Spec Sheet
Spec Sheet
Diesel generator
set
6L9.5 series engine
50HZ
60HZ
power.cummins.com
©2017 Cummins Inc. | S-6291-EN (05/17)
Generator set specifications
Governor regulation class ISO 8528
Voltage regulation, No load to Full load 1%
Random voltage variation 1%
Frequency regulation Isochronous
Random frequency variation ± 0.25%
Engine specifications
Design 4 cycle, in-line, turbo charged and after cooled
Bore 116.5 mm (4.59 in.)
Stroke 148 mm (5.83 in.)
Displacement 9.5 L ( 579.7in3)
Cylinder block Cast iron, 6 cylinder
Battery capacity 96 Ah
Battery charging alternator 70 amps
Starting voltage 24 volts, negative ground
Fuel system Direct injection
Fuel filter Spin-on fuel filters with water separator
Air cleaner type Dry replaceable element
Lube oil filter type(s) Spin-on full flow filters
Standard cooling system 122 ºF (50 ºC) at 50Hz,131 ºF (55 ºC) at 60Hz ambient radiator
Alternator specifications
Design Brushless, single bearing, revolving field
Stator 2/3 pitch
Rotor Direct coupled by flexible disc
Insulation system Class H
Standard temperature rise 150-163°C standby
Exciter type Self-excited or Permanent Magnet Generator (PMG)
Phase rotation A (U), B (V), C (W)
Alternator cooling Direct drive centrifugal blower fan
AC waveform Total Harmonic Distortion (THDV) No load <1.5%. Non distorting balanced linear load <5%
Telephone Influence Factor (TIF) TIF <50
Telephone Harmonic Factor (THF) THF <2%
Available voltages
50 Hz Line – Line /Line – Neutral 60 Hz Line – Line /Line – Neutral
• 220/127 • 208/220
• 380/220 • 220/127
• 400/230 • 440/255
• 416/240 • 480/277
*Derate may be applicable at this voltage. Please consult factory for details.
*Note: Some options may not be available on all models - consult factory for availability.
power.cummins.com
©2017 Cummins Inc. | S-6291-EN (05/17)
Control system
PowerCommand® 1.2 – The PowerCommand® Service adjustments – The HMI includes provisions
control system is a microprocessor- based generator for adjustment of generator set control functions.
set monitoring, metering and control system designed Adjustments are protected by a password. Functions
to meet the demands of today’s engine driven genera- include:
tor sets. The integration of all control functions into a • Engine speed governor adjustments.
single control system provides enhanced reliability • Voltage regulation adjustments.
and performance compared to conventional generator • Cycle cranking.
set control systems. These control systems have been • Configurable fault set up.
designed and tested to meet the harsh environment in • Configurable output set up.
which gensets are typically applied. • Meter calibration.
• Units of measurement.
Description
The PowerCommand® generator set control is suitable Protective functions
for use on a wide range of generator sets in non- Protective functions include:
paralleling applications. The PowerCommand control • Battle short mode.
is compatible with shunt or PMG excitation style. It is • Configurable alarm and status inputs.
suitable for use with connectable or non reconnect- • Emergency stop.
able generators, and it can be configured for any • Hydro mechanical fuel system engine protection.
frequency, voltage and power connection from • Overspeed shutdown.
120-600 VAC line-to-line. • Low lube oil pressure warning.
Power for this control system is derived from the • High lube oil temperature warning/shutdown.
generator set starting batteries. The control functions • High engine temperature warning/shutdown.
over a voltage range from 8 VDC to 30 VDC. • Low coolant temperature warning.
• Sensor failure indication.
Major features • Full authority electronic engine protection.
• General engine protection.
• 128 x 128 pixels graphic LED backlight LCD. • Low and high battery voltage warning.
• Digital voltage regulation. Single phase full wave • Weak battery warning.
SCR type regulator compatible with either shunt or • Fail to start (overcrank) shutdown.
PMG systems. • Fail to crank.
• Digital engine speed governing (where applicable). • Cranking lockout.
• Generator set monitoring and protection.
• Advanced over-current protection. Alternator protection
• Modbus® interface for interconnecting to customer • High AC voltage shutdown (59).
equipment. • Low AC voltage shutdown (27).
• Warranty and service. Backed by a comprehensive • Overcurrent warning/shutdown.
warranty and worldwide distributor service network. • Under frequency shutdown (81 u).
• Certification. Suitable for use on generator sets that • Over frequency shutdown/warning (81 o).
are designed, manufactured, tested and certified to • Loss of sensing voltage shutdown.
relevant UL, NFPA, ISO, IEC Mil Std., CE and CSA • Field overload shutdown.
standards.
Field control interface
Base control functions
Input signals to the base control include:
HDMI capability. • Remote start.
Operator adjustments - The HMI includes provi- • Local and emergency stop.
sions for many set up and adjustment functions. • Configurable inputs: Control includes (4) input
Data logs - Includes engine run time, controller on signals from customer.
time, number of start attempts.
Fault history - Provides a record of the most recent Output signals from the PowerCommand
fault conditions with control hours time stamp. Up to control include:
10 events are stored in the control non-volatile • Configurable relay outputs: Control includes (2) relay
memory. output contacts rated at 2 A.
Alternator data
• Voltage (single or three phase line-to-line and line-to
neutral).
• Current (single or three phase).
• KVA (three phase and total).
PowerCommand 1.2®
• Frequency. control operator /
display panel
Engine data
• Starting battery voltage.
• Engine speed.
• Engine temperature.
• Engine oil pressure.
power.cummins.com
©2017 Cummins Inc. | S-6291-EN (05/17)
Ratings definitions
Emergency Standby Power (ESP):
Applicable for supplying power to varying electrical
load for the duration of power interruption of a reliable
utility source. Emergency Standby Power (ESP) is in
accordance with ISO 8528. Fuel stop power in accor-
dance with ISO 3046, AS 2789, DIN 6271 and BS
5514.
Limited-Time Running Power (LTP):
Applicable for supplying power to a constant electrical
load for limited hours. Limited Time Running Power
This outline drawing is to provide representative configuration
(LTP) is in accordance with ISO 8528.
details for model series only.
Prime Power (PRP):
Applicable for supplying power to varying electrical See respective model data sheet for specific model outline
drawing number.
load for unlimited hours. Prime Power (PRP) is in
accordance with ISO 8528. Ten percent overload
capability is available in accordance with ISO 3046, Do not use for installation design
AS 2789, DIN 6271 and BS 5514.
Base Load (Continuous) Power (COP):
Applicable for supplying power continuously to a constant electrical load for unlimited hours. Continuous Power
(COP) in accordance with ISO 8528, ISO 3046, AS 2789, DIN 6271 and BS 5514.
C275D5B 2800 1100 1871 2282 2738 4256 1424 2216 3640 4190
C300D5B 2800 1100 1871 2495 2951 4256 1424 2216 3853 4403
C330D5B 2800 1100 1871 2495 2951 4256 1424 2216 3853 4403
C350D5B 2800 1100 1871 2579 3035 4256 1424 2216 3937 4487
C250D6B 2800 1100 1871 2282 2738 4256 1424 2216 3640 4190
C275D6B 2800 1100 1871 2579 3035 4256 1424 2216 3937 4487
* Note: Weights represent a set with standard features. See outline drawings for weights of other configurations.