HASSI Project Nº: 10745

MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 1 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING


PROCEDURE

Note: Document issued on previous phase with Rev 1 under transmittal number 80080-CON-OWN-
TRA-00643 on 22/10/2020. Approval received on 23/11/2021. Issued to update JV related
information (Logo, …)

2 09/10/2024 ISSUED FOR DESIGN AML YAZ ANH

1 20/10/2020 ISSUED FOR DESIGN JNH YL EBL

0 01/07/2020 ISSUED FOR REVIEW JNH YL EBL

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 2 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

INDEX
1 PURPOSE ................................................................................................................................. 5
2 SCOPE ...................................................................................................................................... 5
3 DEFINITIONS AND ACRONYMS .............................................................................................. 5
4 REFERENCES .......................................................................................................................... 5
4.1 Project Specifications ..................................................................................................... 5
5 METHODOLOGY ...................................................................................................................... 5
5.1 LOOP NAMES and loop order range .............................................................................. 8
LOOP ORDER RANGE ................................................................................................................ 9
5.2 ANALYSERS .................................................................................................................. 10
5.2.1 pH Analyzer ............................................................................................................... 10
5.2.2 Moisture Analyzer ...................................................................................................... 11
5.2.3 Reid Vapor Pressure Analyzer................................................................................... 12
5.2.4 Dissolved O2 Analyzer .............................................................................................. 13
5.2.5 Oil in water Analyzer .................................................................................................. 14
5.2.6 Chlorine Analyzer ...................................................................................................... 15
5.2.7 Total disolved solids (conductivity) Analyzer .............................................................. 16
5.2.8 Gas Chromatograph .................................................................................................. 17
5.2.9 H2 Analyzer ............................................................................................................... 18
5.2.10 CH4 Analyzer ............................................................................................................ 19
5.2.11 CO2 Analyzer ............................................................................................................ 20
5.2.12 Other Analyzer........................................................................................................... 21
5.3 FLOW INSTRUMENT ..................................................................................................... 22
5.3.1 Flow Orifice Plate ...................................................................................................... 22
5.3.2 Flow Orifice Plate with Control Valve ......................................................................... 23
5.3.3 Vortex Flow Meter ..................................................................................................... 24
5.3.4 Coriolis Mass Flow Meter .......................................................................................... 24
5.3.5 Coriolis Mass Flow Meter with remote transmitter ...................................................... 25
5.3.6 Rotameter Type Flow Meter ...................................................................................... 25
5.3.7 Magnetic Flow Meter ................................................................................................. 26
5.3.8 Ultrasonic Flow Meter ................................................................................................ 26
5.3.9 Ultrasonic Flow Meter with remote transmitter ........................................................... 27
5.3.10 Flow Orifice Plate, ESD input..................................................................................... 28
5.3.11 Flow Orifice with DCS/ESD control ............................................................................ 29
5.3.12 Positive Displacement Flow Meter ............................................................................. 30
5.3.13 Pitot tube flow transmeter .......................................................................................... 31
5.3.14 Venturi Flow Transmitter ............................................................................................ 32
5.3.15 V-Cone Flow Meter .................................................................................................... 33
5.3.16 Flow Nozzle ............................................................................................................... 34
5.3.17 Turbine Flow Meter .................................................................................................... 35
5.3.18 Thermal Mass Flow Meter ......................................................................................... 36
5.3.19 Rotameter Type Flow Transmeter ............................................................................. 37
5.3.20 Restriction Orifice ...................................................................................................... 37
5.3.21 Vortex Flow Transmitter with Control Valve ............................................................... 38
5.3.22 Venturi Flow Transmitter with Control Valve .............................................................. 39
5.3.23 Control Loop with Two Control Valves (Split Range) ................................................. 40
5.3.24 Vortex Flow Transmitter with Two Control Valve ........................................................ 41
5.3.25 Venturi Flow Transmitter with Two Control Valve ....................................................... 42

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 3 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.26 Wedge Flow Meter .................................................................................................... 43


5.3.27 Pitot Tube Flow Transmitter with Control Valve ......................................................... 44
5.3.28 Pitot Tube Flow Transmitter, ESD input ..................................................................... 45
5.4 LEVEL INSTRUMENT .................................................................................................... 46
5.4.1 Level Transmitter D/P Type ....................................................................................... 46
5.4.2 Level Transmitter D/P Type with Control Valve .......................................................... 47
5.4.3 Level Gauge – Magnetic ............................................................................................ 48
5.4.4 Guided Wave Radar Type ......................................................................................... 49
5.4.5 Guided Wave Radar Type with Control Valve ............................................................ 50
5.4.6 Radar Type................................................................................................................ 51
5.4.7 Radar Type with Control Valve .................................................................................. 52
5.4.8 Nuclear Type ............................................................................................................. 53
5.4.9 Nuclear Type with Control Valve ................................................................................ 54
5.4.10 GWR 2oo3 ESD input ................................................................................................ 55
5.4.11 Level Transmitter Displacer ....................................................................................... 56
5.4.12 Level Transmitter – Radar Type ESD Input ............................................................... 57
5.4.13 Level Transmitter D/P Type – ESD Input ................................................................... 58
5.5 PRESSURE INSTRUMENT ............................................................................................ 59
5.5.1 Pressure Gauge ........................................................................................................ 59
5.5.2 Differential Pressure Gauge....................................................................................... 59
5.5.3 Differential Pressure Transmitter ............................................................................... 60
5.5.4 Single Pressure Transmitter ...................................................................................... 60
5.5.5 Single Pressure Transmitter with Control Valve ......................................................... 61
5.5.6 Single Pressure Transmitter 2XCV ............................................................................ 62
5.5.7 Differential Pressure with Control Valve ..................................................................... 63
5.5.8 Single Pressure Transmitter ESD Input ..................................................................... 64
5.5.9 Single Pressure Transmitter 2oo3 ESD Input ............................................................ 65
5.5.10 Differential Pressure Transmitter ESD Input .............................................................. 66
5.6 TEMPERATURE INSTRUMENT ..................................................................................... 67
5.6.1 Temperature Instrument – Dual Element ................................................................... 67
5.6.2 Single Temperature Transmitter with Control Valve ................................................... 68
5.6.3 Temperature Gauge .................................................................................................. 69
5.6.4 Temperature Instrument – Skin Type......................................................................... 70
5.6.5 Temperature Instrument – 2 out of 3 ESD Input......................................................... 71
5.6.6 Temperature Instrument – TC ESD Input................................................................... 72
5.6.7 Temperature Instrument – TC.................................................................................... 73
5.7 CONTROL / ON-OFF VALVE ......................................................................................... 74
5.7.1 ON/OFF Sequential Valve – Single Acting (From DCS) -TYPICAL 5 ......................... 74
5.7.2 Hand Operated ON/OFF Valve – Single Acting- TYPICAL TBD ................................ 75
5.7.3 Hand Operated ON/OFF Valve – Double Acting- TYPICAL TBD ............................... 76
5.7.4 DCS Operated ON/OFF Valve – (Double Acting)....................................................... 77
5.7.5 Pressure Relief Valve ................................................................................................ 78
5.7.6 Pressure & Vacuum Safety Valve .............................................................................. 78
5.7.7 Vacuum Safety Valve ................................................................................................ 79
5.7.8 Emergency Shutdown Valve (ESV)-TYPICAL 3 (Or TYP. 3-R, 3-ST) ........................ 80
5.7.9 Emergency Shutdown Valve (ESV) with dual Solenoid TYPICAL 4 (Or TYP. 4-R, 4-
ST) 81
5.7.10 Emergency Isolation Valve (EIV) with dual Solenoid and Partial Stroke Test –
TYPICAL 1 (Or TYP. 1-R, 1-ST) .............................................................................................. 82
5.7.11 Emergency De-Pressurization Valve (EDV) with two Solenoids 1oo2 Voting (TYPICAL
2H) or 2oo2 (TYPICAL 2)......................................................................................................... 84

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 4 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.12 Motor Operated Valve- TYPICAL MOV 1 – MOV operated by DCS ........................... 86
5.7.13 Motor Operated Valve- TYPICAL MOV 2 – MOV operated by DCS with emergency
close from ESD. ....................................................................................................................... 87
5.7.14 Motor Operated Valve- TYPICAL MOV 3 MOV operated by DCS with emergency
close 88
from ESD and from operator console. ...................................................................................... 88
5.7.15 Motor Operated Valve- TYPICAL MOV 5 MOV operated by DCS with emergency
close from ESD and feedback signals connected to ESD ........................................................ 89
5.7.16 Manual Indication Controller with Control Valve ......................................................... 90
5.7.17 Self-Regulator Valve (PCV) ....................................................................................... 90
5.7.18 Manual Indication Controller with Motor Operated Control Valve ............................... 91
5.8 HAND SWITCH ............................................................................................................... 92
5.8.1 ESD Hand Switch Local............................................................................................. 92
5.9 MOTOR ........................................................................................................................... 93
5.9.1 Motor with DCS Control TYPICAL M.4....................................................................... 93
5.9.2 Motor with DCS Control and ESD Trip (General)- TYPICAL M.1 ............................... 94
5.9.3 Motor with DCS Control and ESD Trip (General) and SPARE pump LOGIC- TYPICAL
M.5 95
5.9.4 Motor with DCS Control and ESD Trip (General) and Speed Control- TYPICAL M.6 . 96
5.9.5 Motors not linked to logic (only monitoring) ................................................................ 97
5.9.6 Motors linked to logic ................................................................................................. 98
5.9.7 Fixed Speed Fans- Without VFD ............................................................................... 99
5.9.8 Fans with Variable Speed Driver (VFD) ................................................................... 100
5.10 PROCESS SAFETY ...................................................................................................... 101
5.10.1 Flame Detector ........................................................................................................ 101
5.10.2 Gas Detector- Flammable Gas Detector – Infrared Open Path ................................ 102
5.10.3 Gas Detector- Flammable Gas Detector – Infrared Open ........................................ 103
5.10.4 Gas Detector- Hydrogen .......................................................................................... 104
5.10.5 Gas Detector- Toxic Gas (H2S/SO2/CL2)................................................................ 105
5.10.6 Gas Detector- Flammable Gas Detector – Ultrasonic .............................................. 106
5.10.7 Flame Detector- UV/IR ............................................................................................ 107
5.10.8 Manual Call Point- Field Mounted ............................................................................ 108
5.10.9 Smoke Detector Ionization ....................................................................................... 109
5.10.10 Smoke Detector (Optical) ........................................................................................ 110
5.10.11 Heat Detector-Point Type ........................................................................................ 111
5.10.12 Toxic Gas Visual Alarm Beacon (Blue Lamp) .......................................................... 112
5.10.13 Fire Visual Alarm Beacon (Red Lamp) ..................................................................... 113
5.10.14 Flammable gas Visible Beacon (Yellow Lamp) ........................................................ 114
5.10.15 Normal Condition Visible Beacon (Green Lamp)...................................................... 115
5.10.16 Fire General Audible ................................................................................................ 116

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 5 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

1 PURPOSE

This document is aimed to describe the typical loops to be used for SmartPlant P&ID and SPI. It
will be used to achieve consistency of data entry in SPI between companies.

2 SCOPE

This document is applicable to all detail of instrument I/O types and P&ID legends, while
preparation of SPI instrument index to be issued for the PROJECT.

3 DEFINITIONS AND ACRONYMS

• PROJECT: REALISATION D’UNE RAFFINERIE DE PETROLE BRUT A CONVERSION


PROFONDE A HAOUD EL HAMRA-HASSI MESSAOUD ALGERIE
• OWNER: SONATRACH
• CONTRACTOR: UTE TR-SE HASSI MESSAOUD PROJECT (JOINT VENTURE between
TECNICAS REUNIDAS, S. A. and SINOPEC).
• SUPPLIER/VENDOR: The party that bids to sell, sells, manufactures, fabricates or
otherwise produces or supplies the equipment and/or goods and services.
• SUBCONTRACTOR: The party that bids to supply construction, assembly or other
services according to the agreed Subcontract.
• MAY / CAN: Is used where alternatives/actions are equally acceptable.
• SHOULD: Is used where provision is preferred.
• SHALL / WILL / MUST: Is used where a provision is mandatory/vital.
• SPI: SMARTPLANT INSTRUMENTATION

4 REFERENCES
4.1 PROJECT SPECIFICATIONS

CODE TITLE

80080-ED-INS-0000-PRC-001 SMARTPLANT INSTRUMENTATION (SPI)


COORDINATION PROCEDURE

5 METHODOLOGY

Instruments are divided in categories in order to make it easier to use.


Regarding alarms, if they are configured in an instrument their set points will be included in the
properties of the instrument.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 6 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

All alarms defined as independient instruments in P&ID must be included as an individual


instrument in SPI, following the notes in each typical loop below. Note that if alarms are part of
DCS device/transmitter will not ne included as individual instrument.
Instrument type used with this purpose are:

PROCESS TAG
FUNCTION INSTRUMENT TYPE
FUNCTION

Analyzer AAH Analyzer High Alarm

Analyzer AAHH Analyzer High High Alarm

Analyzer AAL Analyzer Low Alarm

Analyzer AALL Analyzer Low Low Alarm

Flow FAH Flow Alarm High

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 7 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

PROCESS TAG
FUNCTION INSTRUMENT TYPE
FUNCTION

Flow FAHH Flow Alarm High High

Flow FAL Flow Alarm Low

Flow FALL Flow Alarm Low Low

Level LAH Level Alarm High

Level LAHH Level Alarm High High

Level LAL Level Alarm Low

Level LALL Level Alarm Low Low

Pressure PAH Pressure Alarm High

Pressure PAHH Pressure Alarm High High

Pressure PAL Pressure Alarm Low

Pressure PALL Pressure Alarm Low Low

Pressure PDAH Differential Pressure Alarm High

Pressure PDAHH Differential Pressure Alarm High High

Pressure PDAL Differential Pressure Alarm Low

Pressure PDALL Diff. Press. Alarm Low Low

Temperature TAH Temperature Alarm High

Temperature TAHH Temperature Alarm High High

Temperature TAL Temperature Alarm Low

Temperature TALL Temperature Alarm Low Low

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 8 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.1 LOOP NAMES AND LOOP ORDER RANGE

Loop names will use normally one letter related to the function of the elements that it contains as per
ISA-5.1. Loop names will follow same naming convention as instruments but will have some
exceptions to avoid conflicts in some cases where the same letter can be used for more than one
function, see above table:

PROCESS FUNCTION LOOP NAME LETTER ID

Analyzer A

Flame detector BMS B

Air Cooler EM

Control Valve EDV

Control Valve EIV

Control Valve ESV

Motor Operated Valve MOV

Flow F

Hand operation/Hand switches H

Current I

Level L

Pressure P

Differencial Pressure PD

Pressure Limiting Valve PLV

Pressure safety relief Valve PSV

Press./Vac Rupture Disk PSE

Motor Pump PM

Pressure Vacuum Valve PVV

Restriction orifice RO

Speed S

Temperature T

Thermal relief Valve TSV

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 9 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

PROCESS FUNCTION LOOP NAME LETTER ID

Undefined function X

Position Z

LOOP ORDER RANGE

Loop sequence criteria must follow:

LOOP ORDER RANGE INSTRUMENTS THAT IT APPLIES


10-19 Field elements (tags without signal propagated)
20-29 Field instruments with signal (ex: gauges, transmitters)
30-39 DCS Indications, switches, signal converters, controllers
40-49 HH, H, L LL Alarms
50-59 Control Valves, PSV, Emergency Valves, MOV
60-69 Solenoid Valves, Hand Switches, Pump/Motor/Fans related signals

Limit switches, position indicators, position alarms, push buttons


70-79
and other valves related elements

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 10 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2 ANALYSERS

5.2.1 pH Analyzer

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

AT pH Analyzer HART AI DCS Field 20 -

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 11 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.2 Moisture Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

AE Analyzer Element - - Field 10 -

AT H2O Analyzer HART AI DCS Field 20 -

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 12 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.3 Reid Vapor Pressure Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Reid Vapor
AT Pressure Analyzer HART AI DCS Field 20 -
Transmitter
Reid Vapor
AI SOFT DCS - 30 -
Pressure Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 13 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.4 Dissolved O2 Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

AT O2 Analyzer HART AI DCS Field 20 -

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 14 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.5 Oil in water Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Oil in Water
AT HART AI DCS Field 20 -
Analyzer

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 15 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.6 Chlorine Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

AT Cl2 Analyzer HART AI DCS Field 20 -

AI Analyzer Indication SOFT DCS - 30 .

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 16 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.7 Total disolved solids (conductivity) Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Conductivity
AT HART AI DCS Field 20 -
Analyzer

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 17 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.8 Gas Chromatograph

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
G. Chromatograph
AT HART AI DCS Field 20 -
Analyzer

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 18 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.9 H2 Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
H2 Analyzer
AT HART AI DCS Field 20 -
Transmitter

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 19 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.10 CH4 Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
CH4 Analyzer
AT HART AI DCS Field 20 -
Transmitter

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 20 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.11 CO2 Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

AT CO2 Analyzer HART AI DCS Field 20 -

CO2 Analyzer
AI SOFT DCS - 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 21 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.2.12 Other Analyzer

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
X Analyzer
AT HART AI DCS Field 20 -
Transmitter

AI Analyzer Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 22 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3 FLOW INSTRUMENT

Only orifice plates,Nozzle, V-Cone and venturi primary elements are represented, please check
it before create an element in SPI.
5.3.1 Flow Orifice Plate

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Orifice Plate - - Field 10 -

FT Flow Transmitter HART AI DCS Field 20 -

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 23 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.2 Flow Orifice Plate with Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Orifice Plate - - Field 10 -

FT Flow Transmitter HART AI DCS Field 20 -

FI Local Indicator - - Field 21 Suffix L

FIC Valve Controller SOFT DCS - 30

FV Control Valve HART AO DCS Field 50

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS Field 22
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 24 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.3 Vortex Flow Meter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Vortex Flow Integrated Flow
FT HART AI DCS Field 20
Transmitter Meter

FI Flow Indication SOFT DCS - 30 -

5.3.4 Coriolis Mass Flow Meter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Integrated Flow
FT Coriolis Flowmeter HART AI DCS Field 20
Meter
Flow Indication

FI SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 25 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.5 Coriolis Mass Flow Meter with remote transmitter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Integrated Flow
FT Coriolis Flowmeter HART AI DCS Field 20
Meter

FI Flow Indication SOFT DCS - 30 -

5.3.6 Rotameter Type Flow Meter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FG Flow Gauge - - Field 10 Local Gauge

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 26 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.7 Magnetic Flow Meter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Integrated Flow
FT Magnetic Flowmeter HART AI DCS Field 20
Meter

FI Flow Indication SOFT DCS - 30 -

5.3.8 Ultrasonic Flow Meter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Integrated Flow
FT Ultrasonic Flowmeter HART AI DCS Field 20
Meter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 27 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.9 Ultrasonic Flow Meter with remote transmitter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Flow Element - - Field 10 -

Remote
FT Ultrasonic Flowmeter HART AI DCS Field 20
transmitter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 28 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.10 Flow Orifice Plate, ESD input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Orifice Plate - - Field 10 -

FT Flow Transmitter HART AI-R ESD Field 20 -

Alarms as
identified on
Flow Indication
FI SOFT DCS ESD 30 P&ID, FALL in
this case (Loop
order 40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 29 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.11 Flow Orifice with DCS/ESD control

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Orifice Plate - - Field 10 -

FT Flow Transmitter HART AI DCS Field 20 -

FI Local Indicator - - Field 21 Suffix L

Only if required in
FIC Valve Controller SOFT DCS - 30
P&ID

Only if required in
FV Control Valve HART AO DCS Field 50
P&ID
Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS Field 23
P&ID

FT Flow Transmitter HART AI-R ESD Field 22 -

Alarms as
identified on
Flow Indication
FI SOFT DCS ESD 31 P&ID, FALL in this
case (Loop order
40,41,42…)

Note 1: Similar representation for any other flow element where the DCS and ESD share the same
flow element.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 30 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.12 Positive Displacement Flow Meter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Positive Integrated Flow
FT HART AI DCS Field 20
Displacement Meter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 31 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.13 Pitot tube flow transmeter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Pitot Tube - - Field 10 -

Integrated Flow
FT Flow Transmitter HART AI DCS Field 20
Meter

FI Local Indicator - - Field 21 Suffix L

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 32 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.14 Venturi Flow Transmitter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Venturi - - Field 10 -

DP – Flow
FT Flow Transmitter HART AI DCS Field 20
Transmitter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 33 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.15 V-Cone Flow Meter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE V Cone - - Field 10 -

DP – Flow
FT Flow Transmitter HART AI DCS Field 20
Transmitter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 34 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.16 Flow Nozzle

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Flow Nozzle - - Field 10 -

DP – Flow
FT Flow Transmitter HART AI DCS Field 20
Transmitter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 35 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.17 Turbine Flow Meter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Turbine Flow Integrated Flow
FQIT HART AI DCS Field 20
Transmitter Meter

Flow Totalizing
FQI SOFT DCS - 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 36 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.18 Thermal Mass Flow Meter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Mass Flow Integrated Flow
FT HART AI DCS Field 20
Transmitter Meter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 37 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.19 Rotameter Type Flow Transmeter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Integrated Flow
FT Rotameter HART AI DCS Field 20
Meter

FI Flow Indication SOFT DCS - 30 -

5.3.20 Restriction Orifice

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
RO Restriction Orifice - - Field 10 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 38 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.21 Vortex Flow Transmitter with Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Vortex Flow Integrated Flow
FT HART AI DCS Field 20
Transmitter Meter

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 -

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 39 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.22 Venturi Flow Transmitter with Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Venturi - - Field 10 -

Integrated Flow
FT Flow Transmitter HART AI DCS Field 20
Meter

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 -

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 40 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.23 Control Loop with Two Control Valves (Split Range)

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Orifice Plate - - Field 10 -

FT Flow Transmitter HART AI DCS Field 20 -

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 Suffix A

FV Control Valve HART AO DCS Field 51 Suffix B

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 41 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.24 Vortex Flow Transmitter with Two Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Vortex Flow Integrated Flow
FT HART AI DCS Field 20
Transmitter Meter

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 Suffix A

FV Control Valve HART AO DCS Field 51 Suffix B

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 42 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.25 Venturi Flow Transmitter with Two Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE
Integrated Flow
FE Venturi - - Field 10
Meter

FT Flow Transmitter HART AI DCS Field 20 -

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 Suffix A

FV Control Valve HART AO DCS Field 51 Suffix B

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 43 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.26 Wedge Flow Meter

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Wedge - - Field 10 -

Integrated Flow
FT Flow Transmitter HART AI DCS Field 20
Meter

FI Flow Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 44 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.27 Pitot Tube Flow Transmitter with Control Valve

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

FE Pitot Tube - - Field 10 -

Integrated Flow
FT Flow Transmitter HART AI DCS Field 20
Meter

FIC Valve Controller SOFT DCS - 30 -

FV Control Valve HART AO DCS Field 50 -

Only if required in
FZI Position Indication SOFT DCS - -
P&ID
Only if required in
FZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 45 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.3.28 Pitot Tube Flow Transmitter, ESD input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

FE Pitot Tube - - Field 10 -

Integrated Flow
FT Flow Transmitter HART AI-R ESD Field 20
Meter
Alarms as
identified on P&ID,
FI Flow Indication SOFT DCS ESD 30 FALL in this case
(Loop order
40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 46 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4 LEVEL INSTRUMENT

5.4.1 Level Transmitter D/P Type

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

Level Transmitter
LT HART AI DCS Field 20 -
(Diff. Pressure)

LI Level Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 47 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.2 Level Transmitter D/P Type with Control Valve

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Level Transmitter
LT HART AI DCS Field 20 -
(Diff. Pressure)

Level Indicating
LIC SOFT DCS - 30 -
Controller

LV Level Control Valve HART AO DCS Field 50 -

Only if required in
LZI Position Indication SOFT DCS - -
P&ID

Only if required in
LZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 48 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.3 Level Gauge – Magnetic

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

Magnetic Level
LG - - Field 10 -
Gauge

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 49 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.4 Guided Wave Radar Type

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Level Transmitter
LT HART AI DCS Field 20 -
(GWR)

LI Level Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 50 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.5 Guided Wave Radar Type with Control Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Level Transmitter
LT HART AI DCS Field 20 -
(GWR)

LI Local Indicator - - Field 21 Suffix L

Level Indicating
LIC SOFT DCS - 30 -
Controller

LV Level Control Valve HART AO DCS Field 50 -

Only if required in
LZI Position Indication SOFT DCS - -
P&ID
Only if required in
LZT Position Transmiter HART AI DCS On Valve 22
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 51 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.6 Radar Type

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Level Transmitter
LT HART AI DCS Field 20 -
(Radar)

LI Level Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 52 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.7 Radar Type with Control Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Level Transmitter
LT HART AI DCS Field 20 -
(Radar)

LI Local indicator - - Field 21 Suffix L

Level Indicating
LIC SOFT DCS - 30 -
Controller

LV Level Control Valve HART AO DCS Field 50 -

Only if required in
LZI Position Indication SOFT DCS - -
P&ID
Only if required in
LZT Position Transmiter HART AI DCS On Valve 22
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 53 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.8 Nuclear Type

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

LX Nuclear Source - - Field 10 -

Level Transmitter
LT HART AI DCS Field 20 -
(Nuclear)

LI Level Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 54 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.9 Nuclear Type with Control Valve

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

LX Nuclear Source - - Field 10 -

Level Transmitter
LT HART AI DCS Field 20 -
(Nuclear)
Level Indicating
LIC SOFT DCS - 30 -
Controller

LV Level Control Valve HART AO DCS Field 50 -

Only if required in
LZI Position Indication SOFT DCS - -
P&ID
Only if required in
LZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 55 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.10 GWR 2oo3 ESD input

TAG INSTRUMENT
I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION TYPE

Level Transmitter
LT HART AI-R ESD Field 20 Suffix A
(GWR)

Level Transmitter
LT HART AI-R ESD Field 21 Suffix B
(GWR)

Level Transmitter
LT HART AI-R ESD Field 22 Suffix C
(GWR)
Suffix A (Alarms
as identified on
LI Level Indication SOFT DCS ESD 30 P&ID, LAHH in
this case (Loop
order 40,41,42…))
Suffix B (Alarms
as identified on
LI Level Indication SOFT DCS ESD 31 P&ID, LAHH in
this case (Loop
order 40,41,42…))
Suffix C (Alarms
as identified on
LI Level Indication SOFT DCS ESD 32 P&ID, LAHH in
this case (Loop
order 40,41,42…))

LI Level Indication SOFT DCS ESD 33 Median

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 56 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.11 Level Transmitter Displacer

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Level Transmitter
LT HART AI DCS Field 20 -
(Displacer)

LI Level Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 57 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.12 Level Transmitter – Radar Type ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Level Transmitter
LT HART AI-R ESD Field 20 -
(Radar)
Alarms as
identified on P&ID,
LI Level Indication SOFT DCS ESD 30 LAHH in this case
(Loop order
40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 58 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.4.13 Level Transmitter D/P Type – ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Level Transmitter
LT HART AI-R ESD Field 20 -
(Diff. Pressure)
Alarms as
identified on P&ID,
LI Level Indication SOFT DCS ESD 30 LALL in this case
(Loop order
40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 59 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5 PRESSURE INSTRUMENT

5.5.1 Pressure Gauge

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

PG Pressure Gauge - - Field 10 -

5.5.2 Differential Pressure Gauge

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Differential Pressure
PDG - - Field 10 -
Gauge

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 60 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.3 Differential Pressure Transmitter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Differential Pressure
PDT HART AI DCS Field 20 -
Transmitter

Differential Pressure
PDI SOFT DCS - 30 -
Indication

5.5.4 Single Pressure Transmitter

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

PT Pressure Transmitter HART AI DCS Field 20 -

PI Pressure Indication SOFT DCS - 30 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 61 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.5 Single Pressure Transmitter with Control Valve

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

PT Pressure Transmitter HART AI DCS Field 20 -

PIC Pressure Controller SOFT DCS - 30 -

Pressure Control
PV HART AO DCS Field 50 -
Valve
Only if required in
PZI Position Indication SOFT DCS - -
P&ID
Only if required in
PZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 62 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.6 Single Pressure Transmitter 2XCV

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

PT Pressure Transmitter HART AI DCS Field 20 -

PI Local Indicator - - Field 21 Suffix L

PIC Pressure Controller SOFT DCS - 30 -

PV Control Valve HART AO DCS Field 50 Suffix A

PV Control Valve HART AO DCS Field 51 Suffix B

Only if required in
PZI Position Indication SOFT DCS - -
P&ID
Only if required in
PZT Position Transmiter HART AI DCS On Valve 22
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 63 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.7 Differential Pressure with Control Valve

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Differential Pressure
PDT HART AI DCS Field 20 -
Transmitter
DP Indicating
PDIC SOFT DCS - 30 -
Controller

PDV Control Valve HART AO DCS Field 50 -

Only if required in
PDZI Position Indication SOFT DCS - -
P&ID
Only if required in
PDZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 64 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.8 Single Pressure Transmitter ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

PT Pressure Transmitter HART AI-R ESD Field 20 -

Alarms as
identified on P&ID,
PI Pressure Indication SOFT DCS ESD 30 PALL,PAHH in
this case (Loop
order 40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 65 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.9 Single Pressure Transmitter 2oo3 ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

PT Pressure Transmitter HART AI-R ESD Field 20 Suffix A

PT Pressure Transmitter HART AI-R ESD Field 21 Suffix B

PT Pressure Transmitter HART AI-R ESD Field 22 Suffix C

Suffix A (Alarms
as identified on
PI Pressure Indication SOFT DCS ESD 30 P&ID, PAHH in
this case (Loop
order 40,41,42…)
Suffix B (Alarms
as identified on
PI Pressure Indication SOFT DCS ESD 31 P&ID, PAHH in
this case (Loop
order 40,41,42…)
Suffix C (Alarms
as identified on
PI Pressure Indication SOFT DCS ESD 32 P&ID, PAHH in
this case (Loop
order 40,41,42…)

PI Pressure Indication SOFT DCS ESD 33 Median

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 66 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.5.10 Differential Pressure Transmitter ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Differential Pressure
PDT HART AI-R ESD Field 20 -
Transmitter
Alarms as
identified on P&ID,
Differential Pressure
PDI SOFT DCS ESD 30 PDALL in this
Indication
case (Loop order
40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 67 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6 TEMPERATURE INSTRUMENT

5.6.1 Temperature Instrument – Dual Element

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

TW Thermowell - - Field 10 -

TE RTD RTD - Field 11 -

Temperature
TT HART AI DCS Field 20 -
Transmitter

Temperature
TI SOFT DCS - 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 68 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.2 Single Temperature Transmitter with Control Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

TW Thermowell - - Field 10 -

TE RTD RTD - Field 11 -

Temperature
TT HART AI DCS Field 20 -
Transmitter
Temperature
TIC SOFT DCS - 30 -
Indicating Controller
Temperature Control
TV HART AO DCS Field 50 -
Valve
Only if required in
TZI Position Indication SOFT DCS - -
P&ID
Only if required in
TZT Position Transmiter HART AI DCS On Valve 21
P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 69 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.3 Temperature Gauge

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

TW Thermowell - - Field 10 -

TG Thermometer - - Field 11 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 70 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.4 Temperature Instrument – Skin Type

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Temperature
TXE TC - Field 10 Skin Temperature
Element Skin
Temperature
TT HART AI DCS Field 20 -
Transmitter
Temperature
TI SOFT DCS - 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 71 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.5 Temperature Instrument – 2 out of 3 ESD Input

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

TW Thermowell - - Field 10,11,12 Suffix A,B and C

TE Thermocouple TC - Field 13 Suffix A

TE Thermocouple TC - Field 14 Suffix B

TE Thermocouple TC - Field 15 Suffix C

Temperature
TT HART AI-R ESD Field 20 Suffix A
Transmitter
Temperature
TT HART AI-R ESD Field 21 Suffix B
Transmitter
Temperature
TT HART AI-R ESD Field 22 Suffix C
Transmitter
Alarms as identified
Temperature on P&ID, TAHH in
TI SOFT DCS ESD 30
Indication this case (Loop order
40,41,42…)
Alarms as identified
Temperature on P&ID, TAHH in
TI SOFT DCS ESD 31
Indication this case (Loop order
40,41,42…)
Alarms as identified
Temperature on P&ID, TAHH in
TI SOFT DCS ESD 32
Indication this case (Loop order
40,41,42…)
Temperature
TI SOFT DCS ESD 33 Median
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 72 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.6 Temperature Instrument – TC ESD Input

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

TW Thermowell - - Field 10 -

TE Thermocouple TC - Field 11 -

Temperature
TT HART AI-R ESD Field 20 -
Transmitter
Alarms as identified
Temperature on P&ID, TAHH in
TI SOFT DCS ESD 30
Indication this case (Loop order
40,41,42…)

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 73 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.6.7 Temperature Instrument – TC

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

TW Thermowell - - Field 10 -

TE Thermocouple TC - Field 11 -

Temperature
TT HART AI DCS Field 20 -
Transmitter
Temperature
TI SOFT DCS - 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 74 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7 CONTROL / ON-OFF VALVE

5.7.1 ON/OFF Sequential Valve – Single Acting (From DCS) -TYPICAL 5

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER
On-off Valve Single
xV - - Field 50 -
Operated
XY Solenoid Valve DO DCS On valve 60 -
Limit Switch Open
XZSO DI DCS On valve 70 Integrated with XV
Position
Open Position
XZLO SOFT DCS - 71 -
Indication
Limit Switch Close
XZSC DI DCS On valve 72 Integrated with XV
Position
Close Position
XZLC SOFT DCS - 73 -
Indication
Suffix A. This signal
shall be used for
XHS Hand Switch Open SOFT DCS - 61
logic reset purpose
(fail close valves)
Suffix B. This signal
shall be used for
XHS Hand Switch Close SOFT DCS - 61
logic reset purpose
(fail open valves)
(*) Actual failure action will be indicated in relevant P&ID.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 75 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.2 Hand Operated ON/OFF Valve – Single Acting- TYPICAL TBD

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

HV On/Off Valve - - Field 50 -

HY SOLENOID VALVE DO DCS On valve 60 -

HS Hand Switch SOFT DCS - 61 -

Limit Switch Open


HZSO DI DCS On valve 70 Integrated with HV
Position
Limit Alarm Open
HZLO SOFT DCS - 71 -
Position
Limit Switch Close
HZSC DI DCS On valve 72 Integrated with HV
Position
Limit Alarm Close
HZLC SOFT DCS - 73 -
Position

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 76 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.3 Hand Operated ON/OFF Valve – Double Acting- TYPICAL TBD

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER
On-off Valve,
HV - - Field 50 -
Double Acting

HY Solenoid Valve DO DCS On valve 60 Suffix A

HY Solenoid Valve DO DCS On valve 62 Suffix B

HS Hand Switch SOFT DCS - 61 Suffix A

HS Hand Switch SOFT DCS - 63 Suffix B

Limit Switch Open


HZSO DI DCS On valve 70 Integrated with HV
Position
Limit Alarm Open
HZLO SOFT DCS - 71 -
Position
Limit Switch Close
HZSC DI DCS On valve 72 Integrated with HV
Position
Limit Alarm Close
HZLC SOFT DCS - 73 -
Position

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 77 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.4 DCS Operated ON/OFF Valve – (Double Acting)

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER
On-off Valve, Double
XV - - Field 50 -
Acting
Integrated with XV,
XY Solenoid Valve DO DCS On valve 60
Suffix A
Integrated with XV,
XY Solenoid Valve DO DCS On valve 62
Suffix B
Hand switch
XS SOFT DCS - 61 Suffix A
Open/Close
Hand switch
XS SOFT DCS - 63 Suffix B
Open/Close
Limit Switch Open
XZSO DI DCS On valve 70 Integrated with XV
Position
Open Position
XZLO SOFT DCS - 71 -
Indication
Limit Switch Close
XZSC DI DCS On valve 72 Integrated with XV
Position
Close Position
XZLC SOFT DCS - 73 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 78 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.5 Pressure Relief Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Pressure Relief
PSV - - Field 50 -
Valve

5.7.6 Pressure & Vacuum Safety Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Press./Vac Relief
PSV - - Field 50 -
Valve

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 79 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.7 Vacuum Safety Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
PVV Vac Relief Valve - - Field 50 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 80 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.8 Emergency Shutdown Valve (ESV)-TYPICAL 3 (Or TYP. 3-R, 3-ST)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Emergency
ESV ShutDown On-Off -- - Field 51 -
Valve

ESXY Solenoid Valve DO-R ESD On Valve 60 -

Limit Switch Closed


ESZSC DI-R ESD On valve 70 -
Position
Closed Position
ESZLC SOFT DCS - 71 -
Indication
Limit Switch Open
ESZSO DI-R ESD On Valve 73 -
Position
Open Position
ESZLO SOFT DCS - 74 -
Indication
Suffix A. This signal
shall be used for
ESHS Hand Switch Open SOFT DCS - 78
logic reset purpose.
(fail close valves)
Suffix B. This signal
shall be used for
ESHS Hand Switch Close SOFT DCS - 79
logic reset purpose
(fail open valves)
Suffix R. Required
Pressure Relief
PSV - - Field 50 only when typical 3-R
Valve
is indicated
Suffix R. Required
PT Pressure Transmitter HART AI DCS Field 20 only when typical 3-R
is indicated
Suffix R. Required
PI Pressure Indication SOFT DCS - 30 only when typical 3-R
is indicated

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 81 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Only if required in
Valve Partial Stroke P&ID. Required only
ESY HART AO-R ESD On Valve 76
Command when typical 3ST is
indicated
(*) Actual failure action will be indicated in relevant P&ID.

5.7.9 Emergency Shutdown Valve (ESV) with dual Solenoid TYPICAL 4 (Or TYP. 4-R, 4-ST)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Emergency
ESV ShutDown On-Off -- - Field 51 -
Valve
Integrated with ESV,
ESXY Solenoid Valve DO-R ESD On Valve 60
Suffix A
Integrated with ESV,
ESXY Solenoid Valve DO-R ESD On Valve 61
Suffix B
Limit Switch Closed
ESZSC DI-R ESD On valve 70 -
Position
Closed Position
ESZLC SOFT DCS - 71 -
Indication
Limit Switch Open
ESZSO DI-R ESD On Valve 73 -
Position
Open Position
ESZLO SOFT DCS - 74 -
Indication
Only if required in
Valve Partial Stroke P&ID. Required only
ESY HART AO-R ESD On Valve 76
Command when typical 4ST is
indicated
Suffix R. Required
Pressure Relief
PSV - - Field 50 only when typical 4-R
Valve
is indicated
Suffix R. Required
PT Pressure Transmitter HART AI DCS Field 20 only when typical 4-R
is indicated

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 82 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Suffix R. Required
PI Pressure Indication SOFT DCS - 30 only when typical 4-R
is indicated
Suffix A. This signal
Remote Close Push shall be used for
ESHS SOFT DCS - 78
Button logic reset purpose
(fail open valves)
Suffix B. This signal
Remote Open Push shall be used for
ESHS SOFT DCS - 79
Button logic reset purpose
(fail close valves)
(*) Actual failure action will be indicated in relevant P&ID.

5.7.10 Emergency Isolation Valve (EIV) with dual Solenoid and Partial Stroke Test – TYPICAL
1 (Or TYP. 1-R, 1-ST)

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Emergency Isolation
EIV -- - Field 51 -
On-Off Valve
Integrated with EIV,
EIXY Solenoid Valve DO-R ESD On Valve 60
Suffix A
Integrated with EIV,
EIXY Solenoid Valve DO-R ESD On Valve 61
Suffix B
Limit Switch Closed
EIZSC DI-R ESD On valve 70 -
Position

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 83 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Closed Position
EIZLC SOFT DCS - 71 Suffix A
Indication
Field status Lamp Suffix L (Only if
EIZLC DO-R ESD Field 72
Closed required in P&ID)
Limit Switch Open
EIZSO DI-R ESD On Valve 73 -
Position
Open Position
EIZLO SOFT DCS - 74 Suffix A
Indication
Field status Lamp Suffix L (Only if
EIZLO DO-R ESD Field 75
Open required in P&ID)
Only if required in
Valve Partial Stroke P&ID. Required only
EIY HART AO-R ESD On Valve 76
Command when typical 1ST is
indicated
Suffix R. Required
PSV Pressure Relief Valve - - Field 50 only when typical 1-R
is indicated
Suffix R. Required
PT Pressure Transmitter HART AI DCS Field 20 only when typical 1-R
is indicated
Suffix R. Required
PI Pressure Indication SOFT DCS - 30 only when typical 1-R
is indicated
MCR Emergency
EIHS DI-R ESD MCR 77 Suffix A
Close Push Button
Local Emergency Suffix B (Only if
EIHS DI-R ESD Field 78
Close Push Button required in P&ID)
Suffix C (Only if
required in P&ID).
Local Open Push
EIHS DI-R ESD Field 79 This signal shall be
Button
used for logic reset
purpose

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 84 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.11 Emergency De-Pressurization Valve (EDV) with two Solenoids 1oo2 Voting (TYPICAL
2H) or 2oo2 (TYPICAL 2)

Typical 2H

Typical 2

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 85 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Suffix R. Required
PSV Pressure Relief Valve - - Field 50 only when typical 1-R
is indicated
PT Pressure Transmitter HART AI DCS Field 20 Suffix R

PI Pressure Indication SOFT DCS - 30 Suffix R


Emergency De-
EDV Presurization On-Off -- - Field 51 Suffix R
Valve
Integrated with EDV,
EDXY Solenoid Valve DO-R ESD On Valve 60
Suffix A
Integrated with EDV,
EDXY Solenoid Valve DO-R ESD On Valve 61
Suffix B
Limit Switch Closed
EDZSC DI-R ESD On valve 70 -
Position
Closed Position
EDZLC SOFT DCS - 71 Suffix A
Indication
Field status Lamp
EDZLC DO-R ESD Field 72 Suffix L
Closed
Limit Switch Open
EDZSO DI-R ESD On Valve 73 -
Position
Open Position
EDZLO SOFT DCS - 74 Suffix A
Indication
Field status Lamp
EDZLO DO-R ESD Field 75 Suffix L
Open
MCR Emergency
EDHS DI-R ESD Field 76 Suffix A
Open Push Button
Local Emergency
EDHS DI-R ESD Field 77 Suffix B
Open Push Button
Suffix C. This signal
Local Close Push
EDHS DI-R ESD Field 78 shall be used for logic
Button
reset purpose

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 86 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.12 Motor Operated Valve- TYPICAL MOV 1 – MOV operated by DCS

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Electrical Operated
MOV - - Field 50 -
On/off Valve
MOV Open
MSO DO DCS On Valve 60 -
Command
MOV Close
MSC DO DCS On Valve 61 -
Command

MSS MOV Stop Command DO DCS On Valve 62 -

Remote Start / Stop


MHS DI DCS On Valve 77 -
Switch

XA Status Indication DI DCS On Valve 70 -

Limit Switch Open


MZSO DI DCS On Valve 71 -
Position
Open Position
MZLO SOFT DCS DCS 72 -
Indication
Limit Switch Close
MZSC DI DCS On Valve 73 -
Position
Close Position
MZLC SOFT DCS DCS 74 -
Indication
Limit switch Only if required in
MZSM DI DCS On Valve 75
intermediate P&ID
Medium Position Only if required in
MZLM SOFT DCS - 76
Indication P&ID

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 87 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.13 Motor Operated Valve- TYPICAL MOV 2 – MOV operated by DCS with emergency
close from ESD.

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Electrical Operated
MOV - - Field 50 -
On/off Valve
MOV Open
MSO DO DCS On Valve 60 -
Command
MOV Close
MSC DO DCS On Valve 61 -
Command

MSS MOV Stop Command DO DCS On Valve 62 -

XA Status Indication DI DCS On Valve 70 -

Limit Switch Open


MZSO DI DCS On Valve 71 -
Position
Open Position
MZLO SOFT DCS DCS 72 -
Indication
Limit Switch Close
MZSC DI DCS On Valve 73 -
Position
Close Position
MZLC SOFT DCS DCS 74 -
Indication
Limit switch Only if required in
MZSM DI DCS On Valve 75
intermediate P&ID
Medium Position Only if required in
MZLM SOFT DCS - 76
Indication P&ID
Remote Start / Stop
MHS DI DCS On Valve 77
Switch

HS Emergency Stop DO-R ESD ESD 80

Local Emergency
HS DI-R ESD Field 81
Stop

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 88 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.14 Motor Operated Valve- TYPICAL MOV 3 MOV operated by DCS with emergency close

from ESD and from operator console.

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Electrical Operated
MOV - - Field 50 -
On/off Valve
MOV Open
MSO DO DCS On Valve 60 -
Command
MOV Close
MSC DO DCS On Valve 61 -
Command

MSS MOV Stop Command DO DCS On Valve 62 -

XA Status Indication DI DCS On Valve 70 -

Limit Switch Open


MZSO DI DCS On Valve 71 -
Position
Open Position
MZLO SOFT DCS DCS 72 -
Indication
Limit Switch Close
MZSC DI DCS On Valve 73 -
Position
Close Position
MZLC SOFT DCS DCS 74 -
Indication
Limit switch Only if required in
MZSM DI DCS On Valve 75
intermediate P&ID
Medium Position Only if required in
MZLM SOFT DCS - 76
Indication P&ID
Remote Start / Stop
HS DI DCS On Valve 77
Switch

HS Emergency Stop DO-R ESD ESD 80

Local Emergency
HS DI-R ESD Field 81 Suffix B
Stop
MCR Emergency
HS DI-R ESD Field 82 Suffix A
Stop

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 89 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.15 Motor Operated Valve- TYPICAL MOV 5 MOV operated by DCS with emergency close
from ESD and feedback signals connected to ESD

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Electrical Operated
MOV - - Field 50 -
On/off Valve
MOV Open
MSO DO DCS On Valve 60 -
Command
MOV Close
MSC DO DCS On Valve 61 -
Command

MSS MOV Stop Command DO DCS On Valve 62 -

XA Status Indication DI ESD On Valve 70 -

Limit Switch Open


MZSO DI ESD On Valve 71 -
Position
Open Position
MZLO SOFT DCS DESD 72 -
Indication
Limit Switch Close
MZSC DI ESD On Valve 73 -
Position
Close Position
MZLC SOFT DCS ESD 74 -
Indication
Limit switch Only if required in
MZSM DI ESD On Valve 75
intermediate P&ID
Medium Position Only if required in
MZLM SOFT DCS ESD 76
Indication P&ID
Remote Start / Stop
HS DI ESD On Valve 77
Switch

HS Emergency Stop DO-R ESD ESD 80

Local Emergency
HS DI-R ESD Field 81 Suffix B
Stop
MCR Emergency
HS DI-R ESD Field 82 Suffix A
Stop

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 90 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.16 Manual Indication Controller with Control Valve

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Manual Controlled
HV HART-AO DCS Field 50 -
Valve

HIC Position Controller SOFT DCS - 60 -

5.7.17 Self-Regulator Valve (PCV)

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

PCV Self Regulator Valve - - Field 50 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 91 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.7.18 Manual Indication Controller with Motor Operated Control Valve

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER
Motor Operated
HV HART-AO DCS Field 50 -
Valve

HIC Position Controller SOFT DCS - 60 -

Limit Alarm Close


HZLC DI DCS - 70 -
Position

Limit Alarm Open


HZLO DI DCS - 71 -
Position

Remote Start / Stop


HS DI DCS - 73 -
Switch

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 92 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.8 HAND SWITCH

5.8.1 ESD Hand Switch Local

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

HS ESD Hand Switch DI-R ESD Field 60 -

HA Hand Switch Alarm SOFT DCS ESD - -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 93 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9 MOTOR

5.9.1 Motor with DCS Control TYPICAL M.4

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

*XYR * Start DO DCS/PLC MCC 60 -

*XYS * Stop DO DCS/PLC MCC 61 -

*XSR * Running Status DI DCS/PLC MCC 65 -

* Loc/Rem Selector
*XSL DI DCS/PLC MCC 66 -
Status

*XSA * Unavailable/Fault DI DCS/PLC MCC 67 -

NOTE 1: system and signal to be specified case by case per each motor. Depending on particular logic diagrams.
NOTE 2: “*” shall be replaced with the equipment function letter (P: pump, E: air fan, C: compressor, H: heater, etc).

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 94 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.2 Motor with DCS Control and ESD Trip (General)- TYPICAL M.1

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

*XYR * Start DO DCS/PLC MCC 60 -

*XYS * Stop DO DCS/PLC MCC 61 -

*SYS * Emergency Stop DO-R ESD/PLC MCC 63 -

Only if required in
*HS * Emergency Stop DI-R ESD/PLC Field 64
P&ID

*XSR * Running Status DI DCS/PLC MCC 65 -

* Loc/Rem Selector
*XSL DI DCS/PLC MCC 66 -
Status

*XSA * Unavailable/Fault DI DCS/PLC MCC 67 -

NOTE 1: system and signal to be specified case by case per each motor. Depending on particular logic diagrams.
NOTE 2: “*” shall be replaced with the equipment function letter (P: pump, E: air fan, C: compressor, H: heater, etc).

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 95 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.3 Motor with DCS Control and ESD Trip (General) and SPARE pump LOGIC- TYPICAL
M.5

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

*XYR * Start DO DCS/PLC MCC 60 -

*XYS * Stop DO DCS/PLC MCC 61 -

*SYR * Start Spare DO-R ESD/PLC MCC 62 -

*SYS * Emergency Stop DO-R ESD/PLC MCC 63 -

Only if required in
*HS * Emergency Stop DI ESD/PLC Field 64
P&ID

*XSR * Running Status DI DCS/PLC MCC 65 -

* Loc/Rem Selector
*XSL DI DCS/PLC MCC 66 -
Status

*XSA * Unavailable/Fault DI DCS/PLC MCC 67 -

NOTE 1: system and signal to be specified case by case per each motor. Depending on particular logic diagrams.
NOTE 2: “*” shall be replaced with the equipment function letter (P: pump, E: air fan, C: compressor, H: heater, etc).

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 96 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.4 Motor with DCS Control and ESD Trip (General) and Speed Control- TYPICAL M.6

TAG INSTRUMENT LOOP


I/O TYPE SYSTEM LOCATION NOTES
FUNCTION TYPE ORDER

*XYR * Start DO DCS/PLC MCC 60 -

*XYS * Stop DO DCS/PLC MCC 61 -

*SYS * Emergency Stop DO-R ESD/PLC MCC 63 -

Only if required in
*HS * Emergency Stop DI-R ESD/PLC Field 64
P&ID

*XSR * Running Status DI DCS/PLC MCC 65 -

* Loc/Rem Selector
*XSL DI DCS/PLC MCC 66 -
Status

*XSA * Unavailable/Fault DI DCS/PLC MCC 67 -

*XSB * Bypass Status DI DCS/PLC MCC 68 -

*SY * Speed Reference AO-R DCS/PLC MCC 69 -

*XSB * Speed Feedback AI DCS/PLC MCC 70 -

NOTE 1: system and signal to be specified case by case per each motor. Depending on particular logic diagrams.
NOTE 2: “*” shall be replaced with the equipment function letter (P: pump, E: air fan, C: compressor, H: heater, etc).

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 97 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.5 Motors not linked to logic (only monitoring)

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
XSR Running Status DI DCS CCM 60 -

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 98 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.6 Motors linked to logic

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

*XYR Motor DCS Start DO DCS/PLC MCC 60 Note 1

Note 1
*XYS Motor DCS Stop DO DCS/PLC MCC 61

Note 1
*SYR Start Spare Motor DO ESD/PLC MCC 62

Note 1
*XYS DCS permit to start DO DCS/PLC MCC 63

Note 1
*SYS ESD start DO ESD/PLC MCC 64

Note 1
*SYS Emergency Stop DO ESD/PLC MCC 65

Note 1
*HS Emergency Stop DI ESD/PLC Field 66

Note 1
*XSR Running Status DI DCS/ESD MCC 67

Loc/Rem Selector Note 1


*XSL DI DCS/ESD MCC 68
Status
Note 1
*XSA Unavailable/Fault DI DCS/ESD MCC 69

Note 1: System and signals to be specified case by case per each motor, depending on particular logic diagram

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 99 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.7 Fixed Speed Fans- Without VFD

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

VSH Vibration Switch DI DCS Field 61 -

EXSA Unavailable/Fault DI DCS MCC 62 -

EXSR Running Status DI DCS MCC 63 -

EXYS Stop Order DO DCS MCC 65 Suffix A

EHS Stop Push Button SOFT DCS DCS 66 Suffix A

EXYS Start Order DO DCS MCC 67 Suffix B (Note 1)

EHS Start Push Button SOFT DCS DCS 68 Suffix B (Note 1)

Note 1: DCS start push button, if any, to be specified case by case on P&IDs.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 100 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.9.8 Fans with Variable Speed Driver (VFD)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER

VSH Vibration Switch DI DCS Field 61 -

EXSA Unavailable/Fault DI DCS MCC 62 -

EXSR Running Status DI DCS MCC 63 -

EXYS Stop Order DO DCS MCC 65 Suffix A

EHS Stop Push Button SOFT DCS DCS 66 Suffix A

EXYS Start Order DO DCS MCC 67 Suffix B (Note 1)

EHS Start Push Button SOFT DCS DCS 68 Suffix B (Note 1)

ST Speed Transmitter AI DCS MCC 69 -

SI Speed Indication SOFT DCS DCS 70 -

SY Speed Control AO-R DCS MCC 71 -

Note 1: DCS start push button, if any, to be specified case by case on P&IDs.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 101 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10 PROCESS SAFETY

5.10.1 Flame Detector

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
BE Flame Detector - - Field 10 -

Flame Detector
BT DI FGS Field 20 Alarms as identified
Transmsiter

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 102 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.2 Gas Detector- Flammable Gas Detector – Infrared Open Path

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Gas Detector-
NFT Infrared Open Path- PWR Note 1 Field 20 Suffix A
Transmitter
Gas Detector-
NFT Infrared Open Path- HART AI FGS Field 21 Suffix B
Receiver
Gas Detector-
NFI Infrared Open SOFT DCS FGS 30 Alarm as Identified
Path/Point-Indication

Note 1: Marshalling cabinet or ICSS power distribution cabinet if greater than 24 VDC.

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 103 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.3 Gas Detector- Flammable Gas Detector – Infrared Open

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Gas Detector-Infrared
NFT HART AI FGS Field 20 -
Point
Gas Detector-Infrared
NFI Open Path/Point- SOFT DCS FGS 30 Alarm as indicated
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 104 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.4 Gas Detector- Hydrogen

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Gas Detector-
NFT HART AI FGS Field 20 -
Hydrogen
Gas Detector-
NFI SOFT DCS FGS 30 Alarm as indicated
Hydrogen Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 105 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.5 Gas Detector- Toxic Gas (H2S/SO2/CL2)

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

NTT Toxic Gas Detector HART AI FGS Field 20 -

Toxic Gas Detector-


NTI SOFT DCS FGS 30 Alarm as indicated
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 106 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.6 Gas Detector- Flammable Gas Detector – Ultrasonic

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Gas Detector-
NFT HART AI FGS Field 20 -
Ultrasonic

Gas Detector-
NFT SOFT DCS FGS 30 Alarm as indicated
Ultrasonic Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 107 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.7 Flame Detector- UV/IR

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Flame Detector-
NBT HART AI FGS Field 20 -
Infrared
Flame Detector-
NBI SOFT DCS FGS 30 Alarm as indicated
Infrared Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 108 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.8 Manual Call Point- Field Mounted

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Manual Call Point-
NAC DI FGS Field 20 -
Alarm
Manual Call Point-
NAI SOFT DCS FGS 30 -
Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 109 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.9 Smoke Detector Ionization

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Smoke Detector-
NF DI FGS Field 20 -
Ionization
Smoke Detector-
NFI SOFT DCS FGS 30 -
Ionization-Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 110 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.10 Smoke Detector (Optical)

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Smoke Detector-
NF DI FGS Field 20 -
Optical
Smoke Detector-
NFI SOFT DCS FGS 30 -
Optical-Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 111 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.11 Heat Detector-Point Type

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Heat Detector-Point
NT DI FGS Field 20 -
Type

Heat Detector-
NTI SOFT DCS FGS 30 -
Indication

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 112 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.12 Toxic Gas Visual Alarm Beacon (Blue Lamp)

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION
Toxic Gas Visual
NTL DO FGS Field 20 -
(Blue lens)

Toxic Gas Visual


NTA SOFT DCS FGS 30 -
(Blue lens)- Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 113 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.13 Fire Visual Alarm Beacon (Red Lamp)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Fire Visual Beacon
NBL DO FGS Field 20 -
(Red Lens)
Fire Visual Beacon
NBA SOFT DCS FGS 30 -
(Red Lens)- Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 114 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.14 Flammable gas Visible Beacon (Yellow Lamp)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Flammable Gas
NFL Visible (Yellow DO FGS Field 20 -
Lamp)
Flammable Gas
NFA Visible (Yellow SOFT DCS FGS 30 -
Lamp)- Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 115 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.15 Normal Condition Visible Beacon (Green Lamp)

TAG LOOP
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION NOTES
FUNCTION ORDER
Normal Condition
NNL DO FGS Field 20 -
Visible (Green Lamp)
Normal Cond Visible
NNA SOFT DCS FGS 30 -
(Green Lamp)- Alarm

80080-IZ-005-B, Rev. 4
HASSI Project Nº: 10745
MESSAOUD
Doc. Number: 80080-ED-INS-0000-PRC-002
REFINERY
PROJECT Rev. 2 Page 116 of 116
SMARTPLANT INSTRUMENTATION (SPI) DATABASE ENGINEERING PROCEDURE

5.10.16 Fire General Audible

TAG
INSTRUMENT TYPE I/O TYPE SYSTEM LOCATION LOOP ORDER NOTES
FUNCTION

NAY Fire General Audible DO FGS Field 20 -

Fire General Audible-


NAA SOFT DCS FGS 30 -
Alarm

80080-IZ-005-B, Rev. 4