

Procedure

Step Action
1 Remove the filter elements (1).
2 Fit the new filter elements (1).
3 Reset the service warning after carrying out all service actions in all applicable service
plans. Refer to the service menu section of the regulator.

8.2 Coolers

Warning

Stop the compressor, press the emergency stop button and switch off the voltage. The
operator must apply all relevant Safety precautions.

9829 3178 62 113


Instruction book

Procedure

Air-cooled cooler block

Water-cooled cooler block

On air-cooled compressors proceed as follows:

114 9829 3178 62


Instruction book

Service panel of the air-cooled cooler

Step Action
1 Open the service door at the cooler side.
2 Remove the service panel (1) at the cooler side.
3 Remove any dirt form the coolers with a fibre brush, brush in the direction of the fins.
Also remove any dirt from the fans.
4 Clean the coolers with an air jet in the reverse direction to normal flow. Use low
pressure air; if necessary, the pressure may be increased up to 6 bar (e) (87 psig).
5 If it is necessary to clean the coolers with a cleaning agent, consult Atlas Copco.
6 Mount the service panel.
7 Close the door.

On water-cooled compressors, consult the Atlas Copco Customer Centre if it is necessary to


clean the coolers.

8.3 Safety valve

Warning

Stop the compressor and switch off the voltage. The operator must apply all relevant
Safety precautions.

Never run the compressor without safety valves.


No adjustments are allowed.

9829 3178 62 115


Instruction book

Testing

Location of safety valve on air-cooled compressor

The valve can be tested on a separate compressed air line.


Consult the Atlas Copco Customer Centre if the valve does not open at the correct pressure (see
the section Settings of safety valve).

116 9829 3178 62


Instruction book

9 Problem solving

9.1 Problem solving

Warning

Before carrying out any maintenance, repair work or adjustment, stop the compressor,
press the emergency stop button and switch off the voltage. Close the air outlet valve
and open the manual condensate drain valves.
Open and lock the isolating switch.
The operator must apply all relevant Safety precautions.

Control panel

Reference Name
1 Start button
2 Stop button
3 Warning sign
4 Service sign
5 Operation sign
6 Voltage sign

Faults and remedies

A service message appears on the display


Stop the compressor and carry out the indicated service actions.
Reset the message. Refer to the Service menu section.

A shut-down warning message appears on the display


The warning sign (3) will light up indicating that the temperature at the outlet of the compressor elements is
too high. The message disappears as soon as the cause of the problem is remedied.

9829 3178 62 117


Instruction book

Unit is shut down


The warning sign (3) will flash indicating that a shutdown level has been triggered. Remedy the problem.
Move the cursor to the action button Menu and push the Enter key. Using the Scroll keys, move the cursor
to the protections icon. Push the Enter key. Move the cursor to the blinking icon and press the Enter key.
Move the cursor to the Reset button and press the enter key again.

Multiple shut-down
If there are multiple sequential failures with short time intervals on a specific shut-down functionality,
consult your Atlas Copco Customer Centre.

Excessive oil consumption


Have the compressor inspected by your Atlas Copco Customer Centre.

Condition Fault Remedy


Condensate is not discharged from Discharge pipe of condensate Check and correct as necessary.
condensate traps during loading. trap clogged.
WSD (electronic water drain) Consult Atlas Copco.
malfunctioning.

Condition Fault Remedy


Compressor air delivery or pressure Air consumption exceeds air Check equipment connected.
below normal. delivery of compressor.
Choked air filters. Replace filters.
Air leakage. Check and correct.

Condition Fault Remedy


Compressor element outlet Oil level too low. Check and correct.
temperature or delivery air Oil coolers clogged. Refer to the Coolers section.
temperature above normal.
Air cooler clogged. Refer to the Coolers section.
On air-cooled compressors, Check and correct as necessary.
insufficient cooling air or cooling
air temperature too high.
On water-cooled compressors, Increase flow.
cooling water flow too low.
On water-cooled compressors, Consult Atlas Copco Customer
restriction in cooling water Centre.
system.

118 9829 3178 62


Instruction book

10 Technical data

10.1 Readings on display

Important

The readings are valid when operating under reference conditions. See the
section Reference conditions.

Normally the main display is shown, indicating the actual air outlet pressure and
the actual compressor status. The arrow down key allows the operator to call up
other information such as actually measured pressures and temperatures.

Important readings

Compressor outlet pressure bar(e) (psig) Depends on programmed


unloading and loading
pressures
Pressure drop over air filters bar Below 0.05
Pressure drop over air filters psi Below 0.73
Pressure difference over oil separator bar Below 0.8
Pressure difference over oil separator psi Below 12
Oil injection pressure at the compressor elements bar(e) (psig) Depends on programmed
unloading and loading
pressures
Compressor outlet temperature, air-cooled Pack compressors ˚C Approx. 28
Compressor outlet temperature, air-cooled Pack compressors ˚F Approx. 82
Compressor outlet temperature, air-cooled Full-Feature ˚C Approx. 25
compressors
Compressor outlet temperature, air-cooled Full-Feature ˚F Approx. 77
compressors
Compressor outlet temperature, water-cooled compressors ˚C Approx. 22
Compressor outlet temperature, water-cooled compressors ˚F Approx. 72
Cooling air inlet temperature of Pack compressor ˚C Below 46
Cooling air inlet temperature of Pack compressor ˚F Below 115
Cooling air inlet temperature of Full-Feature compressor ˚C Below 46
Cooling air inlet temperature of Full-Feature compressor ˚F Below 115
Cooling air inlet temperature of Pack compressor (high ˚C Below 55
ambient temperature variant)
Cooling air inlet temperature of Pack compressor (high ˚F Below 131
ambient temperature variant)
Cooling water temperature ˚C Below 50
Cooling water temperature ˚F Below 122
Pressure dew-point ˚C Approx. 3
Pressure dew-point ˚F Approx. 37

9829 3178 62 119


Instruction book

10.2 Reference conditions

Reference conditions

Absolute inlet pressure bar(a) 1


Absolute inlet pressure psi 14.5
Relative air humidity % 0
Air inlet temperature ˚C 20
Air inlet temperature ˚F 68
Nominal working pressure See Compressor data
Cooling medium inlet temperature ˚C 20
Cooling medium inlet temperature ˚F 68
Cooling water temperature rise °C 10
Cooling water temperature rise °F 18

10.3 Limits

Limits

Minimum air inlet/ambient temperature ˚C 0


Minimum air inlet/ambient temperature ˚F 32
Maximum air inlet/ambient temperature ˚C 46
Maximum air inlet/ambient temperature ˚F 115
Maximum air inlet/ambient temperature of Pack compressors ˚C 55
(high ambient temperature variant)
Maximum air inlet/ambient temperature of Pack compressors ˚F 131
(high ambient temperature variant)
Minimum cooling air temperature ˚C 0
Minimum cooling air temperature ˚F 32
Maximum cooling air temperature ˚C 46
Maximum cooling air temperature ˚F 115
Maximum cooling air temperature of Pack compressors (high ˚C 55
ambient temperature variant)
Maximum cooling air temperature of Pack compressors (high ˚F 131
ambient temperature variant)
Maximum working pressure See section Compressor
data
Maximum cooling water inlet temperature ˚C 40
Maximum cooling water inlet temperature ˚F 104
Maximum cooling water outlet temperature (open systems) ˚C 50
Maximum cooling water outlet temperature (open systems) ˚F 122
Maximum cooling water outlet temperature (recirculating ˚C 60
systems)

120 9829 3178 62


Instruction book

Maximum cooling water outlet temperature (recirculating ˚F 140


systems)
Maximum cooling water inlet pressure bar(e) 10
Maximum cooling water inlet pressure psig 145

10.4 Settings of safety valve


The safety valve setting is 12 bar.
The safety valve setting is 174 psig.

10.5 Settings of overload relays, fuses and circuit breakers

Setting of fan protection for air-cooled compressors

Supply voltage (V) Q25F/Q26F(A) Q25S/Q26S (A)


380 6.5 3.1
400 6.0 2.5
440 6.0 2.5
460 6.0 2.5

Setting of fan protection for water-cooled compressors

Supply voltage (V) Q16 (A)


380 1.1
400 1.1
440 1.1
460 1.1

Setting of dryer protection for air-cooled Full-Feature 50 Hz compressors

Q41, Q42
Model Working pressure (bar) Supply voltage (V) Q40 (A)
(A)
GA 90+ 5.5 400 10 1.3
GA 90+ 7.5 400 8 1.9
GA 90+ 8.5 400 8 1.9
GA 90+ 10 400 8 1.9
GA 110 5.5 400 12 1.9
GA 110 7.5 400 8 1.9
GA 110 8.5 400 8 1.9
GA 110 10 400 8 1.9
GA 132 5.5 400 12 1.9
GA 132 7.5 400 10 1.3

9829 3178 62 121


Instruction book

Q41, Q42
Model Working pressure (bar) Supply voltage (V) Q40 (A)
(A)
GA 132 8.5 400 8 1.9
GA 132 10 400 8 1.9
GA 160 7.5 400 12 1.9
GA 160 8.5 400 10 1.3
GA 160 10 400 8 1.9

Setting of dryer protection for water-cooled Full-Feature 50 Hz compressors

Model Working pressure (bar) Supply voltage (V) Q40 (A)


GA 90+ 5.5 400 10
GA 90+ 7.5 400 8
GA 90+ 8.5 400 8
GA 90+ 10 400 8
GA 110 5.5 400 12
GA 110 7.5 400 8
GA 110 8.5 400 8
GA 110 10 400 8
GA 132 5.5 400 12
GA 132 7.5 400 10
GA 132 8.5 400 8
GA 132 10 400 8
GA 160 7.5 400 12
GA 160 8.5 400 10
GA 160 10 400 8

Setting of dryer protection for air-cooled Full-Feature 60 Hz compressors

Q41, Q42
Model Working pressure (psi) Supply voltage (V) Q40 (A)
(A)
GA 90+ 75 380 9.5 1.45
GA 90+ 100 380 6.7 2
GA 90+ 125 380 6.7 2
GA 90+ 150 380 6.7 2
GA 90+ 75 440 9.5 1.45
GA 90+ 100 440 6.7 2
GA 90+ 125 440 6.7 2
GA 90+ 150 440 6.7 2
GA 90+ 75 460 9.5 1.45
GA 90+ 100 460 6.7 2
GA 90+ 125 460 6.7 2
GA 90+ 150 460 6.7 2

122 9829 3178 62


Instruction book

Q41, Q42
Model Working pressure (psi) Supply voltage (V) Q40 (A)
(A)
GA 110 75 380 12 2
GA 110 100 380 6.7 2
GA 110 125 380 6.7 2
GA 110 150 380 6.7 2
GA 110 75 440 12 2
GA 110 100 440 6.7 2
GA 110 125 440 6.7 2
GA 110 150 440 6.7 2
GA 110 75 460 12 2
GA 110 100 460 6.7 2
GA 110 125 460 6.7 2
GA 110 150 460 6.7 2
GA 132 75 380 12 2
GA 132 100 380 9.5 1.45
GA 132 125 380 6.7 2
GA 132 150 380 6.7 2
GA 132 75 440 12 2
GA 132 100 440 9.5 1.45
GA 132 125 440 6.7 2
GA 132 150 440 6.7 2
GA 132 75 460 12 2
GA 132 100 460 9.5 1.45
GA 132 125 460 6.7 2
GA 132 150 460 6.7 2
GA 160 100 380 12 2
GA 160 125 380 9.5 1.45
GA 160 150 380 6.7 2
GA 160 100 440 12 2
GA 160 125 440 9.5 1.45
GA 160 150 440 6.7 2
GA 160 100 460 12 2
GA 160 125 460 9.5 1.45
GA 160 150 460 6.7 2

9829 3178 62 123


Instruction book

Setting of dryer protection for water-cooled Full-Feature 60 Hz compressors

Model Working pressure (psi) Supply voltage (V) Q40 (A)


GA 90+ 75 380 9.5
GA 90+ 100 380 6.7
GA 90+ 125 380 6.7
GA 90+ 150 380 6.7
GA 90+ 75 440 9.5
GA 90+ 100 440 6.7
GA 90+ 125 440 6.7
GA 90+ 150 440 6.7
GA 90+ 75 460 9.5
GA 90+ 100 460 6.7
GA 90+ 125 460 6.7
GA 90+ 150 460 6.7
GA 110 75 380 12
GA 110 100 380 6.7
GA 110 125 380 6.7
GA 110 150 380 6.7
GA 110 75 440 12
GA 110 100 440 6.7
GA 110 125 440 6.7
GA 110 150 440 6.7
GA 110 75 460 12
GA 110 100 460 6.7
GA 110 125 460 6.7
GA 110 150 460 6.7
GA 132 75 380 12
GA 132 100 380 9.5
GA 132 125 380 6.7
GA 132 150 380 6.7
GA 132 75 440 12
GA 132 100 440 9.5
GA 132 125 440 6.7
GA 132 150 440 6.7
GA 132 75 460 12
GA 132 100 460 9.5
GA 132 125 460 6.7
GA 132 150 460 6.7
GA 160 100 380 12
GA 160 125 380 9.5
GA 160 150 380 6.7
GA 160 100 440 12

124 9829 3178 62


Instruction book

Model Working pressure (psi) Supply voltage (V) Q40 (A)


GA 160 125 440 9.5
GA 160 150 440 6.7
GA 160 100 460 12
GA 160 125 460 9.5
GA 160 150 460 6.7

9829 3178 62 125


Instruction book

10.6 Compressor data


For high ambient temperature versions operating above 46 °C (115 °F) a derating factor has
been applied. The derating factor lowers the maximum compressor element speed/input power
(at constant maximum pressure) to avoid overheating of the compressor element, oil circuit and
motor.
Data for 50 Hz, 5.5 bar (79.8 psi) Full-Feature compressors

Units GA 90+ GA 110 GA 132


Effective working pressure bar(g) 5 5 5
Effective working pressure psi(g) 72.5 72.5 72.5
Motor shaft speed rpm 2980 2980 2980
Maximum effective working pressure bar(g) 5.3 5.3 5.3
Maximum effective working pressure psi(g) 76.9 76.9 76.9
Air-cooled compressor version
Total electrical power input, kW 107.4 129.7 155.2
maximum pressure
Total electrical power input, hp 144.0 173.9 208
maximum pressure
Mean sound pressure level dB(A) 76 79 78
Oil capacity (approx.) l 106 106 110
Oil capacity (approx.) US gal 28 28 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88
Water-cooled compressor version
Total electrical power input, kW 104.8 127.1 152.7
maximum pressure
Total electrical power input, hp 140.5 170.4 204.7
maximum pressure
Mean sound pressure level dB(A) 72 73 73
Oil capacity (approx.) l 94 94 98
Oil capacity (approx.) US gal 24.83 24.83 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46
Cooling medium flow l/s 1.6 1.9 2.3
Cooling medium flow cfm 3.4 4.0 4.9

126 9829 3178 62


Instruction book

Data for 50 Hz, 5.5 bar (79.8 psi) Pack compressors

Units GA 90+ GA 110 GA 132


Effective working pressure bar(g) 5 5 5
Effective working pressure psi(g) 72.5 72.5 72.5
Motor shaft speed rpm 2980 2980 2980
Maximum effective working pressure bar(g) 5.5 5.5 5.5
Maximum effective working pressure psi(g) 79.8 79.8 79.8
Air-cooled compressor version
Total electrical power input, kW 102.3 126.6 149.8
maximum pressure
Total electrical power input, hp 137.1 169.7 200.8
maximum pressure
Mean sound pressure level dB(A) 76 79 78
Oil capacity (approx.) l 106 106 110
Oil capacity (approx.) US gal 28 28 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88
Water-cooled compressor version
Total electrical power input, kW 101.3 123.7 149
maximum pressure
Total electrical power input, hp 135.8 165.8 199.7
maximum pressure
Mean sound pressure level dB(A) 73 73 73
Oil capacity (approx.) l 94 94 98
Oil capacity (approx.) US gal 24.83 24.83 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46
Cooling medium flow l/s 1.6 1.9 2.3
Cooling medium flow cfm 3.4 4.0 4.9

Data for 50 Hz, 7.5 bar (108.8 psi) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 7 7 7 7
Effective working pressure psi(g) 101.5 101.5 101.5 101.5
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 7.3 7.3 7.3 7.3
Maximum effective working pressure psi(g) 105.9 105.9 105.9 105.9
Air-cooled compressor version
Total electrical power input, kW 103.4 129.2 155 186.4
maximum pressure
Total electrical power input, hp 138.6 173.3 207.8 249.9
maximum pressure
Mean sound pressure level dB(A) 75 76 77 78

9829 3178 62 127


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 101.3 126.8 152.2 183.6
maximum pressure
Total electrical power input, hp 135.8 170.0 204 246.1
maximum pressure
Mean sound pressure level dB(A) 71 72 73 73
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.5 2 2.4 2.9
Cooling medium flow cfm 3.2 4.2 5.1 6.1

Data for 50 Hz, 7.5 bar (108.8 psi) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 7 7 7 7
Effective working pressure psi(g) 101.5 101.5 101.5 101.5
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 7.5 7.5 7.5 7.5
Maximum effective working pressure psi(g) 108.8 108.8 108.8 108.8
Air-cooled compressor version
Total electrical power input, kW 99.7 125 149.7 181.3
maximum pressure
Total electrical power input, hp 133.6 167.6 200.7 243
maximum pressure
Mean sound pressure level dB(A) 75 76 77 78
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 98.7 123.7 148.6 180.2
maximum pressure
Total electrical power input, hp 132.3 165.8 199.2 241.6
maximum pressure
Mean sound pressure level dB(A) 72 73 73 74
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89

128 9829 3178 62


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.5 1.9 2.3 2.8
Cooling medium flow cfm 3.2 4.0 4.9 5.9

Data for 50 Hz, 8.5 bar (123.8 psi) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 8 8 8 8
Effective working pressure psi(g) 116 116 116 116
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 8.3 8.3 8.3 8.3
Maximum effective working pressure psi(g) 120.4 120.4 120.4 120.4
Air-cooled compressor version
Total electrical power input, kW 105.7 129.1 153.9 186.7
maximum pressure
Total electrical power input, hp 141.7 173.1 206.3 250.3
maximum pressure
Mean sound pressure level dB(A) 75 76 79 78
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 103.6 126.9 151.7 183.8
maximum pressure
Total electrical power input, hp 138.9 170.1 203.4 246.4
maximum pressure
Mean sound pressure level dB(A) 71 72 73 73
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.4 2.9
Cooling medium flow cfm 3.4 4.2 5.1 6.1

9829 3178 62 129


Instruction book

Data for 50 Hz, 8.5 bar (123.8 psi) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 8 8 8 8
Effective working pressure psi(g) 116 116 116 116
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 8.5 8.5 8.5 8.5
Maximum effective working pressure psi(g) 123.8 123.8 123.8 123.8
Air-cooled compressor version
Total electrical power input, kW 102.2 125.3 149.6 181.1
maximum pressure
Total electrical power input, hp 137 168 200.5 242.8
maximum pressure
Mean sound pressure level dB(A) 75 76 79 78
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 101.1 124.2 148.4 180
maximum pressure
Total electrical power input, hp 135.5 166.5 198.9 241.3
maximum pressure
Mean sound pressure level dB(A) 72 73 73 74
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 1.9 2.3 2.8
Cooling medium flow cfm 3.4 4.0 4.9 5.9

130 9829 3178 62


Instruction book

Data for 50 Hz, 10 bar (145 psi) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 9.5 9.5 9.5 9.5
Effective working pressure psi(g) 137.8 137.8 137.8 137.8
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 9.8 9.8 9.8 9.8
Maximum effective working pressure psi(g) 142.1 142.1 142.1 142.1
Air-cooled compressor version
Total electrical power input, kW 106.2 128.6 154.3 187.4
maximum pressure
Total electrical power input, hp 142.4 172.4 206.8 251.2
maximum pressure
Mean sound pressure level dB(A) 75 76 79 78
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input kW 104 126.3 152.2 185
Total electrical power input hp 139.4 169.3 204 248
Mean sound pressure level dB(A) 71 71 73 73
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 1.9 2.4 2.9
Cooling medium flow cfm 3.4 4.0 5.1 6.1

Data for 50 Hz, 10 bar (145 psi) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 9.5 9.5 9.5 9.5
Effective working pressure psi(g) 137.8 137.8 137.8 137.8
Motor shaft speed rpm 2980 2980 2980 2980
Maximum effective working pressure bar(g) 10 10 10 10
Maximum effective working pressure psi(g) 145 145 145 145
Air-cooled compressor version
Total electrical power input, kW 102.8 125 150.5 182.9
maximum pressure
Total electrical power input, hp 137.8 167.6 201.7 245.2
maximum pressure
Mean sound pressure level dB(A) 75 76 79 78
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05

9829 3178 62 131


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 101.6 123.8 149.4 181.6
maximum pressure
Total electrical power input, hp 136.2 166 200.3 243.4
maximum pressure
Mean sound pressure level dB(A) 72 72 73 73
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 1.9 2.3 2.9
Cooling medium flow cfm 3.4 4.0 4.9 6.1

Data for 60 Hz, 75 psi (5.2 bar) Full-Feature compressors

Units GA 90+ GA 110 GA 132


Effective working pressure bar(g) 5 5 5
Effective working pressure psi(g) 72.5 72.5 72.5
Motor shaft speed rpm 1785 3580 3580
Maximum effective working pressure bar(g) 5.3 5.3 5.3
Maximum effective working pressure psi(g) 76.9 76.9 76.9
Air-cooled compressor version
Total electrical power input, kW 95.6 130.7 156.7
maximum pressure
Total electrical power input, hp 128.1 175.2 210.1
maximum pressure
Mean sound pressure level dB(A) 79 80 80
Oil capacity (approx.) l 106 106 110
Oil capacity (approx.) US gal 28 28 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88
Water-cooled compressor version
Total electrical power input, kW 92.9 128.1 154.1
maximum pressure
Total electrical power input, hp 124.5 171.7 206.6
maximum pressure
Mean sound pressure level dB(A) 74 75 75
Oil capacity (approx.) l 94 94 98
Oil capacity (approx.) US gal 24.83 24.83 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46
Cooling medium flow l/s 1.4 2 2.4

132 9829 3178 62


Instruction book

Units GA 90+ GA 110 GA 132


Cooling medium flow cfm 3.4 4.2 5.1

Data for 60 Hz, 75 psi (5.2 bar) Pack compressors

Units GA 90+ GA 110 GA 132


Effective working pressure bar(g) 5 5 5
Effective working pressure psi(g) 72.5 72.5 72.5
Motor shaft speed rpm 1785 3580 3580
Maximum effective working pressure bar(g) 5.5 5.5 5.5
Maximum effective working pressure psi(g) 79.8 79.8 79.8
Air-cooled compressor version
Total electrical power input, kW 90.6 125.6 151.3
maximum pressure
Total electrical power input, hp 121.4 168.3 202.8
maximum pressure
Mean sound pressure level dB(A) 79 80 80
Oil capacity (approx.) l 106 106 110
Oil capacity (approx.) US gal 28 28 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88
Water-cooled compressor version
Total electrical power input, kW 89.7 124.7 150.5
maximum pressure
Total electrical power input, hp 120.2 167.2 201.8
maximum pressure
Mean sound pressure level dB(A) 75 75 75
Oil capacity (approx.) l 94 94 98
Oil capacity (approx.) US gal 24.83 24.83 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46
Cooling medium flow l/s 1.4 1.9 2.3
Cooling medium flow cfm 3.4 4.0 4.9

Data for 60 Hz, 100 psi (6.9 bar) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 6.9 6.9 6.9 6.9
Effective working pressure psi(g) 100 100 100 100
Motor shaft speed rpm 1785 3580 3580 3580
Maximum effective working pressure bar(g) 7.2 7.2 7.2 7.2
Maximum effective working pressure psi(g) 104.4 104.4 104.4 104.4
Air-cooled compressor version
Total electrical power input, kW 104.6 130.1 156.8 186.8
maximum pressure

9829 3178 62 133


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Total electrical power input, hp 140.2 174.4 210.2 250.4
maximum pressure
Mean sound pressure level dB(A) 79 80 80 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 102.4 127.8 154.0 184.0
maximum pressure
Total electrical power input, hp 137.3 171.3 206.4 246.6
maximum pressure
Mean sound pressure level dB(A) 73 74 75 75
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.4 2.9
Cooling medium flow cfm 3.4 4.2 5.1 6.1

Data for 60 Hz, 100 psi (6.9 bar) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 6.9 6.9 6.9 6.9
Effective working pressure psi(g) 100 100 100 100
Motor shaft speed rpm 1785 3580 3580 3580
Maximum effective working pressure bar(g) 7.4 7.4 7.4 7.4
Maximum effective working pressure psi(g) 107.3 107.3 107.3 107.3
Air-cooled compressor version
Total electrical power input, kW 100.9 126 151.5 181.7
maximum pressure
Total electrical power input, hp 135.3 168.9 203.1 243.6
maximum pressure
Mean sound pressure level dB(A) 79 80 80 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 99.9 124.7 150.4 180.7
maximum pressure
Total electrical power input, hp 133.9 167.2 201.6 242.2
maximum pressure
Mean sound pressure level dB(A) 74 74.8 75.2 75.6

134 9829 3178 62


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.4 2.9
Cooling medium flow cfm 3.4 4.2 5.1 6.1

Data for 60 Hz, 125 psi (8.6 bar) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 8.6 8.6 8.6 8.6
Effective working pressure psi(g) 125 125 125 125
Motor shaft speed rpm 1785 3580 3580 3580
Maximum effective working pressure bar(g) 8.9 8.9 8.9 8.9
Maximum effective working pressure psi(g) 129.1 129.1 129.1 129.1
Air-cooled compressor version
Total electrical power input, kW 105.1 130 155 187.5
maximum pressure
Total electrical power input, hp 140.9 174.3 207.8 251.3
maximum pressure
Mean sound pressure level dB(A) 79 79 80 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 102.9 127.7 152.9 184.9
maximum pressure
Total electrical power input, hp 137.9 171.2 205 247.9
maximum pressure
Mean sound pressure level dB(A) 73.5 74.3 74.7 74.7
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.4 2.9
Cooling medium flow cfm 3.4 4.2 5.1 6.1

Data for 60 Hz, 125 psi (8.6 bar) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 8.6 8.6 8.6 8.6
Effective working pressure psi(g) 125 125 125 125
Motor shaft speed rpm 1785 3580 3580 3580

9829 3178 62 135


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Maximum effective working pressure bar(g) 9.1 9.1 9.1 9.1
Maximum effective working pressure psi(g) 132 132 132 132
Air-cooled compressor version
Total electrical power input, kW 101.6 126.3 150.9 182.2
maximum pressure
Total electrical power input, hp 136.2 169.3 202.3 244.2
maximum pressure
Mean sound pressure level dB(A) 79 79 80 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 100.5 125.1 149.9 180.9
maximum pressure
Total electrical power input, hp 134.7 167.7 200.9 242.5
maximum pressure
Mean sound pressure level dB(A) 74 74.8 75.2 75.2
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.4 2.9
Cooling medium flow cfm 3.4 4.2 5.1 6.1

Data for 60 Hz, 150 psi (10.4 bar) Full-Feature compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 10.4 10.4 10.4 10.4
Effective working pressure psi(g) 150 150 150 150
Motor shaft speed rpm 1785 3580 3580 3580
Maximum effective working pressure bar(g) 10.7 10.7 10.7 10.7
Maximum effective working pressure psi(g) 155.2 155.2 155.2 155.2
Air-cooled compressor version
Total electrical power input, kW 105 128.8 150.9 187.8
maximum pressure
Total electrical power input, hp 140.8 172.7 202.3 251.7
maximum pressure
Mean sound pressure level dB(A) 79 79 79 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version

136 9829 3178 62


Instruction book

Units GA 90+ GA 110 GA 132 GA 160


Total electrical power input, kW 102.9 126.7 148.8 185.6
maximum pressure
Total electrical power input, hp 137.9 169.8 199.5 248.8
maximum pressure
Mean sound pressure level dB(A) 73.5 73.5 74.3 74.7
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 2 2.3 2.9
Cooling medium flow cfm 3.4 4.2 4.9 6.1

Data for 60 Hz, 150 psi (10.4 bar) Pack compressors

Units GA 90+ GA 110 GA 132 GA 160


Effective working pressure bar(g) 10.4 10.4 10.4 10.4
Effective working pressure psi(g) 150 150 150 150
Motor shaft speed rpm 1785 3580 3580 3580
Maximum effective working pressure bar(g) 10.9 10.9 10.9 10.9
Maximum effective working pressure psi(g) 158.1 158.1 158.1 158.1
Air-cooled compressor version
Total electrical power input, kW 101.7 125.4 147.3 183.6
maximum pressure
Total electrical power input, hp 136.3 168.1 197.5 246.1
maximum pressure
Mean sound pressure level dB(A) 79 79 79 80
Oil capacity (approx.) l 106 106 110 110
Oil capacity (approx.) US gal 28 28 29.05 29.05
Oil capacity (approx.) Imp gal 23.32 23.32 24.2 24.2
Oil capacity (approx.) cu.ft 3.74 3.74 3.88 3.88
Water-cooled compressor version
Total electrical power input, kW 100.6 124.3 146.3 182.5
maximum pressure
Total electrical power input, hp 134.9 166.6 196.1 244.6
maximum pressure
Mean sound pressure level dB(A) 74 74 74.8 75.2
Oil capacity (approx.) l 94 94 98 98
Oil capacity (approx.) US gal 24.83 24.83 25.89 25.89
Oil capacity (approx.) Imp gal 20.68 20.68 21.56 21.56
Oil capacity (approx.) cu.ft 3.32 3.32 3.46 3.46
Cooling medium flow l/s 1.6 1.9 2.3 2.9
Cooling medium flow cfm 3.4 4 4.9 6.1

9829 3178 62 137


We stand by our responsibilities towards our customers, towards the environment and
the people around us.
We make performance stand the test of time.
This is what we call - Sustainable Productivity.

Atlas Copco Wuxi


Oil-free Air Division

No. 9829 3178 62 / 2019 - 12 - Printed in Atlas Copco Wuxi. All rights reserved. Designs and specifications are subject to change without notice or obligation.

You might also like